DFD-150X series
H
*
K
Damper
Location
W
*
CL Damper Fram
Sleeve
CL Damper Frame
Damper
Overall Sleeve Length
12 in. (305mm) = DFD-150X12
14 in. (356mm) = DFD-150X14
16 in. (406mm) = DFD-150X16
VERTICAL MOUNT
Fusible Link (replaceable)
HORIZONTAL MOUNT
K
CL Damper
Frame
P
*
10 in. (305mm) = DFD-150X10
HORIZONTAL MOUNT
K
CL Damper
Frame
Dynamic Rated FIRE DAMPERS with Sleeve
11⁄2 Hour Fire Resistance Rating
APPLICATION
Model DFD-150X is approved for use in walls, floors and
partitions with fire resistance ratings less than 3 hours.
1
This model carries a 1
⁄2 hour UL fire damper label. UL
555 classifies dynamic rated fire dampers for use in HVAC
systems that are operational in the event of fire .
RATINGS
UL555 Fire Resistance Rating
Fire Rating: 1 1/2 hours
Dynamic closure rating
Maximum Velocity: 4000 fpm (20.3 m/s) up to 24 in. x 24 in.
(610mm x 610mm) 2000 fpm (10.2 m/s) above
24 in. x 24 in. (610mm x 610mm)
Maximum Pressure: 4 in. wg (1 kPa)
CONSTRUCTION
Damper is galvanized steel (in gauges required by UL listing
R-13317) sleeve is 20 ga. galvanized steel.
STANDARD FEATURES
• Stainless steel closure springs
• Fusible links (165ºF (74ºC) standard, 212ºF (100ºC) and
286ºF (141ºC) available.
• Horizontal or vertical mount available
Model DFD-150X meets the requirements for fire dampers
established by:
National Fire Protection Association
(NFPA Standards 80, 90A & 101)
BOCA National Building Codes
ICBO Uniform Building Codes ( UBC Standard 43-7)
SBCCI Standard Building Codes
New York City ( MEA listing #260-91-M)
California State Fire Marshall
(Listing #3225-981:102 for use in walls)
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see
complete marking on product)”
Standard 555 (Listing #R13317)
OPTIONAL FEATURES
• Security bars
• One piece retaining angles (POC)
• Transitions (B, C, CO, CR, & R)
• Steel stud connection
• Sealed transitions and sleeves
These dimensions are furnished approximately 1⁄4 in. (6mm) undersize.
*
DFD-150X Type A
36in. max.
36 in. max.
(914mm)
(914mm)
48 in. (1219mm) max.
72 in. (1829mm) max.
Dampers larger than maximum single section size are supplied in 2 or more sections of equal size.
The following chart and illustrations show minimum and maximum damper section size and assembly configurations for
multi-section dampers.
SIZE LIMITATIONS
Blade Stack
Dimensional Data
Inches
(mm)
Single
Section
Vertical
Multi
Section**
Vertical
Single
Section
Horizontal
Multi
Section**
Horizontal
Type A Type B
minimum maximum minimum maximum
6 x 4
(152 x 102)
NA
6 x 4
(152 x 102)
NA
36 x 36
(914 x 914)
72 x 48
(1829 x 1219)
or
60 x 60
(1824 x 1524)
30 x 30
(762 x 762)
48 x 36
(1219 x 914)
6 x 6
(152 x 152)
NA
6 x 6
(152 x 152)
NA
36 x 32
(914 x 813)
72 x 45
(1829 x 1143)
or
60 x 56
(1524 x 1422)
30 x 26
(762 x 660)
48 x 32
(1219 x 813)
Installation of sizes larger than the maximums shown requires approval of
the authority having jurisdiction.
** Consult factory for number of sections.
1 MAXIMUM SINGLE
SECTION DIMENSIONS
2 MULTI-SECTION LIMITATIONS
Maximum height is 48 in. (1219mm) when width is 72 in.
(1829mm) or less.
H* P
in. mm in. mm
8 203 1.2 30
9 229 1.3 33
10 254 1.3 33
11 279 1.4 36
12 305 1.6 41
13 330 1.7 43
14 356 1.8 46
15 381 1.8 46
16 406 2.0 51
17 432 2.1 53
18 457 2.2 56
19/37/38 483/940/965 2.3 58
20/39/40 508/991/1016 2.4 61
21/41/42 533/1041/1067 2.6 66
22/43/44 559/1092/1118 2.6 66
23/45/46 584/1143/1168 2.7 69
24/47/48 610/1194/1219 2.9 74
25/49/50 635/1245/1270 3.1 79
26/51/52 660/1295/1321 3.2 81
27/53/54 686/1346/1372 3.2 81
28/55/56 711/1397/1422 3.3 84
29/57/58 737/1448/1473 3.4 86
30/59/60 762/1499/1524 3.6 91
31/32 787/813 3.7 94
33/34 838/864 3.9 99
35 889 4.1 104
36 914 4.2 107
These dimensions are furnished
*
approximately
1
/4 in. (6mm) undersize.