Greenheck Fan No Flow Duct Smoke Detector User Manual

Purpose/Application
#10 TEK SCREW
4 X 4 X 2 1/8 HANDI BOX
SMOKE DETECTOR ASSEMBLY
National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity as to be a serious hazard to life safety unless blowers are shut down and dampers are actuated. The primary purpose of duct smoke detection is to prevent injury, panic, and property damage by reducing the spread (recirculation) of smoke. The detector samples air currents passing through a duct and gives dependable performance for management of smoke and combination fire smoke dampers. Duct smoke detection can also serve to protect the air conditioning system itself from fire and smoke damage.
There are several important documents that provide guidance concerning the performance, application and installation of duct detectors:
1) NFPA Standard 90A, Installation of Air Conditioning
and Ventilation Systems
2) NFPA Standard 92A, Recommended Practice for Smoke Control Systems
3) NFPA Standard 72, National Fire Alarm Code
4) NFPA Standard 101, Life Safety Code
5) UL Standard 268A, Standard for Smoke Detectors for Duct Applications
6) ASHRAE Handbook and Product Directory, “Fire and Smoke Control”
7) System Sensor, Guide for Proper Use of Smoke Detectors in Duct Applications.
NO FLOW DUCT
SMOKE DETECTOR
Duct detectors are: NOT a substitute for an open area smoke detector NOT a substitute for early warning detection NOT a replacement for a building’s regular fire detection system
Specifications
Air Duct Velocity: 0 to 3000 fpm (0 to 15.2 m/s) Operating Temperature Range: 32°F to 120°F (0° to 49°C) Operating Humidty Range: 10% to 93% RH Operation Voltage: 120 VAC
Features
• Designed for mounting on standard electrical box
• Low-profile smoke detector design
• Field adjustable sensitivity
• Built-in test switch
Listings
UL 268A
Refer to Greenheck Installation Supplement: Part # 465915- No flow smoke detector IOM
Type: Photoelectric
Sleeve Length
L2
WHITE
MOTOR
L1
BLACK
OCI
YELLOW
YELLOW
YELLOW
YELLOW
SWITCH #1
SWITCH #2
BLUE
RED
BLUE
BLACK
BLACK
7
6
13 14
12
10
8
9
RED
11
L2
WHITE
MOTOR
L1
BLACK
ORANGE
BLACK
RRL
BLUE
RED
BLUE
BLACK
BLACK
7
6
13 14
12
10
8
9
RED
11
Height less than 11 in. (279mm): 21 in. (533mm) sleeve with 12 in. (305mm) “A” dimension Height equal to or greater than 11 in. (279mm): 16 in. (406mm) sleeve with
9.5 in. (241mm) “A” dimension
Ordering Options
Factory Mounted
Smoke detector will be wired to a 4 x 4 handi-box. The closure device (if RRL or TOR) will also be wired to the handi-box. Dampers provided with the smoke detector option will include single point wiring as standard (includes RRL, OCI, TOR, and detectors).
Shipped Loose
Shipped loose smoke detector will only include the detector itself (no mounting hardware or bracket seals). Note: Dampers ordered with shipped loose smoke detectors will have the standard sleeve length, not a longer sleeve to accommodate the smoke detector installation. If smoke detectors are intended to be field mounted on the damper sleeve, the damper sleeve length and ‘A’ dimension will need to be manually changed to the requirements indicated under ‘Sleeve Length’.
Wiring Diagrams
RRL
OCI