Model FSD-312 is a high performance combination fire smoke
damper with class II leakage. High strength airfoil blades ensure the
lowest resistance to airflow in HVAC systems with velocities to 3000
fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may
be installed vertically (with blades running horizontal) or horizontally
and is rated for airflow and leakage in either direction.
Combination Fire Smoke Dampers
RATINGS
UL 555 Fire Resistance Rating:Fire Rating: 1½ hours
Dynamic Closure Rating: Actual ratings are size dependent
Max. Velocity:up to 3000 fpm (15.2 m/s)
Max. Pressure:4 in. wg (1 kPa)
UL555S Leakage Rating:Leakage Class:II
Operational Rating:Actual ratings are size dependent
Max. Velocity:up to 3000 fpm (15.2m/s)
Max. Pressure:4 in. wg (1 kPa)
Maximum Temperature: 350°F (177°C)- depending upon the actuator
STANDARD CONSTRUCTION
Frame: 5 in. x 1 in. (127mm x 25 mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. (432mm)
Blades:Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Seals:Extruded silicone rubber blade seals.
Flexible stainless steel jamb seals.
Linkage:Concealed in jamb.
Closure Device:RRL 165°F (74°C)
Axles:Bearings:Bronze sleeve type.
1
⁄2 in. (13mm) dia. plated steel.
Steel Airfoil Blades
UL 555S Leakage Class II
UL555 11⁄2 Hour Fire Resistance Rating
Model FSD-312 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
CSFM California State Fire Marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
performance ratings only.
SIZE LIMITATIONS:
Minimum Size:(203 mm W x 152mm H)
Maximum Size:Single Section: 32 in. W x 50 in. H
(813mm W x 1270mm H)
Multiple Section: 96 in. W x 50 in. H
(2435mm W x 1270mm H)
Vertical Only: 128 in. W x 100 in. H
(3251mm W x 2540mm H)
• TOR (remote override closure allows damper to perform smoke
management functions during a fire emergency.)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• POC retaining angles
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves
8 in. W x 6 in. H
LH
RH
*W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
Pressure Drop Data FSD-312
5D6D
5D6D
5D
D
4 (W) (H)
3.14
5D6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All
data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC
system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.
24 in. x 24 in. (610mm x 610mm)36in. x 36 in. (914mm x 914mm
)
12in. X 48 in. (305mm x 1219mm)48 in. x 12 in. (1219mm x 305mm
)
12 in. x 12 in. (305mm x 305mm
)
*
* Sizes are in inches.
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies
to air performance ratings only.
53/8"
5"
Right hand drive is shown
Left hand drive available upon request
LHRH
A
Sleeve Length
Varies
6"
33/4"
11/2" max.
Application Data
53/8"
5"
Right hand drive is shown
Left hand drive available upon request
LHRH
A
Sleeve Length
Varies
6"
33/4"
11/2" max.
B*
S
T*
Damper Sleeve Dimensional Data
The drawings below and corresponding table show the position of the FSD-312 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installa-
tion of retaining angles and duct connections.
The standard location of a damper mounted in a
factory sleeve ("A" dimension) is shown below. The
damper can be positioned at other locations within
a range of 6 in. (152 mm) to 12 in. (305mm) for the "A"
dimension.
in. (mm)
All Dampers*7 3/16 (183)12 (305)
When H is 11 in. (279mm) or
less with OCI, RRL, or TOR
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.
"A" Dimension
StandardMaximum
12 (305)12 (305)
Actuators and Accessories
Space Envelopes
Externally mounted actuators always require space
outside of the damper sleeve. The “S” dimension illustrates the clearance required for various available
actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sleeve. “B” and “T” dimensions are worst case clear-
ance requirements for some dampers less than 18 in.
(457 mm) high. All damper sizes under 18 in. (457mm)
high do not require these worst case clearances. If
space availability above or below the damper sleeve is
limited, each damper size should be individually evaluated.
ML-4XXX Series Honeywell5¼ in. (133mm)¾ in.(19mm)6 in. (152mm)
MS-4XXX Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
MS-4120 Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
ML-8XXX Series Honeywell5¼ in. (133mm)¾ in.(19mm)6 in. (152mm)
MS-8XXX Series Honeywell6 in. (152mm)6 in. (152mm)6 in. (152mm)
MS-8120 Series Honeywell6 in. (152mm)6 in. (152mm)6 in. (152mm)
331-4551 Powers1 in. (25mm)6¼ in. (159mm)6½ in. (165mm)
331-2976 Powers2 3/8 in. (60mm)12 1/8 in. (308mm)9¼ in. (235mm)
MK2-7121 Invensys3 3/4 in. (95mm)16½ in. (419mm)10 in. (254mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
Actuator Type/Model
RRL, RRL/OCI, or TOR
B*T*
With
120 Volt AC
24 Volt AC
Pneumatic (25 psi min.)
RRL, RRL/OCI, or TOR
With
S
50 in.
32 in. (813mm)
32 in. (813mm)
64 in. (1626mm)
50 in.
96 in. (2435mm)
(1270mm)
32 in. (813mm)
(1270mm)
50 in.
(1270mm)
Damper Sizing Information
D* +
2 in. (51mm) +T
s
D*
TYPE R
16 in. (406mm)
Min.
2 1 / 8 in.
D* + 2 in. (51mm)+T
s
TYPE O
W
*
H*
W*
+ 2 in. (51mm)+T
s
H* + 2 in. (51mm)+T
s
W*
H*
TYPE C
H* + 2 in. (51mm)+T
s
(54mm)
16 in. (406mm)
Min.
2 1 / 8 in.
(54mm)
16 in. (406mm)
Min.
W* + 2 in. (51mm)+T
s
(54mm)
2 1 / 8 in.
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The
following figures show maximum damper section size and assembly configurations for multi-section dampers.
Double Section
Single Section
Transitioned Damper
Dimensions
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the
FSD-312 can be supplied in a factory sleeve with round or oval transitions on both ends of
the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show overall damper size.
Specifications
Combination Fire Smoke Dampers meeting the following specifications shall be furnished and installed where shown on plans and/or
as described in schedules. Dampers shall meet the requirements of
NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall be tested, rated
and labeled in accordance with the latest edition of UL Standards
555 and 555S. Dampers shall have a UL555 fire rating of 1½ hours
and be of low leakage design qualified to UL 555S Leakage Class II.
Each damper /actuator combination shall have a UL555S elevated
temperature rating of 250° F (121°C) minimum and shall be operational and dynamic rated to operate at maximum design air flow at
its installed location. Each damper shall be supplied with an appropriate actuator installed by the damper manufacturer at the time of
damper fabrication. Damper actuator shall be (specifier select one
of the following) electric type for 120 (24 or 230) volt operation or
pneumatic type for 25 psi minimum (30 psi maximum) operation.
Damper blades shall be of the double skin airfoil type and shall
have an equivalent thickness of 14 ga. (2mm) . Damper frame shall
These dimensions are furnished
*
approximately
except round and oval dimensions
which are approximately
undersize.
Ts = (2)(Sleeve Thickness)
1
/4 in. (6mm) undersize,
be galvanized steel formed into a structural hat channel shape with
reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a tighter seal
against leakage as pressure on either side of the damper increases.
Jamb seals shall be stainless steel compression type. Blades shall
be completely symmetrical relative to their axle pivot point, presenting identical resistance to airflow in either direction or pressure on
either side of the damper.
Damper must be rated for mounting vertically (with blades running
horizontal) or horizontally and be UL 555S rated for leakage and
airflow in either direction through the damper. Each damper shall be
supplied with a 165°F (74°C) RRL. Testing and ratings to be in accordance with AMCA standard 500-D.