Grieve Corporation 8044 Installation Manual

Installation & Maintenance Instructions
2-WAY FREE HANDLE" MANUAL RESET SHUT-OFF VALVES
WITH VISUAL POSITION INDICATOR
NORMALLY CLOSED OPERATION
3/4, 1, 1 1/4, 1 1/2, 2, 2 1/2 OR 3 NPT
NOTICE: For instructions, see Form No. V6371-Section 1.
Torque Chart
SERIES
8044
(Section 2 of 2)
Part Name
(Note 1)
Solenoid base sub-assembly
Cover screws (4) 3/4 thru 3
Housing nut 3/4 thru 3 175 ± 25 in-lbs 19,8 ± 2,8
Bonnet assembly
Disc nut 3/4 thru 3 75 ± 10 in-lbs 8,5 ± 1,1
Bonnet screws
Valve Body Size (NPT)
3/4 thru 3 175 ± 25 in-lbs 19,8 ± 2,8 Figure 1
3/4 thru 2 175 ± 25 in-lbs 19,8 ± 2,8
2-1/2 and 3 50 ± 5 ft-lbs 67,8 ± 6,8
3/4 (Note 2) 95 ± 10 in-lbs 8,5 ± 1,1
3/4 thru 2 144 ± 15 in-lbs 16,3 ± 1,7
Torque Value
10 +5
-2 in-lbs
Torque Value
Newton-Meters
1,1 +0.6
-0.2
Figure Number
Where Used
Figure 2 & 3
2-1/2 and 3 250 ± 25 in-lbs 28,3 ± 2,8
3/4, 2-1/2 & 3 50 ± 5 ft-lbs 67,8 ± 6,8
End cap
1 thru 2 175 ± 25 in-lbs 19,8 ± 2,8
Indicator screw 3/4 thru 3 25 ± 25 in-lbs 2,8 ± 0,6
Notes:
1. Thread all parts by hand as far as possible. Then torque evenly in a crisscross manner where applicable.
2. Torque for catalog No. 8044A1 only.
ASCO Valves
MCMXCVI All Rights Reserved.
Printed in U.S.A.
50-60 Hanover Road, Florham Park, New Jersey 07932
Page 5 of 8 (Section 2 of 2)
Lubrication Parts to be lubricated
DOW CORNING 111 Compound
lubricant or an equivalent high-grade
silicone grease.
DOW CORNING 200 Fluid lubricant or an equivalent high-grade silicone fluid.
Texaco Inc. Code No. 2346
Low Temp Grease EP
(ASCO No. 208832-9)
When present
Lubrication Chart
disc gasket
solenoid base gasket body gasket housing gasket body passage gaskets (2) solenoid bushing plugnut gasket end cap gasket solenoid bonnet gasket operator gasket
stem/disc sub-assembly
Partial side view of valve body showing location of tapped and
plugged holes for pressure and seat leakage testing
Upper two tapped and plugged holes on either side of valve body are for upstream pressure testing
FLOW
OUT IN
1/8 NPT pipe plug (3/16 hex key wrench)
Lower two tapped and plugged holes on either side of valve body are for downstream seat leakage testing
Figure 1. Provisions for pressure and seat leakage testing.
Page 6 of 8 (Section 2 of 2) Form No.V6371R2-Sec. 2
ASCO Valves
50-60 Hanover Road, Florham Park, New Jersey 07932
Loading...