Grieve Corporation F4P Installation Manual

0600-0032-0013 Rev D
January 2003 $15.00
User ’s Manual
Series F4P
96mm x 96mm Process Controller (1/4 DIN)
1241 Bundy Boulevard, Winona, Minnesota USA
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
English
Registered Company
Winona, Minnesota USA

Safety Information

We use note, caution and warning symbols throughout this book to draw your attention to important operational and safety information.
A “NOTE” marks a short message to alert you to an important detail. A “CAUTION” safety alert appears with information that is important for protecting
your equipment and performance. Be especially careful to read and follow all cautions that apply to your application.
A“WARNING” safety alert appears with information that is important for protecting you, others and equipment from damage. Pay very close attention to all warnings that apply to your application.
The safety alert symbol, ç (an exclamation point in a triangle) precedes a general CAUTION or WARNING statement.
The electrical hazard symbol, Ó (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.
Technical Assistance
If you encounter a problem with your Watlow controller, review your configuration information to verify that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem persists after checking the configuration of the controller, you can get technical assistance from your local Watlow representative (see back cover), or in the U.S., dial +1 (507) 494-5656 between 7 a.m. and 5 p.m., Central Standard Time (CST). Ask for for an Applications Engineer. Please have the following information available when calling:
• Complete model number • All configuration information
• User’s Manual • Diagnostic menu readings
Your Comments
We welcome your comments or suggestions on this user’s manual. Please send them to: Technical Writer, Watlow Winona, 1241 Bundy Blvd., P.O. Box 5580, Winona, Minnesota, USA 55987-5580; telephone: +1 (507) 454-5300; fax: +1 (507) 452-4507.
© Copyright 2003 by Watlow Winona, Inc. All rights reserved. (2328)
ç
CAUTION or
WARNING
Ó
Electrical
Shock Hazard
CAUTION or
WARNING
Watlow Series F4P Table of Contents i
Operating the Controller
Chapter 1: Introduction . . . . . . . . . . . . . . . . . 1.1
Setup Steps . . . . . . . . . . . . . . . . . . . . . . . .1.2
Chapter 2: Operating from the Front Panel . .2.1
Keys, Displays and Lights . . . . . . . . . . . . .2.2
Guided Programming . . . . . . . . . . . . . . . .2.3
Custom Main Page . . . . . . . . . . . . . . . . . .2.3
Auto and Manual Operation . . . . . . . . . . .2.3
Troubleshooting, Alarms and Errors . . . . .2.4
Programming the Controller
Chapter 3: Operations Page . . . . . . . . . . . . . .3.1
Alarm Set Points . . . . . . . . . . . . . . . . . . . .3.1
To Clear an Alarm or Error . . . . . . . . . . . .3.1
Autotune PID . . . . . . . . . . . . . . . . . . . . . . .3.2
Edit PID . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2
Multiple PID Sets . . . . . . . . . . . . . . . . . . . .3.3
Cascade . . . . . . . . . . . . . . . . . . . . . . . . . .3.3
Chapter 4: Setup Page . . . . . . . . . . . . . . . . . .4.1
Parameter Setup Order . . . . . . . . . . . . . . .4.1
Customizing the Main Page . . . . . . . . . . .4.2
Static Messages . . . . . . . . . . . . . . . . . . . .4.2
Chapter 5: Factory Page . . . . . . . . . . . . . . . .5.1
Security . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . .5.3
Calibration . . . . . . . . . . . . . . . . . . . . . . . . .5.3
Chapter 6: Parameters . . . . . . . . . . . . . . . . . .6.1
Pages, Menus and Parameters . . . . . . . . .6.1
Main Page . . . . . . . . . . . . . . . . . . . . . . . . .6.2
Operations Page Parameter Table . . . . . .6.4
Setup Page Parameter Table . . . . . . . . . .6.11
Factory Page Parameter Table . . . . . . . . .6.26
Chapter 7: Features . . . . . . . . . . . . . . . . . . . .7.1
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.2
Control Methods . . . . . . . . . . . . . . . . . . . .7.5
Other Features . . . . . . . . . . . . . . . . . . . . .7.9
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.10
Advanced Features . . . . . . . . . . . . . . . . . .7.12
Features in Enhanced Series F4P Controller
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.15
Installation and Wiring
Chapter 8: Installation and Wiring . . . . . . . . .8.1
Wiring the F4P Controller . . . . . . . . . . . . .8.5
Communications
Chapter 9: Communications . . . . . . . . . . . . . .9.1
Exception Responses . . . . . . . . . . . . . . . .9.1
Modbus Registers (Alphabetical) . . . . . . .9.2
Modbus Registers (Numerical) . . . . . . . . .9.11
Appendix
Specifications . . . . . . . . . . . . . . . . . . . . . .A.2
Ordering Information . . . . . . . . . . . . . . . . .A.3
Declaration of Conformity . . . . . . . . . . . . .A.4
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . .A.5
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A.8
Software Map . . . . . . . . . . . . . . . . . . . . . .A.13
About Watlow and Warranty Information
. . . . . . . . . . . . . . . . . . . . . . Inside Back Cover

Series F4P: Table of Contents

T
A downloadable electronic copy of this user manual is available free of charge through Watlow's web site: http://www.watlow.com/literature/prodtechinfo
ii Table of Contents Watlow Series F4P
Notes
Watlow Series F4P Introduction 1.1
1

Chapter One: Introduction

Inputs and Outputs
Figure 1.1 — Series F4P Inputs and Outputs (Standard, 1 input, F4P _ - _ _ AA - _ _ _ _; and Enhanced, 3 inputs, F4P _ ­_ _ AB - _ _ _ _ ).
1B
1A
Watlow’s Series F4P, 96mm by 96mm (1/4 DIN) Temperature/Process controllers are easy to set up, pro­gram and operate in the most demanding applications. The F4P Temperature/Process controller includes:
• four-line, high resolution LCD display;
• guided setup software;
• context-sensitive information key;
• 16-bit microprocessor;
• universal and digital inputs.
F
4
1A
1B
1 or 3 Universal Analog Inputs
4 Digital Inputs
1 Communication Input/Output
…Alarm1 Lo Deviation
–1
F Adjusts Value Back Next
2 Control Outputs
1
2 Alarm Outputs
2
2 Retransmit Outputs (optional)
ˆ
å
1.2 Introduction Watlow Series F4P
Setup Steps
The
ˆˆ
Key
During all these steps, the Information Key will summon helpful definitions and setup tips. Just position the cur­sor next to the item you want to know more about, then press the key. Press it again to return to your task.
See Chapter 3, Operations Page.
4
Establish a set point for static set point
control.
See Chapter 3, Operations Page.
3
Tune the system and set alarm set points.
Learn to navigate the software in Chapter 2, Operating from the Front Panel, and then go to Chapter 4, Setup Page. For background, you may also want to refer to Chapter 7, Features. (This
step may not be necessary if the Series F4P is already installed in the equipment.)
2
Configure the controller to suit your
application.
See Chapter 8, Installation and Wiring. (This step will not be necessary if the Series F4P is already installed in equipment.)
1
Install and wire the controller.
How to do itWhat to do
Your Series F4P may arrive as an independent unit or already installed in other equipment. The steps below may or may not apply to all units. The Series F4P soft­ware can be locked with different types of security. See Chapter 5, Factory Page.
Watlow Series F4P Operating from the Front Panel 2.1
Chapter Two: Navigation and

Operating from the Front Panel

Displays and Indicator Lights . . . . . . . . . . . . . . . . .2.2
Guided Programming . . . . . . . . . . . . . . . . . . . . . . .2.3
Custom Main Page . . . . . . . . . . . . . . . . . . . . . . . . .2.3
Auto and Manual Operation . . . . . . . . . . . . . . . . . .2.3
Troubleshooting Alarms and Errors . . . . . . . . . . . . .2.4
Figure 2.1 — Page Navigation.
Series F4P software is organized into four sections called “pages.” The Main Page is the central, default page that displays status information on the lower display. To get to the other pages, you must begin in the Main Page.
Note: Access to the software is limited while the con- troller is autotuning (Setup and Factory pages are not accessible).
2
Main Page_____
The Main Page presents error messages, static messages and the status of inputs, outputs and depending on the Custom Main Page, parameter settings in the Setup Page.
Scroll to the bottom of the Main Page to reach the other pages.
When you exit the Setup or Factory Page, the controller prompts you to restore the old settings or save the new ones.
Input 1 Error Input 2 Error Input 3 Error
Alarm 1 Condition Alarm 2 Condition
Tune Status 1 Input 1 Value In 1 ■■■■ Input 2 Value Set Point 1 Set Point 2 Digital Set Point Power 1A 1A% ■■ Power 1B 1B% ■■■ Digital Ins 1234 Active PID Set Message 1 Message 2 Message 3
>Go to Operations Go to Setup Go to Factory
Operations Page Autotune PID Edit PID Alarm Set Point PID Crossover Ramp to Set Point Control Set Points
Setup Page System Analog Inputs Digital Inputs Control Outputs Alarm Outputs Retransmit Outputs Communications Custom Main Page Static Message
Factory Page Set Lockout Diagnostic Test Calibration

Keys, Displays and Lights

Figure 2.2 — Series F4P Displays and Indicator Lights.
1B
1A
2.2 Operating from the Front Panel Watlow Series F4P
Upper Display
Displays Channel 1 actual process values during operation. Displays error information if errors occur.
Lower Display
Guides setup and operation, displays status information.
Cursor (>):
Points to the selected parameter or present value. Moves via the Up, Down, Right and Left keys.
Auto/Manual Status Light (Indicates mode status):
• Lit when in manual mode.
• Blinks for 10 seconds after key pressed, while user
can change mode.
• Not lit during automatic
mode.
Auto/Manual Key
Press to toggle between auto (closed-loop) and manual (open-loop) control.
Information Key
Press for tips and definitions, press again to return to the original task.
Main Page___________
Go to Operations
Go to Setup Go to Factory
i
F
4
1A
1B
1
Left and Right Keys
Press Right key to select the item to the right of the cursor (>) and proceed to the next screen. Press Left key to move left or exit.
2
Active Output Status Lights
Lit when the corresponding controller channel output is active.
Alarm Output Status Lights
Lit during an alarm state.
Communications Status Light
Blinks when the controller sends or receives data.
Scroll Bar
Indicates that more informa­tion exists above or below. Use Up and Down keys.
Up and Down Keys
Press to move the cursor (>), increase or decrease a value or change a letter in a name.
To Clear an Alarm or Error
In an alarm condition, the alarm status light will be lit. An alarm message will appear on the Main Page if configured to do so. To silence the alarm, move the cursor to the alarm message and press the Right key. A message will confirm the alarm silencing, and the alarm status light will turn off.
After correcting the condition that caused the error or alarm, return to the error or alarm message on the Main Page, and press the Right key again. A message will confirm that the alarm is unlatched.
Watlow Series F4P Operating from the Front Panel 2.3

Guided Programming

The Series F4P software guides users through most tasks. To accomplish a task, simply proceed through the sequence of parameters. For each parameter, choose the appropriate option or establish the value, then press the Right key to proceed to the parameter on the next screen. The task is complete when you return to the ini­tial menu.
1. Use
> or < to move the cursor to select an item
in a list.
2. Press the Right key
...
3. Enter the value and make a choice.
4. Press
. again.
5. Repeat until you return to the original list.
To change a specific, single parameter, proceed through the parameter sequence without changing values until you reach that parameter, then make your change. After changing the value, you may back out of the sequence by pressing the Left key or continue on through the sequence by pressing the Right key. When you exit the page, you must choose to Save Changes or Restore Values.
.
.
.
Choose Cycle Time:__ >Variable Burst
Fixed Time
Choose Function:____ >Heat
Cool
Choose to Setup:____ >Control Output 1A
Control Output 2A
Main Page___________
Go to Operations
>Go to Setup
Go to Factory

Custom Main Page

The Main Page shows error messages; input and output status; and allows access to controller software. You can customize the Main Page to display chosen information by going to the Setup Page, Custom Main Page Menu. (See Chapter 4, Setup Page, for instructions.)

Auto and Manual Operation

The Series F4P controller can function as a static set point controller (auto mode); or the user can directly
control the outputs (manual mode). In the static set point mode, the Series F4P can only be
operated in a closed-loop configuration. The Auto/Manual Indicator Light is on when the con-
troller is in manual mode. To toggle between manual and auto mode, first press the Auto/Manual key
å , then con-
firm your selection in the lower display. The indicator light will flash after you press
å until you confirm your
choice or 10 seconds have elapsed. While in manual mode you can adjust the output power level for process outputs or turn relay or open collector outputs on or off.
çWARNING: Only authorized and qualified personnel
should change the set point on the controller. Failure to comply with these recommendations may result in dam­age to equipment and property and injury to personnel.
Static Set Point Control
When the Series F4P is in static set point mode:
• The Upper Display shows the actual process temper­ature of input 1.
• The Lower Display shows the default or user-config­ured Main Page.
To operate the Series F4P as a static set point controller, select SP1 in the Main Page then use the Up and Down keys to adjust the set point.
Limits may be placed on the set point in the Set Point Low Limit and Set Point High Limit parameters (Setup Page > Analog Input 1).
Note: All control activity stops when you enter the Setup Page, Analog Input, Digital Input, Control Output, Alarm Output and Retransmit menus.
Note: See also differential set point and ratio set point.
2.4 Operating from the Front Panel Watlow Series F4P
• Process value must return to normal by more than the hysteresis value to be cleared.
• Configure alarm type, sides, hysteresis, logic and set points.
• Correct cause of input error.
• Check the alarm output function.
• Alarm latched.
• Alarm output not configured cor­rectly.
• Analog input(s) in error condi­tion.
• Input may be in error condition.
• Alarm won’t clear. (To clear the alarm, correct the
alarm condition. If the alarm is latched, press
. with the cursor at the alarm message on the Main Page.)
• Turn on alarm annunciation.• Alarm annunciation is set to off.
• Exit Diagnostic mode.• Controller in Diagnostic mode.
• Configure alarm type, sides, hysteresis, logic and set points.
• Alarm output not configured.
• Verify that silencing function is required. Disable if not required.
• Alarm silencing is enabled.
Alarms
• Alarm won’t occur.
• Return controller to factory for repair.• Serial port of controller is defective.
• Verify or replace serial cable.• Serial cable is open or not wired correctly.
• Check converter box wiring and its docu­mentation.
• Termination and/or pull up of bus required.
• Check computer communications port set­tings and verify PC communications.
• Computer communications port incorrectly set up or defective.
• Converter must be half duplex.
• Check converter box wiring and settings.
• EIA-232 to EIA-485 converter incorrectly set or wired.
• Verify correct connections and test wiring paths.
• Communications wiring reversed, shorted or open.
• Look for a break in the daisy chain.• Unit-to-unit daisy chain disconnected.
• Check Communications Setup Menu and set to correct baud rate. Be sure it is Modbus RTU protocol.
• Baud rate parameter incorrectly set or incorrect protocol. Use Modbus RTU, 8 data bits, no parity and 1 stop bit.
• Check Communications Setup Menu and set to correct address.
• Address parameter incorrectly set.
Communications
• Unit will not communicate.
• Measure power for required level. Check part number for input power required.
• Check wire size.
• Check for bad connections.
• Input power incorrect.
• Check switches, fuses, breakers, interlocks, limits, connectors, etc. for energized condi­tions and proper connection.
• Power to unit off.
• Fuse blown.
• Breaker tripped.
• Safety Interlock door switch, etc., activated.
• Separate system limit control latched.
• Wiring open.
Power
• No displays.
Corrective ActionProbable Cause(s)Indication
Troubleshooting
Watlow Series F4P Operating from the Front Panel 2.5
• Return to factory for evaluation.• Component failure.
Upper [Atod`] Lower !Timeout x
(x is 1 to 3)
• Repair or replace sensor.
• Reverse sensor wiring connections. Red lead is usually negative for tc.
• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and 3 are not isolated from each other.
• Sensor open.
• Sensor wired backwards. Display decreases as process increases.
• Input type set to wrong sensor.
• Ground loop
Upper [SEnhi] Lower !Input Sensor x+
(x is 1 to 3)
• Repair or replace sensor.
• Reverse sensor wiring connections. Red lead is usually negative for tc.
• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and 3 are not isolated from each other.
• Sensor shorted (RTD).
• Sensor wired backwards. Display decreases as process increases.
• Input type set to wrong sensor.
• Ground loop
Upper [SEnLo] Lower !Input Sensor x-
(x is 1 to 3)
• Repair or replace sensor.
• Reverse sensor wiring connections. Red lead is usually negative for tc.
• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and 3 are not isolated from each other.
• Sensor open.
• Sensor wired backwards. Display decreases as process increases.
• Input type set to wrong sensor.
• Ground loop
Upper [A-dhi] Lower !Input x AtoD+
(x is 1 to 3)
• Repair or replace sensor.
• Reverse sensor wiring connections. Red lead is usually negative for tc.
• Set analog input to match sensor.
• Check sensor isolation. Inputs 2 and 3 are not isolated from each other.
• Sensor shorted (RTD).
• Sensor wired backwards. Display decreases as process increases.
• Input type set to wrong sensor.
• Ground loop
Upper [A-dLO] Lower !Input x AtoD
(x is 1 to 3)
Input Errors
(Upper Display shows error code
for input 1 only. Lower Display shows additional errors. Input 2 and 3 error messages appear in Lower Display. Alarm Output Indicator is lit.)
• Tune PID set.
• Check power limit settings.
• Replace fuse or reset circuit breaker.
• Reposition sensor to accurately mea­sure process.
• Check slidewire settings.
• PID values set incorrectly.
• Power limit set incorrectly.
• Open fuse or circuit breaker on energy source.
• Incorrect sensor location in the pro­cess.
• Slidewire (if used) settings incorrect.
• Process will not reach set point.
• Check operation mode. Automatic is closed loop, manual is open loop.
• Check power limit settings.
• Check sensor, repair or replace.
• Check outputs, repair or replace.
• Check output settings.
• Check system wiring.
• Controller in manual operation mode (percent power).
• Power limit set incorrectly.
• Thermocouple shorted.
• Shorted power switching device.
• Output set incorrectly (heat vs. cool).
• System wired incorrectly.
• Process runs away (too high or too low).
• Check power limit settings.
• Tune PID set.
• Use correct PID set.
• Power limit set incorrectly.
• PID values set incorrectly.
• Incorrect PID set active.
Controllability
• Process will not stabilize.
• Check alarm logic setting and output wiring.
• Alarm logic setting incorrect or output wired incorrectly.
• Alarm output action is reversed.
Corrective ActionProbable Cause(s)Indication
2.6 Operating from the Front Panel Watlow Series F4P
• Add power line filter for input power.
• Return controller to factory for repair.
• Noise on power line.
• Component failure.
• Checksum error in Cycle device power.
• Press any key. All parameters will de­fault.
• Module changed.• Module change. Defaults will
occur. Accept with any key.
• Replace incorrect module with re­transmit module.
• Wrong module in retransmit 2 slot.• Retransmit 2 Module Error! Only process modules supported.
• Replace incorrect module with re­transmit module.
• Wrong module in retransmit 2 slot.• Retransmit 1 Module Error! Only process modules supported.
• Check for correct installation of mod­ule.
• Module not seated correctly in slot.• Verify the module.
• Check for correct installation of mod­ule.
• Module installed incorrectly or in wrong slot.
• Module not allowed
• Replace output module.• Output module failure.• Output 1A
• Output 1B
• Output 2A
• Output 2A
• Move module to correct input slot.
• Move module to correct input slot.
• Input module 2 or 3 is in input 1 slot.
• Input module 1 is in input 2 or 3 slot.
• Verify Input 1
• Verify Input 2 or 3
• Replace module or return controller to factory for repair
• Amodule has lost its programming ID. • Incorrect ID!
• Contact factory for further informa­tion and diagnosis.
• Component failure. • Unknown Error! Record this number. Contact the factory.
• Add filter to AC power line and verify unit is power by AC voltage.
• Controller can’t detect zero cross point. Noise is present on AC power line or unit is not powered by AC voltage.
• Zero Cross Failure! Switched to Fixed Time control.
System Errors
(Upper Display shows error
numbers. Lower Display mes­sages indicate cause and action to take.)
• Check wiring and process valve for compatibility.
• Process valve is wired incorrectly or in­compatible.
Upper Lower Slidewire time out
• Increase slidewire time out value.
• Replace process valve.
• Increase slidewire time out value.
• Check wiring and process valve for compatibility.
• Slidewire time out value set too short.
• Slidewire valve is stuck or not responding.
• Process valve is wired incorrectly or in­compatible.
Upper Lower Slidewire time out
• Return to factory for evaluation.• Component failure.
Upper Lower !Input x Error
(x is 1 to 3)
Corrective ActionProbable Cause(s)Indication
Watlow Series F4P Operating from the Front Panel 2.7
• Repair heating/cooling circuits.
• Check circuit breakers, switches, heater elements, compressor.
• Heater/cooling non-functional.
• Replace sensor.• Sensor shorted.
• Replace relay.• Output relay open or shorted.
• Place sensor near source.• Sensor not properly located
• Check all wiring and components.
• Turn the controller off, then on again.
Open Loop Detect
(Upper Display shows error code for input 1 only. Lower Display shows additional errors. Upper: [oPLP`] Lower: Open Loop
• Return controller to factory for repair.• Controller has failed.• Flash memory Failed. Return controller to the Factory.
• Return controller to factory for repair.• Controller has failed.• RAM Test Failed! Return controller to the Factory.
• Turn the controller off, then on again.
If problem persists, power line filter is required.
• Power line noise has corrupted memory.• Checksum Error!
Parameter memory.
• Checksum Error! Unit Config memory
• Checksum Error! Profile memory.
• Normal operation following flash up­date of firmware.
• Controller firmware has been updated.• Firmware change.
Parameters are initializing.
• Return controller to factory for repair.• Power was interrupted during a flash
update or there is a component failure.
• Flash Memory Failed! Return controller to the Factory.
• Return controller to factory for repair.• Component failure.• RAM Test Failed! Return controller to the Factory.
• Should not appear in the field. Call
the factory if you get this message.
• Controller powered up for the first time.• First power-up.
Parameters are initializing.
• This is normal upon module change.• Input or output module was changed.• Module change.
All parameters are initializing.
Corrective ActionProbable Cause(s)Indication
2.8 Operating from the Front Panel Watlow Series F4P
Notes:
Watlow Series F4P Operations Page 3.1

Chapter Three: Operations Page

Alarm Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1
Autotune PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2
Edit PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2
Multiple PID Sets . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3
Cascade Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3
This chapter explains how to establish alarm set points, autotune and manually tune and establish cascade con­trol through the Operations Page of the software.
To configure the alarm outputs, go to the Setup Page of the software (see related information in the Parameters Chapter).
For the alarm clearing procedure, go to the Troubleshoot­ing Alarms and Errors table in the Navigation and Operating from the Front Panel Chapter.
For background information about alarms; proportional, integral and derivative control; and cascade, see the Fea­tures Chapter.

Alarm Set Points

The Series F4P includes two alarm outputs, which can be programmed as process, deviation or rate alarms.
Process alarms notify the operator when process values exceed or fall below Alarm Low and Alarm High Set Points. Deviation alarms notify the operator when the process has deviated from the set point beyond the devia­tion limits. Rate alarms are triggered by a change in temperature or process value that is faster than the se­lected rate.
For more information, see the Features Chapter. To set up the alarms, see the Setup Chapter.
Alarm set points are the points at which alarms switch on or off, depending on the alarm setting. Alarm set points can be viewed or changed in the Alarm Set Point Menus (Operations Page).
The Alarm High Set Point defines the high value that, if exceeded, will trigger an alarm. This value must be higher than the alarm low set point and lower than the high limit of the sensor range.
The Alarm Low Set Point defines the low value that, if exceeded, will trigger an alarm. This value must be lower than the alarm high set point and higher than the low limit of the sensor range.
The Alarm Low Deviation defines the deviation value on the low side of set point at which the alarm will be triggered.
The Alarm High Deviation defines the deviation value on the high side of set point at which the alarm will be triggered.
Note: You may want to set up the alarms with names that will identify the alarm conditions. See the Setup Page.

To Clear an Alarm or Error

In an alarm condition, the alarm status light will be lit. An alarm message will appear on the Main Page if con­figured to do so. To silence an alarm, the Silencing option in the Alarm Output menu (Setup Page) must be en­abled. To silence the alarm, move the cursor to the alarm message and press the Right key. Amessage will confirm the silencing of the alarm, and the alarm status light will turn off. After correcting the condition that caused the error or alarm, return to the error or alarm message on the Main Page, and press the Right key again. Amessage will confirm that the alarm is unlatched.
3
3.2 Operations Page Watlow Series F4P

Autotune PID

In autotuning, the controller automatically selects the PID parameters for optimal control, based on the ther­mal response of the system. In the Series F4P, five sets of PID values are available. Default PID values exist for all PID sets, although these values typically do not provide optimal control. PID values can be auto-tuned or adjust­ed manually. When autotuning is complete, the PID val­ues will be stored in the Edit PID Menu.
Set point changes for remote, ratio and differential con­trol are ignored until autotuning is complete.
Autotuning Procedure
Autotuning is initiated from the Operation Menu.
1. Before initiating auto-tune, go to the System Menu (Setup Page), and establish the Autotune Set Point to a percentage of set point. This percentage is based on your knowledge of the system and how much overshoot or undershoot there is likely to be in on-off control.
Select to display Tune Status in the Custom Main Page Menu.
2. Go to the Main Page and adjust set point.
3. Go to the Autotune PID Menu (Operations Page) and choose the PID set in which to store the values. You must exit back to Main Page with the left arrow. A message will be displayed on the Main Page during the autotuning process.
4. When autotuning is complete, the controller will store the values for optimum control in the specified PID set.
For additional information about autotuning and propor­tional, integral and derivative control, see the Features Chapter.
Note: While the controller is autotuning, only the Op- eration Page of the software can be entered.
ç
CAUTION: Choose an autotune set point value that will protect your product from possible damage from overshoot or undershoot during the autotuning oscillations. If the product is sensitive, select the autotune set point very carefully to prevent product damage.

Edit PID

The Edit PID Menu is useful when Auto-tune PID does not provide adequate control. Each of the PID parame­ters can be adjusted manually:
Proportional Band: Define a band for PID control, en­tered in degrees or units. Lower values increase gain, which reduces droop but can cause oscillation. Increase the proportional band to eliminate oscillation.
Integral (Reset): Define the integral time in minutes per repeat; define reset in repeats per minute. Set re­peats per minute if units are U.S.; minutes per repeat if units are SI.
Derivative (Rate): Define the derivative (rate) time in minutes. Large values prevent overshoot but can cause sluggishness. Decrease if necessary.
Dead Band: Define the dead band in degrees or units. Heating dead band shifts the set point down. Cooling dead band shifts the set point up. For more information, see the Features Chapter.
For background information, see Chapter 7, Features.
Manual Tuning Procedure
1. Apply power to the Series F4P and establish a set point on the Main Page.
2. Establish Cycle Time in the Control Output Menu (Setup Page), as required. Typical cycle times are 1.0 second for an SSR and 5.0 seconds for a mechanical relay. Faster cycle times sometimes achieve the best system control. However, if a mechanical contactor or solenoid is switching power to the load, a longer cy­cle time may be desirable to minimize wear on the mechanical components. Experiment until the cycle time is consistent with the desired quality of control.
3. Go to the Edit PID Menu (Operations Page), and choose the channel and PID set. Establish values for the PID parameters: Proportional Band, 5; Integral (Reset), 0; Derivative (Rate), 0; and Autotune, Tune Off. Tuning begins when you choose a PID set.
4. When the system stabilizes, watch the value of Input 1 on the Main Page. If this value fluctuates, increase the proportional band setting until it stabilizes. Ad­just the proportional band in 3° to 5° increments, al­lowing time for the system to stabilize between ad­justments.
5. When Input 1 has stabilized, watch the percent pow­er on the Main Page. It should be stable, ±2%. At this point, the process temperature should also be stable, but it will exhibit droop (stabilized below set point). The droop can be eliminated with integral (re­set).
Watlow Series F4P Operations Page 3.3
6. Start with an integral setting of 99.9 minutes and al­low 10 minutes for the process temperature to get to set point. If it has not, decrease the setting by half and wait another 10 minutes. Then halve the setting again and wait another 10 minutes until the process value equals the set point. If the process becomes un­stable, the integral value is too small. Increase it un­til the process stabilizes.
7. Increase Derivative/Rate to 0.10 minute. Then in­crease the set point by 11° to 17°C. Watch the sys­tem's approach to the set point. If the process value overshoots the set point, increase Derivative/Rate to
0.50 minute. Increase the set point by 11° to 17°C and watch the
approach to the new set point. If you increase Derivative/Rate too much, the approach to the set point will be very sluggish. Repeat as necessary until the system rises to the new set point without over­shoot or sluggishness.
For additional information about the burst fire feature, manual tuning and PID control, see the Features Chapter.

Multiple PID Sets

Environmental chambers, ovens and furnaces typically have different thermal requirements at high and low temperatures or pressures. To accommodate this, the Se­ries F4P can store five different PID sets.
Multiple Tuning Procedure
To autotune multiple PID sets, follow the Autotuning procedure above for each PID set. When autotuning is finished for one set, proceed with another.

Cascade

Cascade control is available on enhanced (F4P _ - _ _ AB
- _ _ _ _) Series F4P controllers. For background informa­tion about cascade control, see the Features Chapter.
Select cascade control through the Analog Input 3 Menu (Setup Page), and choose Process Cascade or Deviation Cascade. To set the range for the inner loop set point, Process Cascade uses Low and High Range settings that are independent of set point; Deviation Cascade uses De­viation Low and High settings that are deviations from the primary set point.
When tuning a cascade system, the inner loop must be tuned first. The inner loop comprises outputs 1A and 1B and the Analog Input 1 sensor, which usually measures the energy source temperature. The output device con­trols a power switching device, which in turn switches
the heating and cooling. The set point for the inner loop is generated by the outer loop. For Process Cascade, this will have a range between the Cascade Low Range and Cascade High Range.
Cascade Setup Procedure
1. First, configure Analog Input 3, Cascade Low Range and Cascade High Range.
Go to the Analog Input 3 Menu (Setup Page). Choose Process or Deviation Cascade. Deviation Cascade refer­ences Channel 1 set point allowing a range above and below the current control set point. For Process Cascade control of a heat/cool or cool only system, set the Cascade Low Range to a value slightly lower than the lowest temperature desired in the chamber. For heat-only sys­tems, set the Cascade Low Range to a value slightly low­er than the ambient temperature; otherwise the heat output will never turn fully off.
For heat/cool or heat only systems , set the Cascade High Range to a value slightly higher than the highest temperature desired in the chamber. For cool-only systems, set the Cascade High Range to a value slightly higher than the ambient temperature; otherwise the cooling will never fully turn off.
2. Next, configure the controller to tune and display data for the outer loop. To view Inner Loop Set Point in the upper display, go to the Setup Page, Custom Main Page Menu, select the Inner Set point as one of the parame­ters, P1 to P16, to be displayed in the Main Page.
To also view Analog Input 3 in the upper display, go to the Setup Page, Process Display Menu, and choose Al­ternating. Under Set Display Time, choose a duration for the display of the Input 1 and Input 3 variables.
Cascade Autotuning Procedure
1. Go to Setup Page, Custom Main Page Menu. Choose Tune Status 1 and Tune Status 2 to appear as 2 of the 16 parameters that can be displayed on the Main Page. The Main Page will now display the status of the auto­tuning process.
2. Autotune the inner loop. Go to the Autotune PID Menu (Operations Page), and select Cascade Inner-loop. Choose Cascade Inner Loop PID Set 1 to 5, where PID values will be stored after autotuning. Autotuning be­gins when you choose the PID set. While autotuning, the F4 controller will control the energy source in an on-off mode to a temperature equal to the Cascade High Range setting x Channel 1 Autotune Set Point. For best results, use proportional control only on the inner loop.
3.4 Operations Page Watlow Series F4P
3. Next, autotune the outer loop. Go to the Autotune PID Menu (Operations Page). Choose Cascade Outer Loop, then choose Outer Loop PID set 1 to 5, where PID val­ues will be stored after autotuning. Autotuning begins when you choose the PID set. While autotuning, the outer loop will be controlled in an on-off mode at a set point equal to static set point x Ch 1 Autotune Set Point. In most cases, the autotuning feature will tune for acceptable control. If not, manually tune the outer loop (step 4 below). Before manually tuning, record the values generated by the autotuning feature.
4. To manually tune the outer loop, go to the Edit PID Menu (Operations Page). Choose Cascade Outer Loop, then choose Outer Loop PID set 1 to 5. Begin manual tuning by setting the Proportional Band to 5, Integral (Reset) to 0, and Rate to 0. Establish the desired set point and let the system stabilize. When the system stabilizes, watch the Inner Loop Set Point on the Main Page. If this value fluctuates, increase the proportional band until it stabilizes. Adjust the proportional band in 3° to 5° increments, allowing time for the system to stabilize between adjustments.
5. When Input 1 has stabilized, watch the percent power on the Main Page. It should be stable, ±2%. At this point, the process temperature should also be stable, but it will exhibit droop (stabilized below set point). The droop can be eliminated with Integral (reset).
6. Start with an integral setting of 99.9 minutes, and al­low 10 minutes for the process temperature to come up to set point. If it has not, decrease the setting by half and wait another 10 minutes. Then halve the setting again and wait another 10 minutes until the process value equals the set point. If the process becomes unstable, the integral value is too small. Increase it until the process stabilizes.
Watlow Series F4P Setup Page 4.1

Chapter Four: Setup Page

Parameter Setup Order . . . . . . . . . . . . . . . . . . . . . .4.1
Customizing the Main Page . . . . . . . . . . . . . . . . . .4.2
Static Messages . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2
4
This chapter explains how to configure the controller software through the Setup Page menus. Setup Page pa­rameters affect the way the controller responds to your application, which parameters and functions are visible in other pages, and the way information is displayed on the Main Page. Set up the controller properly to provide a sound foundation for settings in other pages.
For ranges, defaults and other information about specific parameters, see the Parameters Chapter. Record your settings in the Parameter Setup Record, also in that chapter.
For background information about inputs, outputs, alarms and other features, see the Features Chapter.

Parameter Setup Order

Initial configuration of the Series F4P is best done in the following order:
1. Go to the System Menu (Setup Page) to configure:
• PID units — SI (Integral, Derivative) or U.S. (Re­set, Rate);
• Celsius or Fahrenheit scales;
• display of units in the controller’s upper display;
• Autotune set point;
• open-loop detection warnings; and
• controller response to a power outage.
2. Go to other menus on the Setup Page to configure:
• Analog Input x (1 to 3);
• Digital Input x (1 to 4);
• Control Output x (1A, 1B);
• Alarm Output x (1 or 2);
• Retransmit Output x (1 or 2);
• Communications; and
• Custom Main Page and Custom Messages.
3. Go to the Operations Page to tune the PID sets.
4. Go to the Operations Page to set the alarm set points.
After this initial configuration, the most frequent changes will be to the Operations Page (alarm set points and PID sets).
If the Series F4P is already installed in an environmen­tal chamber, oven, furnace or other equipment, most pa­rameters will already be configured and access to the Setup Page may be limited (see Chapter 5, Factory Page).
Changing Setup Page parameters may change other pa­rameters. In some cases, a change in one parameter will affect the defaults of others. To see how all the pages, menus and parameters are grouped, see the software map on the inside back cover of this manual.
Note: For more information about how parameter set- tings affect the controller’s operation, see the Features Chapter.
çWARNING: Only authorized and qualified personnel
should change the factory-default settings, which may cause changes in other settings. Failure to comply with this recommendation may result in damage to equipment and property and injury to personnel.
4.2 Setup Page Watlow Series F4P

Customizing the Main Page

Up to 16 lines can be added to the Main Page to display status and information from the controller.
Go to the Custom Main Page Menu on the Setup Page. The first screen will prompt you to choose one of the 16 lines to customize. "P1 Parameter" is the first line; "P16 Parameter" is the 16th. After choosing this line by press­ing ., select a parameter to monitor.
Your choices are listed under Custom Main Page in the Setup Page Parameter Table in this chapter.
Figure 4.2 — Example of Parameters on the Custom Main Page.
Input1 26°C PID Set 1 Power1A 0% Power1B 55% DigitalIn _234
Choose P:1 Display_ _ >None
Input 1 Value Input 1 Value bar
Choose:_ _ _____ >P1 Parameter
P2 Parameter P3 Parameter

Static Messages

Digital inputs can be configured to display a message that the user enters. The message is displayed on the Main Page when the digital input is active.
This feature could, for instance, display “DOOR OPEN” if an oven door is not closed all the way.
Watlow Series F4P Factory Page 5.1

Chapter Five: Factory Page

Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.3
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.3
5

Security

The Series F4P allows users to set separate security levels for the Static Set Point prompt on the Main Page, for all menus on the Operations Page, as well as for the Setup Page and Factory Page. Four levels of security are available:
Full Access (operators can enter and change settings);
Read Only (operators can read but not change settings);
Password (operators can enter and change settings after entering a password); and
Hidden (operators cannot see the menu or page — it is not displayed). Set Point settings cannot be Hidden.
Note: Full Access is the default for all menus. Unless you change the level of access, operators will be able to read and change every setting in every menu in the Series F4P software.
How to Set Lockout Levels
Using the Lockout Menu, you can limit access to the following menus and pages:
Set Point on Main Page
Operations Page Autotune PID
Operations Page Edit PID
Operations Page Alarm Set Point
Setup Page
Factory Page
Choose the item to lock out, press .. and choose the level of access: Full, Read Only, Password or Hidden. If you choose Password, you must set the password — see below.
Note: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.
ç CAUTION: Only authorized and qualified personnel
should be allowed to perform preventive and corrective maintenance on this unit.
…Lock>Autotune PID___
Full Access Read Only
>Password
.
…Factory>Set Lock___
Set Point
>Oper. Autotune PID
Oper. Edit PID
.
Main>Factory________ >Set Lockout
Diagnostic Test
5.2 Factory Page Watlow Series F4P
Enter a Password
If you try to set password security before any password has been established, a pop-up message will give you the opportunity to enter one. Use the . , , , > and < keys to enter a four-character password, which can consist of letters, numbers or both. After entering and confirming the password, re-enter the chosen menu or page and select Password Security. Record your password and keep it secure.
Confirm Password: _ _ _ _
▲▼ Adjusts Char
< Back >Next
Enter New Password: _ _ _ _
▲▼ Adjusts Char
< Back >Next
Must reset lock after setting the password
■ ■ ■ Press any key!■ ■ ■
>
No Password!
Set Password?
No Yes
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Use a Password
To enter a password-protected area, users must enter the password. If an incorrect password is entered, a pop-up message will tell you it is invalid and you may try again. When the password is correct, choose again to enter the menu or page of your choice.
Change a Password
The Change Password parameter is near the end of the list under Set Lockout on the Factory Page. To change a password, you must first enter the old password for confirmation.
Enter Password:
_ _ _ _
▲▼ Adjusts Char
< Back >Next
.
…Factory>Set Lock___
Setup
Factory >Change password
Invalid, Re-Enter:____
▲▼ Adjusts Char
< Back >Next
Watlow Series F4P Factory Page 5.3

Diagnostics

Diagnostic Menu parameters (on the Factory Page) provide information about the controller unit that is useful in troubleshooting. For example, the Out1A parameter will identify what type of output has been selected for Output 1A.
Select the parameter by pressing the Right Key . . The information will appear on the Lower Display.
Some of the parameters in the Diagnostic Menu provide information for factory use only.
To reset all parameters to their original factory values, use the Full Defaults parameter under the Test Menu.
Test
This menu allows you to test outputs, test the displays (upper, lower and status lights), and cause the controller to revert to the defaults set at the factory. Reverting to factory defaults will erase all preset software and the controller will return to U.S. PID units (Reset and Rate) and the Fahrenheit temperature scale.

Calibration

The Calibration Menu on the Factory Page allows calibration of inputs and outputs. Calibration procedures should be done only by qualified technical personnel with access to the equipment listed in each section.
Before beginning calibration procedures, warm up the controller for at least 20 minutes.
Restore Factory Values
Each controller is calibrated before leaving the factory. If at any time you want to restore the factory
input calibration values, use the last parameters in the menu: Restore Input x (1 to 3) Calibration. Press ... No special equipment is necessary.
Thermocouple Input Procedure
Equipment
•Type J reference compensator with reference junction at 32°F/0°C, or type J thermocouple calibrator to 32°F/0°C.
• Precision millivolt source, 0 to 50mV minimum range, 0.002mV resolution.
Input x (1 to 3) Setup and Calibration
Inputs 2 and 3 appear only if the controller is the enhanced version (F4P _ - _ _ AB - _ _ _ _).
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
2. Connect the millivolt source to input 1 terminals 62 (-) and 61 (+), input 2 terminals 58 (-) and 57 (+), or input 3 terminals 56 (-) and 55 (+), with copper wire.
3. Enter 50.000mV from the millivolt source. Allow at least 10 seconds to stabilize. Press the Right Key . once at the Calibrate Input x (1 to 3) prompt (Factory Page). At the 50.00mV prompt press . once and to store 50.00mV press the Up Key > once.
4. Enter 0.000mV from the millivolt source. Allow at least 10 seconds to stabilize. At the 0.00mV prompt press . once and to store 0.00mV press > once.
5. Disconnect the millivolt source and connect the reference compensator or thermocouple calibrator to input 1 terminals 62 (-) and 61 (+), input 2 terminals 58 (-) and 57 (+), or input 3 terminals 56 (-) and 55 (+). With type J thermocouple wire, if using a compensator, turn it on and short the input wires. When using a type J calibrator, set it to simulate 32°F/0°C. Allow 10 seconds for the controller to stabilize. Press . once at the Calibrate Input x (1 or
2) prompt (Factory Page). At the 32°F Type J prompt press . once and to store type J thermocouple calibration press > once.
6. Rewire for operation and verify calibration.
5.4 Factory Page Watlow Series F4P
RTD Input Procedure
Equipment
•1kΩ decade box with 0.01Ω resolution.
Input x (1 to 3) Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
2. Short Input 1 terminals 60, 61 and 62; Input 2 terminals 54, 57 and 58; or Input 3 terminals 52, 55 and 56 together with less than 0.1Ω. Press the Right Key . once at the Calibrate Input x (1 to 3) prompt. At the Ground prompt press . once and to store ground input press the Up Key > once.
3. Short Input 1 terminals 60 and 61; Input 2 terminals 54 and 57; or Input 3 terminals 52 and 55 together with less than 0.5. Press . once at the Calibrate Input x (1 to 3) prompt. At the Lead prompt press . once and to store lead resistance press > once.
4. Connect the decade box to Input 1 terminals 60 (S2), 61 (S1) and 62 (S3); Input 2 terminals 54 (S2), 57 (S1) and 58 (S3); or Input 3 terminals 52 (S2), 55 (S1) and 56 (S3), with 20- to 24­gauge wire.
5. For 100RTD, enter 15.00. For 500or 1k RTD, enter 240.00. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input x (1 to 3) prompt (Factory Page). At the
15.00or 240.00* RTD prompt press . once and to store the 15.00or 240.00input press > once.
6. For 100RTD, enter 380.00. For 500or 1k RTD, enter 6080.00. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input x (1 to 3) prompt. At the 380.0or
6080.00* RTD prompt press . once and to store the 380.00or 6080.00input press > once.
7. Rewire for operation and verify calibration.
Slidewire Feedback Input Procedure
Equipment
•1kΩ decade box with 0.01Ω resolution.
Input 3 Setup and Calibration
Input 3 appears only if the controller is the enhanced version (F4P _ - _ _ AB - _ _ _ _).
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
2. Connect the decade box to Input 3 terminals 55 (S1) and 56 (S3), with 20- to 24-gauge wire.
3. Enter 15.00. on the decade box. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input 3 prompt (Factory Page). At the
15.00SlWr prompt press . once and to store the 15.00input press > once.
4. Enter 1000.00. from the decade box. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input 3 prompt. At the 1000.00 SlWr prompt press . once and to store the
380.00or 6080.00input press > once.
5. Rewire for operation and verify calibration.
Voltage Process Input Procedure
Equipment
• Precision voltage source, 0 to 10V minimum range, with 0.001V resolution.
Input x (1 to 3) Setup and Calibration
Inputs 2 and 3 appear only if the controller is the enhanced version (F4P _ - _ _ AB - _ _ _ _).
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
2. Connect the voltage source to input 1 terminals 59 (+) and 62 (-), input 2 terminals 53 (+) and 58 (-) or input 3 terminals 51 (+) and 56 (-).
3. Enter 0.000V from the voltage source to the controller. Allow at least 10 seconds to stabilize. Press the Right Key . once at the Calibrate Input 1 prompt. At the 0.000V prompt press . once and to store the 0.000V input press the Up Key > once.
NOTE: You need the equipment listed and technical skills. Controllers come calibrated from the factory. Recalibrate only for other agency requirements or if temperatures aren’t accurate as verified by another calibrated instrument.
*The tenth digit of your model number, F4XX-XXXX-
X
XXX, determines what prompts appear and what
input resistance values to use for RTD calibration. Refer to the Ordering Information in the Appendix.
Watlow Series F4P Factory Page 5.5
4. Enter 10.000V from the voltage source to the controller. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input 1 prompt. At the 10.000V prompt press . once and to store the
10.000V input press > once.
5. Rewire for operation and verify calibration.
Current Process Input Procedure
Equipment
• Precision current source, 0 to 20mA range, with
0.01mA resolution.
Input x (1 to 3) Setup and Calibration
Inputs 2 and 3 appear only if the controller is the enhanced version (F4P _ - _ _ AB - _ _ _ _).
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
2. Connect the current source to input 1 terminals 60 (+) and 62 (-), input 2 terminals 54 (+) and 58 (-), or input 3 terminals 52 (+) and 56 (-).
3. Enter 4.000mA from the current source to the controller. Allow at least 10 seconds to stabilize. Press the Right Key . once at the Calibrate Input 1 prompt. At the 4.000mAprompt press . once and to store 4.000mA press the Up Key > once.
4. Enter 20.000mA from the current source to the controller. Allow at least 10 seconds to stabilize. Press . once at the Calibrate Input 1 prompt. At the 20.000mA prompt press . once and to store
20.000mA press > once.
5. Rewire for operation and verify calibration.
Process Output Procedure
Equipment
• Precision volt/ammeter with 3.5-digit resolution.
Output 1A Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 42 (+) and 43 (-).
3. Press the Right Key . at the Calibrate Output 1A prompt. At the 4.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate Output 1A prompt. At the 20.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the
display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value.
Volts
5. Connect the volt/ammeter to terminals 44 (+) and 43 (-).
6. Press the Right Key . at the Calibrate Output 1A prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value.
7. Press the Right Key . at the Calibrate Output 1A prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 10.000V. Press . to store the value.
8. Rewire for operation and verify calibration.
Output 1B Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 39 (+) and 40 (-).
3. Press the Right Key . at the Calibrate Output 1B prompt. At the 4.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate Output 1B prompt. At the 20.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value.
Volts
5. Connect the volt/ammeter to terminals 41 (+) and 40 (-).
6. Press the Right Key . at the Calibrate Output 1B prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value.
5.6 Factory Page Watlow Series F4P
7. Press the Right Key . at the Calibrate Output 1B prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 10.000V. Press . to store the value.
8. Rewire for operation and verify calibration.
Retransmit Output Procedure
Equipment
• Precision volt/ammeter with 3.5-digit resolution.
Retransmit 1 Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring Chapter and the Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 50 (+) and 49 (-).
3. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 4.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads
4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 20.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value.
Volts
5. Connect the volt/ammeter to terminals 48 (+) and 49 (-).
6. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value.
7. Press the Right Key . at the Calibrate Rexmit 1 prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 10.000V. Press . to store the value.
8. Rewire for operation and verify calibration.
Retransmit 2 Setup and Calibration
1. Connect the correct power supply to terminals 1, 2 and 3 (see the Installing and Wiring Chapter and the Appendix).
Milliamperes
2. Connect the volt/ammeter to terminals 47 (+) and 46 (-).
3. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 4.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 4.000mA. Press . to store the value.
4. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 20.000mAprompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 20.000mA. Press . to store the value.
Volts
5. Connect the volt/ammeter to terminals 45 (+) and 46 (-).
6. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 1.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 1.000V. Press . to store the value.
7. Press the Right Key . at the Calibrate Rexmit 2 prompt. At the 10.000V prompt press . once. Use the Up Key > or the Down Key < to adjust the display to the reading on the volt/ammeter. The controller should stabilize within one second. Repeat until the volt/ammeter reads 10.000V. Press . to store the value.
8. Rewire for operation and verify calibration.
Watlow Series F4P Parameters 6.1

Chapter Six: Parameters

Pages, Menus and Parameters . . . . . . . . . . . . . . . .6.1
Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.2
Operations Page Parameter Table . . . . . . . . . . . . .6.4
Operations Page Parameter Record . . . . . . . . . . . .6.10
Setup Page Parameter Table . . . . . . . . . . . . . . . . .6.11
Setup Page Parameter Record . . . . . . . . . . . . . . . .6.23
Custom Main Page Parameter Record . . . . . . . . . .6.25
Factory Page Parameter Table . . . . . . . . . . . . . . . .6.26
6

Pages, Menus and Parameters

The Series F4P parameters are arranged into four groups, or pages: Main; Operations, Setup and Factory. See the chapters about each page for additional informa­tion. The Features Chapter provides information about features, such as alarms, and the parameters that apply to them.
Only active parameters will appear on the controller. If, for instance, Output 1B is set to Off, no other output 1B parameters will appear.
Changing some parameters will force changes to other parameter settings. The safest and most efficient way to configure the Series F4P controller for the first time is to configure the parameters in the Setup Page in the order in which they appear.
It may also be helpful for you to make copies of the Pa­rameter Records for each of the pages, as well as the Custom Main Page Record, then record your settings for future reference.
Note: If the Series F4P is already installed in an oven, furnace or other equipment, most parameters will already be configured and access to the Setup Page may be limited (locked).
Note: To see how all the pages, menus and parameters are grouped, see the software map on the inside back cover of this manual.
Note: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.
6.2 Parameters Watlow Series F4P
Note: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.
Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
[Defaults de-
pend on the control type selected and set­tings in Setup>Cus­tom Main Page.]
None Input 1 [value] Input 1 Value bar
[graph] Input 2 [value] Input 2 Value bar
[graph] Input 3 [value] Input 3 Value bar
[graph] Dgt. [digital] Diff. [dif-
ferential] Value CTL SP [Differential
Set Point] Set Differential Dgt. [digital] Ratio
Value CTL SP [Ratio Set
Point] Set Ratio Digital Set Point Remote Set Point 2 Remote Set Point 3 Target Set Point [cascade] Inner Set
Point Set Point 1 Set Point 1 bar [graph] % Power 1A % Power 1B % Power 1A bar [graph] % Power 1B bar [graph] Tune Status 1 Digital Inputs
Parameter x (1 to 16)
View customized parame­ter list.
Alarm x (1 to 2) Condition
Input x (1 to 3) Error
Main Page
Main Page

Main Page Parameters

Watlow Series F4P Parameters 6.3
Note: For more information about how parameter settings affect the controller’s operation, see the Features Chapter.
Main Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
Go to Factory
Set security settings, cal­ibrate and restore factory settings, perform diag­nostics, test outputs.
Go to Setup
Set up inputs and out­puts, configure the sys­tem, design the Main Page, configure alarms, configure communication, and define static mes­sages.
Go to Operations
Auto-tune PID sets, edit PID parameters, select alarm set points, select PID crossover, select ramp to set point, select control set points, and mode.
6.4 Parameters Watlow Series F4P
Note: For more information about how param- eter settings affect the controller’s operation, see the Features Chapter.
* None of the B parameters are active if both out­puts are set to cool or heat.
Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear

Operations Page Parameters

Active: Always.* Based on deci-
mal setting.
1A 1B Set 500 550 [1] 510 560 [2] 520 570 [3] 530 580 [4] 540 590 [5] r/w
25°F 14°C
0 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Proportional Band x (A or
B)
Define the proportional band for PID control.
Main > Operations > Edit PID > PID Set Channel 1 > PID Set x (1 to 5)
PID Set x (1 to 5)* (Optional Inner Loop)
Main > Operations > Edit PID
Edit PID
Active if Analog Input 3 Control
Type is set to Cascade.
Outer loop is Input Channel 3.
343 r/w
Tune Off (0)Tune Off (0) Outer Loop PID Set 1 (1) Outer Loop PID Set 2 (2) Outer Loop PID Set 3 (3) Outer Loop PID Set 4 (4) Outer Loop PID Set 5 (5)
Cascade Outer Loop
Select which PID pa­rameters will be au­tomatically tuned.
Active if Analog Input 3 Control
Type is set to Cascade.
Inner loop is Input Channel 1.
305 r/w
Tune Off (0)Tune Off (0) Inner Loop PID Set 1 (1) Inner Loop PID Set 2 (2) Inner Loop PID Set 3 (3) Inner Loop PID Set 4 (4) Inner Loop PID Set 5 (5)
Cascade Inner Loop
Select which PID pa­rameters will be au­tomatically tuned.
Main > Operations > Autotune PID > Cascade
Autotune PID Cascade
Active if controller is in auto
(closed-loop) mode.
307 r/w
OffHeat Only (0) Cool Only (1) Heat and Cool (3)
Autotune PID Type
Select which output to autotune.
Active if controller is in auto
(closed loop) mode.
305 r/w
Tune Off (0)
Tune Off (0) PID Set 1 (1) PID Set 2 (2) PID Set 3 (3) PID Set 4 (4) PID Set 5 (5)
Channel 1 Autotune
Select which PID pa­rameters will be au­tomatically tuned.
Main > Operations > Autotune PID
Autotune PID
Loading...
+ 94 hidden pages