Grieve Corporation Q652B Installation Manual

Q652B
Solid State Ignitor Spark Generator
PRODUCT DATA
• Mounts in the same space used by conventional ignition transformer.
• Withstands 90% relative humidity at 104°F (40°C).
• Weighs 1 pound (0.42 kilogram) versus up to 8-1/2 pounds (3.9 kilograms) for standard transformers.
• Meets Underwriters Laboratories Inc. (UL) requirements for radio frequency interference (RFI).

SPECIFICATIONS

APPLICATION

FEATURES

• Ignites interrupted gas pilots with ignition electrodes spacings between 0.029 to 0.125 inches (0.7 to 3.2 mm).
• Q652B1006 is used for gas applications.
• Q652B1006 has 14.0 kV output peak voltage for reliable light-off.
• Recommended for interrupted ignition applications only.
IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not match the listed specifications exactly. Also, this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed.
Model: Q652B1006 Single high voltage electrode for gas,
with “Rajah” and screw connectors.
Electrical Ratings:
Voltage and Frequency: 120 Vac (+10%, -15%), 60 Hz. Output peak voltage at 21 kHz: 14.0 kV. Secondary open circuit voltage: 10 kV equivalent RMS. Power Consumption:
40 Watts maximum.
Interrupted Ignition only:
Duty cycle: 20%.
45 seconds on. 180 seconds off.
Spark Characteristics:
Spark Gap: 0.029 to 0.125 in. (0.7 to 3.2 mm). Firing Rate: 20,000 sparks per second.
Contents
® U.S. Registered Trademark Copyright © 2003 Honeywell International Inc. All Rights Reserved
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 1
Ordering Information ........................................................ 2
Installation ........................................................................ 2
Operation .......................................................................... 3
Checkout .......................................................................... 4
63-2159-5
Q652B SOLID STATE IGNITOR SPARK GENERATOR
0
1
HIGH VOLTAGE
6
Energy Discharge: 1 millijoule per spark. Discharge TIme: 50 microseconds per spark. Maximum air velocity in gap is 55 ft. (16.76 m) per sec.
Ambient Temperature Range: 14°F to 113°F (-10°C to
+45°C).
Maximum Ambient Humidity: 90% RH at 95°F (40°C).
Weight: 0.925 lb. (0.42 kg).
Dimensions: See Fig. 1.
LEAD WIRES FOR 20V CONNECTION,
19 INCHES LONG
3-3/8 (84)
3-21/32 (89)
4-15/16 (102)
Approvals:
Underwriters Laboratories Inc. Component Recognized: File
No. MH14381 (Gas).
CSA File No. LA66894.
Recommended Ignition Cable:
32004766-001 24 in. (610 mm) Ignition Cable Assembly. 32004766-002 120 in. (3.05 m) Ignition Cable Assembly. 32004766-003 Ignition Cable (per foot, specify required
length). 32004766-004 60 in. (1.52 m) Ignition Cable Assembly. Cable should be rated for 25 kV at 482°F (250°C).
ELECTRODE
2-15/1
(78)
2-25/32
(71)
2-9/32 (58)2-3/4 (74)
M2087
Fig. 1. Q652B dimensions in in. (mm).

INSTALLATION

WARNING
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced, flame safeguard control technician.
4. After installation is complete, check out product operation as provided in these instructions.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Electrical Shock Hazard. Can cause serious injury, death or property damage.
Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be required.
IMPORTANT
1. All wiring must comply with applicable local electrical codes, ordinances and regulations.
2. Voltage and frequency of the power supply connected to this device must be 120 Vac, 60 Hz.
3. Make sure the Q652B is properly grounded.
63-2159—5 2
Loading...
+ 2 hidden pages