and Platinel II; and Pt 100 RTD;
0 to 20 mAdc and 4 to 20 mAdc
0 to 60 mVdc and 12 to 60 mVdc
0 to 5 Vdc or 1 to 5 Vdc
0 to 10 Vdc or 2 to 10 Vdc
Note: All inputs are factory calibrated and
selectable by jumper. Factory set at Type J.
Field 6. OUTPUT (High/Low Limit)
1 - Relay (Form C)
Field 7, 8. ALARMS, OPTIONS
00 -None
10 -One alarm - Relay Form A
11 -One alarm - Relay Form A, plus RS-485 and
one logic input.
Note: When code 11 is specified, instrument
length is 4.8 inches (122 mm)
Field 9. POWER SUPPLY
3 - 100 to 240 Vac
5 - 24 Vac/Vdc
Field 10. Mounting
0 - Panel Mount
R - Wall or Rail Mount
Fields 11 through 15. RESERVED
2
Congratulations
SV
. . . on your purchase of one of the easiest
to configure controllers on the market.
After a three step configuration procedure,
your process will be up and running.
If for any reason you encounter difficulty
with the controller set-up, please call your
supplier.
Unpack the
Instrument
Wiring
Guide to Simple Set-up
To set-up the controller, only four steps are
APPENDIX A ..................................................... 45
Default parameters ------------------------ 45
APPENDIX B ..................................................... 47
Thermocouple Compensating Cable
Color Codes. ------------------------------- 47
CAUTION!
USE WIRE SUITABLE
FOR 75° MINIMUM
NOTES:
• For supply connections use 16 AWG or
larger wires rated for at least 75° C
• Use copper conductors only
• Class 2 wiring must be separated a
minimum of 1/4 inch from any class 1
conductor
IMPORTANT!
Terminal identification of the panel mount
controller is different from terminal identification of the wall/rail mount controller! This
manual contains wiring instructions for both
types of controllers.
Be sure to follow the instructions that pertain
to the controller you are using.
4
Mounting Requirements
Panel Mount Controller
Select a mounting location with the following
characteristics:
1) Minimal vibration.
2) An ambient temperature range between 0 and
50°C (32 and 122 °F).
3) Easy access to the rear of the instrument.
4) No corrosive gases (sulfuric gas, ammonia,
etc.).
5) No water or other fluid (i.e. condensation).
6) Relative humidity of 20% to 80% non
condensing.
Bracke t
Gasket
The instrument can be mounted on a panel up to 15
mm (0.591 in) thick with a square cutout of 45 x 45
mm (1.772 x 1.772 in). For outline refer to Dimensions
and Panel Cutout.
Panel surface texture must be better than 248
microinches.
The instrument is shipped with a rubber panel gasket
(50 to 60 Sh). To assure the IP65 and NEMA 4
protection, insert the panel gasket between the
instrument and the panel as shown below.
Install the instrument as follows:
1) Insert the instrument in the gasket.
2) Insert the instrument in the panel cutout.
3) Pushing the instrument against the panel,
insert the mounting bracket.
4) Torque the mounting bracket screws between
0.3 and 0.4 Nm (2.66 and 3.54 lbf-in).
5) To insure NEMA 4X/IP65 protection, make sure
the instrument does not move within the
cutout .
Panel
5
Mounting Requirements
Wall or Rail Mount Controller
WARNING:
1) The correct functionality of these instruments
is guaranteed only if transport, storage,
installation, wiring, working condition and
maintenance are executed in compliance
with this manual.
2) The protection degree of these instruments is
equal to IP 20 (according to IEC529) and they
are connected to dangerous power lines, for
these reasons:
-installation, wiring and maintenance must
be executed by qualified personnel;
-all warnings contained in this manual must
be complied.
3) The safety requirements for Permanently
Connected Equipment say:
-a switch or circuit-breaker shall be
included in the building installation;
-It shall be in close proximity to the
equipment and easy to reach for the
operator;
-it shall be marked as the disconnecting
device for the equipment.
NOTE: a single switch or circuit-breaker can
drive more than one instrument.
4) Before to executing any operation on the
connections, disconnect the instrument from
the power line by the circuit breaker.
GENERAL ASSEMBLING INFORMATION
Select a cleaned location, easy to reach, where
minimum vibrations are present and the ambient
temperature is within 0 and 50 °C (32 and 122 °F).
These instruments can be mounted either on wall
or DIN rail.
RAIL MOUNTING
Use DIN rail in accordance with EN 50 022 (35 x 7.5
mm or 35 x 15 mm).
WALL MOUNTING
For wall mounting, use the (A) holes.
In this case it is advisable to use four M4
screws with a torque of 1Nm.
(A )
ºF
RESET
AL M
6/
(A )
6
Dimensions and Rear Terminal Blocks
Panel Mount Controllers
1.89 (48)
Dimensions shown in inches;
millimeters in parenthesis
Barber-Colman
2.47
(62.8)
Without RS-485
With RS-485
F
7SL
4.13 (105)
4.80 (122)
7
PANEL CUTOUT
Dimensions shown in inches;
millimeters in parentheses
2.9 5 (75)
2.36 (60)
1.772
+0 .024, -0
(45 +0.6 , -0 )
1.772 +0.024, -0
(45 + 0.6, - 0)
8
Dimensions
Wall or Rail Mount Controller
Dimensions shown in inches;
millimeters in parentheses
4.17 (106.)
2.26 (57.5)
RE SE T
ALM
1.69 (43)
7SL
5
(0. 20 in .)
0.20 (5.)
1.81 (46)
°F
3.78 (96)
0. 1 8 ( 4 .5 )
5.67 (144) for models with serial interface
5 (127) for models without serial interface
9
1.89 (48)
Wiring Guidelines
Panel Mount Controllers
A) Measuring Inputs
NOTE: Any external components (like Zener diodes,
etc.) connected between sensor and input terminals
may cause errors in measurement due to excessive
and/or not balanced line resistance or possible
leakage currents.
RTD INPUT -- Panel Mount Controller
RTD
RTD
TC Input
10
+
_
9
Shield
10
+
_
9
Shield
Thermocouple Input Wiring
NOTE:
1) Do not run input wires with power cables.
2) For TC wiring use proper compensating cable,
preferably shielded (see Appendix B).
3) Shielded cable should be grounded at one end
only.
8
NOTE:
1) Don’t run input wires with power cables.
2) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3) When shielded cable is used, it should be
grounded at one side only to avoid ground loop
currents.
4) Resistance of the 3 wires must be the same.
LINEAR INPUT - Panel Mount Controller
1098
RTD Input Wiring
10
9
mA, mV, and V Inputs Wiring
10
109
+
_
Shield
mA,
mV
or
V
10
9
+
mA
mV
_
or
V
G
mA, mV and V Inputs Wiring
NOTE:
1) Don’t run input wires together with power
cables.
2) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3) When shielded cable is used, it should be
grounded at one side only to avoid ground loop
currents.
4) The input impedance is equal to:
Less than 5 Ω for 20 mAdc input
Greater than 1 MΩ for 60 mVdc input
Greater than 400 KΩ for 5 Vdc and 10 Vdc
input
B) Logic Input - Panel Mount Controller
14
15
This input is used for remote acknowledgement
(reset).
Safety note:
- Do not run logic input wiring with AC power
cables.
Logic input
- Use an external dry contact capable of
switching 0.5 mA, 5 Vdc.
- The instrument needs 100 ms to recognize a
contact status variation.
- The logic inputs are NOT isolated from the
measuring input.
C.1) Relay Outputs Panel Mount Controller
OUT 1
Class 1
OUT 2
Class 1
(Alarm)
The OUT 1 contact rating is 3A/250V AC on
resistive load.
The OUT 2 contact rating is 2A/250V AC on
resistive load.
The number of operations is 1 x 10
rating.
NOTES 1) To avoid electric shock, connect power
line at the end of the wiring procedure.
2) For power connections use No 16 AWG
or larger wires rated for at last 75 °C.
3) Use cupper conductors only.
4) Don’t run input wires with power cables.
All relay contacts are protected by varistor against
inductive load with inductive component up to 0.5 A.
NO - OUT 1
1
C - OUT 1
2
NC - OUT 1
3
C
6
NO
7
5
at specified
11
The following recommendations avoid serious
problems which may occur, when relay outputs
are used with inductive loads.
C.2) Inductive Loads
High voltage transients may occur switching
inductive loads.
Through the internal contacts these transients
may introduce disturbances which can affect the
performance of the instrument.
For all the outputs, the internal protection
(varistor) assures a correct protection up to 0.5 A
of inductive component.
The same problem may occurs when a switch is
used in series with the internal contacts as
shown below:
C
R
LOAD
External Switch in Series with Internal Contact
In this case it is recommended to install an
additional RC network across the external contact
as shown above.
The value of capacitor (C) and resistor (R) are
shown in the following table.
LOAD
(mA)
<40 mA
<150 mA
<0.5 A
C
(µF)
0.047
0.1
0.33
(Ω)
100
22
47
R
P.
(W)
1/2
2
2
POWER
LINE
OPERATING
VOLTAGE
260 V AC
260 V AC
260 V AC
Anyway the cable involved in relay output wiring
must be as far away as possible from input or
communication cables.
D) Serial Interface
Panel Mounted Controllers
SERIAL INTERFACE
For units built with optional RS-485 communication
RS-485 interface allows to connect up to 30
devices with one remote master unit.
I
N
S
T
R
U
M
E
N
T
11
12
13
A/A'
B/B'
COMMON
A'/A
B'/B
RS-485 Wiring
The cable length must not exceed 9/10 mile (1.5
km) at 9600 baud.
NOTE: The following report describes the signal
sense of the voltage appearing across the
interconnection cable as defined by EIA for
RS-485.
a) The ” A ” terminal of the generator shall
be negative with respect to the ” B ” terminal
for a binary 1 (MARK or OFF) state.
b) The ” A ” terminal of the generator shall
be positive with respect to the ” B ” terminal
for a binary 0 (SPACE or ON)
12
M
A
S
T
E
R
I
N
S
T
R
U
M
E
N
T
I
N
S
T
R
U
M
E
N
T
11
12
13
11
12
13
A/A'
B/B'
A'/A
B'/B
COMMON
RS-485 Wiring for Multiple Instruments
E) Power Line and Grounding Panel Mount Controllers
N, L2
4
5
NOTE:
1) Before connecting the power line, check that
the voltage is correct (see Model Number).
2) For supply connections use 16 AWG or larger
wires rated for at least 75 °C.
R (S,T), L1
POWER SUPPLY
100 to 240 Vac
24 Vac/Vdc
N, L2
R (S,T), L1
3) Use copper conductors only.
4) Do not run input wires with power cables.
M
A
S
T
E
R
5) Polarity does not matter for 24 Vdc wiring.
6) The power supply input is NOT fuse
protected.
Please provide it externally.
Power supplyType CurrentVoltage
24 V AC/DCT500 mA250 V
100/240 V ACT125 mA250 V
When fuse is damaged, it is advisable to verify the
power supply circuit, so that it is necessary to
send back the instrument to your supplier.
7) Safety requirements for permanently
connected equipment:
- Include a switch or circuit-breaker in the
installation.
- Place switch in close proximity to the
equipment and within easy reach of the
operator.
- Mark the switch as the disconnecting
device for the equipment.
NOTE: A single switch or circuit-breaker can
drive more than one instrument.
8) When the NEUTRAL line is present, connect it
to terminal 4.
9) To avoid shock and possible instrument
damage, connect power last.
13
Wiring Guidelines
S h ie ld
Wall or Rail Mount Controller
Connections have to be executed when the
instrument is placed in its proper location.
Out 1
T/C (b)
T/C (a ): G, D, C , B , R, S
T/C (b ): J, K , L, N , T, E, U , Plati ne l
Model 7SL Terminal Block
Without RS-485 or Logic Input
Out 1
T/C (b)
Digi
Out 2
T/C(a)
Out 2
T/C(a)
MEASURING INPUTS
NOTES:
1) Any external components (like zener
barriers etc.) connected between
sensor and input terminals may cause
measurement errors due to excessive and/or not balanced line
resistance or possible leakage
currents.
2) The input accuracy is equal to +/- 0.2
% f.s.v. (**) +/- 1 dgt. @ 25 degrees
Celsius of ambient temperature.
(**) For TC input, the f.s.v. should be
referenced to the higher f.s.v. of the
TC selected.
TC INPUT
TC Type G, D, C, B, R and S
(Wall & Rail Mount)
+
15
-
14
S h ie ld
+
15
T/C (a ): G, D, C , B , R, S
T/C (b ): J, K , L, N , T, E, U , Plati ne l
Model 7SL Terminal Block
With RS-485 and Logic Input
-
14
Input Wiring for TC
Type G, D, C, B, R and S
14
TC Type J, K, L, N, T, E, U and
1615RTD
Platinel (Wall & Rail Mount)
+
15
-
11
S hie ld
+
15
-
11
S hie ld
Input Wiring for
TC Types J, K, L, N, T, E, U and Platinel
NOTE:
1) Do not run input wires with power
cables.
2) For T/C wiring use proper compensating cable, preferably shielded (see
appendix B).
3) When a shielded cable is used, it
should be connected to one side only.
RTD INPUT (Wall & Rail Mount)
RTD
1615
14
14
RTD Input Wiring
NOTE:
1) Don’t run input wires together with
power cables.
2) Pay attention to the line resistance; an
high line resistance may cause
measurement errors.
3) When shielded cable is used, it should
be grounded at one side only to avoid
ground loop currents.
4) The resistance of the 3 wires must be
the same.
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.