Grieve Corporation 2216E Installation Manual

2216e
Temperature controllers
Installation and Operation handbook
ENG
Installation and Operation Handbook Contents
TEMPERATURE CONTROLLER
INSTALLATION AND OPERATION HANDBOOK
1. Chapter 1 OPERATION .................................................................................. 1-1
1.1 FRONT PANEL LAYOUT ........................................................................................................1-1
1.2 GETTING STARTED ...............................................................................................................1-3
1.2.1 Viewing The Process Value and Setpoint .........................................................................................................1-3
1.2.2 To Adjust The Setpoint ..........................................................................................................................................1-3
1.2.3 Viewing The Display Units ..................................................................................................................................... 1-4
1.2.4 Use Of The “SCROLL” Button ............................................................................................................................... 1-4
1.2.5 Use Of The ‘PAGE’ Button .....................................................................................................................................1-5
1.3 PARAMETER LISTS ...............................................................................................................1-6
1.4 MANUAL OR AUTOMATIC CONTROL ...................................................................................1-7
1.4.1 Selecting Auto/Manual Operation...................................................................................................................... 1-7
1.4.2 How To Manually Adjust Output Power...........................................................................................................1-8
1.5 SUMMARY ...........................................................................................................................1-8
1.6 SETPOINT 1 OR SETPOINT 2.................................................................................................1-9
1.6.1 To Select Setpoint 1 or Setpoint 2.....................................................................................................................1-9
1.7 RAMP DWELL FUNCTION ...................................................................................................1-10
1.7.1 To Set up a Ramp/Time Program......................................................................................................................1-10
1.7.2 To Run the Program.............................................................................................................................................. 1-11
1.7.3 Power Failure During Program Run ..................................................................................................................1-11
1.8 LOCATION OF PARAMETERS - BLOCK DIAGRAM................................................................1-12
1.9 NAVIGATION DIAGRAM (Part A) ........................................................................................1-13
1.10 PARAMETER TABLES ..........................................................................................................1-15
1.10.1 HOME Display .........................................................................................................................................................1-15
1.10.2 Alarm List .................................................................................................................................................................1-16
1.10.3 Autotune List...........................................................................................................................................................1-17
1.10.4 PID List ......................................................................................................................................................................1-17
1.10.5 Setpoint List.............................................................................................................................................................1-18
1.10.6 Input List................................................................................................................................................................... 1-19
1.10.7 On/Off List ...............................................................................................................................................................1-19
1.10.8 Output List ...............................................................................................................................................................1-20
1.10.9 Communications List............................................................................................................................................. 1-20
1.10.10 Access List .........................................................................................................................................................1-20
1.11 ALARMS.............................................................................................................................1-21
1.11.1 Types of Alarm Used in the 2200......................................................................................................................1-21
1.12 ALARM RELAY OUTPUT .....................................................................................................1-22
1.12.1 SETTING ALARM LEVELS ......................................................................................................................................1-23
1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT....................................................................................... 1-24
1.12.3 DIAGNOSTIC ALARMS ..........................................................................................................................................1-25
2. Chapter 2 INSTALLATION.............................................................................. 2-1
2.1 INSTRUMENT LAYOUT .........................................................................................................2-1
2.1.1 Outline Dimensions Model 2216e ...................................................................................................................... 2-2
2.2 Introduction ........................................................................................................................2-3
2.2.1 Controller Labels ......................................................................................................................................................2-3
2.3 MECHANICAL INSTALLATION...............................................................................................2-3
2.3.1 Unplugging and Plugging-in the Controller..................................................................................................... 2-3
2.4 WIRING................................................................................................................................2-4
2.4.1 Wire Sizes ................................................................................................................................................................... 2-4
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1
Contents Installation and Operation Handbook
2.4.2 Wiring Connections .................................................................................................................................................2-4
2.4.3 Sensor Input Connections...................................................................................................................................... 2-5
2.4.4 Outputs 1 and 2 Connections...............................................................................................................................2-5
2.5 PDS MODES ........................................................................................................................ 2-6
2.6 SNUBBERS .......................................................................................................................... 2-6
2.7 TYPICAL SINGLE LOOP WIRING DIAGRAM .......................................................................... 2-7
2.8 LOGIC DRIVE FAN OUT ....................................................................................................... 2-8
2.9 COMMUNICATION CONNECTIONS...................................................................................... 2-8
2.9.1 Wiring of EIA-485 Serial Communication Links ...............................................................................................2-9
2.10 DEVICENET WIRING TO SERIES 2200E CONTROLLERS.........................................................2-10
2.10.1 DeviceNet Terminal Functions.......................................................................................................................... 2-10
2.10.2 Wiring Interconnections for DeviceNet Communications ........................................................................ 2-11
3. Chapter 3 ACCESS LEVELS................................................................................ 1
3.1 THE DIFFERENT ACCESS LEVELS ............................................................................................. 1
3.2 SELECTING AN ACCESS LEVEL ............................................................................................. 3-2
3.2.1 Access list header .....................................................................................................................................................3-2
3.2.2 Password entry ..........................................................................................................................................................3-2
3.2.3 Level Selection ..........................................................................................................................................................3-3
3.2.4 Configuration password..........................................................................................................................................3-3
3.2.5 Configuration level ..................................................................................................................................................3-3
3.2.6 Returning to Operator Level .................................................................................................................................3-4
3.3 EDIT LEVEL.......................................................................................................................... 3-4
3.3.1 Setting operator access to a parameter............................................................................................................ 3-4
3.3.2 Hiding or revealing a complete list.....................................................................................................................3-4
3.3.3 Promoting a parameter ..........................................................................................................................................3-4
4. Chapter 4 TUNING....................................................................................... 4-1
4.1 WHAT IS TUNING? .............................................................................................................. 4-1
4.2 AUTOMATIC TUNING .......................................................................................................... 4-2
4.2.1 Heating and Cooling Output Cycle Times.........................................................................................................4-2
4.3 HOW TO TUNE.................................................................................................................... 4-3
4.3.1 Typical automatic tuning cycle .............................................................................................................................4-3
4.3.2 Calculation of the cutback values.......................................................................................................................4-3
4.4 MANUAL TUNING ............................................................................................................... 4-4
4.4.1 Setting the cutback values.....................................................................................................................................4-5
4.4.2 Integrating action and manual reset ..................................................................................................................4-6
4.4.3 Automatic droop compensation (Adc) ..............................................................................................................4-6
5. Chapter 5 CONFIGURATION ......................................................................... 5-1
5.1 Selecting Configuration Level ............................................................................................. 5-2
5.2 Selecting a Configuration Parameter.................................................................................. 5-3
5.3 Leaving Configuration Level ............................................................................................... 5-3
5.4 STEPS INVOLVED IN CONFIGURING A CONTROLLER........................................................... 5-3
5.5 Navigation Diagram (PART A) ............................................................................................ 5-4
5.6 navigation diagram (PART B).............................................................................................. 5-5
5.7 CONfIGURATION PARAMETER TABLES ................................................................................ 5-6
5.8 CONFIGURATION of digital communications.....................................................................5-14
5.8.1 To Configure the Function, and Baud Rate ................................................................................................... 5-14
5.8.2 To Set Instrument Address ................................................................................................................................. 5-15
5.9 DeviceNet ..........................................................................................................................5-15
5.9.1 The EDS File ............................................................................................................................................................ 5-15
5.9.2 ODVA Compliance ................................................................................................................................................5-15
6. Chapter 6 USER CALIBRATION ......................................................................... 1
6.1 WHAT IS THE PURPOSE OF USER CALIBRATION?................................................................... 1
2 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Contents
6.2 USER CALIBRATION ENABLE ...................................................................................................2
6.3 SINGLE POINT CALIBRATION ..................................................................................................3
6.4 TWO POINT CALIBRATION......................................................................................................4
6.5 CALIBRATION POINTS AND CALIBRATION OFFSETS ...............................................................5
7. Chapter 7 ALARM CONFIGURATION ............................................................. 7-1
7.1 DEFINITION OF ALARMS AND EVENTS.................................................................................7-1
7.1.1 Types Of Alarms ....................................................................................................................................................... 7-1
7.2 DIGITAL OUTPUT FUNCTIONS .............................................................................................7-3
7.3 STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS ..............................................................7-4
7.4 STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUT..................................................7-5
7.5 STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT ...........................................................7-6
7.6 STEP 4 - REMOVING ALARMS FROM AN OUTPUT................................................................7-6
8. Chapter 8 MOTORISED VALVE CONTROL .................................................... 8-1
8.1 PARAMETERS FOR MOTORISED VALVE CONTROL ...............................................................8-1
8.2 COMMISSIONING THE MOTORISED VALVE CONTROLLER....................................................8-1
8.2.1 Adjusting the minimum on-time ‘Ont.H’.........................................................................................................8-1
8.3 MOTORISED VALVE APPLICATIONS .....................................................................................8-2
8.3.1 Auto Tuning............................................................................................................................................................... 8-2
8.3.2 Valve Positioner Set-up Table.............................................................................................................................. 8-2
9. Chapter 9 LOAD CURRENT MONITORING AND DIAGNOSTICS...................... 9-1
9.1 LOAD CURRENT MONITORING AND DIAGNOSTICS .............................................................9-1
9.2 EXAMPLE WIRING DIAGRAM (MODE 1 & 2 OPERATION) .....................................................9-2
9.3 OPERATION .........................................................................................................................9-3
9.3.1 To Read Load Current (mode 2 only)................................................................................................................9-3
9.3.2 To Display Load Current Continuously in the Lower Readout (mode 2 only) ......................................9-3
9.3.3 Display Modes...........................................................................................................................................................9-3
9.3.4 How Heater Alarms Are Displayed .....................................................................................................................9-4
9.4 TO SET THE ALARM TRIP LEVELS .........................................................................................9-5
9.5 RELAY OUTPUTS ..................................................................................................................9-5
9.6 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS............................................................9-6
9.6.1 To Configure the Logic Module for PDS modes 1 or 2................................................................................ 9-6
9.6.2 To Configure Low and High Current Trip Alarms .......................................................................................... 9-7
9.6.3 To Attach Soft Alarms To A Relay Output .......................................................................................................9-8
9.6.4 The Scaling Factor ...................................................................................................................................................9-9
9.6.5 To Adjust The Scaling Factor ................................................................................................................................9-9
10. Chapter 10 RETRANSMISSION.................................................................... 10-1
10.1 What is retransmission ......................................................................................................10-1
10.2 To configure retransmission ..............................................................................................10-2
10.3 scaling retransmitted output signals.................................................................................10-3
10.3.1 To Range Retransmitted Output OP...............................................................................................................10-3
10.3.2 To Range Retransmitted Setpoint SP or Process Variable PV..............................................................10-4
10.3.3 To Range Retransmitted Error Err................................................................................................................ 10-4
11. Appendix A UNDERSTANDING THE ORDERING CODE ................................ 11-1
12. Appendix B SAFETY and EMC INFORMATION............................................. 12-1
13. Appendix C RoHS ...................................................................................... 13-1
2216e Controller Part Number HA026639 Issue 4 (CN22918) 3
Contents Installation and Operation Handbook
4 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1. Chapter 1 OPERATION
1.1 FRONT PANEL LAYOUT
Setpoint 2
Manual mode
Output 1
active
OP2
OP1
20.00
20.00
SP2 REM
MAN
Page
Button
Figure 1-1 Model 2216e front panel layout
Scroll
Button
Down
Button
HOLD
2216e
Output 2
Upper readout
Lower readout
Remote Setpoint
Setpoint rate limit active
Up
Button
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-1
Operation Installation and Operation Handbook
Button or indicator Name Explanation
OP1 Output 1
OP2 Output 2
SP2 Setpoint 2
REM Remote Setpoint
MAN Manual light
RUN Run light
Page button Press to select a new list of parameters.
Scroll button Press to select a new parameter in a list.
Down button Press to decrease a value in the lower readout.
Up button Press to increase a value in lower readout.
When lit, it indicates that heating output is on.
When lit, it indicates that cooling output is on.
When lit, this indicates that Setpoint 2 has been selected.
When lit, this indicates that the PDS remote Setpoint input has been selected. ‘REM’ is also used to indicate that user comms is active.
When lit, it indicates that manual mode has been selected
When lit, it indicates that Setpoint rate limit is active.
Figure 1-2 Controller buttons and indicators
For Valve Positioning, please refer to Appendix D ‘Motorised Valve Control
1-2 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.2 GETTING STARTED
Thank you for selecting the 2216e controller.
This section shows the principle of operation.
1.2.1 Viewing The Process Value and Setpoint
Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3 second self­test sequence, this is the display you will see,
Output 1
OP1
OP2
20.0
SP2
Rem
23.0
Figure 1-3 The “Home Display”
Output 2
Actual Temperature (Process Value)
Required Temperature (Setpoint)
The display may flash an alarm message. Refer to the Parameter Tables later in this
chapter for a complete list and meaning of the messages.
1.2.2 To Adjust The Setpoint
After 2 seconds the lower readout will ‘blink’ indicating that the new value has been accepted.
For everyday use you may not need to do anymore than this.
OP1
OP2
20.0
SP2
Rem
140.0
Press and hold to decrease temperature
Figure 1-4 The lower readout shows the setpoint
Press and hold to
increase temperature
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-3
Operation Installation and Operation Handbook
1.2.3 Viewing The Display Units
Figure 1.5 Pressing
0.5 sec.
20.0
140.0
23.0
C
Momentarily press either
or will flash the display units for 0.5 secs
button
Display Units
C Degrees Centigrade
F Degrees Farenheit
K Degrees Kelvin
No units - Linear inputs
If you get lost, pressing and together will return you to the Home display
1.2.4 Use Of The “SCROLL” Button
Pressing the scroll button will display the output power level. Continued pressing will display further parameters in the operator scroll list.
Figure 1-6 Upper readout is parameter name. Lower is value
OP
100.0
m-A
Auto
2nd press
Output
Actual output level %
3rd press
Manual/Auto
Actual state
Keep pressing to return to the Home display or select further parameters (if available)
1-4 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.2.5 Use Of The ‘PAGE’ Button
The “PAGE” button accesses parameter LISTS.
Parameters are settings in the instrument which, generally, can be changed by the user to suit the process. Examples are: Alarms, Self Tune, etc. They are found under headings called LISTS and a full set is given later in this chapter.
0.2 sec.
20.0
14.00
20.0 1400
2nd press
23.0
C
LiSt
AL
1st press
3rd press
atun
LiSt
Keep pressing to select more list headings
Figure 1-7 Press to choose a parameter list
The actual list headings may be longer or shorter than indicated above and you can
customise this for the operator’s convenience in EDIT level, Chapter 3.
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-5
Operation Installation and Operation Handbook
1.3 PARAMETER LISTS
Press to choose a LIST - “ALARMS” is a good one. This list allows you to set the alarm trip levels. The parameters which appear in the list will vary according to the configuration of your controller.
0.2 sec.
20.0
140.0
23.0
C
2nd press
larm
A List
AL
LiSt
There are 4 alarms in the controller. The first character is the alarm number. The following three letters indicate alarm type as follows:
-FSL F
-FSH F
-dHi D
-dLo D
-dEv Dev
-Lcr L
-Hcr H
Disabled alarms will not be displayed. Chapter 7 gives a full description of alarms.
Figure 1-8 Choose a list. Press to select a parameter
1st press
ull Scale Low
ull Scale High
eviation High
eviation Low
iation Band
ow current
igh current
1---
50.0
2---
200.0
Keep pressing
1. to scroll through further parameters
2. to return to list header
Now press the SCROLL button
Alarm 1
or to change
trip level
2nd press
Alarm 2
or to change trip level
1-6 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
If, at any time, no key is pressed within 45 seconds, the display will always return to the
“HOME” display.
A complete description of the parameter lists is given on page 1-14.
Installation and Operation Handbook Operation
1.4 MANUAL OR AUTOMATIC CONTROL
The controller can be used in two modes:
Automatic mode - in which the output power is automatically adjusted to hold the temperature at the required value. The controller normally operates in this mode.
Manual mode - in which the output is manually adjusted by the Operator. In this mode the ‘MAN’ light will be on.
One other mode is available:
Remote setpoint - The setpoint is generated as an input signal from a master 2000 series controller. In this mode the REM light is on.
1.4.1 Selecting Auto/Manual Operation
2 sec.
23.0
20.0
140.0
OP
100.0
m-A
mAn
Keep pressing to return to “HOME” display
Figure 1-9 Auto/Manual select
C
1st press
2nd press
O
utput
Actual output level %
3rd press
anual/Auto
M
or to select
Auto automatic mode Man manual mode
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-7
Operation Installation and Operation Handbook
1.4.2 How To Manually Adjust Output Power
Manual mode is generally used for test and commissioning purposes, take care not
to leave the controller in this mode since damage or personal injury could occur.
Press and hold to decrease power
Figure 1-10 The “Home Display” in manual mode
20.0
50.0
OP1
OP2
Press and hold to
increase power
Actual Temperature (Process Value)
Output Power Demand
Manual Indicator on
1.5 SUMMARY
To step through list headers press the Page button until the required header is obtained
To step through parameters within a particular list press the Scroll button until the required parameter is obtained
To change the value (or state) of a parameter press the Raise button or the Lower button
The remainder of this chapter provides a complete list of all parameters available.
1-8 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.6 SETPOINT 1 OR SETPOINT 2
The instrument has the facility to select two setpoints. This may be useful where it is required to switch control between two different setpoints, for example, from an operating to a standby condition, thus avoiding the necessity to change the setpoint manually each time.
1.6.1 To Select Setpoint 1 or Setpoint 2
This may be done in two ways:-
1. By an external switch or relay contact wired to a digital input
2. Through the front panel using the SP list
20.0
140.0
When setpoint 2 is selected the SP2 beacon illuminates.
Press to select SP list
Figure 1-11 To Select Setpoint 1 or 2
Setpoint List
SP
LiSt
SSEL
SP 1
Press scroll button to SSEL
or
Press between SP 1 and SP 2
to change
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-9
Operation Installation and Operation Handbook
1.7 RAMP DWELL FUNCTION
The ramp dwell function is selected by turning the setpoint rate limit parameter SPrr to a value. It can be set to RUN in two ways:-
1. Through the front panel using the SP list
2. By an external switch or relay contact wired to a digital input (Module 2 only) configured for reset
(rset). When closed the program will reset. When open the program will run. To run the program from the initial reset state, it is necessary to first close the switch then open it.
The controller will then ramp from setpoint 1 to setpoint 2 at a rate set by the SPrr parameter.
When the controller reaches setpoint 2 it can remain at this level for a timed period, using the dwel parameter.
At the end of the dwell period the action of the controller is determined by the End Type parameter End.t.
1.7.1 To Set up a Ramp/Time Program
Set setpoint 1 to the value at which to start the ramp. Set setpoint 2 to the value which you wish to ramp to. This is described in the previous section.
Now press until SPrr is displayed
or
Press
amp rate in units per minute
r
to set the SP
Press scroll button to dwEl
or
Press time in minutes
to set the dwell
Press scroll button to End.t
or
Press action required at the end of the dwell time
to choose the
SPrr
20.0
dwel
60.0
End.t
rESt
Figure 1-12 Ramp/Dwell Program
In Run mode the controller will ramp from SP 1 to SP 2 at 20.0 units per minute
In Run mode the controller will dwell at SP 2 for 60 minutes
In Run mode the controller will reset at the end of the dwell time. Other choices are:-
HoLd StbY dwel
The program will go into Hold The program will go into standby The program will dwell for an unlimited period
1-10 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.7.2 To Run the Program
From the previous view, press scroll button to ProG
Press run
or
to choose
Prog
run
To reset the controller to start conditions, select rSEt
In Full access level the Status of the program can be read as follows:-
From the previous view, press scroll button to StAt
StAt
rmp
The status may be any one of the following:
rmp
dwel
End
OFF
Ramping from SP1 to SP2
Dwelling at SP2
The program is complete. If End.t = rSEt, End will flash briefly
before changing to OFF
The program is in the reset state
A program may also be reset or run using an external switch contact if a digital input, in Module 2, has been configured. See Configuration section.
Figure 1-13 To Run the Ramp/Dwell Program
1.7.3 Power Failure During Program Run
1. During Ramp. After return of power, the working setpoint will servo to the current PV value, and
the ramp continues to SP2 followed by the timed dwell.
2. During Dwell. After return of power the working setpoint will servo to PV, the ramp continues to
SP2 followed by full programmed dwell. In effect this causes the program to restart.
Use the Hide, Reveal and Promote features to customise the display for a programmer. See Chapter
3.
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-11
Operation Installation and Operation Handbook
r
1.8 LOCATION OF PARAMETERS - BLOCK DIAGRAM
The controller consists of a number of internal function blocks connected together to create a temperature controller. Each function block has a number of parameters found in lists to which the user has access. The block diagram shows location of these parameters within the controller.
Display Parameters
PLANT INPUTS
Remote SP
TCs PRT Pyrometer mA. mV, Volts
Control Parameters
iP List
Input
PV
SP List
Timer
SP1/SP2
Setpoint
SP
Erro
These are available in configuration level only
AL List
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarms
OR
Other alarms
logic input on module 2 (if configured)
Logic Input
Module 2 Logic I/P
Figure 1-14 Controller Block Diagram
Functions listed in 2A conf list
OP1
20.0
23.0
Atun List
Autotune
PID
PiD List
Digital Comms
Normal
OP2
Heat
Cool
Retrans-mission
OP PV Err SP
HOME List
For example Output power Setpoint Auto/Manual
OP List
OP1
OP2
cms List
Digital Comms
Relay
Retrans­mission
PLANT OUTPUTS
Relay, Logic, triac, mA, Volts
RS232 RS484 RS422
Relay, Logic, triac
mA, Volts
1-12 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.9 NAVIGATION DIAGRAM (Part A)
Home
List
20.0
20.0
Alarm
List
AL
LiSt
Autotune
List
Atun
LiSt
4
VPOS
100.0
OP
100.0
WSP
20.0
SP
20.0
AmPS
5
m-A
Auto
diSP
stnd
CID
1.0
9
5
1---
100.0
2--
20.00
3--
0.0
4--
0.0
HY
1.0
Lbt
OFF
2
2
2
2
TunE
OFF
Adc
OFF
The navigation diagram shows a full list of possible parameters. However, some may not appear because they are dependent upon the particular controller variant.
Figure 1.15a Navigation diagram
PID List
Pid
LiSt
Pb
50
Ti
300
td
50.0
rES
0.0
Lcb
Auto
Hcb
Auto
rEL.C
1.00
(1)
Setpoint List
SP
LiSt
SSEL
SP 1
8
L-r
SP 1
20.0
SP 2
0.0
8
rm.SP
8
Loc.t
SP1.L3
0.0
SP1.H3
1.
SP2.L3
0.0
SP2.H3
1.
8
Loc.L
8
Loc.H
DwEl
0.0
End.t
rset
ProG
rset
StAt
OFF
SPrr
OFF
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-13
Operation Installation and Operation Handbook
6
NAVIGATION Diagram (Part B)
Input List
.
iP
LiSt
FiLt
1.0
OFST
0.0
7
CAL
FACT
7
CAL.S
Lo
7
AdJ
0.0
CJC
21.0
mV
1.17
Figure 1.15b Navigation diagram
Output
List
oP
LiSt
OP.Lo
0.0
OP.Hi
100.0
Sb.OP
100.0
CYC.H
20.0
ont.H
1.0
CYC.C
5.0
ont.C
1.0
M
r
20.0
On Off
(1)
List
OnOF
LiSt
hYS.H
1.0
Comms
List
CmS
LiSt
Addr
1
hYS.C
1.0
HC.db
0.0
Notes:
1. Either the PID list or the On/Off list will be present depending upon the type of control in use.
2. The last three characters depend upon the type of alarm configured
3. Absolute setpoint limits are set in configuration, see Chapter 5.
4. VPOS only for VP. Refer to VP Chapter 8.
5. Amps is Mode 2 PDS.
6. mtr used for VP version. Refer to VP Chapter 8.
7. Beware! Used for calibration. See chapter 6.
8. Is only available if using PDS comms in the HA slot.
9. WSP is available if using ramp to setpoint.
Access
List
ACCS
LiSt
coDE
PASS
Goto
OPEr
ConF
0
Return to Home Display
Complete lists or individual parameters normally hidden in Operator level. To see all the available parameters you must select Full level. See Chapter 3, Access Levels
Only displayed when option selected
1-14 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.10 PARAMETER TABLES
The tables which follow list all parameters that are available in Full operator level.
Name Parameter
UK USA
Display mnemonic
Brief description of
Factory configured value
Description
parameter or function
1.10.1 HOME Display
Name Parameter
UK USA
Home List Home Measured Value and
vPoS
OP wSP
SP
AmPS
m-A diSP
Cid
Additional parameters may appear in the Home display if the ‘promote’ feature has been used (see Edit Level, Chapter 3).
Description
Setpoint(SP) Valve positioner output power
utput Level
% O
Working setpoint
Setpoint
Heater current (PDS modes 2 and 5)
uto/manual select
A Configure lower readout of home display
Customer ID
Default Value Min
Default Value Min
SP=25°C SP=75°F
Auto Auto StD StD
0 0 0 9999
Value
Value
0.0 100.0
-100.0 100.0
-999 9999
0 100 Amps
Max Value
Max Value
as
Units Customer
Units Customer
display
%of mtr
%
as display
as display
Setting
Setting
None StD AmPS OP stat vPoS
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-15
Operation Installation and Operation Handbook
1.10.2 Alarm List
Name Parameter
UK USA
AL 1---
2---
3---
4---
In place of dashes, the last three characters indicate the alarm type, as follows:
-FSH
-FSL
-DEv
-dHi
-dLo
-Lcr
-Hcr Hy
Hy.EV
Lbt
Description
Alarm List
set point value
Alarm 1
set point value
Alarm 2
set point value
Alarm 3
set point value
Alarm 4
ull Scale High alarm
F
ull Scale Low alarm
F
iation band alarm
Dev
eviation High alarm
D
eviation Low alarm
D
Low current alarm
High current alarm
Hysteresis
Hysteresis for event alarms. See Note 1
oop break time
L
Default Value Min
Value
0 0
0 0
0 0
0 0
-999 9999
-999 9999
0 9999
0 9999
0 9999
0 100 0 100 0 9999
0 9999
OFF OFF 0 9999
Max Value
Units Customer
as display
as display
as display
as display
as display
as display
as display
as display
as display
Amps
Amps
as display
as display
secs
Setting
1-16 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.10.3 Autotune List
Atun tunE Adc
Autotune List
enable
Self tune
utomatic droop
A
ompensation (Manual
c Reset) enable (only present if ti set to OFF)
OFF OFF OFF On MAn MAn MAn CALC
1.10.4 PID List
Name Parameter
UK USA
Pid Pb
Description
PID List
roportional band
P
Default Value Min
Value
20.0 30 1 9999
Max Value
Units Customer
Setting
as display
ti td rES
Lcb Hcb rEL.C
ntegral time
I
erivative time
D
Manual res (appears when ti set to OFF)
C
C
Rel (set 1)
et
utback low
utback high
ative cool gain
360 360 OFF 9999 60 60 OFF 9999
0.0 0.0 0.00 100.0
Auto Auto 0 9999 Auto Auto 0 9999
1.00 1.00 0.01 9.99
seconds
seconds
%
as display
as display
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-17
Operation Installation and Operation Handbook
1.10.5 Setpoint List
Name Parameter
UK USA
SP SSEL L-r
SP1 SP2 rm.SP Loc.t SP1.L SP1.H SP2.L SP2.H Loc.L
Loc.H
SPrr dwEl EnD.t
ProG
Stat
Description
Set Point List
ect SP1 or SP2
Sel
ocal or remote
L setpoint select
etpoint 1 value
S
etpoint 2 value
S
emote setpoint
R
al trim
Loc
etpoint 1 low limit
S
etpoint 1 high limit
S
etpoint 2 low limit
S
etpoint 2 high limit
S
al setpoint trim low
Loc limit
al setpoint trim
Loc
igh limit
h
etpoint rate limit
S
Dwell time
End type
Program control
Status of program
Default Value Min
SP1 SP1 SP1 SP2 Loc Loc Loc rmt
25 70 25 70 0 0 0 0 0 32 1000 2100 0 32 1000 2100
-210 -346
1200 2192
OFF Off OFF OFF rES rset rset
rset rset run
OFF rmp
Value
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
As display range
Units per minute
0.1 to 999.9 minutes
hoLd Stby dwel
rset
dwel end Off
Max Value
Units Customer
Setting
1-18 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.10.6 Input List
Name Parameter
UK USA
iP *FiLt
OFSt
Description
Input list
er time
Input filt constant
PV Offset
Default Value Min
Value
1.6 1.6 0.0 off 999.9
-999 9999
Max Value
Units Customer
secs
as
Setting
display
The next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.
CAL
CAL.S
Adj~
The following two parameters are always present in Full Access level but not in Operator level
CJCo
mV
FACt will re-instate factory settings and disable User Calibration. Default setting FACt USEr will re-instate any previously set User Calibration offsets and make available User Calibration
parameters as follows:
ibration select
User cal
Adj
ust calibrated
reference source
old Junction
C
ompensation
c temperature
illivolt input
M
none none
Hi Lo none
* A minimum filter time constant of one second is recommended to provide sufficient noise immunity.
~ Do not make adjustments to the AdJ parameter unless you wish to offset the controller
calibration.
1.10.7 On/Off List
OnOf
This set of parameters only appear if On/Off control has been configured
hYS.H
hYS.C
HC.db
On/off list
eat hysteresis
H
ool hysteresis
C
eat/Cool dead band
H
0 0 0 9999
0 0 0 9999
1 1 0 9999
as display
as display
as display
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-19
Operation Installation and Operation Handbook
1.10.8 Output List
Name Parameter
Description
Default Value Min
Value
Max Value
Units Customer
Setting
UK USA
Output list Note; If On/Off control is configured only Sb.OP, ont.H and ont.C will
oP
appear in the following list
Lo
OP.Lo
OP.Hi
Sb.OP
1
CYC.H
w (power) output
limit
Hi
gh (power) output
limit
O
utput setting when in
s
ensor break
H
eat cycle time
0.0 or
-100.0 100.0
-100.0 (cool)
100.0 100.0 -100.0 100.0
0.0 -100.0 100.0
1.0 (logic)
0.2 999.9
%
%
%
secs
20 (relay)
ont.H
1
CYC.C
eat output min. on
H time
C
ool cycle time
0.1 0.1 Auto
1.0 (logic)
(50mS)
0.2 999.9
999.9
secs
20 (relay)
1
ont.C
mtr
C
ool output min. on
t
ime
VP motor travel time
1
Are not used for Valve Position Control.
0.1 0.1 Auto
0.0 999.9
(50mS)
999.9
secs
secs
1.10.9 Communications List
cmS Addr
Comms list
Communications
ess
addr
1 1 1 254
1.10.10 Access List
ACCS codE
Access list
Full and Edit level
1 1 0 9999
password
Goto
Goto
level
OPEr OPEr OPEr conF
OPErFuLL Editor conF
ConF
iguration level
Conf
2 2 0 9999
password
1-20 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.11 ALARMS
Alarms are used to alert an operator when a pre-set level has been exceeded. They are normally used to switch an output (see 1.12) – usually a relay – to provide external actions to the process.
Soft Alarms are indication only and do not operate an output.
Events are generally defined as conditions, which occur as part of the operation of the plant. They do not
require operator intervention and, therefore, do not cause an alarm message to be displayed. They can be attached to operate an output (relay) in the same way as an alarm.
1.11.1 Types of Alarm Used in the 2200
This section shows graphically the operation of different types of alarm used in the controller. The graphs show changes in PV plotted against time.
Alarm Type
Full Scale High
Deviation High
Setpoint (SP)
Deviation Low
Full Scale Low
Rate of Change
Output State
Full scale low
Deviation low
Deviation high
Deviation band
Full scale high
Rate of change
PV
Process Variable (PV)
Deviation
Band
On On
On On
On
On On On
On
On
Time
Figure 1-16: Alarm Types
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-21
Operation Installation and Operation Handbook
A
A
A
A
A
Hysteresis is the difference between the point at which the alarm switches ON and the point at which it switches OFF.
It is used to prevent relay chatter.
Blocking Alarms only occur after alarm is only indicated the next time it is active. It is used, for example, to ignore start up conditions which are not representative of running conditions.
Latching Alarms see 7.1.1.
Loop Break Alarm. The control loop is considered to be open if the output demand signal increases to
saturation level but the error does not reduce after a set period of time. The time period can be set manually, depending on the response time of the loop, using the parameter Lbt in the Alarm List (section
1.10.2). It is, also set automatically, following an autotune (see chapter 4), to 3 x Ti (integral time). The time period, Lbt, starts from the point at which the output demand reaches saturation. The loop break alarm L.br is displayed (as a diagnostic alarm, see section 1.12.3.) at the end of this period.
the start up phase when the alarm has first entered a safe state. The
1.12 ALARM RELAY OUTPUT
Alarms can operate a specific output (usually a relay). Any individual alarm can operate an
individual relay or any combination of alarms can operate an individual relay. They are either supplied pre-configured in accordance with the ordering code or set up in configuration level.
See Chapter 5 for further information.
larm 1
larm 2
larm 3
Input fail
Sensor break
Figure 1-17: Attaching Alarms to an Output
Relay
nor
NY
ny combination of alarms can operate the relay.
Typical alarms are shown
dIG
SEnS
inv
1-22 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Installation and Operation Handbook Operation
1.12.1 SETTING ALARM LEVELS
Up to 4 Alarms may be configured. Each alarm is given a name to describe its function - see table below:
If an alarm is not configured it does not appear in the list below.
larm List
AL
LiSt
A
1---
100
In place of dashes, letters indicate alarm type as follows:
ull Scale Low
-FSL F
ull Scale High
-FSH F
-dEv Dev
-dHi D
-dLo D
-Lcr L
-Hcr H
iation Band
eviation High
eviation Low
ow current
igh current
2---
200
3---
Alarm 1
or to change
2nd press
Alarm 2
or to change
3rd press
Alarm 3
0
or to change
4th press
4---
Alarm 4
0
or to change
Press to return to list header
Lb t
OFF
5th press
oop break time
L
or to change
Figure 1-18 To Set Alarm Trip Levels
2216e Controller Part Number HA026639 Issue 4 (CN22918) 1-23
Operation Installation and Operation Handbook
1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT
When an alarm occurs, the alarm mnemonic (e.g. 1FSH) will be indicated by a double flash in the HOME display. Similarly, if more than one alarm occurs the relevant mnemonics are flashed in the HOME display. The double flash will continue whilst the alarm condition is present and is not acknowledged.
Press
If the alarm condition is still present when the alarm is acknowledged, it will be indicated by a single flash of the alarm mnemonic and this single flash will be repeated for as long as the alarm condition remains. When the alarm condition disappears the indication will also disappear.
If the alarm condition is no longer present when the alarm is acknowledged, the flashing message will disappear immediately on acknowledgement.
If a relay has been attached to the alarm output (see Chapter 7 ‘Alarm Operation’), it will operate when the alarm condition occurs and remain in the operated condition until the alarm is acknowledged AND it is no longer present
and together to acknowledge the alarm.
1-24 Part Number HA026639 Issue 4 (CN22918) 2216e Controller
Loading...
+ 82 hidden pages