Grieve Corporation DB10 Installation Manual

Page 1
DIN-A-MITE
®
Style B
Solid-State Power Controller
User’s Manual
DIN-A-MITE Solid-State Power Controller
0600-0025-0005 Rev H Made in the USA
Please consult this user’s manual when you place your new DIN-A-MITE into service. It contains all the necessary information to mount and wire the product into the application. This manual also contains all user-pertinent specifications and semiconductor fusing recommendations. Refer to national and local electrical code safety guidelines whenever you install electrical equipment.
This DIN-A-MITE product is capable of switching up to 40 amps single-phase; 33 amps 3-phase, 2-leg; and 22 amps 3-phase, 3-leg at 600V
Å (ac). (See the output rating curve in the
specifications section of this manual.) The DIN-
A-MITE is electrically touch-safe, and includes DIN rail or standard back panel mounting. An optional shorted SCR (silicon controlled rectifier) alarm feature is available on specific models. UL
®
508-listed, C-UL®and CE with filter.
The DIN-A-MITE solid-state power controller is designed and manufactured by Watlow in Winona, Minnesota.
1241 Bundy Boulevard, Winona, Minnesota USA 55987
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
Page 2
2
WATLOW DIN-A-MITE Style B User's Manual
General Specifications
Operator Interface
• Command signal input and indication light
• Alarm output and indication light
• Input indicator LED
Amperage Rating
• See the output rating curve chart on page 3.
• Ratings are into a resistive heater load.
• Maximum surge current for 16.6 milliseconds, 380 A peak
• Maximum I
2
t for fusing is 4000 A2s
• Latching current: 200mA minimum
• Holding current: 100mA minimum
• Off-state leakage 1mA at 25°C (77°F) maximum
• Power Dissipation: 1.2 watts per amp switched
• 200KA SCCR type 1 and 2 approved with the recommended fusing (see page 3)
Line Voltage
• 24 to 48V~ (ac) units: 20.4V~ minimum to 53V~ maximum
• 120 to 240V~ (ac) units: 48V~ minimum to 265V~ maximum
• 277 to 600V~ (ac) units: 85V~ minimum to 660V~ maximum
Control Mode, Zero-Cross
• Input Control Signal Type C: VÎ (dc) input contactor. To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type K: V~ (ac) input contactor. To increase service life, the cycle time should be less than 3 seconds.
• Input Control Signal Type F: 4 to 20mAÎ (dc) proportional variable time base control.
Input Command Signal
AC contactor
24VÅ ±10%, 120VÅ +10%/-25%, 240VÅ (ac)
+10%/-25% @ 25mA maximum per controlled leg
• Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
DC Contactor
4.5VÎ to 32VÎ (dc): maximum current @ 4.5VÎ (dc) is 6mA per leg, plus 2mA per LED used.
Loop powered linear current
4mAÎ to 20mAÎ (dc): loop-powered. Input Type F0 option only. (Requires current source with 6.2VÎ (dc) available. No more than three DIN-A-MITE inputs connected in series)
Linearity (Input Control Signal Type F)
• Full on point 19.5 to 19.9mAÎ (dc), maximum voltage
of 6.2V peak.
• ±5% input to output power accuracy, 0% to 100% of
span (4.3 to 19.7mA).
• Temperature stability is less than 0.15%/°C change.
Alarm (not available on multizone models)
Shorted SCR Alarm Option
• Alarm state when the input command signal off and a 10 A or more load current is detected by the current transformer (two turns required for 5A and three turns for 2.5A).
Alarm output
• Energizes on alarm, non-latching
• Triac 24 to 240V~ (ac), external supply with a current rating of 300mA @ 25°C (77°F), 200mA @ 50°C (122°F), 100mA @ 80°C (176°F) and a holding current of 200µA with a latching current of 5mA typical.
Agency Approvals
• CE with proper filter:
89/336/EEC Electromagnetic Compatibility Directive
EN 61326: Industrial Immunity Class A emissions
73/23/EEC Low Voltage Directive
EN 50178 Safety Requirements
Installation category III, pollution degree 2
•UL
®
508 listed and C-UL®, File E73741
Input Terminals
• Compression: Will accept 0.2 to 1.5 mm2(24 to 16
AWG) wire
• Torque to 0.5 Nm (4.4 in-lb) maximum with a 3.5 mm
(1/8 in) blade screwdriver
• Wire strip length 5.5 mm (0.22 in)
Line and Load Terminals
• Compression: Will accept 0.75 to 10 mm2 (18 to 8
AWG) wire
• Torque to 1.4 Nm (12 in-lb) with a 6.4 mm (1/4 in)
blade screwdriver, or a Type 1A #2 Pozi driver.
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 6.35 mm (0.25 in)
• Ground terminal use spade terminal for No. 8 screw,
with upturned lugs.
Operating Environment
• See the output rating curve.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters
DIN Rail Mount
• DIN EN 50022, 35 mm by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)
Note: Mount cooling fins vertically.
Back Panel Mount
• Four mounting holes M4 (No. 8) fastener
Weight
• 0.7 kg (1.6 lb)
Specifications are subject to change without notice.
Page 3
WATLOW DIN-A-MITE Style B User's Manual
3
DIN-A-MITE B Ordering Information
To order, complete the code number on the right with the information below:
Style B = solid-state power controller D B _ _ - _ _ _ _ - _ _ _ _ Phase
1 = single-phase, 1 controlled leg 2 = 3-phase, 2 controlled legs 3 = 3-phase, 3 controlled legs (for 4-wire wye) 8 = 2 independent zones (input control C or K) 9 = 3 independent zones (input control C or K)
Cooling and Current Rating Per Pole
0 = Natural convection standard DIN rail or panel heatsink
Line and Load Voltage
02 = 24 to 48VÅ (ac) 24 = 120 to 240VÅ (ac) 60 = 277 to 600VÅ (ac)
Input Control Signal
C0 = 4.5 to 32VÎ (dc) contactor K1 = 22 to 26VÅ contactor K2 = 100 to 120VÅ contactor K3 = 200 to 240VÅ contactor F0 = Proportional 4 to 20mA
Alarm
0 = No alarm S = Shorted SCR Alarm (not available with phase options 8 or 9 above)
User Manual Language
0 = English 1 = German 2 = Spanish 3 = French
Custom Part Numbers
00 = Standard part XX = Any letter or number, custom options, labeling, etc.
Current Rating Table
Model Current
at 50°C (122°F)
DB10 35A DB20, DB80 25A DB30, DB90 17A
Note:
• Recommended fusing options to meet 200KA SCCR, type 1 and 2 approved. All other fuse and SCR combinations are defaulted to 5KA SCCR per UL508A and NEC guidelines.
Output Rating Curves
0 5 10 15 20 25 30 35 40 45 50 55 60
25
30
35
40
45
50
55
60
65
70
75
80
90
85
Current (Amps) into a Resistive Load
Maximum Internal Enclosure Ambient Temperature (°C)
DIN-A-MITE Style B Ratings at 100% On
Natural Convection
3-phase, 3-leg
3-phase, 2-leg
Single-phase
Recommended Semiconductor Fuse and Fuse Holder
Bussmann
Fuse Watlow Bussmann Combination
20 A 17-8020 FWP20A10F DFJ20 30 A 17-8030 FWP30A14F DFJ30 40 A 17-8040 FWP40A14F DFJ40 50 A 17-8050 FWP50A14F DFJ50
Holders
20 A 17-5110 17-5110 CH30J1i 30 A 17-5114 17-5114 CH30J1i 40 A 17-5114 17-5114 CH60J1i 50 A 17-5114 17-5114 CH60J1i
Page 4
4
WATLOW DIN-A-MITE Style B User's Manual
1. Push the unit in and down to catch the rail hook on top of the rail.
2. Rotate the bottom of the unit in toward the rail.
3. The rail clasp will audibly “snap” into place. If the DIN-A-MITE does not snap into place, check to see if the rail is bent.
4. Mount the cooling fins vertically.
ç
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
5
WARNING: Hot surface, do not touch the heat sink. Failure to follow this guideline could result in personal injury.
ç
Mount the cooling fins vertically.
1
1
2
Mount
Dismount
ç Ó
3
5
Unit Dimensions - Rail-Mounted
1. Press down on the release tab while rotating the unit up and away from the rail.
4
3
Top
54 mm
(2.11 in)
46 mm
(1.81 in)
38 mm
(1.51 in)
49 mm
(1.91 in)
to 35.3 (1.390 in)
83 mm
(3.25 in)
124 mm (4.88 in)
Front
DIN-EN 50022 35 mm by 7.5 mm rail (clipping distance 34.7 mm (1.366 in)
Allowance for #8 fastener, metric = M4
Grounding screw (#6)
83 mm
(3.25 in)
49 mm
(1.92 in)
Allowance for #8 fastener,
metric = M4
94 mm
(3.69 in)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Side
75 mm
(2.97 in)
Rail release tab
(pull down)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Zero electrical clearance required
26 mm
(1.03 in)
41 mm
(1.60 in)
40 mm
(1.56 in)
102 mm (4.00 in)
71 mm
(2.80 in)
102 mm (4.00 in)
Page 5
WATLOW DIN-A-MITE Style B User's Manual
5
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A­MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to-neutral, 100 VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Ó
4
WARNING: Do not use the DIN-A-MITE Vac­input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
NOTE: Shorted SCR (silicon- controlled rectifier) alarm option not available with multizone input option.
Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DB [1, 2, 3] _ - _ _ [C, F, K] _ - _ _ _ _)
2-zone
3-zone
Multizone Input Wiring
ç Ó
1
Ó
3
Ó
4
(For models DB [8, 9] _ - _ _ [C, K] _ - _ _ _ _)
3-zone
Multizone Output Wiring
2-zone
(For models DB [8, 9] _
- _ _ [C, K] _
- ____
ç Ó
1
Ó
2
Ó
3
NOTE: Independent loads do not have to be on the same phase.
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10 AWG) wire.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
23
V~ (ac) Input:
4 to 20 mAÎ (dc) Input: +
4.5 to 32 VÎ (dc) Input: +
+
7
-
8
-
9
+
7
-
8
-
9
1
7 8
9 10 11 12 13 14 15 16
4
56
Zone 1 VÎ (dc) Input: +
Zone 2 VÎ (dc) Input: +
Zone 1 VÅ (ac) Input:
Zone 2 VÅ (ac) Input:
Zone 1 VÎ (dc) Input: +
Zone 2 VÎ (dc) Input: + Zone 3 VÎ (dc) Input: +
Zone 1 VÅ (ac) Input:
Zone 2 VÅ (ac) Input:
Zone 3 VÅ (ac) Input:
7 8
-
9
10 11 12
-
13 14 15 16
7 8
9 10 11 12 13
7 8
-
9
10
-
11 12
-
13 14
7
15
8
16
9 10 11 12 13
1
4
1
4
23
56
23
56
Semiconductor Fuses
23
1
7 8
9 10 11 12 13 14 15 16
Heater 1
4
L2
Zone 1
56
Limit Control
Contacts
(if required)
Line
Voltage
L1
L1
Zone 2
2 Independent,
Single-Phase
Heater 2
L2
Heaters
Line
Semiconductor Fuses
23
1
7 8
9 10 11 12 13 14 15 16
Heater
Zone 2
56
L2
Heater
2
Zone 3
Heater
3
3 Independent,
Single-Phase Heaters
L2
Zone 1
4
1
L2
Limit Control
Contacts
(if required)
Voltage
L1
L1
L1
Page 6
6
WATLOW DIN-A-MITE Style B User's Manual
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10 AWG)
wire.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
Single-phase Output
ç Ó
1
Ó
2
Ó
3
3-phase, 2-leg Output
ç Ó
1
Ó
2
Ó
3
3-phase, 3-leg Output
ç Ó
1
Ó
2
Ó
3
Semiconductor Fuse
7 8
9 10 11 12 13 14 15 16
7 8
9 10 11 12 13 14 15 16
7
8
9 10 11 12 13 14 15 16
1
4
1
4
1
4
23
56
23
56
23
56
Phase-to-phase 200V~ (ac) and above
Limit Control Contacts (if required)
Heater
Semiconductor Fuses
Semiconductor Fuses
L1
L2
Limit Control
Contacts
(if required)
Limit Control
Contacts
(if required)
Heater
T2
Heater
Phase-to-neutral 100V~ (ac) and above
L1
Neutral
L1
L2
L3
T3
T1
L1
L2
L3
Neutral
Page 7
WATLOW DIN-A-MITE Style B User's Manual
7
Current Transformer and Alarm Wiring
ç Ó
1
Ó
2
Ó
3
DB _ _ - _ _ _ _ - S_ _ _
The Watlow DIN-A-MITE alarm option provides a common alarm output for shorted SCR conditions.
This is a non-latching alarm.
A shorted SCR alarm is detected when there is no command signal and a load current is detected. The alarm output is then energized.
Load Current Passes of Load
Wire Through the
Current Transformer
5 to 9A 2
10 to 30A 1
3-phase, 3-leg Current Transformer Wiring
3-phase, 2-leg Current Transformer Wiring
ç Ó
1
Ó
2
Ó
3
ç Ó
1
Ó
2
Ó
3
ç Ó
1
WARNING: Use National Electric (NEC) or other country-specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above configuration. In phase-to­neutral, 100VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
This configuration is for a 4 wire configured heater only!
V~
120 or 240 V~
@ 300 mA maximum
energizes on alarm
Alarm Relay
or Indicator
Alarm
1A
Current
Transformer
(CT)
23
1
56
4
Transformer (CT)
Current
CT
7 8
9 10 11 12 13 14 15 16
7 8
9 10 11 12 13 14 15
CT
16
Load Wire
1
4
Heater
23
56
T2
T3
Heater
T1
CT
23
1
7 8
9 10 11 12 13 14 15 16
4
56
Current
Transformer (CT)
T2
T3
Heater
Neutral
T1
Page 8
8
WATLOW DIN-A-MITE Style B User's Manual
ç Ó
1
WARNING: Use National Electric (NEC) or other country­specific standard wiring practices to install and operate the DIN-A-MITE. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Ó
2
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above configuration. In phase-to­neutral, 100 VÅ (ac) and above applications, L2 is neutral and must not be fused or switched. Failure to follow this guideline could result in personal injury or death.
Ó
3
WARNING: Only authorized and qualified personnel should be allowed to install and perform preventive and corrective maintenance on this unit. Failure to follow this guideline could result in damage to equipment, and personal injury or death.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to include an intermediate relay for each DIN-A-MITE used.
Torque Guidelines
• Properly torque line and load terminals to 1.4 Nm (12 in-lb).
• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
System Wiring Example
Latching Alarm Option (models DB _ _ -
_ _ _ _ - S _ _ _ )
Alternative Latching Alarm Circuit
If there is a need for a latching alarm, the DIN-A-MITE alarm circuit could be used as shown at right in the latching alarm example. If the DIN-A-MITE triac alarm output energizes, it will energize the RY1 (external alarm relay) mechanical relay coil. Once the RY1 coil is energized it will latch on (via the RY1A normally open contact) until the power to the relay is removed. You could cycle the power via a reset switch. The RY1B contact can be used for alarm signaling.
11
22 33 44 55 66
8 9 10 11
12 13 14
Breaker
+ –
Controller TC
120V~ (ac)
CR1
LP1
Alarm
Over-
Temperature
Coil
AC Common
High Limit TC
AC High
SD6C-HCAA-AARG
L3
480VÅ (ac)
L2
L1
480V~ (ac)
CR1 = High-Limit Contactor
+ –
LF-C4JW-0120-AAAA-A
Reset Switch
(customer supplied)
7. COM
6. N.O.
8. N.C.
4. TC+
3. TC-
1. SW-1
2. SW-2
10. L1
9. L2
Page 9
WATLOW DIN-A-MITE Style B User's Manual
9
NOTE: The current transformer must be in the center uncontrolled leg on a 2-leg DIN-A-MITE.
Non-latching Alarm Option (models DB_ _ -
_ _ _ _ - S _ _ _ )
Shorted SCR (silicon-controlled rectifier) Alarm Non-latching Operation
The shorted SCR detector compares the input command signal and actual load current. If load current is present without an input signal then the shorted SCR alarm will energize the alarm triac output. This is a non-latching alarm. This output can be used to drive various indication devices, such as a coil, light, buzzer, etc. See the alternative latching circuit section below.
VÅ
13
14
Triac
RY1 Coil
Reset Switch
RY1A
L1
L2
RY1B
Normally open
Common
Normally closed
(External alarm relay contacts, set A)
(External alarm relay contacts, set B)
Latching Alarm Relay Circuit
Ungrounded Delta or Wye Load 3-phase, 2-leg DIN-A-MITE
Current
Transformer (CT)
Delta Load
Ungrounded
Wye Load
6
54
V~
(ac)
120 or 240V~ (ac) @ 300mA maximum energizes on alarm
Semiconductor
Fuses
Signal
Alarm Relay
or Indicator
1A
7 8
9 10 11 12 13 14 15 16
1
23
4
56
High-limit
Contactor (CR1)
CT
DB20-60C0-S000
NOTE: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm
2
(10 AWG)
wire.
Page 10
10
WATLOW DIN-A-MITE Style B User's Manual
Declaration of Conformity
DIN-A-MITE®“B” Power Controller
Watlow Winona, Inc.
1241 Bundy Blvd Winona, MN 55987 USA
Declares that the following product:
Designation: DIN-A-MITE® “B” Power Control Model Numbers: DB (1, 2, 3, 4, 8 or 9) 0 – (02, 24 or 60)(CX, FX, K1, K2, K3) – (0, C, D, H or
S)(followed by any 3 numbers or letters) (where X = any number 0-9)
Classification: Power Control, Installation Category III, Pollution degree 2 Rated Voltage: 24 to 600VÅ (ac)
Rated Frequency: 50 or 60 Hz Meets the essential requirements of the following European Union Directives by using the relevant standards shown below to indicate compliance.
889/336/EEC Electromagnetic Compatibility Directive
EN 61326: 1997 With A1:1998 – Electrical equipment for measurement, control and laboratory use – EMC
requirements (Industrial Immunity, Class A Emissions)
Not for use in a Class B environment without additional filtering. EN 61000-4-2 1996, With A1, 1998 Electrostatic Discharge Immunity EN 61000-4-3 1997 Radiated Field Immunity EN 61000-4-4 1995 Electrical Fast-Transient / Burst Immunity EN 61000-4-5 1995, With A1, 1996 Surge Immunity EN 61000-4-6 1996 Conducted Immunity EN 61000-4-11 1994 Voltage Dips, Short Interruptions and Voltage Variations
Immunity
EN 61000-3-2 1995, With A1-3, 1999 Harmonic Current Emission EN 61000-3-3: 1995, With A1, 1998 Voltage Fluctuations and Flicker. See note 3.
NOTE 1: Use of an external filter is required to comply with conducted emissions limits. See page 11 for
information and instructions.
NOTE 2: A Line Impedance Stabilization Network (LISN) was used for conducted emissions measure-
ments.
NOTE 3: To comply with flicker requirements, command signal models FX may not be used, and cycle
time must be set greater than 4 seconds on CX,K1, K2, and K3 models.
73/23/EEC Low-Voltage Directive
EN 50178 1997 Electronic equipment for use in power installations.
Raymond D.Feller III
Winona, Minnesota, USA
Name of Authorized Representative Place of Issue
General Manager
September 2003
Title of Authorized Representative Date of Issue
Signature of Authorized Representative
Page 11
WATLOW DIN-A-MITE Style B User's Manual
11
An external EMI filter must be used in conjunction with the DIN-A-MITE for loads in excess of six amperes (6 A) at 150 to 250 kHz. Without a filter applied, the DIN-A-MITE does not comply with the conducted emissions standard for loads above 6 A at 150 to 250 KHz.
Watlow has verified that two types of filters will suppress electromagnetic interference (EMI) created by the DIN-A­MITE power controller to within the CE requirements.
A tank filter supplied by Crydom or Watlow, installed across the power lines, suppresses EMI on the power lines. See Figures 1 and 2.
See Table 1 for the correct filter.
Table 1— DIN-A-MITE EMI Filters.
çWARNING:
The isolating and tank filters specified may suppress desirable communications carried on power lines in the 150 to 250 kHz region. The filters may suppress carrier current such as that used for infant monitors and medical alert systems. Verify that suppressed carrier current or other desirable communications on power lines creates no hazard to people or property. Failure to observe this warning could result in damage to property, and injury or death for personnel.
ÓWARNING:
All filter installation and wiring must be performed by qualified personnel, and conform to local and national electrical codes. Failure to observe this warning could result in damage to property, and injury or death for personnel.
Figure 1 — Tank filter, single-phase, 230V.
Required External EMI Filters for DIN-A-MITE with More than 6 A Loads
Description Crydom Watlow
Filter Filter
Single-phase, 230VÅ (ac) 1F25 14-0019 Three-phase, 440VÅ (ac) 3F20 14-0020
Figure 2 — Tank filter, three-phase, 440V.
A
Breaker or fused disconnect
N
PE
A protective earth (PE) connection is required.
Semiconductor Fuse
Filter
2
DIN-A-MITE
Heater
Breaker or fused disconnect
A
B
C
Filter
PE
A protective earth (PE) connection is required.
3
6
5
Semiconductor Fuses
5
A third semiconductor fuse is not needed with a 2-leg DIN-A-MITE.
3
2
1
DIN-A-MITE
5
64
4
Alternate
6
Heater
Page 12
12
WATLOW DIN-A-MITE Style B User's Manual
The Watlow DIN-A-MITE is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, abuse or improper fusing.
Warranty
Watlow DIN-A-MITE Style B User's Manual
1241 Bundy Boulevard, Winona, Minnesota USA 55987
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
Return Material Authorization (RMA)
1. Call Watlow Customer Service, (507) 454­5300, for a Return Material Authorization (RMA) number before returning any item for repair. We need this information:
Ship to address
Bill to address
Contact name
Phone number
Method of return shipment
Your P.O. number
Detailed description of the problem
Any special instructions
Name and phone number of person returning the product.
2. Prior approval and an RMA number from the Customer Service Department is needed when returning any product for credit, repair or evaluation. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis.
3. After we receive your return, we will examine it and try to verify the reason for returning it.
4. In cases of manufacturing defect, we will enter a repair order, replacement order or issue credit for material returned.
5. To return products that are not defective, goods must be be in new condition, in the original boxes and they must be returned within 120 days of receipt. A 20 percent restocking charge is applied for all returned stock controls and accessories.
6. If the unit is unrepairable, it will be returned to you with a letter of explanation.
7. Watlow reserves the right to charge for no trouble found (NTF) returns.
If you encounter a problem with your Watlow power controller, review your configuration information to verify that your selections are consistent with your application: inputs, outputs, alarms, limits, etc. If the problem persists, you can get technical assistance from your local Watlow representative, by e-mailing your questions to wintechsupport@watlow.com
or by dialing +1 (507) 494-5656 between 7 a.m. and 5 p.m., Central Standard Time (CST). Ask for an Applications Engineer. Please have the following information available when calling:
• Complete model number
• All configuration information
• User’s Manual
• Wiring diagram of your system
The DIN-A-MITE B User’s Manual is copyrighted by Watlow, Inc., © September 2004, with all rights reserved.
Technical Assistance