17
Item
Ralay output type
AC type
100 to 240 V AC
50/60 Hz common
Max. 10 V A
5 A, 250 V AC
9.999 s, 99.99 s, 999.9 s, 9999 s, 99 min 59 s, 999.9 min, 99 h 59 min, 999.9 h (selected by DIP switch)
Addition (UP)/Subtraction (DOWN)
(2 directions selectable by DIP switch)
A (Power ON delay), A2 (Power ON delay), B (Signal ON delay), C (Signal OFF delay), D (Pulse one-shot),
E (Self-hold), F (Flicker), G (Totalizing) (Selectable by DIP switch)
Min. input signal width: 1 ms, 20 ms (2 directions by selected by DIP switch)
Min. input signal width: 20 ms
Open collector input Input impedance: Max. 1 k
Ω; Residual voltage: Max. 2 V
Open impedance: 100kΩ or less, Max. energized voltage: 40V DC
7-segment LCD, Elapsed value (backlight red LED), Setting value (backlight yellow LED)
EE-PROM (Min. 10
5
overwriting)
± (0.005 % + 50 ms) in case of power on start
± (0.005 % + 20 ms) in case of reset or input signal start
(at fixed power off time)
100 ms
Timed-out 1 Form C
100 mΩ (at 1 A6 V DC)
Ag alloy/Au flash
2.0 × 10
7
ope. (Except for switch operation parts)
1.0 × 105ope. (At rated control voltage)
85 to 110 % of rated operating voltage
2,000 Vrms for 1 min: Between live and dead metal parts
2,000 Vrms for 1 min: Between input and output
2,000 Vrms for 1 min: Between live and dead metal parts
2,000 Vrms for 1 min: Between input and output
1,000 Vrms for 1 min: Between contacts
Between live and dead metal parts
Min. 100 MΩ: Between input and output
Between contacts
Min. 100 MΩ: Between live and dead metal parts
Between input and output
Max. 0.5 s
10 to 55 Hz: 1 cycle/min single amplitude of 0.35 mm .014 inch (10 min on 3 axes)
10 to 55 Hz: 1 cycle/min single amplitude of 0.75 mm .030 inch (1 h on 3 axes)
Timed-out 1 Form A(Open collector)
—
—
—
1.0 × 10
7
ope. (At rated control voltage)
12 to 24 V DC
—
Max. 3 W
100 to 240 V AC
50/60 Hz common
Max. 10 V A
100 mA, 30 V DC
12 to 24 V DC
—
Max. 3 W
DC type
Transistor output type
AC type DC type
Rating
Time
accuracy
(max.)
Contact
Life
Electrical
Mechanical
Operating
conditions
Operating voltage
Frequency
Power consumption
Control capacity (resistive)
Time range
Time counting direction
Operation mode
Signal, Reset, Stop input
Lock input
Input signal
Indication
Power failure memory
method
Operating time fluctuation
Temperature error
Voltage error
Setting error
Power off time change
error
Contact arrangement
Initial contact resistance
Contact material
Mechanical
Electrical
Operating voltage range
Initial breakdown voltage
Initial insulation resistance
(At 500 V DC)
Operating voltage reset
time
Max. 65° C (under the flow of nominal operating current at nominal voltage)
Temperature rise
Functional
Destructive
Vibration
resistance
Min. 98 m 321.522 ft./s
2
(4 times on 3 axes)
Min. 294 m 964.567 ft./s
2
(5 times on 3 axes)
–10° C to 55° C +14° F to +131° F
Max. 85 % RH
860 to 1,060 h Pa
—
11-pin/screw terminal
IP66 (front panel with rubber gasket)
20 % or less — 20 % or less
Functional
Destructive
Ambient temperature
Ambient humidity
Air pressure
Ripple rate
Connection
Protective construction
Shock
resistance
Specifications