R7824, R7847, R7848, R7849,
R7851, R7852, R7861, R7886 Amplifiers
for 7800 SERIES and R7140 Relay Modules
PRODUCT DATA
APPLICATION
The R7824C Rectification Flame Amplifier is a solid state
plug-in amplifier that responds to a rectified signal from a
C7024E,F Self-Check Ultraviolet Flame Detector to indicate
the presence of flame when used with the 24 Vdc RM7824
Relay Module.
The R7847A,B Rectification Flame Amplifiers are solid state
plug-in amplifiers that respond to a rectified signal from a
rectification type flame detector to indicate the presence of
flame when used with 7800 SERIES and R7140 Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a
solid state plug-in amplifier that responds to a rectified signal
from a C7012E,F Self-Check Ultraviolet Flame Detector to
indicate the presence of flame when used with 7800 SERIES
and R7140 Relay Modules. This is not European Community
(CE) approved for EC7810, EC7820, EC/RM7830 or EC/
RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plugin amplifiers that respond to an infrared signal from a C7015
Infrared Flame Detector to indicate the presence of flame
when used with 7800 SERIES and R7140 Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state
plug-in amplifiers that respond to an ultraviolet signal from a
C7027, C7035 or C7044 Ultraviolet Flame Detector to indicate
the presence of flame when used with 7800 SERIES and
R7140 Relay Modules.
The R7851B Optical Flame Amplifiers are solid state plug-in
amplifiers that respond to optical signals from C7927 and C7962
Flame Detectors to indicate the presence of flame when used
with 7800 SERIES and R7140 Relay Modules.
The R7852A,B Infrared Flame Amplifiers are solid state plugin amplifiers that respond to an infrared signal from a C7915
Infrared Flame Detector to indicate the presence of flame
when used with 7800 SERIES and R7140 Relay Modules.
The R7851C Dynamic Self-Check Optical Flame Amplifier is a
solid state plug-in amplifier that responds to ultraviolet signals
from C7961E Dynamic Shutter-Check ultraviolet flame
detectors to indicate the presence of flame when used with
7800 SERIES and R7140 Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid
state plug-in amplifier that responds to an ultraviolet signal
from a C7061 Self-Check Ultraviolet Flame Detector to
indicate the presence of flame when used with 7800 SERIES
and R7140 Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a
solid state plug-in amplifier that responds to a pulsed direct
current signal from a C7076A,C Ultraviolet Flame Detector
with adjustable sensitivity to indicate the presence of flame
when used with 7800 SERIES and R7140 Relay Modules.
Contents
Application ........................................................................ 1
Features ........................................................................... 2
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 5
Checkout .......................................................................... 7
65-0109-11
R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES
FEATURES
• Flame failure response time of 0.8 or 1 second; or 2.0
or 3.0 seconds, depending on the amplifier and relay
module selected. See Table 1.
• Plug-in to 7800 SERIES and R7140 Relay Module
through printed circuit board edge connector keyed
for proper orientation.
• Flame signal test jacks measure amplifier flame signal
voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:
— Green—rectification. Red—infrared.
— Purple—ultraviolet. Blue—pulsed rectification.
— White—optical.
• R7847B, R7848B, R7849B Dynamic Ampli-Check®
circuitry tests all flame amplifier components 12 times
per minute. The 7800 SERIES and R7140 Relay Module
locks out on safety shutdown with amplifier failure.
• R7824C Dynamic Self-Check Rectification Amplifier,
R7851C Dynamic Self-Check Optical Flame Amplifier,
R7861 Self-Check Ultraviolet Flame Amplifier and
R7886A Dynamic Self-Check Ultraviolet Amplifier test
the detectors and all electronic components in the
flame detection system 12 times per minute. The 7800
SERIES and R7140 Relay Module locks out on safety
shutdown with flame detection system failure.
NOTE: R7824C, Series 2 or greater, pulse shutter when sig-
nal of 1.5 Vac is sensed. Display readings of 0.7 to
2.4 Vdc are common.
Infrared:
R7848A,B for use with C7015 Infrared (lead sulfide)
Detector.
R7852A,B for use with C7915 Infrared (lead sulfide)
Detector.
Ultraviolet:
R7849A,B for use with C7027/C7035/C7044 Minipeeper
Ultraviolet Detectors.
R7861A for use with C7061A Ultraviolet Detector.
R7886A for use with C7076A,D Ultraviolet Detectors with
adjustable sensitivity.
Optical:
R7851B for use with C7927 and C7962 Flame Detectors.
R7851C for use with C7961E Flame Detectors.
NOTE: R7824C, Series 2 or greater, pulse shutter when sig-
nal of 1.5 Vac is sensed. Display readings of 0.7 to
2.4 Vdc are common.
Flame Failure Response Time: See Table 1.
Flame Signal (Volts dc):
Minimum Acceptable: 1.25 Vdc.
Flame Signal Voltage Range (displayed on Keyboard Display
Module or measured with a 1M ohm/volt meter plugged
into amplifier test jacks): 0.0 to 5.0 Vdc.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C).
Storage: -40°F to 150°F (-40°C to 65°C).
Humidity: Operating 85% rh continuous, noncondensing.
Vibration: Continuous 0.5G environment.
Weight: 2.5 oz (71g), unpacked.
Dimensions: See Fig. 1.
SPECIFICATIONS
Approvals:
Models:
Flame Detection Systems (see Table 2):
Rectification:
R7824C for use with C7024E,F Solid State Ultraviolet
Detectors.
R7847A,B for use with flame rods or C7012A,C Solid State
Ultraviolet Detectors.
Underwriters Laboratories Inc. Listed: File no. MP268, Guide
no. MCCZZ: R7847A, R7847B, R7847C, R7861A,
R7886A, R7848A, R7848B, R7849A, R7849B, R7851B,
R7851C.
Underwriters Laboratories Inc. Component Recognized: File
no. MP268, Guide no. MCCZZ: R7824C.
Canadian Standards Association Certified: LR95329-3.
Factory Mutual Approved: Report J.I.1V9A0.AF. (R7851B,
Report Number 3011020, June 16 2003, R7851C Pending.)
Industrial Risk Insurers: Acceptable.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—11 2
R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES
Table 1. Relay Module Flame Failure
Response Time (FFRT).
Flame Failure Response
S
–+
Time (FFRT) in seconds
Relay Module
EC7810, EC7820, EC/RM7830,
EC/RM7850
EC/RM7823, EC/RM7885, EC/
0.8 or 1 2.0 or 3.0
1.0 2.0
0.8 3.0
FLAME AMPLIFIER
(76)
3
RM7890, RM7895, RM7896,
RM7897, RM7898, RM7888,
RM7838, RM7800, RM7840,
R7140
RM7824 N/A 3.0
3-9/16 (91)
3/8 (9)
7/8
(23)
M11460
Fig. 1. Flame amplifier dimensions in in. (mm).
NOTE: EN298 Approved: When these amplifiers are used
with an EC7810, EC7820, EC/RM7830, or
EC/RM7850 Relay Module.
Accessories:
Flame Simulators:
Rectification: 123514A.
Ultraviolet: 203659.
Flame Detectors (ordered separately): select from Table 2.
3 65-0109—11