Grieve Corporation 221508A Installation Manual

221508A Modutrol IV Resistor Board
INSTALLATION INSTRUCTIONS

APPLICATION

The 221508A Resistor Board can be configured to provide the functions of the 4074BYK, 4074EAU, 4074EDC, or 4074EED resistor kits for Series 90 Modutrol IV motors. For 4074BYK applications, it can allow a single controller to operate up to six Modutrol IV M91XX motors in unison. For 4074EAU application, it adapts an M91XX motor to operate from a 4-20 mA controller. In 4074EED applications, it permits operation of up to four M91XX motors from a 4-20 mA signal. The Resistor Board mounts inside the motor's wiring box and provides screw terminals for field wiring.

CONFIGURATIONS

INSTALLATION

WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, checkout product operation as provided in these instructions.
CAUTION
Disconnect power supply before wiring to prevent electrical shock or equipment damage.
Function
Drive 2 motors in parallel from a series 90 controller.
Drive 3 motors in parallel from a series 90 controller.
Drive 4 motors in parallel from a series 90 controller.
Drive 5 motors in parallel from a series 90 controller.
Drive 6 motors in parallel from a series 90 controller.
Drive 1 motor from a 4-20 mA controller.
Can Be Used
In Place Of Dip Switch Configuration Function
4074BYK Drive 2
4074BYK Drive 3
4074BYK Drive 4
4074BYK Drive 2
4074BYK Drive 3
4074EED or EDC
1 2 3 4 5 6 7 8 9 10
M13794
1 2 3 4 5 6 7 8 9 10
M13795
1 2 3 4 5 6 7 8 9 10
M13796
1 2 3 4 5 6 7 8 9 10
M13797
1 2 3 4 5 6 7 8 9 10
M13798
1 2 3 4 5 6 7 8 9 10
M13799
motors from a 4-20 mA controller.
motors from a 4-20 mA controller.
motors from a 4-20 mA controller.
motors from a W973 controller.
motors from a W973 controller.
Can Be Used
In Place Of Dip Switch Configuration
4074EED
4074EED
4074EED
4074EAU
4074EAU
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
62-0078—2
M13800
M13801
M13802
M13803
M13804
221508A MODUTROL IV RESISTOR BOARD
T1 T2
M23822A
R(-)
B W1 W1 W(+)
54 321 54321
DIP SWITCH
ACCESS HOLE TO MOTOR'S STROKE ADJUST POTENTIOMETER

MOUNTING

1. Remove top cover to motors wiring box.
2. Make any necessary adjustments to motor stroke
or auxiliary switches.
3. If motor has an internal transformer, disconnect the transformer secondary wires (brown) from the motor's T1, T2 quick-connect terminals. Clip the quick-connect terminations off from these two wires. Trim 1/4 inch of insulation from wire ends.
4. Set dip switch (switches 1-8) to configure the Resister Board for the desired function (see Ta bl e 1 ).
5. Plug Resistor Board onto motor's quick-connect terminals. Secure in place by tightening the 2 screws provided.
6. Connect field wiring to screw terminals. Refer to M91XX instruction sheet for appropriate wiring connections for your application.
7. Replace wiring box cover and secure with 4 cover screws.
8. Reconnect power and check motor operation.
54321 54321
RESISTOR BOARD
POWER END

WIRING

1. Connect trimmed transformer secondary wires to T1, T2.
2. Connect wiring from a Series 90 controller and W973 to R, W, and B terminals as if wiring to a Series 90 Modutrol IV motor.
NOTE: With switch 8 closed, W1, W1 and W[+] are
common. All combinations listed call for switch 8 to be closed.
3. Connect wiring from a 4-20 mA controller to R[-] and W[+].
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2007 Honeywell International Inc. 62-0078—2 J.I. Rev. 03-07
Loading...