18 281/4 13 23 10 401/4 271/4 48 x 51 18 201/2
20 301/4 16 27 11 441/4 281/4 54 x 51 20 221/2
24 341/4 18 29 11 461/4 281/4 66 x 63 24 261/2
30 401/4 20 34 14 511/4 311/4 75 x 75 30 321/2
36 461/4 22 391/2 171/2 563/4 343/4 88 x 87 36 381/2
42 521/4 24 421/2 181/2 593/4 353/4 86 x 99 42 441/2
48 581/4 24 431/2 191/2 603/4 363/4 93 x 111 48 501/2
54 641/4 261/2 49 221/2 661/4 393/4 112 x 111 54 561/2
60 701/4 261/2 50 231/2 671/4 403/4 124 x 123 60 621/2
72 821/2 29 53 24 701/4 411/4 136 x 135 72 741/2
GREENHECK
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171
®
READ AND SAVE THESE INSTRUCTIONS
Hooded Propeller Roof Fans
Belt Drive and Direct Drive
Installation, Operating and Maintenance Manual
Upon receiving the unit, check for any damage and report it immediately to the shipper. Also assure all accessory
items are accounted for.
To minimize installation time, most fans are shipped completely assembled. Due to shipping size limitations, hoods for larger
fans will be shipped in sections. For these fans the hood and fan components can be transported to the roof location
separately. Hood assembly should begin after the fan is attached to the roof curb. Hood assembly instructions are included
with the hood components.
Care must be taken not to bend or distort the fan panel or drive components during installation.
Part # 455305
Exhaust / Supply (Direct Drive Sizes 18-54 - Belt Drive Sizes 20-72)
Filtered Supply (Belt Drive Sizes Only 20 - 72)
All dimensions given in inches
W
C
B
D
A sq.
2
1
/2"
Tall Base Option
TB
TD
Access to the motor compartment
On fan sizes 18 to 48:
- Remove two fasteners shown in fig. 1.
Carefully swing the hood 180 degrees and let it rest on
the roof. If desired, the entire hood may be removed
by removing the two additional fasteners on the
opposite side of the fan.
Use caution when handling the hood in strong winds.
On fan sizes 36 to 60 access to the motor compartment can
also be made by either:
- Removing birdscreen or filters and standing
under the hood of large fans.
- Removing one interlocking hood end section of
smaller units
Fasteners
Fig. 1
Fan
Size
A
Base
Sq.
C
BDTBTD
W x L
Damper
Size
Sq.
Roof
Opg.
Sq.
Standard
Base
Tall
Base
20 301/4 16 27 11 441/4 281/4 54 x 51 20 221/2
24 341/4 18 29 11 461/4 281/4 66 x 63 24 261/2
30 401/4 20 34 14 511/4 311/4 78 x 87 30 321/2
36 461/4 22 391/2 171/2 563/4 343/4 94 x 87 36 381/2
42 521/4 24 421/2 181/2 593/4 353/4 93 x 99 42 441/2
48 581/4 24 431/2 191/2 603/4 363/4 112 x 111 48 501/2
54 641/4 261/2 49 221/2 661/4 393/4 124 x 123 54 561/2
60 701/4 261/2 50 231/2 671/4 403/4 136 x 135 60 621/2
72 821/2 29 53 24 701/4 411/4 136 x 147 72 741/2
Fan
Size
A
Base
Sq.
C
BDTBTD
W x L
Damper
Size
Sq.
Roof
Opg.
Sq.
Standard
Base
Tall
Base
Belt Span
Deflection =
Belt Span
64
ROUTINE MAINTENANCE
Once the fan has been put into operation, a periodic maintenance program should be set up to preserve the reliability
and performance of the fan. Items to be included in this program are:
• BELTS
• BEARINGS
• FASTENERS
• SET SCREWS
• LUBRICATION
• REMOVAL OF DUST/DIRT
WRONG WRONG
WRONG CORRECT
WARNING
DISCONNECT AND SECURE TO THE "OFF" POSITION ALL ELECTRICAL POWER TO THE FAN
PRIOR TO INSPECTION OR SERVICING. FAILURE TO COMPLY WITH THIS SAFETY PRECAUTION
COULD RESULT IN SERIOUS INJURY OR DEATH.
Fig. 3
Fig. 4
BELTS
Premature belt failures are frequently caused by improper belt tension
(either too tight or too loose) or misaligned pulleys. The proper tension for
operating a V-belt is the lowest tension at which the belts will not slip at
peak load conditions. For initial tensioning, the proper belt deflection half
way between pulley centers is 1/64" for each inch of belt span. For
example, if the belt span is 64 inches, the belt deflection should be one
inch using moderate thumb pressure at midpoint of the drive (Fig. 3).
Check belt tension two times during the first 24 hours of operation and
periodically thereafter. To adjust belt tension, simply loosen four fasteners
(two on each side of the motor plate) and slide the motor plate away from
the fan shaft until proper belt tension is attained. On some fans, fasteners
attaching the motor to the motor plate must be loosened in order to
adjust the belt.
It is very important that the drive pulleys remain in proper alignment after
adjustments are made. Misalignment of pulleys will result in premature
belt wear, noise, vibration and power loss. See Fig. 4 .
PRESTARTING CHECKS
Check all fasteners and set screws for tightness. This is especially important for
bearing set screws.
The propeller should rotate freely and not rub on the fan panel venturi. Rotation
direction of the propeller should be checked by momentarily turning the unit on.
Rotation should be in the same direction as the rotation decal affixed to the unit
or as shown in Fig. 2. For 3-phase installations, fan rotation can be reversed by
simply interchanging any two of the three electrical leads. For single phase
installations follow the wiring diagram located on the motor.
FOR BELT DRIVE FANS
The adjustable motor pulley is preset at the factory for the specified fan RPM. Fan
speed can be increased by closing or decreased by opening the adjustable pulley.
Two or three groove variable pitch pulleys must be adjusted an equal number of turns
open. Any increase in fan speed represents a substantial increase in horsepower
required from the motor. Always check motor load amperage and compare to name
plate rating when changing fan speed.
Fig. 2
ELECTRICAL CONNECTIONS
Before electrical connections are made, the supply voltage, phase and ampere capacity must be checked for
compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to local and national
electrical codes.
If the electrical supply is to be routed to the fan from the interior of the building, it should pass through the conduit hole in
the fan panel. The supply wires are then connected to an optional safety disconnect switch (if supplied) or wired directly
to the motor.
Airflow
Rotation
Airflow
Rotation