Greenheck Fan Modutrol IV User Manual

APPLICATION

The Series 41 and Series 81 Modutrol IV Motors are 2-position (line- and low- voltage, respectively) spring-return motors. They are used to operate dampers or valves in applications where it is necessary or desirable to have the controlled element return to the starting position in the event of power failure or interruption.
Series 41 and 81
Modutrol IV™ Motors
PRODUCT DATA

FEATURES

• Used to replace M445, M845 and M865 motors.
• Models rated for 25 lb.-in. or 60 lb.-in. torque.
• Integral spring return returns motor to normal position (open or closed) when power is interrupted.
• Oil immersed motor and gear train for reliable performance and long life.
• Wiring box provides NEMA 3 weather protection.
• Motor operates from 24 Vac. Models are available with factory installed transformer, or an internal transformer can be field added.
• Quick-connect terminals are standard—screw terminal adapter is available.
• Adapter bracket for matching shaft height of older motors is standard with TRADELINE motors.
• TRADELINE motors have field adjustable stroke (90° to 160°).
• Die-cast aluminum housing.
• Motors are designed for either normally open or normally closed valves and dampers.
• Integral auxiliary switches are available factory mounted, or can be field added to TRADELINE models.
• TRADELINE motors may operate valve linkages from the power end or auxiliary end shafts for normally closed or normally open valve applications.
® U.S. Registered Trademark Copyright © 2000 Honeywell • All Rights Reserved
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Settings and Adjustments ................................................. 7
Operation and Checkout .................................................. 10
Replacement .................................................................... 11
63-2187-3
SERIES 41 AND 81 MODUTROL IV™ MOTORS

SPECIFICATIONS

Models: TRADELINE models are selected and packaged to provide ease of stocking, ease of handling and maximum replacement value. TRADELINE model specifications are the same as those of standard models unless specified otherwise. TRADELINE models have auxiliary switch cams.
NOTE: Auxiliary switches can only be added to motors that
M Motor
include auxiliary switch cams. (These cams cannot be field-added.)
Table 1. Series 41 and Series 81 Modutrol IV Order Number Guide.
41 Series 41, line voltage, two-position control
81 Series 81, low voltage, two-position control
7 25 lb-in. torque
8 60 lb-in. torque
2
5
6
Normally Closed
Normally Closed
Normally Openb Spring Return, dual-ended shaft
A 0 Auxiliary Switches Fixed Stroke
B 1 Auxiliary Switch
C 2 Auxiliary Switches
D 0 Auxiliary Switch Adjustable Stroke
E 1 Auxiliary Switch
F 2 Auxiliary Switches
G 0 Auxiliary Switch Fixed Stroke
H 1 Auxiliary Switch
J 2 Auxiliary Switches
K 0 Auxiliary Switch Adjustable Stroke
L 1 Auxiliary Switch
M 2 Auxiliary Switches
Modutrol IV Order Number Guide: See Table 1.
Dimensions: See Fig. 1.
Crankshaft: 3/8 in. (9.5 mm) square.
Electrical Ratings: See Table 2.
Controller Type: Two wire, on-off switching action.
Auxiliary Switch Ratings: See Table 3.
a
Spring Return, single-ended shaft
a
Spring Return, dual-ended shaft
Normally Closed
Normally Open
a
b
M 81 8 5 A XXXX See Catalog for Complete O.S. Number
a
Electrically normally closed. Shaft rotates clockwise (viewed from the power end) with control signal increase. Motor drives to normally closed position when powered with control wiring not connected.
b
Electrically normally open. Shaft rotates counter-clockwise (viewed from the power end) with control signal increase. Motor drives to normally open position when powered with control wiring not connected.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2187—3 2
SERIES 41 AND 81 MODUTROL IV™ MOTORS
TOP VIEW OF BRACKET TOP VIEW
1/4
(7)
1
AUXILARY END
9/16 (15)
ADAPTER BRACKET
4
3
4-1/16 (103)
4-1/16 (103)
2
13/16
(20)
POWER
END
1-1/2 (37)
4-7/8 (124)
WIRING BOX
BASE MOTOR
2-9/16
(66)
3/4
(19)
5-1/2 (140)
5-3/8 (137)
6-7/16
(164)
4-5/8 (116)
POWER END
1/4 (7)
4-7/8 (124)
SOME MODELS DO NOT HAVE AN AUXILIARY
1
SHAFT. ALL OTHER DIMENSIONS ARE THE SAME.
2
FOR HIGH TORQUE (60 LB-IN.) SPRING RETURN MODELS 8-3/4 (222); FOR LOW TORQUE (25 LB-IN.) SPRING RETURN MODELS 8-1/4 (210).
FOR HIGH TORQUE (60 LB-IN.) SPRING
3
RETURN MODELS (SHOWN).
4
FOR LOW TORQUE (25 LB-IN.) SPRING RETURN MODELS.
5-9/16 (141)
2-5/16
(58)
11/16
(17)
4-1/4 (107)
5-13/16
(148)
M17711
Fig. 1. Series 41 and Series 81 Modutrol IV Motor mounting dimensions in in. (mm).
Dead Weight Load On Shaft (maximum):
Power or Auxiliary End: 200 lb. [90.8 kg]. Combined Load: 300 lb. [136 kg]. (Dual-stroke motors only.)
Maximum Damper Rating [B Dimension]:
25 lb.-in. Models: 68 in. 60 lb.-in. Models: 34 in.
NOTE: The B dimension is the length of the damper side
perpendicular to the drive shaft.
Ambient Temperature Ratings:
Maximum: 150°F (66°C). Minimum: -40°F (-40°C).
Torque and Timing: See Table 4.
Approvals:
Underwriters Laboratories Inc. Listed: File No. E4436, Guide
No. XAPX.
Canadian Standards Association Certified: General listed File
No. LR1620, Guide No. 400-E.
Accessories:
198162AA Internal Transformer; 120/208/240 Vac 50/60 Hz
primary, 24 Vac secondary.
198162EA Internal Transformer; 120 Vac 50/60 Hz primary,
24 Vac secondary.
198162GA Internal Transformer; 220 Vac 50/60 Hz primary,
24 Vac secondary.
198162JA Internal Transformer; 24 Vac 50/60 Hz primary,
24 Vac secondary (for electrical isolation).
220736 Internal Auxiliary Switch Kit can be field-installed
on TRADELINE models. One- (220736A) and Two­(220736B) switch kits available.
220738A Adapter Bracket raises motor shaft height by 19 mm
to match that of previous Modutrol
®
Motor models.
220741A Screw Terminal Adapter converts the standard
quick-connect terminals to screw terminals.
221455A Infinitely Adjustable Crank Arm approximately
0.75 in. shorter than the 4074ELY Crank Arm, can rotate through downward position and clear motor base without requiring adapter bracket.
4074ERU Weatherproofing Kit provides NEMA 3 rating for
Modutrol IV Motors mounted in position other than upright.
3 63-2187—3
SERIES 41 AND 81 MODUTROL IV™ MOTORS
Accessories (continued):
4074EZE Bag Assembly with parts to provide CE compliance. 7617ADW Crank Arm approximately 0.75 in. shorter than
7616BR Crank Arm. Can rotate through downward position and clear motor base without requiring adapter bracket.
ES650-117 Explosion-Proof Housing encloses motor for use
in explosive atmospheres. Not for use with Q5001 (or any other valve linkages). Order separately from O-Z/Gedney Inc. To order, contact: O-Z/Gedney, Nelson Enclosures and Controls, (918) 641-7381 or (918) 641-7374; or write to: O-Z/Gedney, Nelson Enclosures and Controls P.O. Box 471650 Tulsa, OK 74147-1650 Requires Honeywell 7617DM Coupling.
Q100 Linkage connects Modutrol
Valve. Requires the 220738A Adapter Bracket (packed with TRADELINE Modutrol IV motors).
Q5001 Bracket and Linkage Assembly connects Modutrol
motor to a water or steam globe valve.
Q605 Damper Linkage connects motor to damper. Includes
motor crank arm.
Q607 External Auxiliary Switch controls auxiliary equipment
as a function of motor position.
Table 2. Electrical Ratings.
Voltage (at
50/60 Hz)
Without Transformer
With Internal Transformer
One Contact Rating
Full Load 7.2 3.6
Locked Rotor 43.2 21.6
a
40 VA pilot duty, 120/240 Vac on opposite contact.
M8175 25 (2.8) 30 60
Other models 60 (6.8)
24 0.86 21 20
24 1.25 30 25
120 0.25
208 0.14
240 0.13
Table 3. Auxiliary Switch Ratings.
a
(Amps) 120 V 240 V
Table 4. Torque and Timing.
Torqu e lb- i n.
(N-m)
®
motor to V51 Butterfly
Current
Draw (A)
Power Consumption
(VA) (W)
Timing (sec.)
90° Stroke 160° Stroke

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect all power supplies before installation. Motors with auxiliary switches can have more than one disconnect.
CAUTION
Equipment Damage Hazard. Can damage the motor beyond repair.
Never turn the motor shaft by hand or with a wrench. Forcibly turning the motor shaft damages the gear train and stroke limit contacts.

Location

Allow enough clearance for installing accessories and motor servicing when selecting a location (see Fig. 1). If located outdoors, use liquid-tight conduit connectors with the junction box to provide NEMA 3 weather protection. If mounted outdoors in a position other than upright, install a 4074ERU Weatherproofing Kit and liquid-tight connectors to provide NEMA 3 protection.
CAUTION
Motor Damage Hazard. Deteriorating vapors and acid fumes can damage metal parts.
Install motor in areas free of acid fumes and other deteriorating vapors.
In excessive salt environments, mounting base and screws should be zinc or cadmium plated, not stainless steel or brass. Use the 220738A Adapter Bracket for mounting on these surfaces.
63-2187—3 4