Greenheck Fan DFD-155 User Manual

Dynamic Rated FIRE DAMPERS
H*
K
Damper
Location
L
Overall Sleeve Length
W*
CL Damper Frame
Sleeve
Damper
D*
+
2 in
.
O*
D*
TYPE CR TYPE CO
W*
+
2 in
.
6 in.
Max.
W
*
H*
W* +
2 in.
O*
W*
H*
TYPE C
6 in.
Max.
O*
6 in
Max.
21/2 in.
2
1
/
2
in
.
2
1
/
2
in.
3
1
1
/
16
"
W*
H*
Stainless Steel Closure Spring
Fusible Link (replaceable) 165ºF
[74ºC]Standard (212º
[100ºC]available)
HORIZONTAL MOUNT
VERTICAL
“K” side
)
(94mm)
Application
Model DFD-155 is approved for use in walls, floors and partitions with fire resistance ratings less than 3 hours. This model carries a 11⁄2 hour UL fire damper label. UL 555 classifies dynamic rated fire dampers for use in HVAC systems that are operational in the event of fire .
Ratings
UL555 Fire Resistance Rating Fire Rating: 1 1/2 hours Dynamic closure rating Maximum Velocity: 4000 fpm (20.3 m/s) vertical mount only, up to 24 in. x 24 in. (610mm x 610mm) 2000 fpm (10.2 m/s) vertical or horizontal mount, on all sizes. Maximum Pressure: 4 in wg (1 kPa)
Construction
Galvanized steel (in gauges required by UL listing R-13317)
Installation
All fire damper installations require the use of sleeves, angles and methods described in Greenheck Fire Damper Installation Instructions #452763, included with every damper shipment. Sleeves can be field fabricated or factory furnished as a complete damper/sleeve assembly. See Factory Sleeve Option below for details.
Model DFD-155
100% Free Area - Sealed for High Pressure Systems
11⁄2 Hour Fire Resistance Rating
Model DFD-155 meets the requirements for fire dampers established by:
National Fire Protection Association
(NFPA Standards 80, 90A & 101)
BOCA National Building Codes IBC International Building Codes ICBO Uniform Building Codes ( UBC Standard 43-7) SBCCI Standard Building Codes New York City ( MEA listing #260-91-M)
California State Fire Marshal (Listing #3225-981:102)
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555
(Listing #R13317)
Features
• Stainless steel closure springs
• Fusible links - 165ºF (74ºC) standard, 212ºF (100ºC) and 286ºF (141ºC) available
• Horizontal or vertical mount available
• Sealed for use in high pressure systems
Optional Features
• Security bars
• One piece retaining angle (POC)
• Tranhhsitions (C, CO, CR, & R)
These dimensions are furnished approximately 1/4in. (6mm) undersize, except
*
round and oval dimensions which are 1/8 in. (3mm) undersize. (Add sleeve thickness for overall sleeved damper dimension)
Factory Sleeve Option
DFD-155 Fire Dampers are available in factory furnished sleeves. Sleeves are galvanized steel and are available in 10 thru 20 ga.(1mm - 3.5mm) thicknesses and lengths up to 36 in. (914mm).
“K” dimension specifies location of damper within the sleeve. Minimum is 4 in. (102mm), maximum is “L” less 4 in. (102mm), which allows for mounting angle installation and duct connection at each end of sleeve. If “K” dimension is not specified, it will be provided as one half of “L” dimension (damper centered in sleeve).
Horizontally mounted dampers must be installed with the “K” dimension on the bottom side.
Note: If using access doors, the doors should be installed on the “K” side of the damper.
O*
H*
Type C
W*+2
W*
O*
H*
Type CO
W*+2
W*
D*
Type CR
O*
D*+2
31 in. (787mm)
Max.
Maximum Single Section Dimensions
Type COType C
31in. (787mm)
Max.
31 in. (787mm)
Max.
34 in. (864mm)
Max.
34 in. (864mm)
Max.
DFD-155 TYPE CR, CO, C, & RSIZING DATA
34 in. (889mm) max.
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. These multi-section damper assemblies may have slightly less than 100% free area because of the mullions where damper sections join.
The following charts shows minimum and maximum damper section sizes . Dimensions are in inches (mm in parentheses).
Inches (mm)
Single Section
Vertical
Multi Section
Vertical**
Single Section
Horizontal
Multi Section
Horizontal**
*1 With 2 in. (50mm) offset. Sizes adjust with 0 offset & 1 in. (25mm) offset. ** Consult factory for number of sections.
Type R
Type R transition is centered on damper frame. Dimensions are with 2 in. (50mm) offset.
* All multiple section dampers, with transitions, will include a factory installed 8 in. (203mm) sleeve.
C, CO, & CR transitions
are positioned 1 in.(25mm)
from bottom of sleeve.
Type CR Type CO & C Type R*
Minimum Maximum Minimum Maximum Minimum Maximum
(76)
NA
(76)
NA
3
3
31
(787)
55
(1397)
25
(635)
31
(787)
3 x 3
(76 x 76)
NA
3 x 3
(76 x 76)
NA
34 x 31
(864 x 787)
70 x 44
(1778 x 1118)
or
58 x 55
(1473 x 1397)
28 x 25
(711 x 635)
46 x 31
(1163 x 787)
(76)
NA
(76)
NA
3
3
Type CR
1
34
(864)
58
(1473)
28
(711)
34
(864)
Overall Damper Dimensions
H or D* O* H or D* O*
3 (76) 6 (152) 27 (686) 32 (813)
4 (102) 7 (178) 28 (711) 33 (838)
5 (127) 8 (203) 29 (737) 34 (864)
6 (152) 9 (229) 30 (762) 35 (889)
7 (178) 10 (254) 31 (787) 36 (914)
8 (203) 11 (279) 32 (813) 36 (914)
9 (229) 12 (305) 33 (838) 37 (940)
10 (254) 13 (330) 34 (864) 38 (965)
11 (279) 14 (356) 35 (889) 39 (991)
12 (305) 15 (381) 36 (914) 40 (1016)
13 (330) 16 (406) 37 (940) 41 (1041)
14 (356) 17 (432) 38 (965) 42 (1067)
15 (381) 19 (483) 39 (991) 43 (1092)
16 (406) 20 (508) 40 (1016) 44 (1118)
17 (432) 21 (533) 41 (1041) 45 (1143)
18 (457) 22 (559) 42 (1067) 46 (1168)
19 (483) 23 (584) 43 (1092) 47 (1194)
20 (508) 24 (610) 44 (1118) 48 (1219)
21 (533) 25 (635) 45 (1143) 50 (1270)
22 (559) 27 (686) 46 (1168) 51 (1295)
23 (584) 28 (711) 47 (1194) 52 (1321)
24 (610) 29 (737) 48 (1219) 53 (1346)
25 (635) 30 (762) 49 (1245) 54 (1372)
26 (660) 31 (787) 50 (1270) 55 (1397)
Dimensions are in inches (mm in parentheses).
*
These dimensions are furnished approximately 1/4 in. (6mm) undersize. (All 'H' dimensions larger than single section height are two sections high. Refer to chart.) Dimension are in inches (mm).