The Series 41 and Series 81 Modutrol IV Motors are
2-position (line- and low- voltage, respectively) spring-return
motors. They are used to operate dampers or valves in
applications where it is necessary or desirable to have the
controlled element return to the starting position in the event
of power failure or interruption.
Series 41 and 81
Modutrol IV™ Motors
PRODUCT DATA
FEATURES
• Used to replace M445, M845 and M865 motors.
• Models rated for 25 lb.-in. or 60 lb.-in. torque.
• Integral spring return returns motor to normal position
(open or closed) when power is interrupted.
• Oil immersed motor and gear train for reliable
performance and long life.
• Wiring box provides NEMA 3 weather protection.
• Motor operates from 24 Vac. Models are available
with factory installed transformer, or an internal
transformer can be field added.
• Quick-connect terminals are standard—screw terminal
adapter is available.
• Adapter bracket for matching shaft height of older
motors is standard with TRADELINE motors.
• TRADELINE motors have field adjustable stroke
(90° to 160°).
• Die-cast aluminum housing.
• Motors are designed for either normally open or
normally closed valves and dampers.
• Integral auxiliary switches are available factory
mounted, or can be field added to TRADELINE models.
• TRADELINE motors may operate valve linkages from
the power end or auxiliary end shafts for normally
closed or normally open valve applications.
Models: TRADELINE models are selected and packaged to
provide ease of stocking, ease of handling and maximum
replacement value. TRADELINE model specifications are the
same as those of standard models unless specified otherwise.
TRADELINE models have auxiliary switch cams.
NOTE: Auxiliary switches can only be added to motors that
MMotor
include auxiliary switch cams. (These cams cannot
be field-added.)
Table 1. Series 41 and Series 81 Modutrol IV Order Number Guide.
41Series 41, line voltage, two-position control
81Series 81, low voltage, two-position control
725 lb-in. torque
860 lb-in. torque
2
5
6
Normally Closed
Normally Closed
Normally Openb Spring Return, dual-ended shaft
A0 Auxiliary SwitchesFixed Stroke
B1 Auxiliary Switch
C2 Auxiliary Switches
D0 Auxiliary SwitchAdjustable Stroke
E1 Auxiliary Switch
F2 Auxiliary Switches
G0 Auxiliary SwitchFixed Stroke
H1 Auxiliary Switch
J2 Auxiliary Switches
K0 Auxiliary SwitchAdjustable Stroke
L1 Auxiliary Switch
M2 Auxiliary Switches
Modutrol IV Order Number Guide: See Table 1.
Dimensions: See Fig. 1.
Crankshaft: 3/8 in. (9.5 mm) square.
Electrical Ratings: See Table 2.
Controller Type: Two wire, on-off switching action.
Auxiliary Switch Ratings: See Table 3.
a
Spring Return, single-ended shaft
a
Spring Return, dual-ended shaft
Normally Closed
Normally Open
a
b
M8185AXXXXSee Catalog for Complete O.S. Number
a
Electrically normally closed. Shaft rotates clockwise (viewed from the power end) with control signal increase.
Motor drives to normally closed position when powered with control wiring not connected.
b
Electrically normally open. Shaft rotates counter-clockwise (viewed from the power end) with control signal increase.
Motor drives to normally open position when powered with control wiring not connected.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2187—32
SERIES 41 AND 81 MODUTROL IV™ MOTORS
TOP VIEW OF BRACKET TOP VIEW
1/4
(7)
1
AUXILARY
END
9/16 (15)
ADAPTER
BRACKET
4
3
4-1/16 (103)
4-1/16 (103)
2
13/16
(20)
POWER
END
1-1/2 (37)
4-7/8
(124)
WIRING
BOX
BASE
MOTOR
2-9/16
(66)
3/4
(19)
5-1/2
(140)
5-3/8
(137)
6-7/16
(164)
4-5/8
(116)
POWER END
1/4 (7)
4-7/8 (124)
SOME MODELS DO NOT HAVE AN AUXILIARY
1
SHAFT. ALL OTHER DIMENSIONS ARE THE SAME.
2
FOR HIGH TORQUE (60 LB-IN.) SPRING RETURN
MODELS 8-3/4 (222); FOR LOW TORQUE (25 LB-IN.)
SPRING RETURN MODELS 8-1/4 (210).
FOR HIGH TORQUE (60 LB-IN.) SPRING
3
RETURN MODELS (SHOWN).
4
FOR LOW TORQUE (25 LB-IN.) SPRING
RETURN MODELS.
5-9/16 (141)
2-5/16
(58)
11/16
(17)
4-1/4
(107)
5-13/16
(148)
M17711
Fig. 1. Series 41 and Series 81 Modutrol IV Motor mounting dimensions in in. (mm).
Dead Weight Load On Shaft (maximum):
Power or Auxiliary End: 200 lb. [90.8 kg].
Combined Load: 300 lb. [136 kg]. (Dual-stroke motors only.)
Maximum Damper Rating [B Dimension]:
25 lb.-in. Models: 68 in.
60 lb.-in. Models: 34 in.
NOTE: The B dimension is the length of the damper side
perpendicular to the drive shaft.
Ambient Temperature Ratings:
Maximum: 150°F (66°C).
Minimum: -40°F (-40°C).
Torque and Timing: See Table 4.
Approvals:
Underwriters Laboratories Inc. Listed: File No. E4436, Guide
No. XAPX.
Canadian Standards Association Certified: General listed File
220736 Internal Auxiliary Switch Kit can be field-installed
on TRADELINE models. One- (220736A) and Two(220736B) switch kits available.
220738A Adapter Bracket raises motor shaft height by 19 mm
to match that of previous Modutrol
®
Motor models.
220741A Screw Terminal Adapter converts the standard
quick-connect terminals to screw terminals.
221455A Infinitely Adjustable Crank Arm approximately
0.75 in. shorter than the 4074ELY Crank Arm, can rotate
through downward position and clear motor base without
requiring adapter bracket.
4074ERU Weatherproofing Kit provides NEMA 3 rating for
Modutrol IV Motors mounted in position other than upright.
363-2187—3
SERIES 41 AND 81 MODUTROL IV™ MOTORS
Accessories (continued):
4074EZE Bag Assembly with parts to provide CE compliance.
7617ADW Crank Arm approximately 0.75 in. shorter than
7616BR Crank Arm. Can rotate through downward position
and clear motor base without requiring adapter bracket.
ES650-117 Explosion-Proof Housing encloses motor for use
in explosive atmospheres. Not for use with Q5001 (or any
other valve linkages). Order separately from O-Z/Gedney
Inc. To order, contact: O-Z/Gedney, Nelson Enclosures and
Controls, (918) 641-7381 or (918) 641-7374; or write to:
O-Z/Gedney, Nelson Enclosures and Controls
P.O. Box 471650
Tulsa, OK 74147-1650
Requires Honeywell 7617DM Coupling.
Q100 Linkage connects Modutrol
Valve. Requires the 220738A Adapter Bracket (packed
with TRADELINE Modutrol IV motors).
Q5001 Bracket and Linkage Assembly connects Modutrol
motor to a water or steam globe valve.
Q605 Damper Linkage connects motor to damper. Includes
40 VA pilot duty, 120/240 Vac on opposite contact.
M817525 (2.8)3060
Other models 60 (6.8)
240.862120
241.253025
1200.25
2080.14
2400.13
Table 3. Auxiliary Switch Ratings.
a
(Amps)120 V240 V
Table 4. Torque and Timing.
Torqu e lb- i n.
(N-m)
®
motor to V51 Butterfly
Current
Draw (A)
Power Consumption
(VA)(W)
Timing (sec.)
90° Stroke160° Stroke
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect all power supplies before installation.
Motors with auxiliary switches can have more than
one disconnect.
CAUTION
Equipment Damage Hazard.
Can damage the motor beyond repair.
Never turn the motor shaft by hand or with a wrench.
Forcibly turning the motor shaft damages the gear
train and stroke limit contacts.
Location
Allow enough clearance for installing accessories and motor
servicing when selecting a location (see Fig. 1). If located
outdoors, use liquid-tight conduit connectors with the junction
box to provide NEMA 3 weather protection. If mounted
outdoors in a position other than upright, install a 4074ERU
Weatherproofing Kit and liquid-tight connectors to provide
NEMA 3 protection.
CAUTION
Motor Damage Hazard.
Deteriorating vapors and acid fumes can damage
metal parts.
Install motor in areas free of acid fumes and other
deteriorating vapors.
In excessive salt environments, mounting base and screws
should be zinc or cadmium plated, not stainless steel or
brass. Use the 220738A Adapter Bracket for mounting on
these surfaces.
63-2187—34