Model FSD-211
APPLICATION
Model FSD-211 is a combination fire smoke damper with 3V style
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire
smoke situations. Model FSD-211 may be installed vertically (with
blades running horizontal) or horizontally and is rated for airflow and
leakage in either direction.
Combination FIRE SMOKE DAMPERS
RATINGS
UL 555 Fi re Resistance Rating
Fire Rating: 1
Dynamic Closure Rating: Actual ratings are size dependent
Maximum Velocity: 2000 fpm (10.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
Maximum Temperature: 350ºF (177°C) -- Depending on
actuator
UL 555S Leakage Rating
Leakage Class: I
Operational Rating: Actual ratings are actuator dependent
Maximum Velocity: 2000 fpm (10.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
Maximum Temperature: 350ºF (177°C) - Depending on
actuator
1
⁄2 Hours
STANDARD CONSTRUCTION
Frame: 5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile head
and sill are used on sizes less than
17 in. (432mm) high to maximize free
area and performance.
Blades: 16 ga. (1.5mm) galvanized steel,
reinforced with 3 longitudinal
structurally designed vee’s.
Seals: Extruded silicone rubber blade seals
Jamb Seals: Flexible stainless steel jamb seals
Linkage: Concealed in jamb.
Closure Device: UL listed 165°F (74°C) RRL
Axles:
Bearings: Bronze sleeve type
1
⁄2 in. (13mm) dia. plated steel
Steel 3-V Blades
UL 555S Leakage Class I
UL555 11⁄2 Hour Fire Resistance Rating
Model FSD-211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
CSFM California State Fire Marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
SIZE LIMITATIONS:
Minimum Size:
Maximum Size: Single Section: 32 in. W x 50 in. H
(813mm W x 1270mm H)
36 in. W x 48 in. H
(914mm x 1219mm)
Multiple Section:
Horizontal: 144 in. W x 96 in. H
(3658mm W x 2438mm H)
Vertical: 128 in. W x 100 in. H
(3251mm W x 2540mm H)
8 in. W x 6 in. H (203mm W x 152mm H)
RH
OPTIONAL FEATURES:
• RRL/OCI (Open closed indication switches)
• Electric or pneumatic actuators
• POC retaining angles
• Smoke detectors
• Momentary switch
• Pneumatic Relief Valve (PRV)
• Security bars
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure
allows damper to perform smoke management functions during a
fire emergency)
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)
RRL's available.
• Sealed transitions and sleeves
Installation installations available at www.greenheck.com
*W&H dimensions furnished approximately ¼in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
LH
Pressure Drop Data FSD-211
5D 6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All
data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC
system.
3
(1.201 kg/m3).
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.
AMCA 5.2 Pressure Drop FSD-211
5D 6D
5D
D
=
4 (W) (H )
3.14
Figure 5.3
Figure 5.2
500 0.04 500 0.02 500 0.01 5000.01
1000 0.14 10000.07 10000.04 1000 0.06
15000.31 15000.16 15000.09 1500 0.13
2000 0.55 20000.29 20000.1620000.23
2500 0.86 25000.45 25000.2525000.36
30001.24 30000.65 30000.3630000.52
3500 1.69 3500 0.89 3500 0.49 3500 0.70
4000 2.20 4000 1.16 4000 0.64 4000 0.92
12 in. x 12 in. (305mm x 305mm)
24 in. x 24 in. (610mm x 610mm)
36 in. x 36 in. (914mm x 914mm)
12 in. x 48 in. (305mm x 1219mm)
5000.03
1000 0.10
1500 0.23
2000 0.41
2500 0.63
3000 0.91
3500 1.24
48 in. x 12 in. (1219mm x 305mm)
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to
air performance ratings only.