221508A Modutrol IV Resistor Board
INSTALLATION INSTRUCTIONS
APPLICATION
The 221508A Resistor Board can be configured to
provide the functions of the 4074BYK, 4074EAU,
4074EDC, or 4074EED resistor kits for Series 90
Modutrol IV motors. For 4074BYK applications, it can
allow a single controller to operate up to six Modutrol IV
M91XX motors in unison. For 4074EAU application, it
adapts an M91XX motor to operate from a 4-20 mA
controller. In 4074EED applications, it permits operation
of up to four M91XX motors from a 4-20 mA signal. The
Resistor Board mounts inside the motor's wiring box and
provides screw terminals for field wiring.
CONFIGURATIONS
INSTALLATION
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, checkout product
operation as provided in these instructions.
CAUTION
Disconnect power supply before wiring to
prevent electrical shock or equipment
damage.
Function
Drive 2
motors in
parallel from
a series 90
controller.
Drive 3
motors in
parallel from
a series 90
controller.
Drive 4
motors in
parallel from
a series 90
controller.
Drive 5
motors in
parallel from
a series 90
controller.
Drive 6
motors in
parallel from
a series 90
controller.
Drive 1
motor from
a 4-20 mA
controller.
Can Be Used
In Place Of Dip Switch Configuration Function
4074BYK Drive 2
4074BYK Drive 3
4074BYK Drive 4
4074BYK Drive 2
4074BYK Drive 3
4074EED or
EDC
1 2 3 4 5 6 7 8 9 10
M13794
1 2 3 4 5 6 7 8 9 10
M13795
1 2 3 4 5 6 7 8 9 10
M13796
1 2 3 4 5 6 7 8 9 10
M13797
1 2 3 4 5 6 7 8 9 10
M13798
1 2 3 4 5 6 7 8 9 10
M13799
motors from
a 4-20 mA
controller.
motors from
a 4-20 mA
controller.
motors from
a 4-20 mA
controller.
motors from
a W973
controller.
motors from
a W973
controller.
Can Be Used
In Place Of Dip Switch Configuration
4074EED
4074EED
4074EED
4074EAU
4074EAU
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
62-0078—2
M13800
M13801
M13802
M13803
M13804
221508A MODUTROL IV RESISTOR BOARD
T1 T2
M23822A
R(-)
B W1 W1 W(+)
54 321 54321
DIP SWITCH
ACCESS HOLE TO MOTOR'S
STROKE ADJUST POTENTIOMETER
MOUNTING
1. Remove top cover to motors wiring box.
2. Make any necessary adjustments to motor stroke
or auxiliary switches.
3. If motor has an internal transformer, disconnect the
transformer secondary wires (brown) from the
motor's T1, T2 quick-connect terminals. Clip the
quick-connect terminations off from these two
wires. Trim 1/4 inch of insulation from wire ends.
4. Set dip switch (switches 1-8) to configure the
Resister Board for the desired function (see
Ta bl e 1 ).
5. Plug Resistor Board onto motor's quick-connect
terminals. Secure in place by tightening the 2
screws provided.
6. Connect field wiring to screw terminals. Refer to
M91XX instruction sheet for appropriate wiring
connections for your application.
7. Replace wiring box cover and secure with 4 cover
screws.
8. Reconnect power and check motor operation.
54321 54321
RESISTOR
BOARD
POWER
END
WIRING
1. Connect trimmed transformer secondary wires to
T1, T2.
2. Connect wiring from a Series 90 controller and
W973 to R, W, and B terminals as if wiring to a
Series 90 Modutrol IV motor.
NOTE: With switch 8 closed, W1, W1 and W[+] are
common. All combinations listed call for switch
8 to be closed.
3. Connect wiring from a 4-20 mA controller to R[-]
and W[+].
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
62-0078—2 J.I. Rev. 03-07