Grieve Corporation F4D Installation Manual

0600-0032-0000 Rev G
*0600-0032-0000*
April 2004 $15.00
User’s Manual

Series F4S/D

96mm x 96mm Ramping Controller (1/4 DIN)
with Guided Setup and Programming
1241 Bundy Boulevard, Winona, Minnesota USA
Registered Company
Winona, Minnesota USA
Watlow Winona is a division of Watlow Electric Mfg. Co., St. Louis, Missouri, a manufacturer of industrial electric heating products since 1922. Watlow begins with a full set of specifications and completes an indus­trial product that is manufactured in-house, in the U.S.A. Watlow products include electric heaters, sensors, controllers and switching devices. The Winona operation has been designing solid-state electronic control devices since 1962, and has earned the reputation as an excellent supplier to original equipment manufac­turers. These OEMs and end users depend upon Watlow Winona to provide compatibly engineered controls that they can incorporate into their products with confidence. Watlow Winona resides in a 100,000-square­foot marketing, engineering and manufacturing facility in Winona, Minnesota.

About Watlow Winona

About This Manual

The Series F4 User’s Manual covers hardware and software in both the Single­Channel and Dual-Channel controllers. Instructions and illustrations pertain
to both unless otherwise specified. If a given feature or parameter operates on only the Single or the Dual Channel controller, it will be identified by an icon in the margin or nearby.
Your comments or suggestions on this manual are welcome. Please send them to the Technical Literature , Watlow Winona, 1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota, 55987-5580 U.S.; Telephone: +1 (507) 454-5300; fax: +1 (507) 452-4507.
Copyright July 2002 by Watlow, Inc., with all rights reserved. (2249)

Your Comments

1
Single
Channel
F4S
2
Dual
Channel
F4D
Watlow Series F4S/D Table of Contents ■ i
Introduction
Chapter 1: Introduction . . . . . . . . . . . . . . . . . 1.1
Chapter 2: Keys, Displays and Navigation . . .2.1
Operations
Chapter 3: Operations . . . . . . . . . . . . . . . . . .3.1
Profiles
Chapter 4: Profile Programming . . . . . . . . . . .4.1
Setup
Chapter 5: Setup . . . . . . . . . . . . . . . . . . . . . .5.1
Chapter 6: Features . . . . . . . . . . . . . . . . . . . .6.1
Chapter 7: Communications . . . . . . . . . . . . . .7.1
Factory
Chapter 8: Security and Locks . . . . . . . . . . . .8.1
Chapter 9: Calibration . . . . . . . . . . . . . . . . . . .9.1
Chapter 10: Diagnostics . . . . . . . . . . . . . . . .10.1
Installation and Wiring
Chapter 11: Installation . . . . . . . . . . . . . . . . .11.1
Chapter 12: Wiring . . . . . . . . . . . . . . . . . . . .12.1
Appendix
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . .A.2
CE Declaration of Conformity . . . . . . . . . .A.5
Product Specifications . . . . . . . . . . . . . . .A.6
Ordering Information . . . . . . . . . . . . . . . . .A.7
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A.8
List of Figures . . . . . . . . . . . . . . . . . . . . . .A.13
Software Map . . . . . . . . . . . . . . . . . . . . . .A.16
Series F4S/D: Table of Contents
T
A downloadable electronic copy of this user manual is available free of charge through Watlow's web site: http://www.watlow.com/prodtechinfo. Search on Series F4.
ii Table of Contents Watlow Series F4S/D
Safety Information in this Manual
Note, caution and warning symbols appear throughout this book to draw your attention to important operational and safety information.
A “NOTE” marks a short message to alert you to an important detail. A “CAUTION” safety alert appears with information that is important for protecting your
equipment and performance. A“WARNING” safety alert appears with information that is important for protecting you,
others and equipment from damage. Pay very close attention to all warnings that apply to your application.
The ç symbol (an exclamation point in a triangle) precedes a general CAUTION or WARNING statement.
The Ó symbol (a lightning bolt in a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.

Technical Assistance

If you encounter a problem with your Watlow controller, review all configuration information to verify that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem persists after checking the above, you can get technical assistance by calling your local Watlow representative (see back cover of this manual), or in the U.S., dial +1 (507) 494-5656. For technical support, ask for an Applications Engineer.
Please have the following information available when you call:
• Complete model number • All configuration information
• User’s Manual • Diagnostic menu readings

Warranty

The Watlow Series F4 is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse or abuse.

Returns

Call or fax your distributor or the nearest Watlow sales office for best information about returns. (See outside back cover.)
•To return directly to Watlow Winona in the U.S., first call or fax Customer Service for a Return Material Authorization (RMA) number (telephone: +1 (507) 454-5300; fax: +1 (507) 452-4507).
Put the RMA number on the shipping label, along with on a written description of the problem.
•Arestocking charge of 20% of the net price is charged for all standard units returned to stock. Returned units must be in like new condition and must be returned within 120 days of initial receipt of the product.
ç
Safety Alert
CAUTION or
WARNING
Electrical Shock Hazard
CAUTION or
WARNING
Watlow Series F4S/D Introduction 1.1
1

Chapter One: Introduction

Overview

Inputs and Outputs

Figure 1.1a — Single-Channel Series F4 (F4S_ - _ _ _ _ - ____ ) Inputs and Outputs.
Figure 1.1b — Dual-Channel Series F4 (F4D_ - _ _ _ _ - ____ ) Inputs and Outputs.
1B
2A
2B
1A
1B
1A
Watlow’s Series F4 1/4 DIN industrial ramping controllers are easy to set up, program and operate in the most demanding ramp-and-soak-processing applications. The F4 includes:
• four-line, high resolution LCD display
• guided setup and programming software
• 16-bit microprocessor
• 256 possible ramp steps in as many as 40 vari­able-length, nameable profiles
• six step types
• eight programmable event outputs, compressor control, boost heat/boost cool, power-out selec­tions and a real-time clock.
• Note: the F4S has two less analog inputs and two less control outputs than the F4D.
1 Universal
1
Single
Channel
F4S
1 Communication I/O
Analog Input (2 optional)
4 Digital Inputs
…Alarm1 Lo Deviation
Adjusts Value Back Next
–1
i
F
4
1A
1B
2 Control Outputs
1
F
2 Alarm Outputs
2
2 Retransmit Outputs (optional)
8 Digital Outputs
F
4
1A
2
Dual
Channel
F4D
3 Universal Analog Inputs
4 Digital Inputs
…Alarm2 Low SP_______
32 F Adjusts Value Back Next
1B
2A
4 Control Outputs
2B
1
2 Alarm Outputs
2
2 Retransmit Outputs (optional)
1 Communication I/O
i
8 Digital Outputs
Sample Application: Environmental Testing
with a Dual Channel F4 Using Multiple Inputs and Outputs
Figure 1.2 — Sample Application 1: Series F4 Dual Channel Using Multiple Inputs and Outputs.
F
4
1
2
i
1B1B
2A2A
2B2B
1A1A
Main Page___________
Go to Profiles
Go to Setup Go to Factory
Overview
Andy, an engineer with the Ajax Testing Company, is running tempera­ture and humidity tests on navigation­al equipment. He wants to be able to control temperature and humidity in the environmental chamber, and moni­tor the temperature of the equipment itself. With the Watlow Series F4 ramp­ing controller, he can:
•program the test as a ramping profile and control it remotely;
•use boost heat and cool to maintain precise temperatures;
•record the equipment temperature on a chart recorder;
•notify the operator with a bell if pro­cess temperatures do not follow the profile;
•pause the profile if someone opens the chamber door during the test;
•set up communications with a PC later.
5. Run the Profile
Andy pressed the Profile Key and selected the test profile. He monitored the progress of the test on the display and the equipment temperature on the chart recorder.
See the Operations Chapter.
1. Wire
Following diagrams in the user manual, Andy connected the analog input terminals to temper­ature and humidity sensors, channel 1 output terminals to the heater and cooler, channel 2 outputs to the humidifier/dehumidifier, alarm output 1 to an alarm bell and retransmit output 1 to a chart recorder to track the equipment temperature. Digital output 6 and 7 controlled the boost heater and cooler, and 8 controlled the mechanical refrigeration compressor.
See the Wiring Chapter.
1.2 Introduction Watlow Series F4S/D
Watlow Series F4S/D Introduction 1.3
This sample application is continued in the Operations, Profile Programming and Setup Chapters.
Main Page___________
3. Customize and Name
Andy customized the Main Page so he could tell the status of the digital outputs by glanc­ing at the controller's Lower Display (Setup Page > Custom Main Page Menu).
He also named one of the Alarms "TEMP DEV", which will make it easy to identify the alarm condition (Setup Page > Alarm Output 1 Menu). Three digital inputs, two alarms and eight digital outputs can be given 10­character names.
See the Setup Chapter.
4. Program the Profile
Andy programmed the test as a ramping pro­file of 21 steps. To make sure the equipment is at the ambient chamber temperature, he put a Wait condition on Step 2. Step 20 is a Jump step that puts the equipment through the same heat and humidity cycle 21 times.
See the Profile Programming Chapter.
NOTE: The profile in this sample application is embedded in the Series F4 software for use as a teaching tool or a template. It is the first profile, MILSTD810D, located in the Profiles Page > Edit Profile Menu. You can change or delete this profile and later recall it through factory defaults. If you have a single-channel controller, you will see only the tem­perature on Channel 1. This is not the true Military Standard Test 810D.
1B
2A
2B
1A
Step 1: Ramp Time Step 2: Ramp Time Step 3: Soak Step 4: Jump
2. Set up the F4
After checking the navigation instructions in the user manual, Andy went to the Setup Page of the software to configure the controller for the equipment and the ramp­ing profiles. He named the alarm to make it easier to identify an alarm condition. The alarm message will appear on the Lower Display, which also informs about the progress of the test.
See the Keys, Displays and Navigation Chapter. See the Setup Chapter.
Go to Profiles
Go to Setup Go to Factory
Choose to Setup:____
Digital Output8
Communications Custom Main Page
F
4
1A
1B
2A
Main Page___________
Go to Profiles
Go to Setup Go to Factory
i
2B
1
2
1.4 Introduction Watlow Series F4S/D

Setup Steps

The ˆ Key
During all these steps, the Information Key will summon helpful definitions and setup tips. Just position the cursor next to the item you want to know more about, then press the key. Press it again to return to your task.
See Chapter 3, Operations.
7
Run the profile (or establish a set point
for static set point control).
See Chapter 4, Profile Programming.
6
Program a profile.
See Chapter 7, Communications.
5
Set up serial communications.
See Chapter 3, Operations.
4
Tune the system and set alarm set points.
Learn to navigate the software in Chapter 2, Keys, Displays and Navigation, and then go to Chapter 5, Setup. For background, you may also
want to refer to Chapter 6, Features. (This step
may not be necessary if the Series F4 is already installed in the equipment.)
3
Set up the controller to suit your basic
application.
See Chapter 12, Wiring. (This step will not be necessary if the Series F4 is already installed in equipment.)
2
Wire the controller.
See Chapter 11, Installation. (This step will not be necessary if the Series F4 is already installed in equipment.)
1
Install the controller.
How to do itWhat to do
• If the Series F4 is an independent unit, start with Step 1 below.
• If the Series F4 is already installed in and set up for a piece of equipment, proceed to Steps 4, 5, 6 and 7 below.
• If the Series F4 is already installed in a piece of equipment and the setup and profile pro­gramming functions are locked, proceed direct­ly to Step 5 or 7.
Watlow Series F4S/D Keys, Displays and Navigation 2.1
Chapter Two: Keys, Displays &
Navigation
Displays and Indicator Lights . . . . . . . . . . . . . . . . .2.2
Custom Main Page . . . . . . . . . . . . . . . . . . . . . . . . .2.3
Keys and Navigation . . . . . . . . . . . . . . . . . . . . . . . .2.4
Guided Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5
How to Enter Numbers and Names . . . . . . . . . . . .2.6
ˆ Information Key Answers Your Questions . . . . .2.7
Main Page Parameter Table . . . . . . . . . . . . . . . . . .2.8
Overview
This chapter introduces the user interface of the Series F4S/D controller — the displays, keys and indicator lights, and the principles of navigating the software to program profiles and change setup settings. The Series F4 is designed with user­friendly features to facilitate setup, programming and operation of the Series F4.
The four-line LCD display facilitates setup and programming, and presents informative messages about status, error and alarm conditions.
Digital inputs, digital outputs, profiles and alarms can be named for easy reference.
The Information Key summons information about the pages, menus, parameters and values, as well as error and alarm conditions if they occur.
The software is organized into five pages of menus. The Main Page gives access to the other four — Operations, Profiles, Setup and Factory. The Main Page can be customized to display user-chosen information.
2

Displays and Indicator Lights

Figure 2.2 — Series F4S/D Displays and Indicator Lights. (F4D shown)
1B
2A
2B
1A
2.2 Keys, Displays and Navigation Watlow Series F4S/D
Upper Display
Displays Channel 1 actual process values during operation. Displays error information if errors occur.
Lower Display
Displays information about the setup, operation and programming of the controller.
Cursor (>):
Indicates selected parameter or present value in F4 mem­ory. Moves via the four navi­gation keys.
Profile Indicator Light (Run/Hold status):
• Lit when a ramping profile runs.
• When blinking, the profile is on hold.
• When not lit, the controller operates as a static set point controller.
Main Page___________
Go to Profiles
Go to Setup Go to Factory
i
Active Output Indicator Lights (Output status):
Lit when the corresponding controller channel output is active. (F4D shown)
F
4
1A
1B
2A
2B
1
2
Alarm Output Indicator Lights (Alarm status):
Lit during an alarm state.
Communications Indicator Light (Communication status):
Lit (pulsates) when the con­troller sends or receives valid data.
Scroll Bar (Scroll up or down):
Appears when the Up or Down Keys can reveal more information in the Lower Display.
Watlow Series F4S/D Keys, Displays and Navigation 2.3

Custom Main Page

Figure 2.3 — Default Main Page Parameters.
The first and central page on the Lower Display is the Main Page, which shows error messages, input, output and profile status, and allows access to con­troller software (Go to Operations, Profiles, Setup and Factory).
The Main Page can be customized to display cho-
sen information. (To do so, go to the Setup Page, Custom Main Page Menu. See Chapter 5, Setup, for instructions.)
The following parameters will appear by default on the Main Page, unless the Main Page has been cus­tomized.
Main Page_____
Will always appear if active:
Will appear if active and if set up to appear:
Will appear if active and selected to appear:
Will appear by default (Profile information will appear by default if a profile is running.)
Will always appear unless customized:
:
Input 1 Error Input 2 Error Input 3 Error
Alarm 1 Condition Alarm 2 Condition
Autotuning Ch 1 Autotuning Ch 2
Current File Current Step Input2 Set Point 1 Set Point 2 Step Type Target SP1 Target SP2 Wait for Status Time Remaining Digital Ins Digital Outs % Power1 % Power2 Date Time
Press < to scroll down the list.
Read-only information
Static set point control
Read-only information
>Go to Operations Go to Profiles Go to Setup Go to Factory
Access to software
2
Dual
Channel
F4D
2.4 Keys, Displays and Navigation Watlow Series F4S/D

Keys and Navigation

Figure 2.4 — Series F4 Keys and Navigation.
1B
2A
2B
1A
T
f
Setup Page
Main>Setup Choose to Setup System
hink of this display as a window into the software table. You move around in the software using the
ollowing navigation keys:
> Move Up/Increase
, . < Move Down/Decrease
Back Next
Profile Key (Profile Run/Hold):
Summons a menu that allows you to start, hold, resume or terminate a profile.
Information Key (Toggle for more information):
Provides information in the Lower Display about the cursor-selected parameter. Another press toggles the display back to the parameter.
Analog Input 1
Main Page___________
Go to Profiles
Go to Setup Go to Factory
i
4-20mA 0-20mA 0-10V 0-5V 1-5V 0-50mV Choose Units Temperatur 2500 ft %rh PSI units Choose Decimal 0
0.0
0.00
0.000
F
4
1A
1B
2A
2B
1
2
Up and Down Keys (Move Up/Increase and Move Down/Decrease):
Move the cursor (>) position in the Lower Display through the software in the direction of the key arrow. Increase or decrease a value, or change a letter in a user­nameable field, such as alarms, events and profile names.
Left and Right Keys (Back Out and Next):
Move right to select the choice to the right of the cursor and proceed to the next screen. Move left to exit.
Watlow Series F4S/D Keys, Displays and Navigation 2.5

Guided Setup

In most F4 menus, setup and programming tasks are guided. For example, once you select Analog Input 1 on the Setup Page, all parameters neces­sary to configure that input are linked:
1. Use > < to move the cursor to select an item in a list.
2. Press the Right Key ..
3. Enter the value and make a choice.
4. Press . again.
5. Repeat until you return to the original list.
. saves the value and proceeds to the next
parameter in the series.
, saves the value and backs out of the series, and
returns to the Main Page.
For initial setup and programming, we recommend that you answer all the questions in the series, entering values for all linked parameters and pressing . until you return to your starting point.
To edit a parameter, proceed through the series without changing values until you find the parame­ter you want to change. After making the change, you may back out or proceed to the end of the series.
NOTE: The Edit PID Menu (Operations Page) presents lists of parameters that can be entered and edited individually. Press either
. or , to enter the value and return to
the list.
NOTE: Make sure your setup is complete before entering profiles. Certain analog input setup changes will delete profiles.
.
.
.
.
.
.
,
Save setup changes or restore values?
Restore Save
Choose to Setup:____ >Control Output 1A
Control Output 1B Control Output 2A
Enter Lo Power Limit
0%
▲▼ Adjusts Value
< Back > Next
Enter Hi Power Limit
100%
▲▼ Adjusts Value
< Back > Next
Choose Cycle Time:__ >Variable Burst
Fixed Time
Choose Function:____ >Heat
Cool
Choose to Setup:____ >Control Output 1A
Control Output 1B Control Output 2A
Main Page___________
Go to Operations Go to Profiles
>Go to Setup
2.6 Keys, Displays and Navigation Watlow Series F4S/D

How to Enter Numbers and Names

Figure 2.6 — How to Enter Numbers and Names. (F4D shown)
1B
2A
2B
1A
1B
2A
2B
1A
Many parameters require users to enter a numeri­cal value. Alarms, digital inputs, digital outputs and profiles can be customized with easily recog-
nized names, such as TOO HOT for an alarm, DOOR OPEN for a digital input and GLAZE 6 for a profile.
Numbers
Z
Y
X
W
C
B
A
9
8
7
6
5
4
3
2
1
Ø
If the cursor is at Z, press
< to go
down to A, then from 9 to 0. Blank is on the end.
Blank
1. Navigate
to the parameter you want to change.
You'll change the value on this line.
Names
1. Navigate
to the parameter you want to name.
You'll change each letter on this nameable 10-character line.
Alarm Hysteresis:___ 36 °F Adjusts Value Save Changes
Enter Alarm Name:___ ALARM1
Adjusts Char
Back Next
F
4
1A
1B
2A
2B
1
2
4. Press . to enter
the value.
i
3. Scroll to increase or
decrease the value of the digit.
2. Move right or left, if necessary, to choose the digit to change.
(Some numbers increase or decrease as single units; others digit by digit.) The active position is underlined.
F
4
1A
1B
2A
i
2B
1
2
4. Press . to move to the
end of the 10-character name space and proceed to the next screen. This enters the name.
3. Scroll to choose the new
letter or a number.
2. Move right or left to choose the character to change.
(The position is underlined.)
Watlow Series F4S/D Keys, Displays and Navigation 2.7
ˆˆ
Information Key Answers Your Questions
Figure 2.7 — The Information Key. (F4D shown)
1B
2A
2B
1A
There’s a wealth of information about features and parameters right in the Series F4 controller. Use the Information Key to get this information.
1. Use the four navigation keys (< > , . ) to position the cursor (>) next to the parameter you want to know more about.
2. Press the ˆ key. The displayed information will assist you during setup and operation. When information takes more than four lines, the scroll bar will be filled or weighted at the end, directing you to press < or > to see the rest.
3. Press ˆ again to return to your task.
Toggle the Information Key ˆ between the parameter you need to know about and its functional definition.
The second press takes you back to where you were.
Choose to Setup:____
System
Analog Input 1 Analog Input 2
The scroll bar indicates more information above or below; use the keys.
> and <
F
4
1A
1B
2A
2B
1
2
i
i
Main Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
Go to Factory
Set security settings, and calibrate and re­store factory settings.
Go to Setup
Set up inputs and outputs, configure the system and design the Main Page.
Go to Profiles
Create, edit, delete and rename profiles.
Go to Operations
Auto-tune PID sets, edit PID parameters and select alarm set points.
*Digital outputs configured as events can be turned on/off in the static set point mode or when a running profile is on hold. The event output status will remain as set until reset by the profile or by the operator.
Current File Current Step Input 2 value Set Point 1 Set Point 2 Step Type Target SP1 Target SP2 Wait for
Status
Time
Remaining Digital Ins Digital Outs* % Power 1 % Power 2 Date Time
None Input 1 Value Input 2 Value Input 3 Value Set Point 1 Set Point 2 % Power 1 % Power 2 Tune status 1 Tune status 2 Time Date Digital Ins Digital Outs Time Remaining Current File Current Step Active Ch1 PID Set Active Ch2 PID Set Last Jump Step Jump Count WaitFor Status Step Type Target SP1 Target SP2 Inner Set Point Custom Message 1 Custom Message 2 Custom Message 3 Custom Message 4 Input 1 Cal. Offset Input 2 Cal. Offset Input 3 Cal. Offset
Parameter x (1 to 16)
View customized parameter list.
Autotuning Channel x (1 or 2)
Alarm x (1 to 2) Condition
Input x (1 to 3) Error
Main > Setup > Main Page
Main Page
2.8 Keys, Displays and Navigation Watlow Series F4S/D
Watlow Series F4S/D Operations 3.1
3

Chapter Three: Operations

Static Set Point Control . . . . . . . . . . . . . . . . . . . . . .3.1
Profile Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2
Alarm Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4
Clearing Alarms and Errors . . . . . . . . . . . . . . . . . . .3.4
Auto-tune PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4
Edit PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4
Multiple PID Sets . . . . . . . . . . . . . . . . . . . . . . . . . . .3.5
Cascade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.6
Sample Application . . . . . . . . . . . . . . . . . . . . . . . . .3.7
Troubleshooting Alarms and Errors . . . . . . . . . . . . .3.8
Operations Page Map . . . . . . . . . . . . . . . . . . . . . . .3.10
Operations Page Parameter Table . . . . . . . . . . . . .3.11
Operations Page Parameter Record . . . . . . . . . . . .3.15
Series F4S/D Operation
The Series F4S/D controller can function as either
a static set point controller or as a profile con- troller. The information shown on the Lower Dis­play during operation (the Main Page) is pro­grammable and can be customized to support both modes of operation. (See Setup Page.)
In either the static set point mode or the profile mode, the Series F4 can only be operated in a closed-loop configuration. Manual operation (open­loop) mode is not allowed.
Static Set Point Control
The Series F4 is in static mode when it is not con-
trolling a ramping profile. When in static mode:
• The Profile Indicator Light is off.
• The Upper Display shows the actual process temperature of input 1, 2 or 3 depending upon Setup Page configuration.
NOTE:
All control activity stops when you enter the Setup Page, Analog Input, Digital Input, Control Output, Alarm Out­put, Retransmit, and Digital Output menus.
• The Lower Display shows the default or user­configured information set. See the Setup Chapter for instructions in programming the Main Page to display the information you want.
To operate the Series F4 as a static set point con­troller, use the navigation keys (><,.) to select the preferred channel and adjust the set point.
Limits may be placed on the set point in the Set Point Low Limit and Set Point High Limit parame­ters (Setup Page > Analog Inputx).
Setting the set point to Set Point Low Limit minus 1 (-1) will turn control Output 1 off and display the set point as off.
Static Set Point1___
OFF
▲▼ Adjusts Value
< Back > Next
Static Set Point1___
___ °F
▲▼ Adjusts Value
< Back > Next
3.2 Operations Watlow Series F4S/D
ç WARNING
Check the configuration of the controller on the Setup Page before starting and running a profile (if the Setup Page is not locked). Make sure the settings are appropri­ate to the profile: input sensor ranges and limits, digital inputs and outputs as events, guaranteed soak band, re­sponse to power out and Celsius or Fahrenheit scales. If the Setup Page is accessible, failure to check the configu­ration before running a profile could result in damage to equipment and/or property, and/or injury or death to per­sonnel.
Profile Control π
The main purpose of the Series F4 is to control pro­files for ramp-and-soak-processing applications. The instructions below explain how to use an exist­ing profile. To program a profile, see Chapter 4, Profile Programming.
>
Start a Profile?
No Yes
■■■■■■■■■■■■■■■■
To Start/Run a Profile
To initiate the profile mode, press the Profile Key
π and answer the questions that follow.
While running a profile, the Profile Status message on the lower display will keep you informed about the progress of the profile. For example, it could read like the screen at right:
NOTE: As a protective measure, all stored profiles will be cleared if you enter the Setup Page and change values in the Analog Input 1, 2, 3 menus —specifically, the Sensor, Sensor Type, Decimal, Scale (for process inputs), and Set Point High and Low Limits. Pop-up messages will warn that the profiles will be erased from the controller’s mem­ory.
NOTE: You must configure the software for your inputs and out­puts before programming a profile. See the Setup Chap­ter.
NOTE: You must program a profile or use the pre-programmed MILSTD810D profile before running it. See the Profile Programming Chapter.
NOTE: While a profile is running, the controller will not recog­nize digital inputs that are programmed to start a profile. Such digital inputs will be recognized only while the con­troller is in the static set point mode.
NOTE: While a profile is running, profiles can be either created or renamed only while a profile is running. All other pages and menus can be entered only during Static Set Point Control mode.
Glaze 8 Running. Step 2 Remain 00:10:30
.
Start:_______________
Step 1 Autostart
>Step 2 Ramp Time
Step 3 Ramp Time
.
Start Profile:_______
MILSTD810D..........
ALUMINUM
>Glaze 8
Watlow Series F4S/D Operations 3.3
π The Profile Key:
• initiates the ramping profile mode;
• initiates the Hold-profile state;
• initiates the Resume-profile command;
• initiates the Terminate-profile command.
The Profile Key functions only from the Main Page. It will not function from any of the other pages — Operations, Profile, Setup or Factory.
To Resume a Profile on Hold
1. Press the Profile Key π while a profile is holding. The Resume Profile Menu appears.
2. Choose to Continue Holding, Resume or
Terminate the profile.
If you do not make a choice, the profile continues holding and the Profile Indicator Light stays off.
NOTE: When a profile is resumed during a Ramp step, the con­troller uses the Static Set Point from the Main Page to calculate the rate of change needed to get to the set point at the end of the step. When a profile is resumed in a soak step, the new set point value will be used as the soak value for the time remaining in the step.
Resume Profile:_____ >Continue Holding
Resume Terminate
To Terminate a Running/Holding Profile
1. Press the Profile Key π while a profile is
running. The Profile Action Menu appears.
2. Choose to Continue, Hold or Terminate the
profile. (Default is to Continue.) If you choose to terminate, the profile ends with all outputs off. The set point on the Main Page reads off.
If you do not make a choice when the Profile Action Menu appears, the profile continues as it was — running or holding.
NOTE:
The Profile Status message takes precedence over all oth­er information except errors, alarm messages and input status. Errors and alarm messages always take prece­dence over Profile Status.
Hold Profile:_______
Don’t Hold Hold
>Terminate
To Hold a Running Profile
1. Press the Profile Key π while running a pro­file. The Profile Action Menu appears.
2. Choose to Don’t Hold, Hold or Terminate
the profile. (Default is to Don’t Hold.) If you
choose to hold the profile, the Main Page reap­pears, and the Profile Status message reads “Profile X holding.” The Profile Indicator Light is off.
If you do not make a choice when the Profile Action Menu appears, the profile continues running and the profile indicator light stays on.
NOTE: While profiles are on hold, the step set point value can be adjusted using the Static Set Point parameter on the Main Page.
Hold Profile:_______
Don’t Hold
>Hold
Terminate
3.4 Operations Watlow Series F4S/D

Alarm Set Points

The Series F4 includes two alarm outputs, which can be programmed as process or deviation alarms.
Process alarms notify the operator when process values exceed or fall below Alarm Low and Alarm High Set Points. Deviation alarms notify the opera­tor when the process has deviated from the set point beyond the deviation limits. For more infor­mation, see the Features Chapter. To set up the alarms, see the Setup Chapter.
Alarm set points are the points at which alarms switch on or off, depending on the alarm setting. Alarm set points can be viewed or changed in the Alarm Set Point Menus (Operations Page).
The Alarm High Set Point defines the high tem­perature that, if exceeded, will trigger an alarm. This temperature must be higher than the alarm low set point and lower than the high limit of the sensor range.
The Alarm Low Set Point defines the low tem­perature that, if exceeded, will trigger an alarm. This temperature must be lower than the alarm high set point and higher than the low limit of the sensor range.
TIP:
You may want to set up the alarms with names that will identify the alarm conditions. See the Setup Page.
To Clear an Alarm or Error
In an alarm condition, an alarm message will ap­pear on the Main Page (if this option has been se­lected on the Setup Page). To silence it, move the cursor to the alarm message and press the Right Key . . Apop-up message will confirm the silenc­ing of the alarm, and the indicator light will go off.
When the condition causing the error or alarm is corrected, return to the error or alarm message on the Main Page, and press the Right Key again. A pop-up message confirms the alarm is unlatched.

Auto-tune PID

In autotuning, the controller automatically selects the PID parameters for optimal control, based on the thermal response of the system. In the Series F4, five sets of PID values are available for each channel of the controller: sets 1 to 5 for channel 1, and sets 6 to 10 for channel 2. Default PID values exist for all PID sets, although these values typi­cally do not provide optimal control. PID values can be auto-tuned or adjusted manually. When au­totuning is complete, the PID values will be stored in the Edit PID Menu.
NOTE: PID Set 1 for Channel 1 and PID Set 6 for Channel 2 are used in the Static Set Point mode.
Autotuning Procedure
Autotuning cannot be initiated while a profile is running. It can only be initiated in the static set point control mode.
1. Before initiating auto-tune, go to the System
Menu (Setup Page), and set the Channel 1 or 2 Autotune Set Point to the percentage of set point you choose to begin with. This percentage is based on your knowledge of the system and how much overshoot or undershoot there is likely to be in on-off control.
In the Custom Main Page, select to display Tune Status 1 and Tune Status 2. This displays Tune Status in the Main Page.
2. Go to the Main Page and set the static set point.
3. Go to the Autotune PID Menu (Operations Page)
and choose the channel to auto-tune and the PID set in which to store the settings. Amessage will be displayed on the Main Page during the auto­tuning process. (Auto-tune cannot be initiated when a profile is running. It can only be initiated in the static set point mode.)
4. When autotuning is complete, the controller will
store the values for optimum control in the PID set specified.
NOTE: While the controller is autotuning, profiles cannot be run and only the Profiles Page and Operation Page of the software can be entered.
ç
CAUTION: Choose an auto-tune set point value that will protect your product from possible damage from overshoot or undershoot during the autotuning oscillations. If the product is sensitive, select the auto-tune set point very carefully to prevent product damage.
For additional information about autotuning and proportion­al, integral and derivative control, see the Features Chapter.

Edit PID

Edit PID is useful when Auto-tune PID does not provide adequate control. Each of the PID parame­ters can be adjusted manually:
Proportional Band: Define a band for PID con­trol, entered in degrees or units. Lower values in­crease gain, which reduces droop but can cause os­cillation. Increase the proportional band to elimi­nate oscillation.
Watlow Series F4S/D Operations 3.5
Integral (Reset): Define the integral time in min­utes per repeat; define reset in repeats per minute. Set repeats per minute if units are U.S.; minutes per repeat if units are SI.
Derivative (Rate): Define the derivative (rate) time in minutes. Large values prevent overshoot but can cause sluggishness. Decrease if necessary.
Dead Band: Define the dead band in degrees or units. Heating dead band shifts the set point down. Cooling dead band shifts the set point up. For more information, see the Features Chapter.
Manual Tuning Procedure
1. Apply power to the Series F4 and enter a set point. Go to the Operations Page, Edit PID Menu and begin with Proportional Band set to 5; Inte­gral (Reset) set to 0; Derivative (Rate) set to 0; and Autotune set to Tune Off.
2. Start manual tuning by entering the desired set point and let the system stabilize. Once the sys­tem stabilizes, observe the value of Input 1 on the Main Page. If the Input 1 value fluctuates, increase the proportional band setting until it stabilizes. Adjust the proportional band in 5º to 10º increments, allowing time between adjust­ments for the system to stabilize.
3. Once Input 1 has stabilized, observe the percent power on the Main Page. It should be stable, ±2%. At this point, the process temperature should also be stable, but it will exhibit droop (stabilized below set point). The droop can be eliminated with reset or integral.
4. Start with a reset setting of 0.01, and allow 10 minutes for the process temperature to come up to set point. If it has not, increase the setting to
0.05 and wait another 10 minutes. After this, double the reset setting and wait another 10 minutes until the process value equals the set point. If the process becomes unstable, the reset value is too large. Decrease the setting until the process stabilizes.
5. Increase Derivative/Rate to 0.10 minute. Then raise the set point by 20° to 30°F, or 11° to 17°C. Observe the system's approach to the set point. If the load process value overshoots the set point, increase Derivative/Rate to 0.50 minute.
Raise the set point by 20° to 30°F, or 11° to 17°C and watch the approach to the new set point. If you increase Derivative/Rate too much, the ap­proach to the set point will be very sluggish. Re­peat as necessary until the system rises to the
new set point without overshooting or approach­ing the set point too slowly.
For additional information about manual tuning and proportional, integral and derivative control, see the Features Chapter.
Multiple PID Sets
Environmental chambers, ovens and furnaces typi­cally have different thermal requirements when they operate at high and low temperatures or pres­sures. To accommodate varying thermal require­ments, the F4 is capable of storing five different PID sets for each channel. One set for each channel can be chosen in each profile step.
For example, a controller in an environmental chamber with PID settings optimized for control at subzero temperatures may not control well when the set point is set to temperatures above the boil­ing point of water. With the F4, one PID set could be used for subzero operation and another set for temperatures above boiling.
Multiple Tuning Procedure
1. To auto-tune a single PID set, begin by setting the static set point on the Main Page.
2. Go to the Autotune PID Menu (Operations Page), and choose a channel and a set. Autotuning be­gins when you select the set. The Main Page dis­plays information about the autotuning process when Tune Status is selected in the Custom Main Page.
3. When autotuning is finished, proceed with another PID set.
In the example above, the user would first auto­tune a PID set for subzero operation, and then an­other for operation at boiling temperatures. When programming a profile, the user could then select a different PID set for each step, depending on the thermal requirements.
NOTE:
Autotuning cannot be done while running a profile. It can only be initiated when the controller is in the Static Set Point Control mode.
3.6 Operations Watlow Series F4S/D

Cascade

Cascade control is available on the Series F4 con­trollers. For background information about cascade control, see the Features Chapter.
Select cascade control through the Analog Input 3 Menu (Setup Page) and choose Process Cascade or Deviation Cascade. To set the range for the Process Cascade Inner Loop set point, use Low and High Range settings. These are independent of the Chan­nel 1 set point. Deviation Cascade uses Deviation Low and High settings that are referenced to the Channel 1 set point.
Deviation Cascade is used in applications with large set point ranges or where limiting heating or cooling equipment temperatures is required.
When tuning a cascade system, the inner loop must be tuned first. The inner loop comprises outputs 1A and 1B and the Analog Input 1 sensor, which usually measures the energy source temperature. The output device controls a power switching device, which in turn switches the heating and cooling. The set point for the inner loop is generated by the outer loop. For Process Cascade, this will have a range between the Cascade Low Range and Cascade High Range.
Cascade Setup Procedure
1. First, configure Analog Input 3, Cascade Low Range and Cascade High Range.
Go to the Analog Input 3 Menu (Setup Page). Choose Process or Deviation Cascade. Deviation Cascade references Channel 1 set point allowing a range above and below the current control set point. For Process Cascade control of a heat/cool or cool only system, set the Cascade Low Range to a value slightly lower than the lowest temperature desired in the chamber. For heat-only systems, set the Cascade Low Range to a value slightly lower than the ambient temperature; otherwise the heat output will never turn fully off.
For heat/cool or heat only systems , set the Cas­cade High Range to a value slightly higher than the highest temperature desired in the chamber. For cool-only systems, set the Cascade High Range to a value slightly higher than the ambient tem­perature; otherwise the cooling will never fully turn off.
2. Next, configure the controller to tune and display data for the outer loop. To view Inner Loop Set Point in the upper display, go to the Setup Page, Custom Main Page Menu, select the Inner Set point as one of the parameters, P1 to P16, to be displayed in the Main Page.
To also view Analog Input 3 in the upper display, go to the Setup Page, Process Display Menu, and choose Alternating. Under Set Display Time, choose a duration for the display of the Input 1 and Input 3 variables.
Cascade Autotuning Procedure
1. Go to Setup Page, Custom Main Page Menu. Choose Tune Status 1 and Tune Status 2 to ap­pear as 2 of the 16 parameters that can be dis­played on the Main Page. The Main Page will now display the status of the autotuning process.
2. Autotune the inner loop. Go to the Autotune PID Menu (Operations Page), and select Cascade In­ner-loop. Choose Cascade Inner Loop PID Set 1 to 5, where PID values will be stored after autotun­ing. Autotuning begins when you choose the PID set. While autotuning, the F4 controller will con­trol the energy source in an on-off mode to a tem­perature equal to the Cascade High Range setting x Channel 1 Autotune Set Point. For best results, use proportional control only on the inner loop.
3. Next, autotune the outer loop. Go to the Auto­tune PID Menu (Operations Page). Choose Cascade Outer Loop, then choose Outer Loop PID set 1 to 5, where PID values will be stored after autotuning. Autotuning begins when you choose the PID set. While autotuning, the outer loop will be controlled in an on-off mode at a set point equal to static set point x Ch 1 Autotune Set Point. In most cases, the autotuning feature will tune for acceptable control. If not, manually tune the outer loop (step 4 below). Before manually tuning, record the values generated by the auto­tuning feature.
4. To manually tune the outer loop, go to the Edit PID Menu (Operations Page). Choose Cascade Outer Loop, then choose Outer Loop PID set 1 to
5. Begin manual tuning by setting the Propor­tional Band to 5, Integral (Reset) to 0, and Rate to 0. Establish the desired set point and let the system stabilize. When the system stabilizes, watch the Inner Loop Set Point on the Main Page. If this value fluctuates, increase the pro­portional band until it stabilizes. Adjust the pro­portional band in 3° to 5° increments, allowing time for the system to stabilize between adjust­ments.
5. When Input 1 has stabilized, watch the percent power on the Main Page. It should be stable, ±2%. At this point, the process temperature should also be stable, but it will exhibit droop (stabilized below set point). The droop can be eliminated with Integral (reset).
6. Start with an integral setting of 99.9 minutes, and allow 10 minutes for the process tempera­ture to come up to set point. If it has not, decrease the setting by half and wait another 10 minutes. Then halve the setting again and wait another 10 minutes until the process value equals the set point. If the process becomes unstable, the integral value is too small. Increase it until the process stabilizes.
Andy, an engineer with the Ajax Testing Company, is running temperature and humidity tests on navigational equipment. He runs the test profile, Military Standard Test 810D, having already set up the controller and programmed the profile.
In Step 4, the temperature in the chamber exceed­ed the Alarm 1 setting. This triggered the alarm, causing the indicator light on the front panel (next to the bell-shaped icon) to light up and a message to appear on the lower display: "TEMP DEV High."
Because Alarm 1 was set up as a latching alarm (Setup Page), Andy had to clear it manually. First he corrected the alarm condition by widening the gap between low and high deviation alarm set­tings on the Operations Page. He then unlatched the alarm by returning to the Main Page alarm line and pressing the Right Key . again.
If your Series F4 is a single-channel controller, you will see only the temperature on Channel 1. This is not the true Military Standard Test 810D.
NOTE: This profile is embedded in the Series F4 as a teaching tool and a template. Go to the Edit Profile Menu (Pro­files Page) and look for MILSTD810D.
RUN
Andy presses the Profile Key π , moves the cursor to "MILSTD810D" on the Run Profile Menu, then presses the Right Key .. He wants to begin at Step 1, so he presses . to select that step. The Profile Status Message (on the Lower Display) now says: "MILSTD810D Running. Step 1 Re­mains: XX:XX."
π
HOLD
When the alarm occurred, Andy put the profile on hold while he corrected the Alarm Set Points.
π
RESUME
After clearing the alarm, Andy entered the com­mand to resume the profile.
π
Resume Profile:______
Continue Holding
>Resume
Terminate
.
MILSTD810D Holding. Step 1 Remains 00:01:40
Hold Profile:_______
Don’t Hold
>Hold
Terminate
Start Profile:_______
>MILSTD810D..........
ALUMINUM Glaze 8
1B
2A
2B
1A
Sample Application:
Environmental Testing, Running a Profile
Watlow Series F4S/D Operations 3.7
F
4
1A
1B
2A
2B
Main Page___________
1
Go to Profiles
Go to Setup
2
Go to Factory
i
3.8 Operations Watlow Series F4S/D

Troubleshooting Alarms and Errors

• Configure output as an alarm.
• Check alarm set points.
• Check the alarm sides setting.
• Check the alarm type setting.
• Check the alarm logic for compatibility with system peripherals and annunciators.
• Check the power limit setting.
• Check the operation mode.
• Check the alarm output function.
• Check the °C and °F setting.
• Check the calibration offset value. Set it to a lower level.
• Alarm output may be off.
• Alarm set points may be incorrect.
• Alarm sides may be incorrect.
• Controller may be in diagnostics mode.
• Alarm may be latched. Move cursor to alarm message. Press
.
.
• Alarm set points may be incorrect.
• Alarm hysteresis may be incorrect.
• Input may be in error condition.
Alarms
• Alarm won’t occur.
• Alarm won’t clear. (To clear the alarm, cor-
rect the alarm condi­tion. If the alarm is latched, press
. with the cursor at the alarm message on the Main Page.)
• Check Communications Setup Menu and set to correct address.
• Check Communications Setup Menu and set to correct baud rate.
• Look for a break in the daisy chain.
• Verify correct connections and test wiring paths.
• Check converter box wiring and its documen­tation.
• Reconfigure computer’s communications port setup and verify that communications are okay.
• Check the communication card documentation for setable variables and operational testing.
• Restart communications software and check for settings agreement. Verify the communica­tions bus is active.
• Verify operation with Watlow communications tool.
• Address parameter may be incorrectly set.
• Baud rate parameter may be incorrectly set.
• Unit-to-unit daisy chain may be disconnect­ed.
•Communications wiring may be reversed, short or open.
• EIA-485 converter box may be incorrectly wired.
• Computer communications port may be in­correctly set up.
• Communications software setup or address may be incorrect.
• Protocol or parity may be wrong, should be 8, n, 1.
• Application software not working properly.
• May need termination and pull-up and pull­down resistors.
Communications
• Unit will not communicate.
• Check switches, fuses, breakers, interlocks, limits, connectors, etc. for energized condi­tions and proper connection.
• Measure power upstream for required level. Check part number for input power required.
• Check wire size.
• Check for bad connections.
• Power to unit may be off.
• Fuse may be blown.
• Breaker may be tripped.
• Safety Interlock door switch, etc., may be activated.
• Separate system limit control may be latched.
• Wiring may be open.
• Input power may be incorrect.
Power
• Displays are dead.
Corrective ActionProbable Cause(s)Indication
Watlow Series F4S/D Operations 3.9
• Turn the controller off, then on again.
• Turn the controller off, then on again.
• Turn the controller off, then on again.
• Call your Watlow distributor or represen­tative.
• Call your Watlow distributor or represen­tative.
• Loss of power during memory setup.
• Loss of power during memory setup.
• Loss of power during memory setup.
• Component failure.
• Component failure, loss of power during download.
Fatal Errors (Controller shuts
down.)
• Checksum Error!, Parameter memory.
• Checksum Error!, Unit config memory.
• Checksum Error!, Profile mem­ory.
• RAM Test Failed! Return con­troller to the Factory.
• Flash Memory Failed. Return controller to the Factory.
• Move module to correct input slot.
• Move module to correct input slot.
• Replace incorrect module with retransmit module.
• Replace incorrect module with retransmit module.
• Remove the module just installed and replace with a new module.
• Press any key. All parameters will default.
• Wait until initialization is done.
• Wait until initialization is done.
• Input 2-3 module in input 1 slot.
• Input 1 module in input 2-3 slot.
• Wrong module in retransmit 1 slot.
• Wrong module in retransmit 2 slot.
• Component failure.
• Module changed.
• Firmware upgrade.
• Firmware upgrade.
•Input 1 Module Error! Only single-channel modules supported.
• Input 1 Module Error! Only dual-channel modules supported.
• Retransmit 1 Module Error! Only process modules supported.
• Retransmit 2 Module Error! Only process modules supported.
• Cannot identify: Modify: Re­place module.
• Module change. Defaults will occur. Accept with any key.
• First power-up. Parameters are initializing.
• Firmware change. Parameters are initializing.
• Check sensor connections.• Input is in error condition.
System Errors
(Upper Display shows error
numbers. Lower Display mes­sages indicate cause and ac­tion to take.)
• Check sensor connections and sensor wiring.
• Check the Sensor parameter to match the sensor hardware.
• Measure power upstream for required level. Check part number for power re­quirements.
• Check sensor function. The Open Loop Detect parameter indicates it may be broken.
• Check the Calibration Offset parameter value. Set it to a lower level.
• Check sensor connections and sensor wiring.
• Input type may be set to wrong sensor or may not be calibrated.
• Power may be incorrect.
• The open loop detect feature shows a broken sensor.
• The Calibration Offset parameter is set much too high or low.
Upper [A-dLO]
Lower !Input x (1 to 3) AtoD -
Upper [A-dhi]
Lower !Input x (1 to 3) AtoD+
Upper [SEnLo]
Lower !Input x (1 to 3) Sensor-
Upper [SEnhi]
Lower !Input x (1 to 3) Sensor+
Upper [Atod`]
Lower !Timeout
• Check sensor connections.• Input is in error condition.
Input Errors
(Upper Display shows error code
for input 1 only. Lower Display shows error message. Alarm Output Indicator is lit.)
Corrective ActionProbable Cause(s)Indication

Operations Page Map

NOTE: Some parameters may not appear, depending on the mod­el and configuration of the controller.
3.10 Operations Watlow Series F4S/D
Autotune PID
Channel 1 Autotune
Tune Off PID Set 1 PID Set 2 PID Set 3 PID Set 4 PID Set 5
Channel 2 Autotune
Tune Off PID Set 6 PID Set 7 PID Set 8 PID Set 9 PID Set 10
Channel 1 Outer Loop Autotune
PID Set C1 PID Set C2 PID Set C3 PID Set C4 PID Set C5
Edit PID
PID Set Channel 1
PID Set 1-5
Proportional Band A IntegralA / ResetA DerivativeA / RateA Dead Band A Hysteresis A Proportional Band B IntegralB / ResetB DerivativeB / RateB Dead Band B Hysteresis B
PID Set Channel 2
PID Set 6-10
Proportional Band A IntegralA / ResetA DerivativeA / RateA Dead Band A Hysteresis A Proportional Band B IntegralB / ResetB DerivativeB / RateB Dead Band B Hysteresis B
Cascade PID Set
Cascade Set 1-5
Proportional Band A IntegralA / ResetA DerivativeA / RateA Dead Band A Hysteresis A Proportional Band B IntegralB / ResetB DerivativeB / RateB Dead Band B Hysteresis B
Alarm Set Points
Alarm1 Low SP Alarm1 High SP Alarm1 Lo Deviation Alarm1 Hi Deviation Alarm2 Low SP Alarm2 High SP Alarm2 Lo Deviation Alarm2 Hi Deviation
Watlow Series F4S/D Operations 3.11
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
*This section is also applicable for Cascade Inner Loop.
NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
1A 1B Set 503 553 [1] 513 563 [2] 523 573 [3] 533 583 [4] 543 593 [5] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Derivative x (A or B)
Set the derivative time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
1A 1B Set 502 552 [1] 512 562 [2] 522 572 [3] 532 582 [4] 542 592 [5] r/w
0 per minute (0)
0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in repeats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
1A 1B Set 501 551 [1] 511 561 [2] 521 571 [3] 531 581 [4] 541 591 [5] r/w
0 minutes (0)
0.00 to 300.00 minutes (0 to 30000)
Integral x (A or B)
Set the integral time in minutes.
Active: Always (Channel 1).
°F Default for US °C Default for SI
1A 1B Set 500 550 [1] 510 560 [2] 520 570 [3] 530 580 [4] 540 590 [5] r/w
25°F (25) 14°C (14)
0 to 30000 (0 to 30000)
Proportional Band x (A or B)
Define the propor­tional band for PID control.
Main > Operations > Edit PID > PID Set Channel 1 > PID Set x (1 to 5)
PID Set x (1 to 5)* (Optional Inner Loop)
Main > Operations > Edit PID
Edit PID
Active if Analog Input 3 Control
Type is set to Cascade.
343 r/w
Tune Off (0)Tune Off (0) Outer Loop PID Set 1 (1) Outer Loop PID Set 2 (2) Outer Loop PID Set 3 (3) Outer Loop PID Set 4 (4) Outer Loop PID Set 5 (5)
Cascade Outer Loop
Select which PID pa­rameters will be au­tomatically tuned.
Active if Analog Input 3 Control
Type is set to Cascade.
305 r/w
Tune Off (0)Tune Off (0) Inner Loop PID Set 1 (1) Inner Loop PID Set 2 (2) Inner Loop PID Set 3 (3) Inner Loop PID Set 4 (4) Inner Loop PID Set 5 (5)
Cascade Inner Loop
Select which PID pa­rameters will be au­tomatically tuned.
Main > Operations > Autotune PID > Cascade
Autotune PID Cascade
Active: Always (Channel 1). Active if controller is set to Dual
Channel Ramping (Channel 2).
Channel 305 [1] 324 [2] r/w
Tune Off (0)Tune Off (0) Ch1 PID Set 1 (1) Ch1 PID Set 2 (2) Ch1 PID Set 3 (3) Ch1 PID Set 4 (4) Ch1 PID Set 5 (5) Ch2 PID Set 6 (1) Ch2 PID Set 7 (2) Ch2 PID Set 8 (3) Ch2 PID Set 9 (4) Ch2 PID Set 10 (5)
Channel x (1 to 2) Autotune
Select whether PID parameters will be automatically selected.
Main > Operations > Autotune PID
Autotune PID
3.12 Operations Watlow Series F4S/D
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
NOTE: Press the Information Key ˆ for more task-related tips.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
2A 2B Set 2504 2554 [6] 2514 2564 [7] 2524 2574 [8] 2534 2584 [9] 2544 2594 [10] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Rate x (A or B)
Set the rate time.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
2A 2B Set 2503 2553 [6] 2513 2563 [7] 2523 2573 [8] 2533 2583 [9] 2543 2593 [10] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Derivative x (A or B)
Set the derivative time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
2A 2B Set 2502 2552 [6] 2512 2562 [7] 2522 2572 [8] 2532 2582 [9] 2542 2592 [10] r/w
0 per minute (0)
0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in repeats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
2A 2B Set 2501 2551 [6] 2511 2561 [7] 2521 2571 [8] 2531 2581 [9] 2541 2591 [10] r/w
0 minutes (0)
0.00 to 99.99 minutes (0 to 9999)
Integral x (A or B)
Set the integral time in minutes.
Active: Always (Channel 1).
2A 2B Set 2500 2550 [6] 2510 2560 [7] 2520 2570 [8] 2530 2580 [9] 2540 2590 [10] r/w
25°F (25) 14°C (14)
0 to 30000 (1 to 30000)
Proportional Band x (A or B)
Set the proportional band.
Main > Operations > Edit PID > PID Set Channel 2 > PID Set x (6 to 10)
PID Set x (6 to 10)
Active if Proportional Band is set
to 0 and one channel is set to heat and the other to cool (Setup Page).
1A 1B Set 507 557 [1] 517 567 [2] 527 577 [3] 537 587 [4] 547 597 [5] r/w
3 (3)1 to 30000
(1 to 30000)
Hysteresis x (A or B)
Define the process variable change from the set point re­quired to re-energize the output (in on-off mode).
Active if Proportional Band is not
set to 0 and one output is set to heat and the other to cool (Setup Page).
1A 1B Set 505 555 [1] 515 565 [2] 525 575 [3] 535 585 [4] 545 595 [5] r/w
0 (0)
0 to 30000 (0 to 30000)
Dead Band x (A or B)
Define the effective shift in the heating and cooling set points to prevent conflict.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
1A 1B Set 504 554 [1] 514 564 [2] 524 574 [3] 534 584 [4] 544 594 [5] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Rate x (A or B)
Set the rate time.
Watlow Series F4S/D Operations 3.13
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Active if Proportional Band is not
set to 0 and one output is set to heat and the other to cool (Setup Page).
1A 1B Set 2605 2655 [1] 2615 2665 [2] 2625 2675 [3] 2635 2685 [4] 2645 2695 [5] r/w
0 (0)
0 to 30000 (0 to 30000)
Dead Band x (A or B)
Define the effective shift in the heating and cooling set points to prevent conflict.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
1A 1B Set 2604 2654 [1] 2614 2664 [2] 2624 2674 [3] 2634 2684 [4] 2644 2694 [5] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Rate x (A or B)
Set the rate time.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
1A 1B Set 2603 2653 [1] 2613 2663 [2] 2623 2673 [3] 2633 2683 [4] 2643 2693 [5] r/w
0.00 minutes (0)
0.00 to 9.99 minutes (0 to 999)
Derivative x (A or B)
Set the derivative time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional Band is not set to 0.
1A 1B Set 2602 2652 [1] 2612 2662 [2] 2622 2672 [3] 2632 2682 [4] 2642 2692 [5] r/w
0 per minute (0)
0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in repeats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional Band is not set to 0.
1A 1B Set 2601 2651 [1] 2611 2661 [2] 2621 2671 [3] 2631 2681 [4] 2641 2691 [5] r/w
0 minutes (0)
0.00 to 99.99 minutes (0 to 9999)
Integral x (A or B)
Set the integral time in minutes.
Active: Always (Channel 1).
°F Default for US °C Default for SI
1A 1B Set 2600 2650 [1] 2610 2660 [2] 2620 2670 [3] 2630 2680 [4] 2640 2690 [5] r/w
25°F (25) 14°C (14)
0 to 30000 (0 to 30000)
Proportional Band x (A or B)
Define the propor­tional band for PID control.
Main > Operations > Edit PID > Cascade Outer Loop PID Set X (1 to 5)
Cascade Outer Loop PID Set x (1 to 5)
Active if Proportional Band is set
to 0 and one channel is set to heat and the other to cool (Setup Page).
2A 2B Set 2507 2557 [6] 2517 2567 [7] 2527 2577 [8] 2537 2587 [9] 2547 2597 [10] r/w
3 (3)1 to 30000
(1 to 30000)
Hysteresis x (A or B)
Define the process variable change from the set point re­quired to re-energize the output (in on-off mode).
Active if Proportional Band is not
set to 0 and one output is set to heat and the other to cool (Setup Page).
2A 2B Set 2505 2555 [6] 2515 2565 [7] 2525 2575 [8] 2535 2585 [9] 2545 2595 [10] r/w
0 (0)0 to 30000
(1 to 30000)
Dead Band x (A or B)
Define the effective shift in the heating and cooling set points to prevent conflict.
Active if Alarm 2 Type (Setup
Page) is set to Deviation.
322 r/w
999 (999)0 to 30000
(0 to 30000)
Alarm 2 High Deviation
Set the deviation above set point 2 that will trigger an alarm.
Active if Alarm 2 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0
321 r/w
-999 (-999)
-99.9 (-999)
-19999 to -1 (-1 to -19999)
-.1 to -1999.9 (-1 to -19999)
Alarm 2 Low Deviation
Set the deviation below set point 2 that will trigger an alarm.
Active if Alarm 2 Type (Setup
Page) is set to Process.
322 r/w
<per sensor><per sensor> to Alarm
2 Low Set Point
Alarm 2 High SP
Set high value at which alarm is trig­gered.
Active if Alarm 2 Type (Setup
Page) is set to Process.
321 r/w
<per sensor><per sensor> to Alarm
2 High Set Point
Alarm 2 Low SP
Set low value at which alarm is trig­gered.
Active if Alarm 1 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0
303 r/w
999 (999)
99.9 (999)
1 to 30000 (1 to 30000)
.1 to 3000.0 (1 to 30000)
Alarm 1 High Deviation
Set the deviation above set point 1 that will trigger an alarm.
Active if Alarm 1 Type (Setup
Page) is set to Deviation.
Active if decimal is set to 0.0.
302 r/w
-999 (-999)
-99.9 (999)
-19999 to -1 (-1 to 19999)
-.1 to -1999.9 (-1 to 19999)
Alarm 1 Low Deviation
Set the deviation below set point 1 that will trigger an alarm.
Active if Alarm 1 Type (Setup
Page) is set to Process.
303 r/w
<per sensor><per sensor> to Alarm
1 Low Set Point
Alarm 1 High SP
Set high value at which alarm is trig­gered.
Active if Alarm 1 Type (Setup
Page) is set to Process.
302 r/w
<per sensor><per sensor> to Alarm
1 High Set Point
Alarm 1 Low SP
Set low value at which alarm is trig­gered.
Main > Operations > Alarm Set Points
Alarm Set Points
Active if Proportional Band is set
to 0 and one channel is set to heat and the other to cool (Setup Page).
1A 1B Set 2607 2657 [1] 2617 2667 [2] 2627 2677 [3] 2637 2687 [4] 2647 2697 [5] r/w
3 (3)1 to 30000
(1 to 30000)
Hysteresis x (A or B)
Define the process variable change from the set point re­quired to re-energize the output (in on-off mode).
3.14 Operations Watlow Series F4S/D
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
Loading...
+ 122 hidden pages