RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D
7800 SERIES Relay Modules
INSTALLATION INSTRUCTIONS
APPLICATION
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D are
microprocessor-based integrated burner controls for
automatically fired gas, oil, or combination fuel single burner
applications. They are intended to replace the R4795 and
R7795 Primary Controls. The RM7895A,B,C,D/EC7895A;
RM7896A,B,C,D systems consist of a relay module, subbase,
amplifier, and purge card. Options include keyboard display
module (KDM), Personal Computer Interface, Data
ControlBus™ Module, remote display mounting, expanded
annunciator and Combustion System Manager® Software.
Functions provided by the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D include automatic burner sequencing,
flame supervision, system status indication, system or
self-diagnostics and troubleshooting. The RM7896 provides
a postpurge function.
This document provides installation and static checkout
instructions. Other applicable publications are:
Publication
No.Product
63-2278Q7700 Network Interface Unit Product Data
65-0084Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0090S7800A Keyboard Display Module Product
Data
65-0091S7810A Data ControlBus Module™ Product
Data
65-0095S7820 Remote Reset Module Product Data
65-0097221729C Dust Cover Packing Instructions
65-0101S7830 Expanded Annunciator Product Data
65-0102 ZM7850A Combustion System Manager™
Operating Instructions
65-0109R7824, R7847, R7848, R7849, R7851,
R7861, R7886 Flame Amplifiers for the
7800 Series Product Data
Publication
No.Product
65-0131221818A Extension Cable Assembly
Product Data
65-02297800 SERIES Relay Modules Checkout and
Troubleshooting Product Data.
65-0092QS7800A ControlBus™ Module, Standard
65-0227QS7800B ControlBus™ Module, Multidrop
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency:
RM7895/RM7896: 120 Vac (+10/-15%), 50/60 Hz (± 10%).
EC7895A,C: 220/240 Vac (+10%/-15%), 50/60 Hz (±10%)
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
Approvals:
RM7895/RM7896:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Canadian Standards Association Certified: LR9S329-3.
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
IRI Acceptable.
Federal Communications Commission: Part 15, Class B,
Emissions.
EC7895A,C:
Factory Mutual Approved.
66-1090-06
Page 2
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
INSTALLATION
When Installing this Product…
1.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
3. Installer must be a trained, experienced, flame safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury, or death.
Follow applicable safety requirements when installing
a control on a burner to prevent death or severe injury.
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or equipment
damage.
Disconnect power supply before beginning installation.
IMPORTANT
1. Wiring connections for the relay modules are unique;
refer to Fig. 2 and 3 or the appropriate Specifications
for proper subbase wiring.
2. Wiring must comply with all applicable codes, ordi-
nances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D must not exceed those listed on the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D label
or the Specifications; see Table 1.
5. Limits and interlocks must be rated to simultaneously
carry and break current to the ignition transformer,
pilot valve, and main fuel valve(s).
6. All external timers must be listed or component-rec-
ognized by authorities who have proper jurisdiction.
7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or
operating contacts in series between the flame
safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel with
the exception of Infrared Flame Detectors (C7015).
9. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, can cause
interference with radio communications. It has been
tested and found to comply with the limits for a Class
B computing device of Part 15 of FCC rules, which
are designed to provide reasonable protection
against such interference when operated in a
commercial environment. Operation of this
equipment in a residential area may cause
interference, in which case, the users, at their own
expense, may be required to take whatever
measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in
the Radio Interference Regulations of the Canadian
Department of Communications.
Location
Humidity
Install the relay module where the relative humidity never
reaches the saturation point. The relay module is designed to
operate in a maximum 85% relative humidity continuous,
noncondensing, moisture environment. Condensing moisture
can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to
vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When
installed outdoors, protect the relay module in an approved
weather-tight enclosure.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The
standard vertical position is recommended. Any other
position decreases the maximum ambient temperature
rating.
2. Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for service,
installation, access or removal of the RM7895A,B,C,D/
EC7895A,C; RM7896A,B,C,D, expanded annunciator,
keyboard display module, flame amplifier, flame amplifier signal voltage probes, run/test switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a
template to mark the four screw locations. Then drill the
pilot holes.
4. Securely mount the subbase using four no. 6 screws
(not provided).
66-1090—062
Page 3
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Wiring Subbase
WARNING
Electrical Shock Hazard.
Can cause serious injury, death or equipment
damage.
Disconnect the power supply before beginning
installation.
The internal block diagram of the RM7895A,B,C,D/
EC7895A,C;RM7896A,B,C,D is shown in Fig. 1.
1
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
LOCKOUT IF JUMPER JR2 REMOVED.
INDICATES FEEDBACK SENSING
TO RELAY STATUS FEEDBACK
AND LINE VOLT INPUTS
FIELD WIRING
INTERNAL WIRING
OPTIONAL KEYBOARD
DISPLAY MODULE
DDL
DDL
COMMUNICATIONS
M23996
1
RS485
2
3
REMOTE
RESET
5
RUN/TEST
SWITCH
RESET
PUSHBUTTON
STATUS LEDs
LIMITS
CONFIGURATION
JUMPERS
SAFETY RELAY
CIRCUIT
CONTROLLER
6K1
3K1
1. For proper subbase wiring and sequence chart, refer to
Fig. 2 and 3.
2. For remote wiring of the Keyboard Display Module, refer
to the Specifications for the Keyboard Display Module
(65-0090), Network Interface Unit (63-2278), Data ControlBus™ Module (65-0091) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect can
be required.
4. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC, Class 1 (Line Voltage)
wiring.
5. For recommended wire size and type, see Table 1.
6. For recommended grounding practices, see Table 2.
1
MICROCOMPUTER
RELAY
DRIVE
CIRCUIT
6
INTERLOCK
(INCLUDING
AIRFLOW SWITCH)
2
L1
(HOT)
1K
L2
RM7895, RM7896: 120 VAC, 50/60 HZ.
EC7895A,C: 220-240 VAC, 50/60 HZ.
PLUG-IN PURGE
TIMER CARD
FLAME SIGNAL
PLUG-IN
TEST
FLAME
AMPLIFIER
2K
3K
4K
5K
6K
7K
POWER SUPPLY
1K1 2K1 5K1
7
4K1
2K2
RELAY
STATUS
FEEDBACK
AND LINE
VOLTAGE
INPUTS
CONTROL
POWER
10
8
9
4
3
TEST
JACK
F
G
22
IGNITION
PILOT
MAIN VALVE
BLOWER
ALARM
L2
Fig. 1. Internal block diagram of RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
(see Fig. 2 and 3 for detailed wiring instructions).
366-1090—06
Page 4
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Q7800
FOR DIRECT SPARK IGNITION
12
(OIL OR GAS)
13
14
15
16
17
18
19
20
21
22
10
8
2
MASTER
SWITCH
IGNITION
TRANSFORMER
MAIN VALVE
LINE VOLTAGE ALARM
BURNER MOTOR
(BLOWER)
BURNER
CONTROLLER/LIMITS
LOCKOUT INTERLOCK
(INCLUDING
AIRFLOW SWITCH)
INTERMITTENT
PILOT/IGNITION
MAIN FUEL VALVE(S)
IGNITION
FLAME DETECTOR
4
G
L2
3
4
(L1)
5
6
7
8
9
10
F
3
L1
(HOT)
L2
L2
1
LED
DISPLAY
BURNER
START
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
1
RM7895, RM7896: 120 VAC , 50/60 HZ; EC7895: 220-240 VAC,
50/60 HZ POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
2
3
FOR EC7895, A 220 TO 240 VAC TO 120 VAC, 10 VA MINIMUM STEPDOWN
TRANSFORMER (NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER.
INITIATE
AIRFLOW SW CHECK
6
000000
STANDBY
POWERPOWER
START
POWER
LIMITS AND BURNER CONTROLLER CLOSED
SAFE START CHECK
TIMED
PURGE
BURNER/BLOWER MOTOR
LOCKOUT INTERLOCK CLOSED
Fig. 2. Wiring subbase and sequence chart for RM7895A,B/EC7895A; RM7896A,B.
PFEP
4 OR 10 SEC
POWER
PILOT
FLAME
MAIN
ALARMALARM
POWERPOWER
PILOT
FLAME
MAIN
IGN
10
IGN/ PILOT
SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING.
4
FOR RM7895A1048 (ONLY), IGNITION TERMINAL 10
5
IS DE-ENERGIZED WHEN FLAME IS PROVEN.
6
AIRFLOW SWITCH CHECK FEATURE IS FOR THE RM7895B,RM7896B.
RM7896A,B ONLY.
7
RUN
5
MAIN VALVE
6
FLAME
PROVING
POWER
PILOT
FLAME
MAIN
ALARM
4
8
L1
TO
POST PURGE
9
TO
6
7
15 SEC
7
7
STANDBY
POWER
AFSC
SSC
M23997
66-1090—064
Page 5
LINE VOLTAGE
ALARM
BURNER MOTOR
(BLOWER)
BURNER
CONTROLLER/LIMITS
LOCKOUT INTERLOCK
(INCLUDING
AIRFLOW SWITCH).
10 SEC. INTERRUPTED
PILOT/IGNITION
MAIN FUEL VALVE(S)
IGNITION
FLAME DETECTOR
4
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Q7800
FOR DIRECT SPARK IGNITION
(OIL OR GAS)
IGNITION
10
TRANSFORMER
8
9
MAIN VALVE
2
DELAYED
(2ND STAGE)
MAIN VALVE
MASTER
SWITCH
L1
(HOT)
L2
L2
1
(L1)
12
13
14
15
16
17
18
19
20
21
22
G
L2
3
4
5
6
7
8
9
10
F
3
000000
LED
DISPLAY
BURNER
START
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
1
RM7895, RM7896: 120 VAC , 50/60 HZ; EC7895: 220-240 VAC, 50/60 HZ
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
DO NOT CONNECT ANY WIRES TO UNUSED TERMINALS.
3
FOR EC7895, A 220 TO 240 VAC TO 120 VAC, 10 VA MINIMUM STEPDOWN
TRANSFORMER (NOT PROVIDED) MUST BE USED TO DRIVE THE SHUTTER.
SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING.
4
INITIATE
AIRFLOW SW. CHECK
5
STANDBY
POWERPOWER
START
POWER
LIMITS AND BURNER CONTROLLER CLOSED
SAFE START CHECK
TIMED
PURGE
POWER
PILOT
FLAME
MAIN
ALARMALARM
BURNER/BLOWER MOTOR
LOCKOUT INTERLOCK CLOSEDAFSC
7
PFEP
4 OR 10 SEC
IGN.
10 SEC. IGN./ PILOT
MFEP
POWERPOWER
PILOT
FLAME
MAIN
POWER
PILOT
FLAME
MAIN
ALARM
10
8
2ND STAGE MAIN
FLAME PROVING
5
AIRFLOW SWITCH CHECK FEATURE IS FOR THE RM7895D, RM7896D.
RM7895C1020, RM7896C1036: DURING FIRST 8 SECONDS OF PFEP,
WHEN A FLAME SIGNAL IS DETECTED, TERMINAL 10 IS DE-ENERGIZED.
IF FLAME SIGNAL IS LOST, TERMINAL 10 WILL RE-ENERGIZE.
RUN
4
8
MAIN VALVE
L1
6
TO
TO
7
POST PURGE
POWER
PILOT
FLAME
MAIN
ALARM
9
21
6
15SEC
6
STANDBY
POWER
6
SSC
M23998
Fig. 3. Wiring subbase and sequence chart for RM7895C,D/EC7895C; RM7896C,D.
566-1090—06
Page 6
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 1. Recommended Wire Sizes and Part Numbers.
ApplicationRecommended Wire SizeRecommended Part Numbers
Line voltage terminals.14, 16 or 18 AWG copper conductor, 600 volt insulation,
TTW60C, THW75C, THHN90C.
moisture-resistant wire.
Keyboard Display Module22 AWG two-wire twisted pair with ground, or five-wire. Belden 8723 shielded cable or equivalent.
a
Data ControlBus™ Module
22 AWG two-wire twisted pair with ground, or five-wire. Belden 8723 shielded cable or equivalent.
13 Vdc full-wave rectified
transformer power input.
a
The KDM, Data ControlBus™ Module (for remote mounting or communications) or Communication Interface ControlBus™
22 AWG two-wire twisted pair with ground.Belden 8723 shielded cable or equivalent.
18 AWG wire insulated for voltages and temperatures
TTW60C, THW75C, THHN90C.
for given application.
Module must be wired in daisy chain configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of interconnection of all the
devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration
string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors for connections over 100 feet (31 meters).
Table 2. Recommended Grounding Practices.
Ground TypeRecommended Practice
Earth ground (subbase and relay
module).
1. Use to provide a connection between the subbase and the control panel of the
equipment. Earth ground must be capable of conducting enough current to blow the
20A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface area
ground conductors. If a leadwire is required, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground path are free of
nonconductive coatings and protected against corrosion on mating surfaces.
Signal ground (Keyboard Display
Module, Data ControlBus™ Module,
Use the shield of the signal wire to ground the device to the signal ground terminal 3(c) of
each device. Connect the shield at both ends of the daisy chain to earth ground.
Communications Interface
ControlBus™ Module.
7. Recommended wire routing of leadwires:
a. Do not run high voltage ignition transformer wires
in the same conduit with the flame detector, Data
ControlBus Module™, or Remote Reset Module
wiring.
b. Do not route flame detector, Data ControlBus™
Module, or Remote Reset Module leadwires in
conduit with line voltage circuits.
c. Enclose flame detector leadwires without armor
cable in metal cable or conduit.
d. Follow directions in flame detector, Data
ControlBus™ Module, or Remote Reset Module
c. Remote Reset leadwires: The maximum length of
wire is 1000 feet (305 meters) to a Remote Reset
pushbutton.
d. Data ControlBus Module™: The maximum Data
ControlBus™ Module cable length depends on the
number of system modules connected, the noise
conditions and the cable used. The maximum length
of all Data ControlBus™ Module interconnecting
wire is 4000 feet (1219 meters).
10. Be sure loads do not exceed the terminal ratings. Refer
to the label on the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D or to the terminal ratings in Table 3.
Instructions.
8. The KDM is powered from a low voltage, energy limited
source. It can be mounted outside of a control panel if it
is protected from mechanical damage.
Final Wiring Check
1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the
NOTE: A 13 Vdc power supply must be used any time more
than one KDM is used.
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. A
separate power supply circuit can be required for the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. Add
9. Maximum wire lengths:
a. RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
leadwires: The maximum leadwire length is 300 feet
to terminal inputs (Control, Running/Lockout
Interlock).
b. Flame Detector leadwires: The maximum flame
the required disconnect means and overload protection.
2. Check all wiring circuits and complete Static Checkout
in Table 6 before installing the RM7895A,B,C,D/
EC7895A,C; RM7896A,B,C,D on the subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
sensor leadwire length is limited by the flame signal
strength.
66-1090—066
Page 7
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 3. Terminal Ratings.
Terminal
NumberDescription
RM7895/RM7896EC7895
Ratings
GFlame Sensor Ground——
Earth G
Earth Ground
a
——
L2(N)Line Voltage Common——
3Alarm120 Vac, 1A pilot duty.220-240 Vac, 1A pilot duty.
5Line Voltage Supply (L1)120 Vac (+10/-15%), 50 or 60 Hz
(±10%).
b
220-240 Vac (+10/-15%), 50 or 60 Hz
(±10%).
6Burner Controller and Limits120 Vac, 1 mA.220-240 Vac, 1 mA.
7Lockout Interlock120 Vac, 8A run, 43A inrush.8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.
8Pilot Valve/Ignition
9Main Fuel Valve
10Ignition
120 Vac
120 Vac
120 Vac
c
c
c
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac, 2A at PF = 0.2
F(11)Flame Sensor60 to 220 Vac, current limited.60 to 220 Vac, current limited.
12 to 20Unused——
212nd Stage Main Valve (EC7895C,
RM7895C,D; RM7896C,D)
120 Vac
22Shutter120 Vac, 0.5A
a
See Table 2.
b
2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly.
c
See Tables 4 and 5.
d
Requires 220-240 Vac, 10 VA minimum, stepdown transformer to operate the shutter.
c
220-240 Vac, 4A at PF = 0.5, 20A inrush.
220-240 Vac
d
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Combination NumberPilot Fuel 8Main 9Ignition 10Delayed Main Valve 21
1CFNo LoadNo Load
2BFNo LoadNo Load
3
a
F
No LoadANo Load
4FFANo Load
5
a
F
No LoadA F
6DFANo Load
7
a
D
No LoadA D
8 DDANo Load
9
a
RM7895C,D: EC7895C, RM7896C,D only, jumper terminals 8 to 9.
a
D
No LoadA D
Table 5. Composition of each Combination.
ABCDF
4.5A ignition
50 VA Pilot Duty
4.5A ignition.
a
Pilot Duty refers to solenoid-type valves.
a
plus
180 VA Ignition plus
motor valves with:
660 VA inrush,
360 VA open,
240 VA hold.
2A Pilot Duty.
a
65 VA Pilot Dutya plus
motor valves with:
3850 VA inrush,
700 VA open,
250 VA hold.
766-1090—06
Page 8
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
STATIC CHECKOUT
After checking all wiring, perform this checkout before
installing the EC7895A,C/RM7895A,B,C,D/RM7896A,B,C,D
on the subbase. These tests verify the Q7800 Wiring
Subbase is wired correctly, and the external controllers, limits,
interlocks, actuators, valves, transformers, motors and other
devices are operating properly.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Close all manual fuel shutoff valve(s) before starting
these tests.
Use extreme care while testing the system. Line
voltage is present on most terminal connections when
power is on.
Ensure proper selection of configuration jumpers before
starting the burner operation.
CAUTION
Electrical Hazard.
Can cause equipment damage or failure.
Do not perform a dielectric test with the relay module
installed. Internal surge protectors can break down,
allowing relay module to fail the dielectric test and
destroy the internal lightning and high current
protection.
1. Open the master switch before installing or removing a
jumper on the subbase.
2. Before continuing to the next test, be sure to remove the
test jumper(s) used in the previous test.
3. Replace all limits and interlocks that are not operating
properly. Do not bypass limits and interlocks.
Equipment Recommended
1. Voltmeter (1M ohm/volt minimum sensitivity) set on the
0 to 300 Vac scale.
2. Two jumper wires, no. 14 wire, insulated, 12 in.
(304.8 mm) long with insulated alligator clips at both
ends.
General Instructions
1. Perform all applicable tests listed in Static Checkout,
Table 6, in the order listed.
2. Make sure all manual fuel shutoff valve(s) are closed.
3. For each test, open the master switch and install the
jumper wire(s) between the subbase wiring terminals
listed in the Test Jumpers column.
4. Close the master switch before observing operation.
5. Read the voltage between the subbase wiring terminals
listed in the Voltmeter column.
6. If there is no voltage or the operation is abnormal, check
the circuits and external devices as described in the last
column.
7. Check all wiring for correct connections, tight terminal
screws, correct wire, and proper wiring techniques.
Replace all damaged or incorrectly sized wires.
8. Replace faulty controllers, limits, interlocks, actuators,
valves, transformers, motors and other devices, as
required.
9. Make sure normal operation is obtained for each
required test before continuing the checkout.
10. After completing each test, be sure to open the master
power switch and remove the test jumper(s) before proceeding to the next test.
WARNING
Explosion hazard.
Can cause serious injury or death.
Be sure all manual fuel shutoff valves are closed.
Table 6. Static Checkout .
Test
Number
1AllNone5-L2Line voltage at terminal 5.1. Master switch.
2AllNone6-L2Line voltage at terminal 6.1. Limits.
3All4-57-L21. Burner motor (fan or blower)
4All5-10—1. Ignition spark (if ignition
66-1090—068
Relay Module
Model
Test
Jumpers VoltmeterNormal Operation
starts.
2. Line voltage at terminal 7
within 10 seconds.
transformer is connected to
terminal 10).
If Operation is Abnormal,
Check Items Listed Below
2. Power connected to master switch.
3. Overload protection (fuse, circuit breaker,
etc.) has not opened power line.
2. Burner controller.
1. Burner motor circuit.
a. Manual switch of burner motor.
b. Burner motor power supply, overload
protection and starter.
c. Burner motor.
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
Page 9
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Table 6. Static Checkout (Continued).
Test
Number
5All5-8—1. Ignition spark (if ignition
Relay Module
Model
Test
Jumpers VoltmeterNormal Operation
transformer is connected to
terminal 8).
2. Automatic pilot valve opens
(if connected to terminal 8).
If Operation is Abnormal,
Check Items Listed Below
1. Watch for spark or listen for buzz.
2. Listen for click or feel head of valve for
activation.
a. Actuator if used.
b. Pilot valve.
NOTE: Refer to wiring diagram
6All5-9—Automatic fuel valve(s) open(s). If
7EC7895C;
RM7895C,D;
RM7896C,D
8All5-3—Alarm (if used) turns on.1. Alarm.
FinalAll
5-21—Automatic second stage main fuel
using direct spark ignition, check
first stage fuel valve(s) instead of
pilot valve.
valve(s) open(s).
of system being tested.
Same as test 5. If using direct spark
ignition, check first stage fuel valve(s)
instead of pilot valve.
1. Listen for and observe operation of
second stage main fuel valve(s) and
actuator(s).
2. Valve(s) and actuator(s).
CAUTION
Equipment Damage Hazard.
Can cause equipment damage.
After completing these tests, open master switch and remove all test jumpers from subbase
terminals. Also remove bypass jumpers, if used, from low fuel pressure limits.
1. Mount the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D vertically on the Q7800 Subbase or
mount horizontally with the knife blade terminals
pointing down. When mounted on the Q7800A, the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D must be
in an electrical enclosure.
2. When mounting in an electrical enclosure, provide adequate clearance for servicing, installation and removal
of the RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D,
KDM, flame amplifier, flame amplifier signal voltage
probes, electrical signal voltage probes and electrical
connections.
a. Allow an additional two inches (51 mm) below the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D for
the flame amplifier mounting.
b. Allow an optional three-inch (76 mm) minimum on
both sides of the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D for electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the
terminal blocks. Tuck in wiring against the back of the
subbase so it does not interfere with the knife blade terminals or bifurcated contacts.
IMPORTANT
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D
must be installed with a plug-in motion rather than a
hinge action.
4. Mount the RM7895A,B,C,D/EC7895A,C;
RM7896A,B,C,D by aligning the four L-shaped corner
guides and knife blade terminals with the bifurcated
contacts on the wiring subbase and securely tightening
the two screws without deforming the plastic.
Mounting Other System Components (Fig. 4)
Refer to the applicable specifications for mounting other
system components.
PRINCIPAL TECHNICAL FEATURES
The RM7895 provides all customary flame safeguard
functions as well as significant advancements in safety,
annunciation, and system diagnostics.
Safety Shutdown (Lockout) Occurs if:
1. INITIATE PERIOD
a. Purge card is not installed or removed.
b. Purge card is bad.
c. Configuration jumpers have been changed (after
200 hours)—Fault Code 110.
d. AC line power errors occurred, see Operation.
e. Four minute INITIATE period has been exceeded.
966-1090—06
Page 10
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
a. Airflow lockout feature is enabled and the airflow
switch does not close after ten seconds or within the
specified purge card timing.
b. Flame signal is detected after 30 seconds.
c. Ignition/pilot valve/intermittent pilot valve terminal is
energized.
d. Main valve terminal is energized.
e. Delayed main valve terminal is energized
(RM7895C,D).
f.Internal system fault occurred.
g. Purge card is removed.
h. Purge card is bad.
3. PREPURGE PERIOD
a. Airflow lockout feature is enabled and the airflow
switch opens.
b. Ignition/pilot valve terminal is energized.
c. Main valve terminal is energized.
d. Delayed main valve terminal is energized
(RM7895C,D).
e. Internal system fault occurred.
FLAME
AMPLIFIER
M15122
f.Purge card is removed.
g. Purge card is bad.
h. Flame signal is detected.
4. PILOT FLAME ESTABLISHING PERIOD (PFEP)
a. Airflow lockout feature is enabled and the airflow
switch opens.
b. No flame signal at end of PFEP.
c. Ignition/pilot valve/intermittent pilot valve terminal is
not energized.
NOTE: For the RM7895C1020 and RM7896C1036, during
the first 8 seconds of PFEP, when a flame signal is
detected, terminal 10 is de-energized. If the flame
signal is lost, terminal 10 will re-energize.
d. Main valve terminal is energized.
e. Delayed (second stage) main valve terminal is
energized (RM7895C,D/EC7895C; RM7896C,D).
f.Internal system fault occurred.
g. Purge card is removed.
h. Purge card is bad.
66-1090—0610
Page 11
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
5. MAIN FLAME ESTABLISHING PERIOD (MFEP)
(RM7895C, RM7896C,D; EC7895C)
a. Airflow lockout feature is enabled and the airflow
switch opens.
b. Ignition terminal is energized.
c. Ignition/pilot valve terminal is not energized.
d. Main valve terminal is not energized.
e. Delayed main valve terminal is energized.
f.No flame signal at end of Flame Failure Response
Time.
g. Internal system fault occurred.
h. Purge card is removed.
i.Purge card is bad.
6. RUN PERIOD
a. No flame present.
b. Airflow lockout feature is enabled and the airflow
switch opens.
c. Interrupted pilot valve terminal is energized
(RM7895C, RM7896C,D; EC7895C).
d. Main valve terminal is not energized.
e. Delayed main valve terminal is not energized
(RM7895C, RM7896C,D; EC7895C).
f.Internal system fault occurred.
g. Purge card is removed.
h. Purge card is bad.
i.Ignition terminal is energized.
OPERATION
Sequence of Operation
The RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D has the
operating sequences listed below; see Fig. 2 and 3. The
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D LED provide
positive visual indication of the program sequence: POWER,
PILOT, FLAME, MAIN and ALARM.
Initiate
The EC7895A,C/RM7895A,B,C,D;RM7896A,B,C,D Relay
Module enters the INITIATE sequence when the relay module
is powered. The EC7895A,C/RM7895A,B,C,D;
RM7896A,B,C,D can also enter the INITIATE sequence if the
relay module verifies voltage fluctuations of +10/-15% or
frequency fluctuations of ±10% during any part of the
operating sequence. The INITIATE sequence lasts for ten
seconds unless the voltage or frequency tolerances are not
met. When not met, a hold condition is initiated and displayed
on the optional KDM for at least five seconds; when met, the
INITIATE sequence restarts. If the condition is not corrected
and the hold condition exists for four minutes, the
EC7895A,C/RM7895A,B,C,D; RM7896A,B,C,D locks out.
Causes for hold conditions in the INITIATE sequence:
1. AC line dropout detection.
2. AC line noise that can prevent a sufficient reading of the
line voltage inputs.
3. Low line voltage brownouts.
The INITIATE sequence also delays the burner motor starter
from being energized and de-energized from an intermittent
AC line input or control input.
Standby
The EC7895A,C/RM7895A,B,C,D;RM7896A,B,C,D is ready
to start an operating sequence when the operating control
input determines a call for heat is present. The burner switch,
limits, operating limit control and all microcomputer-monitored
circuits must be in the correct state for the relay module to
continue into the PREPURGE sequence.
Normal Start-Up Prepurge
The EC7895A,C/RM7895A,B,C,D/RM7896A,B,C,D Relay
Module provides PREPURGE timing selectable from two
seconds to thirty minutes with power applied and the
operating control indicating a call for heat.
1. The Airflow Interlock, burner switch, Run/Test switch
and all microcomputer-monitored circuits must also be
in the correct operating state.
2. The motor output, terminal 4, is powered to start the
PREPURGE sequence.
3. The Airflow Interlock input closes ten seconds into
PREPURGE or within the specified purge card timing;
otherwise, a recycle to the beginning of PREPURGE or
lockout occurs, depending on how the Airflow Switch
selectable jumper (JR3) is configured.
Ignition Trials
1. Pilot Flame Establishing Period (PFEP):
a. When the PFEP begins:
(1) The pilot valve and ignition transformer,
terminals 8 and 10, are energized. The
EC7895A, RM7895A,B, and RM7896A,B have
an intermittent pilot valve, terminal 8. The
EC7895C, RM7895C,D, and RM7896C,D have
an interrupted pilot valve, terminal 8.
(2) Flame must be proven by the end of the ten
second PFEP (four seconds if Configuration
Jumper JR1 is clipped) to allow the sequence to
continue. If a flame is not proven by the end of
PFEP, a safety shutdown occurs.
b. With flame proven, the ignition, terminal 10, is
de-energized.
NOTE: For the RM7895C1020 and RM7896C1036, during
the first 8 seconds of PFEP, when a flame signal is
detected, terminal 10 is de-energized. If the flame
signal is lost, terminal 10 will re-energize.
2. Main Flame Establishing Period (MFEP):
a. After PFEP, and with the presence of flame,
the main fuel valve, terminal 9, is powered. If a
flameout occurs, the relay module locks out or
recycles (depending on status of jumper JR2) within
0.8 or 3 seconds, depending on the Flame Failure
Response Time (FFRT) of the amplifier.
b. The EC7895C, RM7895C,D and RM7896C,D
have a ten second MFEP. After the Ignition Trials,
the pilot valve, terminal 8, is de-energized. If a
flameout occurs, the relay module locks out or
recycles (depending on status of jumper JR2) within
0.8 or 3 seconds, depending on the Flame Failure
Response Time (FFRT) of the amplifier.
1166-1090—06
Page 12
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
Run
1. The EC7895C, RM7895C,D, RM7896C,D has a
delayed main valve that is energized once the RUN
period is entered.
2. The relay module is now in RUN and remains in RUN
until the controller input, terminal 6, opens, indicating
that the demand is satisfied or a limit has opened.
Post Purge (RM7896A,B,C,D Only)
After demand is satisfied or a limit opens, de-energizing
terminal 6, the Ignition/Pilot valve, main valve and delayed
main valve, terminals 8, 9 and 21, are de-energized. The
blower motor, terminal 4, remains powered for 15 seconds.
Run/Test Switch (RM/EC7895C,D; RM7896C,D only)
The Run/Test Switch is located on the top side of the relay
module, see Fig. 5. The Run/Test Switch allows the burner
sequence to be altered as follows:
1. In the measured PREPURGE sequence, the Run/Test
Switch, placed in the TEST position, causes the
PREPURGE timing to stop.
2. In the Pilot Flame Establishing Period, the Run/Test
Switch, placed in the TEST position, stops the timer during the first eight seconds of a ten-second PFEP selection or during the first three seconds of a four-second
PFEP selection. It also allows for pilot turn-down test
and other burner adjustments. This activates a fifteensecond flameout timer that permits pilot flame adjustment without nuisance safety shutdowns. The Run/Test
Switch is ignored during PFEP for the C and D relay
modules if terminals 8 and 9 or 9 and 21 are jumpered.
IMPORTANT
When the relay module is switched to the TEST
mode, it stops and holds at the next Run/Test Switch
point in the operating sequence. Make sure that the
Run/Test Switch is in the RUN position before
leaving the installation.
RUN/TEST SWITCH
SEQUENCE
STATUS
LEDs
RESET
PUSHBUTTON
FLAME
SIMULATOR INPUT
Fig. 5. Sequence Status LEDs.
FLAME CURRENT
TEST JACKS
CAPTIVE
MOUNTING
SCREW
PLUG-IN
PURGE
CARD
DUST
COVER
RELAY
MODULE
FLAME
AMPLIFIER
M7552A
SETTINGS AND ADJUSTMENTS
Selectable Site-Configurable Jumpers
The relay module has three site-configurable jumper options,
see Fig. 6 and Table 6. If necessary, clip the site-configurable
jumpers with side cutters and remove the resistors from the
relay module.
SERVICE NOTE: Clipping and removing a site-configurable
jumper enhances the level of safety.
SELECTABLE CONFIGURATION JUMPERS
RUN/TEST SWITCH
(EC7895C; RM7895C,D; RM7896C,D)
M7553A
Fig. 6. Selectable site-configurable jumpers.
Table 7. Site-configurable jumper options.
Jumper
NumberDescriptionIntactClipped
a, b
JR1
c
JR2
JR3Airflow Switch (ILK)
a
The RM7895C1020 and RM7896C1036 have fixed PFEP
of ten seconds and do not have jumper JR1 (3 seconds
software revision 4151 or greater).
b
The RM7895C1053 has fixed PFEP of four seconds and
does not have jumper JR1.
c
The RM7895C1053 locks out on Flame Failure Action and
does not have jumper JR2.
IMPORTANT
Pilot Flame Establishing
Period (PFEP)
10
seconds
4 seconds
Flame Failure ActionRecycleLockout
RecycleLockout
Failure
Clipping and removing a jumper after 200 hours of
operation causes a nonresettable Fault 110. The
relay module must then be replaced.
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée