Grieve Corporation 700-HX Installation Manual

Multifunction Digital Timer
700-HX
User Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
IMPORTANT
Allen-Bradley is a trademark of Rockwell Automation
Identifies information that is critical for successful application and understanding of the product.

European Communities (EC) Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial
Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial
Environment
This product is intended for use in an industrial environment.

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61010-1 safety requirements for electrical equipment for measurement, control and laboratory use--Part 1 General Safety Requirements.
This equipment is classified as open equipment and must be mounted as instructed in an enclosure during operation to provide safety protection.

Preface

Manual Objectives

Who Should Use This Manual

Counter/Timer Mode Explanation

The purpose of this manual is to provide you with the additional information necessary to apply the 700-HX Multifunction Digital Timer. Described in this manual are methods for applying and troubleshooting this product.
This manual is intended for qualified personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of wiring diagrams, configuration procedures, related equipment, and safety precautions.
In this manual we refer to the Timer Output Modes with the following designations:
A: Signal ON delay 1
A-1: Signal ON delay 2
A-2: Power ON delay 1
A-3: Power ON delay 2

For Further Information

B: Repeat cycle 1
B-1: Repeat cycle 2
D: Signal OFF delay
E: One Shot
F: Cumulative
Z: ON/OFF-duty adjustable repeat cycle
toff: Repeat cycle OFF start
ton: Repeat cycle ON start
Note: In this manual the 700-HX Multifunction Digital Timer will be referred to as “700-HX.”
Relays and Timers Selection Guide
Publication 700-SG003A-EN-P
1 Publication 70 0-UM002 A-EN-D July 2001

Product Overview

Chapter
1

Bill of Material

Your 700-HX Multifunction Digital Timer product package includes the following items:
Item No. Description Quantity
700-HX Digital Timing Relay 1
6-Language Instruction Sheet 1
Rubber Gasket 1

Basic Product Information

Cat. No. Input Voltage Output Modes Timing Ranges Sockets Output Pins 700-HX86SA17
700-HX86SU24
100…240V AC
12…24V DC 24V AC
A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode toff ton
0.000…9.999 s
0.000…99.99 s
0.000…999.9 s
0.000…9999 s
0.000…99 min. 59 s
0.000…999.9 min.
0.000…9999 min.
0.000…99 h 59 min.
0.000…999.9 h
0.000…9999 h
700-HN100 700-HN125
SPDT 8
1 Publication 700-UM002A-EN-D - July 2001
1-2 Product Overview

Accessories (Order Separately)

Cat. No. Description Pkg. Qty. 70 0-HN100 Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting Guarded Terminal Construction 8-pin for use with Bulletin 700-HX timing relays. Order must be for 10 sockets or multiples of 10.
70 0-HN125 Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting Open Style Construction 8-pin for use with Bulletin 7 00-HX t iming relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.
19 9-DR1 DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10.
700-HN108 Specialty Socket
8-pin backwired socket with solder terminals for use with Bulletin 700-HX timing relays. Order must be for 10 sockets or mult iples of 10 .
70 0-HN130 Frame Adapter
For flush or door mounting of all Bulletin 700-HR and -HX timers.
700-HN132 Protective Cover
Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all Bulletin 700-HRs and -HX timing relays.
70 0-N40 Pre-printed identification tags— contains 10 sheets of
pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
10
10
10
1
1
10
Publication 700-UM002A-EN-D - July 2001
70 0-N41 Blank identification t ags— contains 1 0 sheets of blank
identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10

Product Features

Chapter
2

Block diagram

I/O Functions

Output circuit
(Basic insulation)
Display circuit
Input circuit
Note: Power circuit is not insulated from the input circuit.
In puts Start signal Stops t iming in A-2 and A-3 (power ON delay)
Reset Resets present value. (In elapsed time mode, the
Gate Inhibits timer operation.
Outputs Control ou tput (OUT) Outputs take place according to designated
Internal control circuit
Power supply circuit
modes. Start timing in other modes.
present value returns to 0; in remaining time mode, the present value returns to the set value.) Count inputs are not accepted and control out put turns OFF while reset input is ON. Reset indicator is lit while reset input is ON.
operating mode when timer reaches corresponding set value.
Key switch circuit
(See note.)
Gate capability not available.
1 Publication 700-UM002A-EN-D - July 2001
2-2 Product Features

Engineering Data (Reference Values)

)
4
1,000
500
100
50
Switching operations ( 10
10
250V A C cos =0.4
0 123 45
30V DC L/R=7 ms

Specifications

250V DC/30V cos =1
Load current (A)
Reference:A maximum current of 0.15 A can be switched
at 125V DC (cosφ=1) and a maximum current of 0.1 A
can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5V DC (failure level: P).
Electrical Ratings Pilot Duty Rating NEMA B300 Rated supply voltage 100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible
ripple: 20%(p-p) max.) Operating voltage range 85%…110% of rated supply voltage Power consumption 100…240V AC
24V AC/12…24V DC
Inrush Current 100…240V AC
24V AC/12…24V DC
120V AC
4.3 VA
3.4 VA/1.7 W
3 A
5 A
30 A
15 A Make 240V AC
120V AC
3 A
1.5 A
Break 240V AC Hp at 120V AC 1/4 Hp Hp at 240V AC 1/3 Hp Mechanical Mounting method Flush mounting, surface mounting, DIN mount ing Display 7-segment, negative transmissive LCD;
Present value (red, 8 mm high characters); Set value (green,
4 mm high characters) Digits 4 digits Timer Time ranges 0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s,
0 min. 0.0 s…99 min. 59 s, 0.0…999.9 min., 0 h 00 min.…99
h 59 min., 0.0 h…999.9 h, 0 h…9999 h
Timer modes Elapsed time (Up), remaining t ime (Down), selectable Output modes A, A-1, A-2, A-3, B, B-1, D, E, F, Z, ton or toff
Publication 700-UM002A-EN-D - July 2001
Product Features 2-3
Electrical Ratings Inputs Input signals Start , reset
Input method No-voltage input via:NPN transistor or switching of contact Start , reset, gate Minimum input signal width: 1 or 20 ms (selectable) Power reset Minimum power-opening time: 0.5 s (Except for A-3, B-1, and
F mode) Control output SPDT contact output: 5 A at 250V AC, resistive load
(cosine=1)
Minimum applied load: 10 mA at 5V DC (failure level: P,
reference value) External Power Supply No Key Protect Yes Memory backup EEP-ROM (overwritten 100,000 times min.), which can store
data for 2 0 years min.
Accuracy of Operating Time and Setting Error Power-ON start: +-0.01% +-50 ms max.*
* to be rated against set value
Signal start: +- 0.005 +-30 ms max. *
* to be rated against set value
Signal start at transistor out put model: +- 0.005% +-3 ms
max.
If the set value is within the sensor waiting time
(250 ms max.)
The values are based on the set value. The value is applied for a minimum pulse width of 1 ms.

Characteristics

Insulation resistance 100 M min. (at 500V DC)
Diele ctric strength 20 00V AC, 50/60Hz for 1 min. between current-carrying terminals and
non-current-carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 10 00V AC, 50/60 Hz for 1 min. between non-continuous contacts
Noise immunity '+-1.5 kV (between power terminals) for 100 to 240V AC, +-480V for 24V AC/12
to 24VDC, and +-600V (between input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity ±8 kV (malfunction), ±15 kV (destruction)
Vibr ation resistance Malfunction 10 …55 Hz with 0 .35 mm single amplitude each in three directions for 10 min. Shock resistance Malfunction
Life e xpectancy Mechan ical 10 million operations min.
Electrical 10 0,0 00 operations min. (5 A at 250V AC, resistive load)
EMC (EMI) EN61326
2
(approx. 10 G) each in three directions
98 m/s
Emission Enclosure: EN55011 Group1 class A Emission AC mains: EN55011 Group1 class A (EMS) EN61326 Immunity ESD: EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3) Immunity RF-interference: EN61000-4-3: 10 V/m
Publication 700-UM002A-EN-D - July 2001
2-4 Product Features
Approved standards UL508, CSA C22.2 No.14
Conforms to EN61010-1/IEC61010-1 (Pollution degree 2/ overvoltage category II) Conforms to VDE0106/P 100 (Finger Protection), conforms to NEMA output rating (N/F)
Enclosure rat ings Panel surface:IP66 and NEMA Type 4 (indoors)
Weight Approx. 100 g
An attached waterproof packing is necessary to ensure IP66 waterproofing between the
700-HX and installation pan.

Nomenclature

Indicator
A Reset Indicator (orange)
B Key Protection Indicator (orange)
C Control Output Indicator (orange)
D Present Value
Character height: 11.5 mm
E Time Unit Display (orange): (If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, this display flashes to indicate timing operation.)
F Set Value (green) Character height: 6 mm
G Set Value 1, 2 Display
Operation Key
D
A B C
G
H
I
E F
J K
Front View
H Mode Key (Changes modes and setting items)
I Reset Key (Resets present value and output)
J Up Keys 1 to 4
K Down Keys 1 to 4
Front color: Gray
Switches
LM
L Key-protect Switch
(default setting) OFF
ON
M DIP Switch
Case color: Gray
Publication 700-UM002A-EN-D - July 2001
Settings for Advanced
9

Functions

Power ON
Run mode
See note 1. See note 2.
3 s min. 3 s min.
Functions
For details on operations in run mode, refer to 3-9.
Note: 1. If the mode is switched to the function setting mode during operation,
operation will continue.
2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode. Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Press the mode button for several seconds to display the Time Range setting screen.
Chapter
3
Function setting mode
Set the time range using the keys.
Time range
s
Timer mode
Output mode
Output time
Input signal width
Key protect level
Set the timer mode using the keys.
Set the output mode using the keys.
Set each digit for the output time using the corresponding keys.
(If the output time is set to 0.00, is displayed.) Displayed for modes A, A-1, A-2, A-3, B, and B-1 only.
Set the key protect level using the keys.
ss hs
iA-1 jiA-2 jiA-3 jib-1 jib jid jiE jiF jiZ jiA j
i1 ms ji20 ms j
cc
Time Range List
Display
Set Value
0.01 s to 99.99 s (default setting)
0.1 s to 999.9 s
1 s to 9,999 s
0 min 01 s to 99 min
0.1 min to 999.9 min
1 min to 9,999 min
0 h 01 min to 99 h 5
0.1 h to 999.9 h
1 h to 9,999 h
0.001s to 9.999 s
1 Publication 700-UM002A-EN-D - July 2001
3-2 Functions

Explanations of Functions

Time Range (
Set the range to be timed in the range 0.000 s… 9,999 h. Use the operation keys if these settings are required.
Timer Mode (
Set either the elapsed time (UP) or remaining time (DOWN) mode.
Output Mode (
Set the output mode. The possible settings are A, A-1, A-2, A-3, B, B-1, D, E, F, and Z. (For details on output mode operation, refer to “Timing Charts” on page 3-10.)
Output Time (
When using one-shot output, set the output time for one-shot output (0.01…
99.99 s). One-shot output can be used only if the selected output mode is A, A-1, A-2, B, or B-1. If the output time is set to 0.00, hold is displayed, and the output is held.
timr
timm
outm
otim
)
)
)
)
Input Signal Width (
Set the minimum signal input width (20 ms or 1 ms) for signal and reset inputs. The same setting is used for all external inputs (signal and reset). If contacts are used for the input signal, set the input signal width to 20 ms. Processing to eliminate chattering is performed for this setting.
Key Protect Level (
Set the key protect level.
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-protect switch after the 700-HX is mounted to the panel.
iflt
kypt
)
)
Publication 700-UM002A-EN-D - July 2001
Functions 3-3
(See note)
Note: Factory-set to OFF
ON
OFF
Key protect indicator
Level Meaning KP-1 (default
setting)
Prohibits changing the mode to timer/ twin timer selection mode or function setting mode. The 700-HX can only be used in run mode.
KP-2 Prohibits changing the mode to timer/twin
timer selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset key.
KP-3 Prohibits changing the mode to timer/twin
timer selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the up and down keys.
KP-4 Prohibits changing the mode to timer/twin
timer selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset, up and down keys.
KP-5 Prohibits changing the mode to timer/twin
timer selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of any operation keys.
Publication 700-UM002A-EN-D - July 2001