Read this document and the quick guide before you
install the product. Installation and operation must
comply with local regulations and accepted codes of
good practice.
2
2
3
3
3
3
3
3
3
4
5
1. General information
5
5
1.1 Hazard statements
6
The symbols and hazard statements below may appear in
7
Grundfos installation and operating instructions, safety
7
instructions and service instructions.
7
7
8
8
8
8
8
8
8
8
8
8
9
9
9
The text accompanying the three hazard symbols DANGER,
WARNING and CAUTION is structured in the following way:
The hazard statements are structured in the following way:
This appliance can be used by children aged from 8
years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision
or instruction concerning use of the appliance in a
safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning
and user maintenance shall not be made by children
without supervision.
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
2
Page 3
1.2 Notes
!
0/Off
1/On
The symbols and notes below may appear in Grundfos
installation and operating instructions, safety instructions and
service instructions.
3.1 Mechanical installation
The mechanical installation must be carried out by
trained persons in accordance with local regulations.
A blue or grey circle with a white graphical symbol
indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with
a black graphical symbol, indicates that an action
must not be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Tips and advice that make the work easier.
2. Receiving the product
2.1 Inspecting the product
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when opening the box and
handling the product.
Check that the product received is in accordance with the order.
Check that the voltage and frequency of the product match
voltage and frequency of the installation site. See section
7.1 Nameplate.
3.2 Mounting
English (GB)
TM07 4154 1119TM07 4156 1119
2.2 Scope of delivery
The box contains the following items:
• ALPHA1 pump
• installer plug
•two gaskets
• quick guide.
3. Installing the product
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply before starting any
work on the product. Make sure that the power
supply cannot be accidentally switched on.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when opening the box and
handling the product.
Installation must be carried out by trained persons in
accordance with local regulations.
Fig. 1 Mounting the GRUNDFOS ALPHA1 L
The pump must always be installed with a horizontal
motor shaft within ± 5 °.
3
Page 4
English (GB)
TM07 4158 1119
Fig. 3 Control box positions
Fig. 2 Mounting the GRUNDFOS ALPHA1 L
Arrows on the pump housing indicate the liquid flow direction
through the pump.
See section
XX-40, XX-45, XX-50, XX-60 (international markets)
14.2 Installation dimensions, GRUNDFOS ALPHA1
.
• Fit the two gaskets supplied when the pump is mounted in the
pipe.
• Install the pump with horizontal motor shaft. See figs
1 and 2.
3.3 Control box positions
TM07 4155 1119
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply before starting any
work on the product. Make sure that the power
supply cannot be accidentally switched on.
CAUTION
Hot surface
Minor or moderate personal injury
- The pump housing may be hot due to the pumped
liquid being scalding hot. Close the isolating valves
on both sides of the pump and wait for the pump
housing to cool down.
CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valves on both sides of the
pump. The pumped liquid may be scalding hot
and under high pressure.
Fill the system with the liquid to be pumped or open
the isolating valves when the position of the control
box has been changed.
TM07 4157 1119
4
Page 5
3.4 Changing the control box position
The control box position can be changed in steps of 90 °.
Possible/permissible positions and the procedure of changing the
position of the control box are illustrated in fig.
Procedure:
1. Slacken and remove the four hexagon-socket head screws
holding the pump head with a tee key (M4).
2. Turn the pump head to the desired position.
3. Insert and cross-tighten the screws.
2.
3.5 Insulation of pump housing
4. Electrical installation
DANGER
Electric shock
Death or serious personal injury
- All electrical connections must be carried out by a
qualified electrician in accordance with local
regulations.
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply before starting any
work on the product. Make sure that the power
supply cannot be accidentally switched on.
DANGER
Electric shock
Death or serious personal injury
- Connect the pump to earth.
DANGER
Electric shock
Death or serious personal injury
- If national legislation requires a Residual-Current
Device (RCD) or equivalent in the electrical
installation, or if the pump is connected to an
electric installation where an RCD is used as an
additional protection, this must be type A or better,
due to the nature of the pulsating DC leakage
current. The RCD must be marked with the symbol
shown below:
English (GB)
Fig. 4 Insulation of pump housing
Limit the heat loss from the pump housing and
pipework.
The heat loss from the pump and pipework can be reduced by
insulating the pump housing and the pipe. See fig.
As an alternative, polystyrene insulating shells can be fitted to the
pump. See section
6.1 Product description.
Do not insulate the control box or cover the operating
panel.
4.
TM05 8561 2413
The pump requires no external motor protection.
• Check that the supply voltage and frequency correspond to
the values stated on the nameplate. See section
7.1 Nameplate.
• Connect the pump to the power supply with the plug supplied
with the pump as shown in
Light in the operating panel shows that the power supply has
been switched on.
The pump is not a safety component and cannot be
used to ensure functional safety in the final
appliance.
4.1 Assembling the plug.
5
Page 6
4.1 Assembling the plug
12 mm
17 mm
7 mm
Ø 5.5 - 10 mm
0.5 - 1.5 mm
2
L
N
English (GB)
StepActionIllustration
Fit the cable gland
and plug cover to
the cable. Strip the
1
cable conductors as
illustrated.
Connect the cable
2
conductors to the
power supply plug.
Bend the cable with
the cable
3
conductors pointing
upwards.
StepActionIllustration
Insert the power
supply plug into the
TM05 5538 3812
7
male plug in the
pump control box.
TM 07 415 9 111 9
TM05 5539 3812
Pull out the
conductor guide
4
plate and throw it
away.
Click the plug cover
5
onto the power
supply plug.
Screw the cable
6
gland onto the
power supply plug.
TM05 5540 3812
TM05 5541 3812
TM05 5542 3812
TM05 5543 3812
6
Page 7
5. Starting up the product
1
1
I
II
III
POWER
ON
I
III
= 10 Min.
5.1 Before startup
Do not start the pump until the system has been filled with liquid
and vented. The required minimum inlet pressure must be
available at the pump inlet. See sections
The pump is self-venting. It need not be vented before startup.
Air in the pump may cause noise. This noise will cease after a few
minutes running.
Quick venting of the pump can be obtained by setting the pump to
speed III for a short period, depending on system size and
design.
When the pump has been vented, i.e. when the noise has
ceased, set the pump according to the recommendations. See
section
10. Setting the pump.
The pump must not run dry.
The system cannot be vented through the pump. See section
5.3 Venting of heating systems.
The heating system can be vented via an air escape valve
installed above the pump. When the heating system has been
filled with liquid, follow this procedure:
1. Open the air escape valve.
2. Set the pump to speed III.
TM05 8000 1713
3. Let the pump run for a short period, depending on system size
and design.
4. When the system has been vented, that is when the possible
noise has ceased, set the pump according to the
recommendations. See section
10. Setting the pump.
Repeat the procedure, if necessary.
The pump must not run dry.
7
Page 8
6. Product introduction
75 °C
Min.
0.005 MPa
0.05 bar
90 °C110 °C
Min.
0.028 MPa
0.28 bar
Min.
0.108 MPa
1.08 bar
0.0 0.4 0.8 1.2 1.6 2.0 2.4
Q [m³/h]
0
2
4
6
[m]
H
0
20
40
60
[kPa]
0.00.20.40.6
ALPHA1 /ALPHA2/ALPHA2 L XX-50
ALPHA1 /ALPHA2/ALPHA2 L XX-40 / XX-45
ALPHA1 /ALPHA2/ALPHA2 L XX-60
Max. 1.0 MPa
(10 bar)
< 43 dB(A)
Min./Max.
+2 °C / +110 °C
Min./Max.
0 °C / +40 °C
Max. 95 % RH
IP42
English (GB)
6.1 Product description
Fig. 7 Pumped liquids and operating conditions
p
Q [l/s]
TM07 4160 1119
6.2 Application
The GRUNDFOS ALPHA1 circulator pump is designed for the
circulation of water in heating systems.
The pump is suitable for the following systems:
• underfloor heating systems
• one-pipe systems
• two-pipe systems.
The pump incorporates a permanent-magnet motor and
differential-pressure control enabling continuous adjustment of
the pump performance to the actual system requirements.
The pump has a user-friendly front-mounted operating panel. See
sections
6.3 Advantages of installing a GRUNDFOS ALPHA1
The installation of a GRUNDFOS ALPHA1 means
easy installation and startup
• The pump is easy to install.
With the factory setting, the pump can, in most cases, be
started without making any settings.
high degree of comfort
• Minimum noise from valves, etc.
low energy consumption
• Low energy consumption compared to conventional circulator
pumps.
Energy efficiency index (EEI)
• The Ecodesign directive for energy-using (EuP) and energyrelated (ErP) products is EU legislation requiring
manufacturers to reduce the overall environmental impact of
their products.
• The pumps are energy-optimised and comply with the EuP
directive.
6.4 Intended use
GRUNDFOS ALPHA1 is suitable for
• systems with constant or variable flows where it is desirable to
optimise the setting of the pump duty point.
• systems with variable flow-pipe temperature.
7. Identification and 9. Operating panel.
6.5 Pumped liquids
Clean, thin, non-aggressive and non-explosive liquids, not
containing solid particles, fibres or mineral oil. See fig.
7.
In heating systems, the water should meet the requirements of
accepted standards on water quality in heating systems, for
example the German standard VDI 2035.
CAUTION
Flammable material
Minor or moderate personal injury
- Do not use the pump for flammable liquids, such
as diesel oil and petrol.
CAUTION
Corrosive substance
Minor or moderate personal injury
- Do not use the pump for aggressive liquids, such
as acids and seawater.
6.6 System pressure
Maximum 1.0 MPa (10 bar). See fig.
7.
6.7 Relative air humidity (RH)
Maximum 95 %. See fig. 7.
6.8 Enclosure class
IP42. See fig. 7.
6.9 Inlet pressure
Minimum inlet pressure in relation to liquid temperature. See fig.
7.
Liquid temperature
≤ 75 °C0.0050.05
90 °C0.0280.28
110 °C0.1081.08
Minimum inlet pressure
[MPa][bar]
8
Page 9
7. Identification
ALPHA1
ON
POWER
Prod. No. 95047562
00000001
Serial No.
PC 0833TF110
IP 42 230V
~ 50Hz
Max.
Min. 0.05
I1/1(A) P1(W) MPa
5
221.0
0.19
KM07183
2
3
4
5
67
910 11
12
1314
8
MADE IN DENMARK
0.23 - Part 2
1
7.2 Type key
7.1 Nameplate
Fig. 8 Example of nameplate
Pos.Description
1Pump type
2Product number
3Serial number
Production code:
4
1st and 2nd digits = year
3rd and 4th digits = week
5Enclosure class
6Voltage [V]
7Frequency [Hz]
8Energy efficiency index (EEI)
Rated current [A]:
9
Min.: Minimum current [A]
Max.: Maximum current [A]
Input power P1 [W]:
10
11Maximum system pressure [MPa]
12CE mark and approvals
13Country of manufacture
14Temperature class
Min.: Minimum input power P1 [W]
Max.: Maximum input power P1 [W]
ExampleALPHA125-40180
Pump type
Nominal diameter (DN) of inlet and outlet ports
Changing from recommended to alternative pump setting
Heating systems are "slow" systems that cannot be set to the
optimum operation within minutes or hours.
If the recommended pump setting does not give the desired
distribution of heat in the rooms of the house, change the pump
setting to the shown alternative.
Explanation to pump settings in relation to performance curves,
see section
12. Pump settings and pump performance.
II
PP2).
Pump setting
RecommendedAlternative
CP1)* Highest constant-pressure curve (CP2)*
PP2)* Lowest proportional-pressure curve (PP1)*
PP1)*Highest proportional-pressure curve (PP2)*
10.2 Pump control
During operation, the pump head is controlled according to the
principle "proportional-pressure control" (
pressure control" (
CP).
In these control modes, the pump performance and consequently
the power consumption are adjusted according to the heat
demand in the system.
Proportional-pressure control
In this control mode, the differential pressure across the pump is
controlled according to the flow.
The proportional-pressure curves are indicated by
in the QH diagrams. See section
performance
Constant-pressure control
In this control mode, a constant differential pressure across the
.
pump is maintained, irrespective of the flow.
The constant-pressure curves are indicated by
are the horizontal performance curves in the QH diagrams. See
section
12. Pump settings and pump performance.
PP) or "constant-
12. Pump settings and pump
N
TM05 1921 4512
PP1 and PP2
CP1 and CP2 and
12
Page 13
11. Systems with bypass valve between flow and
BYPASS
Q
min.
1
2
33
IIIIII
POWER
ON
OK
(OK)
IIIIII
POWER
ON
OK
(OK)
IIIIII
POWER
ON
OK
(OK)
IIIIII
POWER
ON
IIIIII
POWER
ON
II
POWER
ON
OK
(OK)
1213
A
return pipes
11.1 Purpose of bypass valve
Fig. 14 Systems with bypass valve
Bypass valve
The purpose of the bypass valve is to ensure that the heat from
the boiler can be distributed when all valves in the underfloorheating circuits and/or thermostatic radiator valves are closed.
System elements:
• bypass valve
• flowmeter, pos. A.
The minimum flow must be present when all valves are closed.
The pump setting depends on the type of bypass valve used, i.e.
manually operated or thermostatically controlled.
English (GB)
TM05 8150 2013
11.2 Manually operated bypass valve
Follow this procedure:
1. Adjust the bypass valve with the pump in setting I (speed I).
The minimum flow (Q
observed. Consult the manufacturer's instructions.
) for the system must always be
min.
2. When the bypass valve has been adjusted, set the pump
according to section
10. Setting the pump.
11.3 Automatic bypass valve (thermostatically
controlled)
Follow this procedure:
1. Adjust the bypass valve with the pump in setting I (speed I).
The minimum flow (Q
observed. Consult the manufacturer's instructions.
2. When the bypass valve has been adjusted, set the pump to
the lowest or highest constant-pressure curve.
Explanation to pump settings in relation to performance
curves, see section
performance
.
) for the system must always be
min.
12. Pump settings and pump
13
Page 14
12. Pump settings and pump performance
III
II
I
AUTO
PP1
PP2
CP1
CP2
H
Q
ON
POWER
English (GB)
15 shows the relation between pump setting and pump performance by means of curves. See also section 15. Performance
Figure
curves
.
Fig. 15 Pump setting in relation to pump performance
TM04 2532 2608
SettingPump curveFunction
The duty point of the pump will move up or down on the lowest proportional-pressure
PP1
PP2
(factory setting)
CP1
CP2
IIISpeed III
IISpeed II
ISpeed I
Lowest proportionalpressure curve
Highest proportionalpressure curve
Lowest constantpressure curve
Highest constantpressure curve
curve, depending on the heat demand in the system. See fig.
The head (pressure) is reduced at falling heat demand and increased at rising heat
demand.
The duty point of the pump will move up or down on the highest proportional-pressure
curve, depending on the heat demand in the system. See fig.
The head (pressure) is reduced at falling heat demand and increased at rising heat
demand.
The duty point of the pump will move out or in on the lowest constant-pressure curve,
depending on the heat demand in the system. See fig.
The head (pressure) is kept constant, irrespective of the heat demand.
The duty point of the pump will move out or in on the highest constant-pressure curve,
depending on the heat demand in the system. See fig.
The head (pressure) is kept constant, irrespective of the heat demand.
The pump runs at a constant speed and consequently on a constant curve.
In speed III, the pump is set to run on the maximum curve under all operating
conditions. See fig.
Quick venting of the pump can be obtained by setting the pump to speed III for a short
period. See section
The pump runs at a constant speed and consequently on a constant curve.
In speed II, the pump is set to run on the intermediate curve under all operating
conditions. See fig.
The pump runs at a constant speed and consequently on a constant curve.
In speed I, the pump is set to run on the minimum curve under all operating conditions.
See fig.
15.
15.
15.
15.
15.
12. Pump settings and pump performance.
15.
15.
14
Page 15
13. Fault finding
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply before starting any
work on the product. Make sure that the power
supply cannot be accidentally switched on.
CAUTION
Pressurised system
Minor or moderate personal injury
- Before dismantling the pump, drain the system or
close the isolating valves on either side of the
pump. The pumped liquid may be scalding hot
and under high pressure.
WARNING
Electric shock
Death or serious personal injury
- A damaged product must be repaired by Grundfos
or a service workshop authorised by Grundfos.
WARNING
Hot surface
Minor or moderate personal injury
- The pump housing may be hot due to the pumped
liquid being scalding hot. Close the isolating valves
on both sides of the pump and wait for the pump
housing to cool down.
13.1 Fault finding table
FaultOperating panelCauseRemedy
1. The pump does
not run.
2. Noise in the
system.
3. Noise in the
pump.
4. Insufficient heat.
Light off.
Display shows "- -".
"POWER ON" is on only.
Shows normal operating
status.
Shows normal operating
status.
Shows normal operating
status.
a) A fuse in the installation is blown.Replace the fuse.
b) The current-operated or voltage-
operated circuit breaker has tripped
out.
c) The pump is defective.Replace the pump.
a) Power supply failure. The power
supply might be too low.
b) The pump is blocked.Remove the impurities.
a) Air in the system.Vent the system. See section
b) The flow is too high.Reduce the suction head. See section
a) Air in the pump.Let the pump run. It vents itself over time.
b) The inlet pressure is too low.Increase the inlet pressure or check the
a) The pump performance is too low.Increase the suction head. See section
Cut in the circuit breaker.
Check that the power supply falls within
the specified range.
of heating systems
12. Pump settings and pump
performance
See section
performance
air volume in the expansion tank, if
installed.
12. Pump settings and pump
performance
English (GB)
5.3 Venting
.
.
12. Pump settings and pump
.
.
15
Page 16
14. Technical data and installation dimensions
English (GB)
14.1 Technical data
Operating conditions
Relative humidityMaximum 95 % RH
System pressureMaximum 1.0 MPa, 10 bar, 102 m head
Liquid temperatureMinimum inlet pressure
Inlet pressure
EMC (electromagnetic
compatibility)
Sound pressure levelThe sound pressure level of the pump is lower than 43 dB(A).
Ambient temperature0-40 °C
Surface temperatureThe maximum surface temperature will not exceed 125 °C.
Liquid temperature2-110 °C
Electrical data
Supply voltage1 x 230 V ± 10 %, 50/60 Hz, PE
Insulation classF
Miscellaneous data
Motor protectionThe pump requires no external motor protection.
Temperature classTF110 to EN 60335-2-51
Enclosure classIP42
To avoid condensation in the control box and stator, the liquid
temperature must always be higher than the ambient
temperature.
≤ 75 °C0.005 MPa, 0.05 bar, 0.5 m head
90 °C0.028 MPa, 0.28 bar, 2.8 m head
110 °C0.108 MPa, 1.08 bar, 10.8 m head
EMC Directive (2014/30/EU).
Standards used: EN 55014-1:2006/A1:2009/A2:2011, EN 55014-2:2015, EN 61000-3-2:2014 and
EN 61000-3-3:2013.
The pump can run at ambient temperatures higher
than the liquid temperature if the plug connection in
the pump head is pointing downwards
If the temperature of the pumped liquid is lower than
the ambient temperature, make sure that the pump is
installed with the pump head and plug in position 6
o'clock.
* ALPHA1 20-45 N 150 is suitable for drinking water only.
Dimensions
18
Page 19
15. Performance curves
AUTO
ADAPT
III
II
I
PP1
PP2
CP1
CP2
Q
P1
H
Q
III
II
I
ON
POWER
15.1 Guide to performance curves
Each pump setting has its own performance curve (QH curve).
A power curve (P1 curve) belongs to each QH curve. The power curve shows the pump power consumption (P1) in Watt at a given QH
curve.
The P1 value corresponds to the value that can be read from the pump display. See fig.
18:
English (GB)
Fig. 18 Performance curves in relation to pump setting
IIIConstant speed, speed III
IIConstant speed, speed II
IConstant speed, speed I
For further information about pump settings, see sections
9.4 Light fields indicating the pump setting
10. Setting the pump
12. Pump settings and pump performance.
15.2 Curve conditions
The guidelines below apply to the performance curves on the
following pages:
• Test liquid: airless water.
• The curves apply to a density of ρ = 983.2 kg/m
temperature of +60 °C.
• All curves show average values and should not be used as
guarantee curves. If a specific minimum performance is
required, individual measurements must be made.
• The curves for speeds I, II and III are marked.
• The curves apply to a kinematic viscosity of = 0.474 mm2/s
(0.474 cSt).
3
and a liquid
TM04 2534 2608
19
Page 20
15.3 Performance curves, ALPHA1 XX-40
0.00.20.40.60.81.01.21.41.61.82.02.2
Q[m³/h]
0
1
2
3
4
[m]
H
0
10
20
30
40
[kPa]
p
0.00.10.20.30.40.50.6
Q[l/s]
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.2
Q[m³/h]
0
5
10
15
20
25
[W]
P1
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.2
Q [m³/h]
0
1
2
3
4
[m]
H
0
10
20
30
40
[kPa]
p
0.00.10.20.30.40.50.6
Q [l/s]
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.2
Q [m³/h]
0
5
10
15
20
25
[W]
P1
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.22.42.6
Q [m³/h]
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
[m]
H
0
10
20
30
40
[kPa]
p
0.00.10.20.30.40.50.60.7
Q [l/s]
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.22.42.6
Q [m³/h]
0
10
20
30
40
50
[W]
P1
III
II
I
English (GB)
Fig. 19 ALPHA1 XX-40
15.4 Performance curves, ALPHA1 20-45 N 150
TM04 2110 2008
Fig. 20 ALPHA1 20-45 N 150
20
TM05 2213 4611
Page 21
15.5 Performance curves, ALPHA1 XX-50
0.00.20.40.60.81.01.21.41.61.82.02.22.42.6
Q [m³/h]
0
1
2
3
4
5
[m]
H
0
10
20
30
40
50
[kPa]
p
0.00.10.20.30.40.50.60.7
Q [l/s]
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.22.42.6
Q [m³/h]
0
5
10
15
20
25
30
35
[W]
P1
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.22.42.62.8
Q [m³/h]
0
1
2
3
4
5
6
[m]
H
0
10
20
30
40
50
60
[kPa]
p
0.00.10.20.30.40.50.60.70.8
Q [l/s]
III
II
I
0.00.20.40.60.81.01.21.41.61.82.02.22.42.62.8
Q [m³/h]
0
10
20
30
40
50
[W]
P1
III
II
I
English (GB)
Fig. 21 ALPHA1 XX-50
15.6 Performance curves, ALPHA1 XX-60
TM04 2109 2008
Fig. 22 ALPHA1 XX-60
TM04 2108 2008
21
Page 22
16. Disposal
English (GB)
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
The crossed-out wheelie bin symbol on a product
means that it must be disposed of separately from
household waste. When a product marked with this
symbol reaches its end of life, take it to a collection
authorities. The separate collection and recycling of such
products will help protect the environment and human health.
See also end-of-life information at www.grundfos.com/productrecycling.
point designated by the local waste disposal
22
Page 23
Argentina
Bombas GRUNDFOS de Argentina S.A.
Ruta Panamericana km. 37.500 Centro
Industrial Garin
1619 Garín Pcia. de B.A.
Phone: +54-3327 414 444
Telefax: +54-3327 45 3190
Australia
GRUNDFOS Pumps Pty. Ltd.
P.O. Box 2040
Regency Park
South Australia 5942
Phone: +61-8-8461-4611
Telefax: +61-8-8340 0155
GRUNDFOS Sarajevo
Zmaja od Bosne 7-7A,
BH-71000 Sarajevo
Phone: +387 33 592 480
Telefax: +387 33 590 465
www.ba.grundfos.com
e-mail: grundfos@bih.net.ba
Brazil
BOMBAS GRUNDFOS DO BRASIL
Av. Humberto de Alencar Castelo Branco,
630
CEP 09850 - 300
São Bernardo do Campo - SP
Phone: +55-11 4393 5533
Telefax: +55-11 4343 5015
Bulgaria
Grundfos Bulgaria EOOD
Slatina District
Iztochna Tangenta street no. 100
BG - 1592 Sofia
Tel. +359 2 49 22 200
Fax. +359 2 49 22 201
email: bulgaria@grundfos.bg
GRUNDFOS Pompe România SRL
Bd. Biruintei, nr 103
Pantelimon county Ilfov
Phone: +40 21 200 4100
Telefax: +40 21 200 4101
E-mail: romania@grundfos.ro
Russia
ООО Грундфос Россия
ул. Школьная, 39-41
Москва, RU-109544, Russia
Тел. (+7) 495 564-88-00 (495) 737-30-00
Факс (+7) 495 564 8811
E-mail grundfos.moscow@grundfos.com
Serbia
Grundfos Srbija d.o.o.
Omladinskih brigada 90b
11070 Novi Beograd
Phone: +381 11 2258 740
Telefax: +381 11 2281 769
www.rs.grundfos.com