conform with local codes or, in the absence of local
codes, with Installation of the National Fuel GasCode, ANSI Z223.1-latest edition, from the American
National Standard Institute. Further reference should
be made to the recommendation of your fuel supplier.
In Canada,Installation must conform with local
codes or, in the absence of local codes, with
Installation Codes for Gas Burning Appliances and
Equipment, CGA Standard CAN/CGA 1B-149.
Further reference should be made to the
recommendation of your fuel supplier.
WARNING: Additions, changes, conversions,
and service must be performed by an authorized
MIDCO representative, service agency, or the fuel
supplier. Use only MIDCO specified and approved
parts.
INSTALLER: Inform and demonstrate to the user
the correct operation and maintenance of the gas
utilization equipment. Inform the user of the
hazards of storing flammable liquids and vapors in
the vicinity of this gas utilization equipment and
remove such hazards. Affix this manual and
associated literature adjacent to the burner. CODE
COMPLIANCE IS THE SOLE RESPONSIBILITY OF
THE INSTALLER.
USER: Retain this manual for future reference. If
other than routine service or maintenance as
described in this manual and associated literature
is required, contact a qualified service agency. DO
NOT ATTEMPT REPAIRS. An inadvertent service
error could result in a dangerous condition.
Economite
RE4850A / RE4400
Gas Burners
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may result,
causing property damage, personal injury or death.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS:
u Do not try to light any appliance.
u Do not touch any electrical switch;do not use any
phone in your building.
u Immediately phone your gas supplier from another
building. Follow the gas supplier’s instructions. If
you cannot reach your gas supplier call the fire
department.
Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
BURNER MODEL
BILL OF MAT'L
NUMBER
SERIAL NUMBER #
WIRING DIAGRAM
FOR SERVICE CONTACT:
Name
Address
Phone
Date of Installation
special notations and have standard meanings throughout this manual. They are printed in all capital letters using a bold
type face as shown below, and preceded by the exclamation mark symbol. When you see the safety alert symbol and one of
the safety information terms as shown below, be aware of the hazard potential.
DANGER: Identifies the most serious hazards which will result in severe personal injury or death.
WARNING: Signifies a hazard that could result in personal injury or death.
CAUTION : Identifies unsafe practices which would result in minor personal injury or product and property damage.
Midco®International Inc.
4140 West Victoria St. - Chicago, Illinois 606 46
tel 773.604.8700 fax 773.604.40 70
web www.midco-intl.com e-mail sales@midco-intl.com
Quality Designed for Proven Performance
The following terms are used to identify hazards, safety precaution of
303p
8471 20
Printed in USA
Page 2
Part 1 Installation
Specifications
The ECONOMITE Models RE 4850A and RE4400 burners with intermittent and interrupted
1
spark ignited pilot are adaptable to most gas utilization equipment, including gravity and
forced circulation furnaces and boilers. They are particularly recommended for firing
horizontal or downdraft equipment since no draft is required to maintain a pilot. Power burner
design makes them perfectly suited for oil burner replacement, including rooftop and
industrial applications.
AIR DELIVERY (Approximate Air Delivery at Zero Draft)
FIRING RATE (NATURAL OR PROPANE )
FLAME SAFETY....Electronic Flame Safety with Spark Ignited Pilot and 100% Shut-Off
RE 4850A and RE4400 .................. 125 SCFM
3
MAXIMUM MBH
MINIMUM MBH
NATURAL ..............................................7.0" to 14.0" W.C.
PROPANE .............................................5.0" TO 14.0" W.C.
WIDTH15"10”
LENGTH30"16.5”
RE 4850ARE4400
850400
4
4
280132
RE 4850ARE4400
2
TABLE 1: Burner Specifications
1.Standard burners are shipped as NATURAL gas models. Contact your Midco dealer for
2.SCFM = Standard Cubic Feet / Minute.
3.All Ratings Based on 1000 BTU/Cu. Ft. NATURAL. Derate burner for altitude over 2,000
4.1 MBH = 1,000 BTU/hr.
intended for outdoor installation and must be protected from excessive moisture.
Provide adequate clearance for service and proper operation.
PROPANE gas burners.
feet by 4% for each 1,000 feet above sea level.
CAUTION: The ECONOMITE Models RE4850A and RE4400 Burners are not
_____________________________________
Part 1
Installation
IVentilation
IIPreparation of
the Gas Utilization
Equipment
2
If the former automatic oil burner gave trouble-free operation, it is probable that the heating
plant area has sufficient infiltration of air for combustion and dilution of flue gases.
Nevertheless, the area must be checked.
o Open basement or utility areas of normal construction, without storm windows or tight
doors, will generally allow sufficient air infiltration. However, if the heating plant is located in
a tight or separate room, ventilation to an open area as described above will be required.
Install two permanently open grills, each sized on the basis of one square inch free area per
1,000 BTU (but not less than 100 square inches) of the total input rating of all gas utilization
equipment in the combined space. One grille should be located within 12 inches of the
ceiling, the other within 12 inches of the floor.
o If the heating plant is located in an area of unusually tight construction, or if an exhaust
fan, kitchen ventilation system, clothes dryer and/or fireplace is installed in the building,
provisions must be made for an outside air supply near the heating appliance area. Install
permanently open grills sized at not less than one square inch free area per 4,000 BTU of
burner input. When ventilating through horizontal ducts, grills should be sized at not less
than one square inch free area per 2,000 BTU of burner input. In any case, the minimum
dimension of rectangular air ducts shall not be less than 3 inches.
o In Canada, for detailed ventilation requirements, refer to standard CAN 1-B149.1 or .2
and/or local codes.
_____________________________________
o Clean the gas utilization equipment combustion chamber, heat exchanger interior, and flue
connections. Remove all adhering tars, scale, dirt and soot. Inspect for actual or potential
leaks.
o Cement all joints, including those in the heating appliance base and around the door
frames, to prevent leakage into, or out of the combustion chamber.
o The access or firing door should open easily to relieve pressure. If positive latches exist,
they should be modified to permit easy opening; a spring loaded door holder is
recommended.
_____________________________________
Page 3
3
Part 1
Part 1 Installation
Installation
Continued
IIICombustion
Chamber
o On all boilers, make certain the pressure relief safety valve is in good operating condition.
A combustion chamber liner is normally required to protect non-heat transfer surfaces and to
provide a radiant bed for rapid heat transfer to the primary surfaces of the heat exchanger.
In most cases the existing chamber liner can be used, if in good condition.
o In the case of wet base boilers, where the entire firing chamber is comprised of heat
exchange surfaces and no chamber liner was provided for oil firing, a liner is usually not
required for the ECONOMITE. However, a liner or target wall may be necessary if the firing
chamber is unusually short, in order to avoid excess flame contact on the heat exchanger
walls or flueways.
o If a built up chamber liner is required, use 2,300°F minimum insulating material.
o The burner tube, or the stainless steel sleeve that is included with the burner, must be
sealed air tight into the combustion chamber opening with refractory material. The sleeve is
preferred as it is designed to properly locate the end of the tube relative to the inside wall of
the combustion chamber, and to permit burner removal without breaking the seal.
CAUTION: In no case should the burner tube be allowed to extend into the
chamber proper; it must be set at least 1" short of the inside surface because high
combustion chamber temperatures will cause premature pilot, electrode, burner tube
and sleeve deterioration.
WARNING: BURNER MUST BE MOUNTED IN ORIENTATION SHOWN IN
FIGURES 1A AND 1B. ANY OTHER MOUNTINGS MAY CAUSE A DANGEROUS
CONDITION, AND WILL VOID BURNER WARRANTY AND AGENCY APPROVALS. NONSTANDARD ARRANGEMENTS MAY BE AVAILABLE FOR SOME MODELS. CONSULT
FACTORY FOR DETAILS IF REQUIRED.
o Before permanently setting the burner in place, check that the main burner and pilot ports
are free of foreign materials, and also that the spark electrode assembly has not been
damaged or displaced. See Figures 6A and 6B.
IVChimney, Vent
Connector and
Draft Control
Figure 1A: Dry Base Boiler with
Combustion Chamber Liner (Warm Air
Furnace Construction is Similar)
_____________________________________
WARNING: The chimney shall be inspected for unsafe conditions such as
deteriorated masonry and excessive soot or other blockage or potential blockage.
Installation must conform with local codes or in the absence of local codes with NFPA,
ANSI Z223.1 latest edition.
WARNING: The vent connector shall not be connected to a chimney already
venting solid fuel burning equipment, an incinerator or an open fireplace.
o The Vent Connector shall be made of non-combustible, corrosion resistant material
capable of withstanding the vent gas temperature produced by the gas utilization equipment
and of sufficient thickness to withstand physical damage.
o The Vent Connector shall be as short as possible. The entire length shall be readily
accessible for inspection, cleaning, and replacement.
o The length of horizontal uninsulated Vent Connector between the chimney and a single
gas utilization equipment shall not exceed 75% of the the height of the chimney above the
connector, or 100% if the Vent Connector is insulated.
o The Vent Connector shall be installed so as to avoid turns or other construction features
which create excessive resistance to flow of vent gas. It shall be installed without any dips or
sags and shall slope upward at least 1/4" per foot.
o A manually operated damper shall not be placed in the Vent Connector or chimney of
any gas utilization equipment.
o The Vent Connector shall be firmly attached to draft hood outlets and flue collars. Joints
between sections of connector piping shall be fastened by sheet-metal screws or other
approved means. The Vent Connector shall be supported for the design and weight of the
material employed to maintain clearance and prevent physical damage and separation of
joints.
o A draft hood or a barometric draft regulator shall be installed in the same room or
enclosure as the equipment in such a manner as to prevent any difference in the pressure
between the hood or regulator and the combustion air supply (see Figures 3 and 4). In no
Figure 1B: Wet Base Boiler with Unlined
Combustion Chamber
Page 4
Part 1
Part 1 Installation
Installation
Continued
IVChimney, Vent
Connector and
Draft Control
Continued
case shall the relief opening of the draft hood or barometric draft regulator be located at a
point lower than the top of the highest flue passage in the equipment.
o Gas utilization equipment requiring controlled draft may be equipped with a listed double
acting barometric draft regulator, if approved by local codes (see Figure 4).
o A device which will automatically shut off gas to the burner in the event of sustained
backdraft is required. It shall be of the listed manual reset type and installed and adjusted by
a qualified service technician in accordance with the manufacturer’s instructions.
o Refer to gas utilization equipment manufacturer for recommended vent connection
requirements.
_____________________________________
Figure 2: Wiring Diagram
4
Figure 3: Recommended Locations for Draft Hoods
Page 5
5
Part 1
Part 1 Installation
Installation
Continued
VElectrical
Installation wiring and grounding to the burner must conform to local codes, or, in their
absence in the United States to National Electric Code, ANSI/NFPA No. 70 latest edition;
in Canada, to Canadian Electrical Code Part 1, CSA Standard C22.1o Use copper wire not less than 14 gage for line voltage wiring. Hook up to a dedicated line
with an on-off disconnect switch and a minimum 10 Amp breaker.
o The frame of the burner should be well grounded. Normally the piping and/or electric
conduit will provide sufficient grounding. However, a ground lug is located in control box for
positive grounding where insulated pipe couplings are used or where any doubt exists
regarding grounding sufficiency.
o Confirm that the polarity is correct—hot wire to strip terminal L1, neutral L2—and that the
neutral line is not subject to induced low voltage (check L2 to earth ground) from other
equipment, as that can cause the primary safety control to malfunction.
o Each installation must include suitable limit control(s). Existing oil burner combination
operating and limit controls are normally NOT SUITABLE for gas burner use.
o Connect motors used on forced air furnace fans or boiler pumps to a combination limit
control and switch.
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. Verify proper operation
after servicing.
_____________________________________
VIPiping
Figure 4: Location for Barometric Draft Regulators
Note: Figure 3 and 4 : Copyright by American Gas Association.
Used by permission of the copyright holder.
CAUTION: The available gas pressure should be within the limits shown in
SPECIFICATIONS section. Excessive pressure may damage electric valves, regulators
and manual valves. If the supply pressure exceeds the 14.0"W.C. maximum, a suitable
high pressure regulator must be installed between the Main Manual Shut-Off Valve and
burner shut-off valve as shown in Figure 5.
o The burner gas supply piping should branch off from the main line as close to the gas
meter as possible. Do not connect to the bottom of a horizontal section. Use new black pipe
and malleable fittings free of cutting and threading burrs or defects.
o Provide a sediment trap, union and 1/8" pressure tap in piping close to burner as shown
in Figure 5.
o Use pipe joint compound approved for use with Liquid Petroleum Gases.
o Piping must also comply with your local codes.
o To obtain the maximum firing rate of the burner, the gas supply piping must be sized to
provide a minimum of 7.0"W.C. pressure to the inlet of the upstream automatic safety shutoff valve when the burner and all other gas utilization equipment are on. The pilot regulator
can be mounted in any position, the main regulator, if equipped, should be mounted upright
and in a horizontal run of pipe.
CAUTION: Because it is difficult to accurately control pressure during supply
pipe leak testing, it is recommended that all low pressure (14.0"W.C. max.)
components, both main and pilot, be disconnected during testing. Exposing low
pressure regulators and valves, including manual valves, to pressures over 1/2 PSIG
(14.0"W.C.) will cause damage and void all warranties.
Page 6
Part 1
Part 1 Installation
Installation
Continued
VIPiping
Continued
RE4400 UL,
Valve Train Assembly,
120VAC
RE4850A UL,
Valve Train Assembly,
120VAC
6
Figure 5: Piping Diagram - RE4400 and RE4850A
Page 7
7
Part 1
Part 1 Installation
Installation
Continued
VIPiping
Continued
Pipe
Size
3/4
3/4
1
1
1 1/4
1 1/4
1 1/2
1 1/2
o If the burner piping must be rearranged because of space limitation, be sure to carry out
the general arrangement shown in Figure 5.
o When the burner is installed in the vestibule of jacketed equipment, it is recommended that
the Automatic Safety Shut-Off Valves be left adjacent to the burner within the vestibule and
the Main Manual Shut-Off Valve be installed outside.
o Run full size pipe or tubing from regulator vent openings to outside of building. Provide no
traps in the vent lines and terminate away from all doors and windows; also make provisions
for keeping rain and foreign objects from entering the vent piping.
o When high supply gas pressure is encountered, as in the case in many industrial plants,
the gas line size can be reduced to allow for a greater pressure drop; however, the size must
be sufficient to deliver burner rating pressure.
reducing regulators. Install two separate high pressure regulators of the Tight Shut-Off
type upstream of the low pressure regulators. One sized for main gas input, and one
suitable for the minimum flow regulating capacity of the pilot.
o The high pressure regulators must be adjustable to 14" W.C. outlet pressure.
o When the gas supply line is about to be put into service it must be tested to insure that it
is gas tight. Use air or inert gas under pressure and test with soap and water or to locate
leaks.
o Before gas is turned onto the system, a check must be made to see that there are no open
fittings and to make sure the burner main and pilot manual valves are closed.
o After checking for leaks, purge the gas line up to the burner inlet. Purging the air from the
gas supply line at this step will expedite the first light-off.
NOTE: If there is more than 1.0" W.C. differential in the inlet pressure to the burner compared
to when all other gas utilization equipment are off, refer to Section IX.
Type
of Gas
Natural
Propane
Natural
Propane
Natural
Propane
Natural
Propane
An explosion could occur during initial start up.
CAUTION: High gas pressure supply lines require the proper pressure
Approximate Capacity -MBH
Pipe Length
10
200
590
400
1075
900
Do not use oxygen for pressure testing.
20
150
400
275
730
600
900
DANGER: Explosion hazard.
40
275
200
500
450
1040
650
75
190
150
360
325
750
475
100
160
300
275
630
400
975
Capacities shown are for a
total pressure drop of
0.3"W.C. For 0.5"W.C.
pressure drop, multiply
capacity shown by 1.3.
Propane capacities shown
are for a total pressure drop
of 0.5”W.C. For higher
permissible pressure drops,
consult your gas supplier.
Table 2: Schedule 40 NPT
Pipe-Capacity Chart
VIIMain Gas
Input Selection
VIIIInitial Start-
up /Adjustment
_____________________________________
Burners are approved for use with NATURAL gas or PROPANE gas and should be used only
with the gas specified on the rating plate.
o The gas input should be set at the heating rate determined by the building heat loss and/or
heating plant survey, but not exceeding the rated maximum input of the gas utilization
equipment or Economite burner.
_____________________________________
WARNING: Ignition is automatic. Make spark observations into combustion
chamber only with Main and Pilot Manual Shut-Off Valves closed. Confirm that gas
utilization equipment does not contain any accumulated gases. Purge as described in
step 3 below.
CAUTION: Cover plates, guards, and enclosures must be maintained in place
at all times except during maintenance and service.
1. Check the burner piping and valves for gas leaks by applying a weak liquid soap
solution to unions and joints with the gas supply on. Leakage will be indicated by the
appearance of soap bubbles. Locate and correct all gas leaks before proceeding.
WARNING: DO NOT USE OPEN FLAME.
2. Purging the air from the gas supply line at this step will expedite first light-off.
IMPORTANT: Purge outside the building. Do not purge into the gas utilization
equipment.
Page 8
Part 1
Part 1 Installation
Installation
Continued
VIIIInitial Start-
up /Adjustment
Continued
Natural Gas / Propane Gas Orifice Size and Pressure Settings
RE4850A
MBTU/HR
850
800
750
700
650
600
550
500
450*
400
280
Input
1
No Orifice
No Orifice
No Orifice
No Orifice
Orifice
Size
(Inches)
0.688
0.688
0.563
0.500
0.500
0.422
0.358
Natural Gas
Letter
Stamp
-
-
I
I
H
G
G
F
J
-
Manifold
Pressure
("W.C)
3.5
3.1
2.7
2.8
2.4
2.8
3.15
2.4
2.6
4.3
0.4
Orifice
Size
(Inches)
0.688
0.563
0.500
0.422
0.422
0.358
0.358
0.358
0.358
0.290
0.688
Propane Gas
Manifold
Pressure
Letter
Stamp
I
H
G
F
F
J
J
J
J
B
I
("W.C)
2.4
2.5
2.7
2.8
2.4
3.9
3.3
2.7
2.2
3.3
0.15
RE4400
400
350
300
250*
200
132
DATA FOR TABLES IS APPROXIMATE AND BASED ON “0" OVERFIRE PRESSURE AT SEA LEVEL
1.
Adjust the main regulator to vary the manifold gas pressure and burner input within the range shown.
Do not exceed pressure as listed in Table 3, under any circumstances. Use combustion readings (CO
or O2) and a flow meter to determine exact inputs.
Orifice Size and approximate manifold gas pressure setting: as shipped. Air shutters are set at full
*
open NOTE: For LP Conversion kit contact the factory
No Orifice
No Orifice
No Orifice
0.358
0.290
No Orifice
Table 3: Capacity and Preliminary Gas Settings
-
-
-
J
B
-
4.3
3.3
2.4
2.9
2.8
0.6
0.358
0.290
0.261
0.219
0.219
0.358
J
2.8
3.6
B
C
3.1
E
3.2
2.1
E
J
0.3
8
3. To purge the gas utilization equipment and chimney of any accumulated gases, turn
main Manual Gas Cock OFF, close Pilot Manual Shut-Off Valve, turn burner power on,
and set operating control to ON or thermostat to call for heat. Let the blower run long
enough to accomplish four combustion chamber volume air changes, but not less than
five minutes.
CAUTION:Make sure that the capacity range of the burner, manifold pressure,
and the preliminary combustion air shutter setting are suitable for capacity rating of
the gas utilization equipment. Refer to Section VII and Table 3.
4. RESET the Primary Safety Control by setting the operating control to OFF or the
thermostat below room temperature for at least 30 seconds. See Section XII.
5. Confirm that Main and Pilot Manual Shut-Off Valves are open. Turn main Manual Gas
Cock ON.
6. Turn operating control to ON or set thermostat above room temperature. After the pre-
purge is complete, the pilot should ignite. Whenever the burner pilot fails to light during
the ignition trial, or if the flame is lost during the burner run and is not reestablished within
15 seconds after the pre-purge, the Primary Safety Control will shut off the Automatic
Safety Shut-off Valves and LOCK OUT. To RESET the Primary Safety Control for
restart, de-energize the Primary Safety Control by setting the operating control to OFF
or thermostat below room temperature for at least 30 seconds. If burner still fails to light,
turn it off and repeat from step 4 above. Then if necessary, refer to the TROUBLE CHART to isolate the problem.
Page 9
9
Part 2 Service
Part 1
Installation
Continued
VIIIInitial Start-
up /Adjustment
Continued
WARNING: Repeated unsuccessful attempts to light will result in accumulated
gases in gas utilization equipment and chimney. To prevent these gases from
reaching an explosive level, periodically purge the gas utilization equipment and
chimney as described in step 3 above.
7. To make a preliminary setting of the burner input, determine the manifold gas pressure
required from Table 3 and adjust the Main Gas Pressure Regulator accordingly. See
Section XI.
8. To determine the firing rate for NATURAL gas, accurately time test dial for the number
of seconds for one revolution and use the following formula. All other gas utilization
equipment must be off.
Then divide by 1,000 for MBH value.
3600 x test dial size x BTU value
No. of seconds for one rev. test dial
= BTU/Hr.
Part 2
Service
Example:3600 x 1 x 1000
10
9. Check the operation of the burner; start and stop it several times with the thermostat
or operating control.
10. With the burner running, check the operation of all limit and associated controls.
11. Perform the following final adjustments for combustion and flue gas temperature. Take the
flue gas samples and temperature immediately ahead of the draft control.
A. The flue gas temperature should be above 325°F but not exceeding 550°F.
Excessive flue gas temperatures will result in low efficiencies. Low flue gas
temperature may cause excessive condensation. Reset gas input, if necessary, to
adjust stack temperature.
B. Make the final setting of the combustion air shutter by checking the flue gases
with an ORSAT or similar combustion testing instrument. The carbon monoxide
content should conform to local codes, or in their absence, to the level specified
in the United States or Canadian Standard referenced on the front cover of this
manual; and the carbon dioxide content should be approximately 9.5% for
NATURAL or 12% for propane , or within the limits prescribed by local codes.
12. Check the draft control to make sure there is no spillage of flue products into the room.
13. FILL OUT THE INSTALLATION ADJUSTMENT DATA TAG and affix to the burner or
gas utilization equipment.
NOTE: For subsequent normal starting and shut off procedure,
refer to CONSUMER INSTRUCTIONS, located in part 3 of this
manual, or to the instruction plate mounted on the burner.
_____________________________________
DANGER: Do not tamper with the unit or controls. If trouble occurs contact
the installing contractor, service agency, or fuel supplier. See front cover.
DANGER: Be sure that the main and pilot manual Shut-Off Valves are closed
and the burner power supply is turned off before removing any parts for service.
CAUTION: Cover plates, guards, and enclosures must be maintained in
place at all times except during maintenance and service.
= 360,000 BTU/HR = 360 MBH
IXPilot
_____________________________________
The pilot is of the premix, blast type. The full force of blower air is brought into the mixing
tube where the proper amount of gas is added through the pilot orifice. This mixture is
discharged through the pilot. The mixture provides the flame that contacts the flame sensing
rod and also ignites the main gas.
Gas Orifice
Model
RE 4850A
RE 4400
Diameter
#54
Wire Drill
0.055"
0.055"
Table 4: Pilot Specifications
Approx.
Capacity
BTU/Hr.
6000
6000
Pilot Gas Pressure
Natural Propane
3.0”
to
4.5”
W.C.
2.5”
to
3.5”
W.C.
Page 10
Part 2
Part 2 Service
Service
Continued
IXPilot
Continued
10
Figure 6A: General Assembly for RE4400
CAUTION: Do not indiscriminately increase pilot orifice size. Pilot troubles are
rarely cured in this manner and new troubles may be created.
o Under normal conditions, with a slight negative pressure in the combustion chamber, pilot
operating pressures should be set as indicated in Table 4.
o Some conditions which may require a change from the normal setting include: extremely
long tubing connections between the regulator and pilot solenoid, high negative or positive
combustion chamber pressure, actual air shutter setting and altitude extremes.
o Do not subject the pilot to an inlet pressure over 14.0"W.C. See Section VI PIPING for
high pressure gas.
o To adjust outlet pressure, remove the seal cap for access to the adjusting screw. Turning
the screw clockwise will increase outlet pressure, counter clockwise will decrease outlet
pressure.
o The spark rod is welded to a round 1/2” retention plate. The 1/2” retention plate is centered
in the 3/8” Tee pilot and is positioned so the high tension voltage will arc to the inside of the
3/8” Tee pilot. (See Figures 6A & 6B).
o The flame sensing rod must be positioned as shown in Figures 6A & 6B so that the primary
safety control will detect a proper flame.
o Both the spark and flame rods are current carrying conductors and, along with their
connecting wires, must be kept free of contact with conductive metal parts of the burner. Rod
insulators and wire insulators should be clean, dry and free of cracks.
o Rods are made from heat resistant alloys and can be expected to have a long service life.
They should be routinely inspected, however, for corrosion or loss of metal.
o The pilot air tubing must be kept free of kinks or inside obstructions and must be positioned
per Figures 6A & 6B, otherwise air flow could be reduced and adversely affect the pilot flame.
Page 11
11
Part 2
Part 2 Service
Service
Continued
IXPilot
Continued
XMotor Blower
Interlock
Figure 6B: General Assembly for RE4850A
_____________________________________
CAUTION: BEFORE SERVICING, mark with a scribe line or measure opening
of air controlling shutter, so that it can be reset to its original position following
servicing.
o Cleaning of the blower wheel is usually the only service required. Need for cleaning is
indicated if the character of the flame indicates a deficiency of air. Motor cooling air vents (if
present) should also be cleaned at this time.
o The motor and wheel are removed as an assembly. Disconnect the motor wires from the
motor terminal strip. Disconnect the motor conduit from the motor and remove the mounting
bolts.
o The burner is equipped with a diaphragm type air pressure switch so as to prevent the
burner from firing if the blower wheel is not running at its operating speed. When the motor
is off there is no air pressure present to activate the pressure switch and in turn there is no
power flow to the primary safety control.
o To make a specific test of the interlock circuit:
1. Turn burner power OFF.
2. Turn Manual Gas Cock OFF.
3. Disconnect the motor wire from the terminal strip to keep the motor off.
4. Turn burner power ON and set the operating control to ON or thermostat to call for
heat. Verify there is 120VAC line voltage by using a multimeter.
A. No voltage: Interlock circuit OK.
B. Voltage present: check that the switch is wired properly or check switch
operation. Replace if switch tests bad.
Page 12
Part 2 Service
Part 2
Service
Continued
XMotor Blower
Interlock
Continued
Figure 7: Motor / Blower Assembly
_____________________________________
XIValve Train
XII Style of
Firing
DIAPHRAGM & SOLENOID GAS SAFETY VALVES
(Main and Redundant Main; Standard Construction.)
When the solenoid valve operator is electrically energized the plungers lift the valve disk
off the valve seats, allowing gas to flow. When the current on the solenoid valve is broken
the valves close. They will normally require no service. However, dirt or foreign matter on
the valve seats could cause leakage. If leakage is detected or if the operator malfunctions
replace the entire valve. After replacement check for leakage. If the valve is removed from
the piping do not use the operator assembly as a lever to turn valve. Apply wrench on the
valve body flat adjacent to pipe being removed.
OPTIONAL MOTORIZED MAIN AUTOMATIC VALVE
(Employed with Redundant Solenoid Valve.)
o Motorized Main On-Off, 2-Step, and Full Modulating Valves, are available on special
order. The redundant and solenoid valve may be omitted if the motorized valve includes
optional "Proof of Closure Switch".
o When the actuator is energized, hydraulic fluid is pumped from a reservoir to a metal
bellows. The bellows transfers the resulting pressure through the drive stem to open the
valve. A separate spring return drive arm operates the blower shutter.
o For general service, the valve should be checked for operation. The valve actuator may
be removed from the valve body, however, do not disassemble actuator; if malfunction
occurs, replace entire actuator assembly. The valve body is also not field reparable. If
leakage is detected the entire valve body must be replaced.
_____________________________________
12
_____________________________________
Page 13
13
Part 2 Service
Part 2
Service
Continued
XIII Primary
Safety Control
WARNING: Explosion hazard. Do not use any electronic device if it gets
wet. It can malfunction and cause serious injury or death. Replace any device that
has been wet.
o The standard RE4850A and RE4400 burners are equipped with a Honeywell RM7895
microprocessor based burner control, employing a flame rectification system of flame
detection. Burner construction for special codes and/or insurance requirements such as
Factory Mutual or Industrial Risk Insurers (IRI) may require alternate controls. A safe
start and run control sequence is provided with instantaneous response to presence or loss
of flame signal. Flame failure response time is 3-seconds.; Pilot Flame Establishing Period
(PFEP) is field selectable from 4 or 10-seconds. The RM7895 features a pre-purge time
(30-seconds for ON-OFF, 90-seconds for 2-Step or Modulating burners), and a plug-in
amplifier. An airflow circuit is also field selectable to allow either lockout or recycle upon
loss of airflow. Five LED’s (light emitting diodes) are provided to display sequence
information. Refer to the Honeywell RM7895 literature for detailed operating information,
configuration requirements, testing, and service.
INITIATE ("POWER" LED is lit).
o The RM7895 enters the INITIATE sequence when it is powered. The INITIATE
sequence lasts for ten seconds unless the voltage or frequency tolerances are not met
(refer to Honeywell RM7895 literature for criteria). When tolerances are met, the INITIATE
sequence will restart. If the conditions not corrected and the hold condition exists for four
minutes, the RM7895 will lock-out. Causes for hold conditions in the INITIATEsequence
are in the Honeywell RM7895 literature.
STANDBY ("POWER" LED is lit).
o The RM7895 is idle in this state of sequencing. When the burner switch, limits, operating
limit controls, and all microprocessor monitored circuits are in the correct state for the
RM7895 to continue, sequencing will advance to PREPURGE.
PREPURGE ("POWER" LED is lit).
o The RM7895 in this application features a prepurge time of 30-seconds for ON-OFF, 90seconds for 2-Step or Modulating burners.
o Once the STANDBY sequence has a "CALL FOR HEAT " input, normal start-up
prepurge will be initiated.
A. The blower motor is powered to start the prepurge sequence.
B. The airflow interlock switch must close in ten seconds of prepurge or within the
specified purge card timing. Otherwise a recycle to the beginning of prepurge
or lockout will occur, depending on how the airflow switch selectable jumper is
configured. Refer to Honeywell RM7895 literature for configuration requirements.
IGNITION TRIAL
1. PILOT FLAME ESTABLISHING PERIOD (PFEP)
A. The pilot valve and spark generator are energized.
B. Flame must be proven by the end of the 4 or 10-second PFEP to allow the
sequence to continue. If flame is not proven by the end of PFEP, a safety shutdown
occurs.
2. MAIN FLAME ESTABLISHING PERIOD (MFEP)
o After the ignition trials, and with the presence of flame, the main valve is energized.
("MAIN" LED will be lit.) If a flame-out occurs, the RM7895 will lockout or recycle within 3seconds, depending on "jumper" configuration. Refer to Honeywell literature for proper
configuration.
RUN
o The RM7895 is now in RUN mode and will remain in run mode until the controller input
opens, indicating that the call for heat has been satisfied or a limit has opened. Once this
occurs the RM7895 will sequence back to the STANDBY mode.Notes: 1. During STANDBY and during RM7895 sequencing the "POWER" LED will
blink every four seconds. This is normal.
2. The "ALARM" LED will be lit in the event of any flame failure.
3. To maintain proper operation of this device in MUST be electrically grounded.
Refer to Honeywell RM7895 literature for criteria.
XIII Special
Equipment (OEM
Version)
_____________________________________
Special equipment, either factory or field installed, can cause variations in the procedures
and descriptions given in this manual. Generally, any burner ordered with special factory
installed equipment will be supplied with the appropriate wiring diagram and related
instruction manuals from the special equipment manufacturer. Consult these manuals to
identify any differences in construction, operation, and testing. Field installed special
equipment is the responsibility of the installing contractor.
Page 14
Part 3 Maintenance
Part 3
Maintenance
Consumer Instructions
CONSUMER INSTRUCTIONS
MAINTENANCE
o Keep the area around the burner clear and free of combustible material, gasoline or other
flammable liquids or vapors. Do not obstruct burner air openings or ventilation grills for
combustion air.
o The motor features permanently lubricated ball bearings and requires no maintenance.
WARNING: If any flame is observed when the burner is on standby, or if the
ignition spark or valve operator is heard to come on before the motor reaches
operating speed, immediately turn off the manual gas control and burner power. A
dangerous condition has developed and must be corrected. CONTACT A QUALIFIED
SERVICE TECHNICIAN FOR CLEANING, READJUSTMENT OR REPAIR.
o Check that the pilot ignition spark does not come on before the motor reaches operating
speed. If it does, the air switch is defective and must be replaced. (See Section X, Motor /
Blower Interlock).
LIGHTING INSTRUCTIONS
1. SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM
TEMPERATURE.
2. TURN MANUAL GAS COCK ON.
3. TURN BURNER POWER ON.
4. SET OPERATING CONTROL TO ON OR THERMOSTAT TO CALL FOR
HEAT.
5. IF THE PILOT FLAME IS NOT PROVEN WITHIN 15 SECONDS, AFTER THE
PRE-PURGE, THE PRIMARY SAFETY CONTROL WILL SHUT OFF THE
AUTOMATIC SAFETY SHUT-OFF VALVES AND LOCK OUT. IF THE PROOF
OF FLAME IS LOST DURING BURNER RUN AND THE PILOT IS NOT RE-
ESTABLISHED WITHIN15 SECONDS AFTER THE PRE-PURGE, THE
PRIMARY SAFETY CONTROL WILL SHUT OFF THE AUTOMATIC SAFETY
SHUT-OFF VALVES AND LOCKOUT. TO RESET FOR RESTART, DE-
ENERGIZE THE CONTROL BY SETTING THE OPERATING CONTROL TO
OFF OR THERMOSTAT BELOW ROOM TEMPERATURE FOR AT LEAST 60
SECONDS.
6. REPEAT STEP 4 FOR RESTART.
TO SHUT OFF
1. TURN MANUAL GAS COCK OFF.
2. TURN BURNER POWER OFF.
SHOULD OVERHEATING OF THE APPLIANCE OCCUR
1. Shut off the manual gas control to the appliance.
2. Do not shut off the electrical supply power to the blower.
14
Page 15
15
Trouble Chart
Trouble Chart
TROUBLE CHART
Make sure the thermostat and operating controls are calling for heat.
CAUTION: If a test indicates an electrical component may be defective,
before replacing it, make sure that its associated wiring is not at fault.
ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED BELOW.
IMotor Will
Not Run or Motor
Runs in Repeated
Cycles
II Motor Runs
Continuously, But
No Flame
III Pilot Lights,
No Main Flame
I.MOTOR WILL NOT RUN
A. Confirm 120V between strip terminals L1 and L2 and verify the circuit polarity and
electrical ground between strip terminal L1 and burner Ground.
B. Check for 120V between strip terminals L1 and L2.
1. No voltage, open circuit in operating controls.
2. Voltage present, motor is defective.
II.MOTOR RUNS CONTINUOUSLY, PILOT WILL NOT LIGHT
A. Confirm that ALL Main Manual Shut-Off Valves are in the ON position.
B. After the pre-purge, if the pilot flame is not proven within the pilot flame
re-establishing period, or if the proof of flame is lost during the burner run and the
pilot is not re-established after the pre-purge, the Primary Safety Control will lock
out. To reset the control for restart, re-set alarm button.
C. Clogged pilot orifice.
D. Pilot regulator mis-adjusted or defective.
E. Defective spark electrode or primary safety control.
F. Defective high tension wire.
G. Wrong pilot orifice.
H. Defective pilot valve.
I.Pilot air tube clogged.
J.Incorrect spark gap.
K. Pilot regulator vent clogged.
L. Defective blower air switch.
M. Slow motor.
III. PILOT LIGHTS, NO MAIN FLAME
A. Poor pilot flame adjustment.
B. Clogged pilot air tube.
C. Defective flame sensing rod or wire.
D. Flame sensing rod mis-located.
E. Defective primary safety control.
F. Defective main gas valve.
G. Low gas pressure.
H. Grossly mis-adjusted main gas and air.
Page 16
16
Midco International Inc.
tel 773.604.8700 fax 773.604.4070 web www.midco-intl.com email sales@midco-intl.com
4140 West Victoria Street * Chicago, Illinois 606 46303p
8471 20
Printed in USA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.