Greenheck Fan FSD-312 User Manual

Model FSD-312
H*
W*
R
APPLICATION
Model FSD-312 is a high performance combination fire smoke damper with class II leakage. High strength airfoil blades ensure the lowest resistance to airflow in HVAC systems with velocities to 3000 fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow and leakage in either direction.
Combination Fire Smoke Dampers
RATINGS
UL555S Leakage Rating: Leakage Class: II Operational Rating: Actual ratings are size dependent Max. Velocity: up to 3000 fpm (15.2m/s) Max. Pressure: 4 in. wg (1 kPa) Maximum Temperature: 350°F (177°C)- depending upon the actuator
STANDARD CONSTRUCTION
Frame: 5 in. x 1 in. (127mm x 25 mm)
galvanized steel hat channel with reinforced corners. A low profile head and sill are used on sizes less than 17 in. (432mm) Blades: Double skin airfoil shape of galvanized steel with full length structural reinforcement. 14 ga. (2 mm) equivalent thickness. Seals: Extruded silicone rubber blade seals. Flexible stainless steel jamb seals. Linkage: Concealed in jamb. Closure Device: RRL 165°F (74°C) Axles: Bearings: Bronze sleeve type.
1
⁄2 in. (13mm) dia. plated steel.
Steel Airfoil Blades
UL 555S Leakage Class II
UL555 11⁄2 Hour Fire Resistance Rating
Model FSD-312 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes ICBO Uniform Building Codes CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“UL CLASSIFIED (see complete marking on prod­uct)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the model FSD-312 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air performance ratings only.
SIZE LIMITATIONS:
Minimum Size: (203 mm W x 152mm H) Maximum Size: Single Section: 32 in. W x 50 in. H (813mm W x 1270mm H) Multiple Section: 96 in. W x 50 in. H (2435mm W x 1270mm H) Vertical Only: 128 in. W x 100 in. H (3251mm W x 2540mm H)
OPTIONAL FEATURES:
• RRL/OCI (Open closed indication switches)
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL’s
available
• TOR (remote override closure allows damper to perform smoke management functions during a fire emergency.)
• Electric or pneumatic actuators to accomplish smoke management and system functions.
• POC retaining angles
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves
8 in. W x 6 in. H
LH
RH
*W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize. (Add sleeve thickness for overall sleeved damper dimension) Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
Pressure Drop Data FSD-312
5D 6D
5D 6D
5D
D
4 (W) (H)
3.14
5D 6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All
data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.
3
(1.201 kg/m3).
Figure 5.3
Figure 5.2
Figure 5.5
12x12
48x12
24x24
36x36
12x48
R
AMCA 5.2 Pressure Drop FSD-312
5D 6D
5D
D
4 (W) (H)
3.14
Ve locity
(fpm)
Pressure Drop
(in. wg)
Ve locity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Ve locity
(fpm)
Pressure Drop
(in. wg)
Ve locity
(fpm)
Pressure Drop
(in. wg)
500 0.03 500 0.01 500 0.01 500 0.01 500 0.02 1000 0.12 1000 0.06 1000 0.061000 0.051000 0.08 1500 0.26 1500 0.12 1500 0.121500 0.12 1500 0.18 2000 0.46 2000 0.22 2000 0.222000 0.21 2000 0.33 2500 0.72 2500 0.34 2500 0.342500 0.332500 0.51 3000 1.04 3000 0.49 3000 0.493000 0.483000 0.74 3500 1.41 3500 0.67 3500 0.673500 0.653500 1.00 4000 1.84 4000 0.87 4000 0.884000 0.854000 1.31
12in. X 48 in.
(
305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36in. x 36 in. (914mm x 914mm) 12 in. x 12 in. (305mm x 305mm)
*
* Sizes are in inches.
Greenheck Fan Corporation certifies that the model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.