Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could
result in personal injury and/or property damage! Retain instructions for future reference.
Model ERCH-HP
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards,
including environmental. Other considerations may be
required if high winds or seismic activity are present.
If more information is needed, contact a licensed
professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affect motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Verify that the power source is compatible with the
equipment.
6. Never open access doors to the unit while it is
running.
DANGER
• Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
• If this unit is equipped with optional gas
accessories, turn off gas supply whenever power is
disconnected.
CAUTION
This unit is equipped with a compressed refrigerant
system. If a leak in the system should occur,
immediately evacuate and ventilate the area. An EPA
Certified Technician must be engaged to make repairs
or corrections. Refrigerant leaks may also cause
bodily harm.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
Model ERCH-HP Energy Recovery Unit
1
Receiving
Upon receiving the product, check to make sure all
items are accounted for by referencing the bill of lading
to ensure all items were received. Inspect each crate for
shipping damage before accepting delivery. Notify the
carrier if any damage is noticed. The carrier will make
notification on the delivery receipt acknowledging any
damage to the product. All damage should be noted on
all the copies of the bill of lading which is countersigned
by the delivering carrier. A Carrier Inspection Report
should be filled out by the carrier upon arrival and filed
with the Traffic Department. If damaged upon arrival, file
claim with carrier. Any physical damage to the unit after
acceptance is not the responsibility of the manufacturer.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Number
and location of lifting brackets varies by model and size.
Handle each piece in such a manner as to keep from
scratching or chipping the coating. Damaged finish may
reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
Inspection and Maintenance during
Storage
While in storage, inspect units once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate all moving components by hand ten
to fifteen revolutions to distribute lubricant on motor and
bearings. If paint deterioration begins, consideration
should be given to touch-up or repainting. Units with
special coatings may require special techniques for
touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe clean thoroughly
with Tectyl® 506 (Ashland Inc.) or the equivalent.
For hard to reach internal surfaces or for occasional
use, consider using Tectyl® 511M Rust Preventive or
WD-40® or the equivalent.
Handling, Lifting and Lifting Lugs ...............9
Roof Curb Mounting, Dimensions, Weights ......10
Ductwork Connections ......................11
Rail Mounting / Layout .......................11
Exhaust Weatherhood .......................11
Start-Up Unit ...............................12
Pre-Start-Up Checklist .......................13
Start-Up Procedure .........................13
Voltage Imbalance ..........................13
Unit Start-Up Checklist ......................14
Electrical Information
General Electrical Information .................15
Discharge Air Temp Sensor ...................16
Plumbing/Piping Overview
Condensate Drain Trap ......................16
Optional Remote Control Panel and
Wiring Schematics .........................17
Typical Control Center Components ............18
Electrical Controls
Optional Frost Control .......................19
Optional Economizer ........................20
Phase Monitor .............................20
Variable Frequency Drive .....................20
Optional Rotation Sensor .....................21
Dirty Filter Sensor ..........................21
Energy Wheel
Start-Up ..................................22
Sequence of Operation ......................22
Maintenance ...............................23
Troubleshooting ............................24
Heat Pump Overview
Heat Pump Components .....................24
Heat Pump Controls ........................25
Refrigeration Schematic ......................26
Typical Operating Conditions ..................26
Unit Protection Module Fault Indicators .........27
Troubleshooting
Controller Alarms ...........................28
Airflow ...................................29
Unit ......................................30
Refrigeration Circuit ......................31-35
Maintenance
Monthly, Semianually, Annually ................36
Heat Pump ................................36
Maintenance Procedures
Lubrication ................................36
Dampers ..................................36
Fan Belts ..............................36-37
Fan Motors ................................37
Fan Wheel and Fasteners ....................37
Fan Bearings ..............................37
Internal Filter Maintenance ...................38
External Filter Maintenance ...................38
Coil Maintenance ...........................38
Maintenance Log ............................39
Warranty ............................Backcover
Model ERCH-HP Energy Recovery Unit
3
Product Overview
Models and Capacities
This unit brings in fresh, outdoor air and removes
stale exhaust air from the building. The intake and
exhaust airstreams move through the unit in opposite
directions in separate passages, and each airstream
passes through an energy wheel. In cooling mode, the
energy wheel removes both heat and moisture from
the incoming airstream and rejects it into the exhaust
airstream. In heating mode, the energy wheel removes
heat and humidity from the exhaust air and rejects
it into the intake air, thus reclaiming energy already
expended to heat the building air.
In addition to the energy wheel, this unit incorporates
a packaged water source heat pump The heat pump
system comes from the factory fully-charged with
refrigerant and is ready for connection to a water source
upon arrival.
For purposes of providing temporary emergency heat,
an optional secondary heating source such as indirect
gas furnace or electric heaters may also be installed.
The smaller tonnage units (4-6 tons) contain a single
compressor, allowing for one stage of cooling. Larger
units (8-30 tons) come standard with two compressors
and a split airside coil. This allows for staging of
compressors to meet a wider range of outdoor air loads
while reducing the amount of cycles per compressor.
Simply put, this unit preconditions the outdoor air to
save money on heating and cooling costs and then
provides supplemental heating and cooling by means
of a highly efficient heat pump.
This unit is manufactured in four different platform sizes;
20, 45, 55 and 90. Each platform has multiple options
for heating and cooling capacities.
All 4, 5 and 6 ton capacity units have a single scroll
type compressor and all other units have two scroll type
compressors and use a split airside heat pump coil.
Heat Pump Capacity
Unit SizeTons
ERCH-HP 20 4, 5, 6
ERCH-HP 45 8, 10, 12.5, 15
ERCH-HP 55 15, 17.5, 20
ERCH-HP 90 20, 25, 30
Heat Pump
Airside Heating
and Cooling Coil
Outdoor
Air Intake
Filters
Energy Wheel
Cassette
Reheat
Coil
Heat Pump
Compressor(s)
Supply Air
Motor & Blower
Heat Pump Module
(component locations
will vary)
Coaxial
Refrigerant-to-Water
Heat Exchanger
Model ERCH-HP Energy Recovery Unit
4
Subassemblies
Coils
The airside coil is connected to the heat pump
compressor(s) and is the primary vehicle for heating
and cooling of the building. A reheat coil is optionally
available and is installed in the supply airstream
adjacent to the airside coil. The reheat coil is also
connected to the heat pump but is used only when the
unit is in cooling mode.
Heat Pump
Airside Coil
Optional Heat Pump
Reheat Coil
Dampers
There are four locations where dampers are optionally
installed.
Energy Wheel
The energy wheel rotates through both the outdoor air
and the exhaust airstreams, removing both sensible
(heat) energy and latent moisture from one airstream
and transferring it to the other airstream. The energy
wheel itself is comprised of segments which can be
removed for servicing.
Bearing Support
Adjustable
Air Seals
Label showing
cassette serial number
and date code
Drive Belt
Drive Pulley
Filters
There are three locations in the unit where filters will be
found.
Gravity Type
Exhaust Damper
Exhaust
Hood
Ooutdoor Air
Motorized Outdoor
Air Intake Damper
Hood
Filters
Wheel Cassette
Motorized Exhaust
Air Damper
Electrical Box
Exhaust Air
Filters
Coil Section
Intake
Motorized Recirculating Air
Damper
Indirect Gas Heater
Exhaust
Hood
Hood
Ooutdoor Air
Filters
Permanent Metal Filters
Two-inch thick MERV 8
pleated filters
Filters
Wheel Cassette
Coil Section
Two-inch thick MERV 8 or
MERV 13 pleated filters
Electrical Box
Exhaust Air
Intake
Indirect Gas Heater
Model ERCH-HP Energy Recovery Unit
5
Heat Pump Module
Every unit has an integral heat pump module that
contains hermetic scroll-type compressor(s), a coaxial
refrigerant-to-water heat exchanger(s), refrigerant flow
reversing valve(s), expansion valve(s), liquid line filter
drier, high pressure manual reset cutout, crankcase
heater(s) and various sensors, service ports and safety
devices which allows the unit to run at less than full
capacity and results in fewer compressor cycles. The
heat pump is intended to be connected to an external
water source such as a water cooling tower or boiler, a
geothermal source or even a ground loop. The module
is piped to the airside coil located in the intake airstream
and optionally to a reheat coil that will control humidity.
The location of components in the module will
vary.
Control circuitry and the Unit Protection Module (UPM)
for the heat pump module are located in the heat pump
module. The UPM is a
printed circuit board and
has LED fault indicator
lights to indicate various
alarm conditions and also
power status. A unitspecific schematic for
electrical circuits is located
in the control center and
another unit-specific
schematic for heat pump
circuitry is located in the heat pump module.
Unit Protection Module
(UPM)
Optional Electric Heaters
There are two optional electric heaters available. One is
a preheater and is used to prevent frost buildup on the
energy wheel. It is located directly in front of the intake
air filter assembly. The second optional heater is used
as a supplementary emergency heat source for the
building and is integrated into the supply airstream.
Optional Electric
Preheater Location
Supply Air Motor and
Blower Assembly
Optional Electric
Heater Location
Optional Indirect Gas Furnace
An optional indirect gas furnace may be installed and
provides supplementary emergency heat to the building.
A complete Installation, Operation and Maintenance
Manual for the furnace is provided with the unit. A unitspecific wiring diagram is located inside the furnace
housing access door.
High Efficiency
Scroll Type
Compressors
Coaxial
Refrigerant-
to-Water Heat
Exchangers
Refrigerant
Reversing
Valves
Indirect Gas Furnace
Water Intake
and Discharge
Connections
Heat Pump Module
Model ERCH-HP Energy Recovery Unit
6
Installation
Dimensional Data
Overall Exterior Dimensions
Model
(including Lifting Lugs)
ERCH-HP 2059.575116
ERCH-HP 4569.586122
ERCH-HP 5579.5101134
ERCH-HP 9099.5123147
All dimensions shown are in inches.
Unit Weights and Recommended Roof Opening
Exhaust
Intake
Width
V
Overall Width
(with Exhaust Hood)
Overall Length
(with Outdoor Air Hood)
U
Supply
Discharge
1/2 inch
Unit SizeUV
1/2 inch1/2 inch
Approximate
Weight (pounds)
ERCH-HP 2046372150
ERCH-HP 4554393500
ERCH-HP 5565474450
ERCH-HP 9085495300
All dimensions are in inches. Unit weights assume rooftop
configuration with weatherhoods, filters, outdoor air damper,
six row DX coil, integral condensing section and an indirect
gas-fired furnace.
Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening (see Service Clearances). Do not face the
outdoor air intake of the unit into prevailing wind and
keep the intake away from any other exhaust fans.
Likewise, position the exhaust discharge opening away
from outdoor air intakes of any other equipment.
Model ERCH-HP Energy Recovery Unit
7
Service Clearances
Minimum clearances are required for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy wheel cassette, coil and filter
sections are always provided with a service door or panel for proper component access. Clearances for component
removal may be greater than the service clearances, refer to drawings for these dimensions.
ERCH-HP 20
ERCH-HP 45
36 IN
WHEEL CASSETTE
ACCESS PANEL
FILTERS
ACCESS PANEL
ELECTRICAL BOX
EXHAUST AIR
INTAKE
ACCESS PANEL
ACCESS PANEL
36 IN
MINIMUM
52 IN
CLEARANCE
WITH IG HEATER
36 IN
ACCESS PANEL
EXHAUST
HOOD
ERCH-HP 55
ERCH-HP 90
HOOD
OUTDOOR AIR
FILTERS
*48 IN**64 IN
ACCESS PANEL
COIL SECTION
ACCESS PANEL
ACCESS PANEL
IG HEATER
Clearances for service and component removal on ERCH-HP 20 and ERCH-HP 45
* Clearance for energy wheel removal on ERCH-HP 20
** Clearance for energy wheel removal on ERCH-HP 45
42 IN
42 IN
ACCESS PANEL
HOOD
OUTDOOR AIR
EXHAUST
HOOD
FILTERS
ACCESS PANEL
WHEEL CASSETTE
FILTERS
COIL SECTION
ACCESS PANEL
ELECTRICAL BOX
EXHAUST AIR
INTAKE
ACCESS PANEL
ACCESS PANEL
IG HEATER
36 IN
MINIMUM
52 IN
CLEARANCE
WITH IG HEATER
Clearances for service and component removal on ERCH-HP 55 and ERCH-HP 90
Model ERCH-HP Energy Recovery Unit
8
ACCESS PANEL
ACCESS PANEL
42 IN
ACCESS PANEL
Handling
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation. Exercise extreme
caution to prevent any damage from occurring to
the refrigerant system. This unit contains a system
pressurized with refrigerant that, if damaged, could
leak into the atmosphere or cause bodily harm due to
the extreme cold nature of expanding refrigerant. Use
protective equipment such as gloves and safety glasses
to minimize or prevent injury in case of a system leak
during installation.
The system design and installation should follow
accepted industry practice, such as described in
the ASHRAE Handbook. Adequate space should be
left around the unit for piping coils and drains, filter
replacement, and maintenance. Sufficient space should
be provided on the side of the unit for routine service
and component removal should that become necessary.
Lifting
1. Before lifting, be sure that all shipping material has
been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Installation, Unit
Weights and Recommended Roof Opening section
of this manual.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach to
unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to lifting
the unit and setting on curb.
11. Do not use fork lifts for handling unit.
WARNING
All factory provided lifting lugs must be used when
lifting the units. Failure to comply with this safety
precaution could result in property damage, serious
injury, or death. Unit weights assume rooftop
configuration with weatherhoods, filters, outdoor air
damper, six row DX coil, integral condensing section
and an indirect gas fired furnace.
Lifting Lugs
NOTE
On some models, one lifting lug may be positioned
directly in front of the condensate drain connection.
Any lifting lug that is located as shown should be
removed in order to permit installation of the P trap
drain kit.
Model ERCH-HP Energy Recovery Unit
9
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
Factory Supplied Roof Curbs: Roof curbs are Model
GKD, which are shipped in a knockdown kit (includes
duct adapter) and require field assembly (by others).
Assembly instructions are included with the curb.
Install Curb: Locate curb over roof opening and
fasten in place. Reference Installation, Unit Weights
and Recommended Roof Openings in this manual.
Check that the diagonal dimensions are within ±1/8
inch of each other and adjust as necessary. For proper
coil drainage and unit operation, it is important that the
installation be level. Shim as required to level.
Install Ductwork:
Installation of all
ducts should be done
in accordance with
SMACNA and AMCA
guidelines. Duct
adapter provided to
support ducts prior to
setting the unit.
Set the Unit: Lift
unit to a point directly
above the curb and
duct openings. Guide
unit while lowering
to align with duct
openings. Roof curbs
fit inside the unit base.
Make sure the unit is
properly seated on the
curb and is level.
Set the Unit
Curb Outside Dimensions and Weights
SIDE OF UNIT
A
B
C
D
E
ROOF CURB
Curb Cap Details for Factory-Supplied Roof Curbs
Curb Cap Dimensions
Unit SizeABCDE
ERCH-HP 202.002.001.000.880.75
ERCH-HP 452.004.252.001.310.50
ERCH-HP 552.004.252.001.310.50
ERCH-HP 902.004.252.001.310.50
All dimensions are in inches.
BASE
1 INCH INSULATION
Curb Outside Dimensions and Curb Weights (lbs)
Unit SizeLWWeight
ERCH-HP 20104.8851.00310
ERCH-HP 45115.7560.63400
ERCH-HP 55129.8871.50510
ERCH-HP 90148.1390.75720
All dimensions are in inches. Weights are for 12 inch high
curbs. Roof curb details, including duct locations dimensions
are available on the roof curb assembly instructions.
Model ERCH-HP Energy Recovery Unit
10
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
Ductwork Connections
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
Examples of poor and good fan-to-duct connections
are shown below. Airflow out of the fan
should be directed straight or curve
the same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.
n
o
i
t
a
t
o
R
Recommended Discharge Duct Size and Length
Unit Size
Blower
ERCH-HP 20914 x 1436
ERCH-HP 451020 x 2036
ERCH-HP 551220 x 2036
ERCH-HP 901528 x 2860
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM)
at minimum airflow and up to 1600 fpm at maximum airflow.
Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication 201.
Calculated values have been rounded up to nearest foot.
Size
Length of Straight Duct
GOOD
Duct Size
Straight Duct
Length
Rail Mounting / Layout
• Rails designed to handle the weight of the unit
should be positioned as shown on the diagram
(rails by others).
• Make sure that rail positioning does not interfere
with the supply air discharge opening or the
exhaust air intake opening on the unit. Avoid area
dimensioned “B” below.
• Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
• Set unit on rails.
Outdoor Air
Intake Hood
Supply/Exhaust
Opening
BA
Side view of unit on rails
Rail Mounting
Unit SizeAB
ERCH-HP 205.041.0
ERCH-HP 457.041.9
ERCH-HP 555.553.0
ERCH-HP 906.059.0
All dimensions are in inches.
Isometric view of unit
Exhaust Weatherhood
The exhaust weatherhood is shipped separately as a kit
with its own instructions.
Model ERCH-HP Energy Recovery Unit
11
Start-Up Unit
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
CAUTION
Do not operate without the filters and birdscreens
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans,
and compressors are set-up to run correctly
when supplied power. If any one fan is running
backwards or the compressor is making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect.
This will ensure proper operation of the unit.
Failure to comply may damage the compressors
and void the warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
• Do not operate compressor when the outdoor
temperature is below 40ºF.
• Do not short-cycle the compressor. Allow
5 minutes between “on” cycles to prevent
compressor damage.
• Prior to starting up the unit, power must be
energized for 24 hours without a call for cooling
to allow the compressor crankcase heaters time
to boil off any liquid refrigerant present in the
compressor.
• DX system is charged with refrigerant. Start-up
must be performed by EPA Certified Technician.
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model No. __________________________________
Unit Serial No. ___________________________________
Heat Pump Model No. ____________________________
Energy Wheel Date Code _________________________
Compressor 1 Model No. _________________________
Compressor 2 Model No. _________________________
Start-Up Date ___________________________________
Start-Up Personnel Name ________________________
Start-Up Company _______________________________
Phone Number ___________________________________
Model ERCH-HP Energy Recovery Unit
12
Pre-Start-Up Checklist
oDisconnect and lock-out all power switches.
o Remove any foreign objects that are located in the
energy recovery unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
o Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
o Check the fan belt drives for proper alignment and
tension.
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify control wire gauge.
o Verify diameter seal settings on the energy recovery
wheel.
o Verify proper drain trap installation.
o Check condensing fans for any damage or
misalignment. Spin the blades and make sure they
don’t contact any parts and are free turning without
any resistance.
o Look over the piping system. Inspect for oil at all
tubing connections. Oil typically highlights a leak in
the system.
o Inspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully
straighten fins with a fin comb.
o If there is an indirect gas-fired furnace in this unit,
refer to the maual provided with this unit for PreStart-Up information.
o This unit contains a crankcase heater for each
compressor which needs power supplied to it
24hours prior to start-up. If start-up is scheduled in
24 hours, unlock the disconnect power and energize
unit.
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
• Incline manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running. In order to measure
volts and amps, the control center door must be open,
and the unit energized using a crescent wrench to turn
the disconnect handle.
o Make sure Pre-Start-Up checklist is complete.
o Jumper R to G, R to Y1, and R to Y2 (if applicable)
on the control board.
o Turn the disconnect on. After 3 minutes
compressors will come on. Make sure all fans and
compressors are rotating the correct direction.
o Allow the unit to run until the refrigerant system
stabilizes. Approximately 1-2 minutes.
Voltage Imbalance
In a 3-phase system, excessive voltage imbalance
between phases will cause motors to overheat and
eventually fail. Maximum allowable imbalance is 2%.
To determine voltage imbalance, use recorded voltage
measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA
Model ERCH-HP Energy Recovery Unit
13
Unit Start-Up Checklist
Line Voltage. Check at unit disconnect.
L1-L2VoltsL2-L3VoltsL1-L3Volts
Motor Amp Draw
Supply Motor AmpsL1AmpsL2AmpsL3Amps
Exhaust Motor AmpsL1AmpsL2AmpsL3Amps
Fan RPM
Supply Fan RPM
Exhaust Fan RPM
Correct fan rotation direction?
Supply FanYes / No
Exhaust FanYes / No
Energy Wheel Motor
L1AmpsL2AmpsL3Amps
Compressors
Compressor 1L1AmpsL2AmpsL3Amps
Crankcase HeaterAmps
Compressor 2L1AmpsL2AmpsL3Amps
Crankcase HeaterAmps
Condensing Fans
Condensing Fan 1L1AmpsL2AmpsL3Amps
Condensing Fan 2L1AmpsL2AmpsL3Amps
Condensing Fan 3L1AmpsL2AmpsL3Amps
Outdoor Air TemperatureDeg F
Return Air TemperatureDeg F
Outdoor Air Relative Humidity% RH
Return Air Relative Humidity% RH
SuperheatDeg F
SubcoolingDeg FShould be between 12º and 17ºF
Should be between 8º and 12ºF
Discharge PressurePSIGShould be between 200 and 280 PSIG for R22 or 300 and 500 PSIG for R410a
Suction Line PressurePSIGShould be between 60 and 80 PSIG for R22 or 100 and 135 PSIG for R410a
Liquid Line TempDeg F
Suction Line TempDeg F
Moisture Indicating Sight GlassLiquid Visible? Yes / No Color of Center Dot: Green / Yellow
Hot Gas Bypass OperationalYes / No
Model ERCH-HP Energy Recovery Unit
14
Electrical Information
SUP HP
MCA
EXH HP
MOP
VOLTSHZPH
Unit’s Total MCA
Voltage, Hertz, Phase
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
Determine the Size of the Main Power
Lines
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be sized
accordingly. The nameplate is located on the outside of
the unit on the control panel side.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the power
supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the
latest edition of the National Electric Code ANSI/
NFPA70 and any local codes that may apply. In
Canada, wiring should be done in accordance with
the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded. Any
wiring running through the unit in the airstream must
be protected by metal conduit, metal clad cable or
raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105ºC, except for an
energy cut-off or sensor lead wire which must be
rated to 150ºC.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to or failure of the unit caused by
incorrect final wiring.
Voltage, Hertz, Phase
VOLTSHZPH
SUP HP
MCA
Electrical Nameplate
EXH HP
MOP
Determine the Size of Electric Heater
Wiring
An optional electric heater may require a separate
power supply. The power connection should be made
to the factory-provided electric heater disconnect and
must be compatible with the ratings on the nameplate,
supply power voltage, phase and amperage. Consult
ANSI/NFPA 70 and CSA C22.1 for proper conductor
sizing.
Provide the Opening(s) for the Electrical
Connections
Electrical openings vary by unit size and arrangement
and are field-supplied.
Connect the Power Supplies
Connect the main power lines and electric heater power
lines to the disconnect switches or terminal blocks
and main grounding lug(s). Torque field connections to
manufacturer’s recommendations.
Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V power
supply circuit. The circuit must include short circuit
protection which may need to be supplied by others.
Connect Field-Wired Low Voltage
Components
Reference the Ladder Diagram on the inside of the
control center door for correct wiring of the following
accessories:
• Remote Panel
• Room Temperature Sensor
• Room Dehumidistat
• Discharge Temperature Sensor
Model ERCH-HP Energy Recovery Unit
15
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field-wiring, refer to the unit-specific
wiring diagram located on the inside of the control
center access door.
The low voltage control circuit is 24 VAC and control
wiring should not exceed 0.75 ohms.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that
field-supplied conduit does not interfere with access
panel operation. All low voltage wiring should be run in
conduit wherever it may be exposed to the weather.
If wire resistance exceeds 0.75 ohms, an insulator relay
should be added to the unit control center and wired in
place of the remote switch (typically between terminal
blocks R and G on the terminal strip. The relay must be
rated for at least 5 amps and have a 24 VAC coil. Failure
to comply with these guidelines may cause motor
starters to “chatter” or not pull in which can cause
contactor failures and/or motor failures.
Discharge Air Temperature Sensor
WARNING
Discharge air temperature sensor is to be fieldinstalled prior to unit start-up.
The sensor is to be installed at least three duct
diameters downstream of the heat
exchangers or where good mixed
average temperature occurs. All
other sensor and low voltage
devices are connected to the low
voltage terminal strip in the control
center. This discharge air sensor is
shipped loose and can be found in
the unit’s control center. See the unitspecific wiring diagram for connection
locations.
Plumbing / Piping Overview
Condensate Drain Trap
This unit is equipped with a stainless steel condensate
pan with a stainless steel connection. It is important
that the drain connection be fitted with a P trap to
ensure proper drainage of condensate while maintaining
internal static pressures.
A P trap assembly (kit) is supplied with each unit and
is to be assembled and installed as local conditions
require and according to the assembly instructions
provided with the P trap. If local
and area codes permit, the
condensate may be drained
back onto the roof, but a
drip pad should be provided
beneath the outlet. If local
and area codes require a
permanent drain line, it should
be fabricated and installed in
accordance with Best Practices
and all codes. In some climates, it will be necessary to
provide freeze protection for the P trap and drain line.
The P trap should be kept filled with water or glycol
solution at all times and it should be protected from
freezing to protect the P trap from damage. If severe
weather conditions occur, it may be necessary to
fabricate a P trap and drain line of metal and install a
heat tape to prevent freezing.
Model ERCH-HP Energy Recovery Unit
16
Optional Remote Control Panel
and Wiring Schematics
The remote panel is a series of junction boxes ganged
together and includes a stainless steel faceplate. The
remote panel is available with a number of different
alarm lights and switches to control the unit. The remote
panel ships loose and requires mounting and wiring in
the field
The remote panel is available with the following options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty lter light
• Economizer light
• Frost control light
• Wheel rotation sensor light
7-Day Timer or On/Off Switch
Indicator Lights powered by the ER Unit
R
C
G
Y1
Y2
W1
6
7
12
PS2
C
NCNO
PS3
C
NC
NO
Unit On/Off
Frost Control
Economizer
Rotation Sensor
Dirty Filter
Dirty Filter Indicator (power by others)
7-Day Timer
R
S1 - Unit On/Off
C
G
For 7-Day Timer, use blue and black wires.
Red wires should be capped off.
Hand/Off/Auto Switch
R
C
On
Off
Auto
BMS
G
Terminal Block
in Unit
Control Center
Terminal Block
in unit
Control Center
C
NC
NC
Hot
L1
NO
C
NO
Dirty Filter
Heating/Cooling Switches and Night Setback
Switch/Timer
R
C
S1
S6
S7
S4
Unit On/Off
Econ/First Stage Cooling
Second Stage Cooling
G
Y1
Y2
W1
6
7
12
Terminal Block
in unit
Control Center
Hand/Off/Auto Switch allows the unit to
“Off” - off
“On” - Manual Operation
“Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.
Night Setback Timer
S5
Night Setback Switch
Model ERCH-HP Energy Recovery Unit
A
17
Typical Control Center Components -individual components and locationswill vary
1. Main disconnect (non-fusible, lockable)
2. Motor starter - exhaust air fan
3. Motor starter - outdoor air fan
4. Motor contactor - energy wheel
5. 24 VAC control transformer
6. 24 VAC terminal strip
7. Fuses for blower motors
8. Grounding lug
9. Distributor block
10. Compressor fuse blocks
11. Terminal block
Optional Control Center Components
12. DDC controller
13. Dirty filter pressure switches
14. Economizer module
15. Thermostats for:
- Economizer module
- Energy recovery wheel frost control
16. Terminal block
17. Frost control pressure switch
18. Energy recovery wheel VFD
8
1
9
4
3
2
7
6
5
1716
15
14
Component #6
Detail of Terminal Strip
Refer to “Heat Pump System”
18
13
section for components in
compressor compartment
10
Model ERCH-HP Energy Recovery Unit
18
12
11
Electrical Controls
Optional Frost Control
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the enthalpy
wheel. Frost control is an optional feature that will
prevent/control wheel frosting. Three options are
available:
1. Timed Exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control
All of these options are provided with a thermostat (with
probe) mounted in the outdoor air intake compartment
and a pressure sensor to monitor pressure drop across
the enthalpy wheel. The typical temperature setting
corresponds to the indoor air relative humidity as
shown in the
Frost Threshold
Temperatures
table and
represents when
frost can occur.
An increase in
pressure drop
would indicate that frost is occurring. Both the pressure
sensor and the outdoor air temperature sensor must
trigger in order to initiate frost control. The two sensors
together ensure that frost control is only initiated
during a real frost condition. Field wiring of a light (or
other alarm) between 6 and C in the control center will
notify personnel when unit is in frost control mode.The
following explains the three options in more detail.
Timed exhaust frost control includes a timer in
addition to the thermostat and wheel pressure sensor.
When timed exhaust frost control is initiated, the timer
will turn the supply blower on and off to allow the warm
exhaust air to defrost the enthalpy wheel. Default factory
settings are 5 minutes off and 30 minutes on. Use the
following test procedure for troubleshooting.
Testing (refer to Timer diagram)
• Jumper the wheel
pressure switch
in the unit control
center. Set the Timer
Scale for T1 and T2
to 1 minute. Set the
Timer Settings for
T1 and T2 to 1.0.
Set the dip switch to
the down position.
(normal position)
Frost Threshold Temperatures
Indoor RH
at 70°F
20%-10º F
30%-5º F
40%0º F
T2
Timer
Scale
T1
Frost Threshold
Temperature
A1B115
0.60.8
0.41.0
0.20
T21 MIN
T11 MIN
0.60.8
0.41.0
0.20
1618A2
Dip
Switch
• Turn the temperature sensor up as high as
possible. The supply blower should cycle on for
one minute, then turn off for one minute.
• After testing, set the Timer Scale as follows:
T1 = 10 minutes, T2 = 1 hour
• Set the Timer Settings as follows:
T1 = 0.5, T2 = 0.5. The timer is now set for 5
minutes off and 30 minutes on. Remember to
remove the jumper.
Electric preheat frost control includes an electric
heater (at outdoor air intake) and an airflow pressure
switch (located at the preheater) in addition to the
thermostat and pressure sensor on wheel. When electric
preheat frost control is initiated, the electric preheater
will turn on and warm the air entering the energy wheel
to avoid frosting. Use the following test procedure for
troubleshooting.
Testing
• If no DDC controller is present, jumper thermodisc
and jumper the wheel pressure sensor. The heater
should turn on.
• If it doesn’t, either put the outdoor airside doors on
or temporarily jumper the airflow pressure switch
in the preheater control center to avoid nuisance
tripping of the pressure switch. Also check the
airflow switch pressure tap located at the supply
discharge blower to ensure the tubing is connected
and the tap is not blocked. Remember to remove
the jumpers.
Modulating wheel frost control includes a variable
frequency drive in addition to the thermostat and
pressure sensor. When modulating wheel frost control
is initiated, the variable frequency drive will reduce the
speed of the wheel. Reducing the speed of the energy
wheel reduces its effectiveness, which keeps the
exhaust air condition from reaching saturation, thus,
eliminating condensation and frosting. If the outdoor
air temperature is greater than the frost threshold
temperature OR the pressure differential is less than
the set point, the wheel will run at full speed. If the
outdoor air temperature is less than the frost threshold
temperature AND the pressure differential is greater
than the set point, the wheel will run at reduced speed
until the pressure differential falls below the set point.
The temperature and pressure differential set points are
set at the factory, but are field-adjustable. The variable
frequency drive will be fully programmed at the factory.
Timer
Model ERCH-HP Energy Recovery Unit
19
Optional Economizer
The energy wheel operation can be altered to take
advantage of economizer operation (free cooling). Two
modes are available:
1. De-energizing the wheel.
2. Modulating the wheel.
A field-supplied call for cool (Y1) is required. Deenergizing the wheel is accomplished with a signal
from a temperature or enthalpy sensor mounted in
the air intake compartment. This primary sensor will
de-energize the energy wheel when the outdoor air
temperature (factory default is 65ºF) or enthalpy (factory
default is the ‘D’ setting) is below the field adjustable set
point. An override temperature sensor is also furnished
in the outdoor air intake compartment to deactivate
economizer mode. The override (with field adjustable set
point) is set at some temperature lower than the primary
sensor (factory default is 50ºF). Effectively, the two
sensors create a deadband where the energy recovery
wheel will not operate and free cooling from outside can
be brought into the building unconditioned.
Testing
Temperature Sensor with Override
• Turn both temperature and override thermostats
down as low as they go. The wheel should be
rotating.
• Turn the temperature sensor up as high as it goes,
and keep the override sensor as low as it will go.
The wheel should stop rotating.
• Turn both sensors as high as they will go. The
wheel should start rotating.
• Set the temperature sensor at desired point for
economizer operation to begin. Set the override
sensor at desired point for economizer operation to
end (factory default is 65ºF and 50ºF, respectively).
Enthalpy Sensor with Override
• Turn unit power off. Disconnect C7400 solid state
enthalpy sensor from terminal So on the enthalpy
controller. Also, disconnect the 620 ohm resistor
from terminal Sr on the enthalpy
controller. Turn unit power on. The
LED on the enthalpy controller
should light and the energy recovery
wheel should not rotate.
• Turn unit power off. Reconnect
620 ohm resistor to terminal Sr on
the enthalpy controller. Turn unit
power on. The LED on the enthalpy
controller should not light and
the energy recovery wheel should
energize and rotate.
If the steps above provide the results described, the
enthalpy economizer is working properly.
• Turn unit power off. Reconnect C7400 solid state
enthalpy sensor to terminal So.
Enthalpy
Controller
Modulating the wheel: In applications in which an
internal heat gain is present in the space, the rotational
speed of the energy wheel may be modulated (via
variable frequency drive) to avoid overheating the space
during the winter. The speed of the energy wheel will be
controlled in response to the discharge temperature set
point.
Sequence of operation: The variable frequency drive
is fully programmed at the factory. A “call for cool” must
be field wired to the unit (terminals provided in unit refer to wiring diagram in unit control center) to allow for
initiation of economizer mode. When the space calls for
cooling, factory supplied controls will drive the following
wheel operations:
Where (T
(T
) is the return air temperature set point, and (T
RA
) is the outdoor air temperature set point,
OA
SA
) is
the supply air discharge thermostat set point.
TAO > T
T
< T
AO
and
T
> T
AO
< T
T
AO
and
T
< T
AO
RA
RA
SA
RA
SA
Wheel runs at full speed.
(maximum energy recovery)
Wheel is stopped.
(no energy recovery)
Wheel will modulate to maintain
discharge temperature.
Phase Monitor
The unit control circuitry includes a phase monitor that
constantly checks for phase
reversal, loss of phase or a
power brownout. It requires
24 VAC to operate and when
it detects a fault, it cuts off the
24 VAC that goes to the low
voltage terminal strip, thereby
shutting off all motors.
Typical Phase Monitor
Variable Frequency Drive (VFD)
If a VFD was provided and installed at the factory, it has
been preset to control the speed of the blower motor for
optimum performance. The motor speed needs to be
verified during test and balance of the unit.
Typical Variable Frequency Drive (VFD)
Refer to unit-specific documentation.
Model ERCH-HP Energy Recovery Unit
20
Optional Rotation Sensor
The rotation sensor monitors energy wheel rotation. If
the wheel should stop rotating, the sensor will close a
set of contacts in the unit control center. Field-wiring of
a light (or other alarm) between terminals R and 12 in
the unit control center will notify maintenance personnel
when a failure has occurred.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit control
center. Field-wiring of a light (or other alarm) to these
contacts will notify maintenance personnel when
filters need to be replaced. The switch has not been
set at the factory due to external system losses that
will affect the switch. This switch will need minor field
adjustments after the unit has been installed with all
ductwork complete. The dirty filter switch is mounted in
the exhaust inlet compartment next to the unit control
center or in unit control center.
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’
of the switch. (senses pressure at air inlet side of filters)
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch. Open the filter compartment and
place a sheet of plastic or cardboard over 50% of the
filter media. Replace the filter compartment door. Check
to see if there is power at the alert signal leads. Whether
there is power or not, turn the adjustment screw on the
dirty filter gauge (clockwise if you did not have power,
counterclockwise if you did have power) until the power
comes on or just before the power goes off. Open the
filter compartment and remove the obstructing material.
Replace the door and check to make sure that you do
not have power at the alert signal leads. The unit is now
ready for operation.
Model ERCH-HP Energy Recovery Unit
21
Energy Wheel
Retaining
Screws
Start-Up
If selected, the energy wheel is installed in the unit’s
airstream with one half of the wheel in the intake
airstream and one half in the exhaust airstream. Air
leakage between the two airstreams has to be kept to
a minimum and the wheel has air seals that must be
adjusted for that purpose. The seals must be adjusted
at time of start-up. The wheel can be accessed through
the door labeled Energy Wheel Access.
should be a slight tug on the paper. Tighten the screws,
repeat the steps on the other set of seals.
Push the wheel cassette back into the unit and plug
in the power connector. Turn the main power supply
back on and then observe the operation of the wheel by
opening the wheel access door slightly. Remove filters if
necessary to observe the wheel.
Bearing Support
Adjustable
Air Seals
Label showing
cassette serial number
and date code
Drive Belt
Drive Pulley
Drive Belt
Inspect the drive belt. Make
sure the belt rides smoothly
in the pulley and around the
outside of the wheel. Note
the directional arrow and
data information shown in the
image.
Motor Pulley and Belt
Adjust the Air Seals
The first step in wheel seal adjustment is to make sure
the unit power supply is locked out. Disconnect the
wiring to the wheel module and pull the wheel cassette
out of the cabinet on its tracks. Large cassettes are not
removable. Then slowly rotate the wheel by hand to
make sure there is no binding or
misalignment. The wheel should
rotate smoothly and should not
bind.
There is a perimeter seal located
around the outside of the wheel
and a diameter seal across the
face of the wheel on both sides.
Check to make sure that all air
seals are secure and in good
condition.
Adjust the air seals by loosening
all the air seal retaining screws
on the bearing support (see
image for reference). Using a
piece of paper as a feeler gauge,
adjust the seals so they almost
touch the face of the wheel while
tugging slightly on the paper.
When the wheel is rotated, there
Bearing Support Bar
showing air seal assembly
Sequence of Operation
Optional Economizer - The economizer will be locked
out when: the outside air is <40°F (- 2°F hysteresis,
adjustable); the unit is operating in dehumidification
mode; or there is a call for heating.
• Stop Wheel: When economizer mode is enabled
and there is a signal for cooling, the wheel will stop
rotating to allow free cooling.
• Modulate Wheel: When economizer mode is
enabled and there is a signal for cooling, the
wheel VFD modulates wheel speed to maintain the
discharge temperature set point.
Optional Frost Control - The DDC controller will
output a signal when wheel frosting is occurring which
is determined by a temperature set point (OA <5°F –
2°F hysterisis, adjustable) and wheel pressure drop
increase.
• Preheat: When frosting is occurring, the preheater
is energized to defrost the wheel. Once the
pressure drop decreases below the set point, the
preheater is de-energized.
• Timed Exhaust: When frosting is occurring, the
supply blower is cycled off. The exhaust blower
shall continue to run, allowing the warm exhaust
air to defrost the wheel. After the 10 minute cycle,
the supply fan are re-energized to continue normal
operation.
Alarms Indication - DDC shall have one digital output
for remote indication of an alarm condition.
• Wheel Rotation Alarm: Monitors wheel rotation,
and sends a signal to controller (after a 15 second
time delay with no rotation) that signals the DDC to
activate an alarm.
22
Model ERCH-HP Energy Recovery Unit
Energy Wheel Maintenance
WARNING
Whenever performing maintenance or inspections,
always disconnect the power source.
Inspection
The wheel should be inspected semiannually
in accordance with the maintenance schedule.
Maintenance of the wheel consists
mainly of inspecting the wheel
for cleanliness and then checking
the drive motor, belt, and pulley
for wear. If the wheel layers
appear dirty, the wheel should be
disassembled and cleaned.
The wheel rotates through the two
airstreams which are moving in
opposite directions, the wheel is
self-cleaning, up to a point. If the
wheel media becomes blocked by
dirt or dust, or if the media collects a layer of smoke
residue or an oily film, the energy transfer efficiency
drops.
The main factor in the frequency of cleaning is the
cleanliness of the air. If air filters are not changed
frequently, the wheel will collect contaminants and will
then have to be cleaned.
Wheel Disassembly
Wheels are part of a cassette that may be pulled from
the unit for easy access. There may be a small damper
assembly or other component that blocks removal of
the cassette. Before sliding out the cassette or any other
component, disconnect any power supply cord and
secure it so it cannot jam or otherwise get damaged.
Each wheel has removable segments that hold the
coated layers of media and each segment is held in
place with two retaining
clips located on the outer
rim of the wheel. When
removing more than one
segment, remove them in
sequence from opposite
sides of the wheel (180 degrees apart) to reduce the
imbalance. Secure the wheel against rotation. Carefully
release the two retaining clips and swing them fully
open. The segment can now be removed by pushing the
face of the segment close to the outer rim of the wheel.
Wheel segments are built to close tolerances and the
segment may have to be jiggled to remove it. Do not
use a hammer or otherwise force the segment because
these are high value items and are not built to withstand
abuse.
Whenever retaining clips are opened, they should be
closed as soon as possible. If the wheel should rotate
when a clip is open, the clip will jam against the bearing
support bar and could cause damage.
Energy Wheel
Cassette
Segment Retaining Clip
Cleaning
Maintenance or cleaning of the wheel segments
should be done with the segments removed from
the wheel cassette to avoid splashing liquids or
cleaning agents inside the cabinet. If the energy wheel
appears excessively dirty, it should be cleaned to
ensure maximum operating efficiency. Only excessive
buildup of foreign materials needs to be removed.
DISCOLORATION AND STAINING OF ENERGY
RECOVERY WHEEL DOES NOT AFFECT ITS
PERFORMANCE.
Thoroughly spray the wheel matrix with a household
cleaner such as Fantastik™ or the equivalent. Gently
rinse with warm water and use a soft brush to remove
any heavy accumulations. A detergent/water solution
can also be used. Avoid aggressive organic solvents,
such as acetone. Wheel segments can be soaked in the
above solution overnight for removal of stubborn dirt or
accumulations.
After cleaning is complete, shake excess water from the
wheel or segments. Dry the wheel or segments before
putting them back into the cassette.
Reassembly
When reinstalling the segments, be sure to install them
with the correct face toward the motor side of the
cassette. Note that one face of each segment is smooth
and the other face has a reinforcing channel or support
cut into the surface.
Wheel Segment
(Pulley Side)
Wheel Segment
(Motor Side)
Energy Recovery Wheel Belt
Inspect belts each time filters are replaced. Belts that
look chewed up or are leaving belt dust near the motor
pulley may indicate a problem with the wheel. Be sure to
inspect wheel for smooth and unrestricted rotation. If a
belt requires replacement, contact the local Greenheck
representative. Instructions for replacement will ship
with the new belt.
Energy Recovery Wheel Bearing
In the unlikely event that a wheel bearing fails, the
bearing is behind a removable plate on the wheel
support beam (slide cassette halfway out of cabinet to
access). Contact the local Greenheck representative for
detailed instructions on how to replace the bearing.
Model ERCH-HP Energy Recovery Unit
23
Energy Wheel Troubleshooting
SymptomPossible CauseCorrective Action
Air seals are too tight.
Energy wheel
does NOT turn
Energy wheel
runs intermittently
Broken belt.Replace.
No power to wheel motor.
Wheel motor overloads are tripping due to
rubbing between wheel and air seals.
Heat Pump Overview
Every unit has a complete, sealed refrigeration system
that is ready for connection to a water source.
The heat pump has all the typical DX components and
also has refrigerant reversing valve(s) to enable the
system to work in both heating and cooling modes.
Factory-Installed Heat Pump System
Components:
Thermostatic Expansion Valve (TXV)
Each compressor is equipped with a thermal expansion
valve. The valve controls the flow of liquid refrigerant
entering the evaporator coil by maintaining a constant,
factory set superheat of 10ºF.
Refrigerant Distributor
Attached to the TXV is a refrigerant distributor. The
refrigerant distributor evenly distributes the refrigerant
to each circuit of the airside coil to provide optimum
performance.
Airside Coil
Each unit uses a single refrigerant coil known as an
airside coil. If two compressors are used in the unit,
then the airside coil will be a split configuration so that
each compressor has a dedicated portion of the airside
coil. Depending on whether the unit is in cooling or
heating mode, the airside coil will function as either
a condensing coil or an evaporator coil. See also
Subassemblies/Coils.
Coaxial Refrigerant-to-Water Heat Exchanger
The unit uses one coaxial heat exchanger per
compressor, essentially a tube inside a tube. Water
flows through the inner copper tube and compressed
refrigerant is forced through the spaces between the
inner and outer tubes. Depending on whether the unit
is functioning in a cooling or a heating capacity, heat is
rejected from one tube to the other.
See air seals under Start-Up, Energy Wheel
section.
Make sure wheel drive is plugged in. Verify
power is available.
Recheck air seals, make sure they are not too
tight. See Adjust the Air Seals under Start-Up,
Energy Wheel section.
Liquid Line Filter Drier
The liquid line filter drier prevents moisture and foreign
matter from entering the thermal expansion valve. It is
located in the compressor compartment.
Hot Gas Bypass Valve
On units equipped with hot bypass, hot gas from the
compressor is injected into the liquid line of the airside
coil after the TXV. This process starts when suction gas
temperatures drop below 28ºF, which is 32º–34ºF coil
surface temperature. Hot gas helps the airside coil from
freezing up and the compressor from cycling. The valve
is factory set, but should be field adjusted to maintain a
suction pressure of 90 psi.
Valve Adjustment: To adjust the valve, connect
a pressure gauge to the suction line and block the
entering air to the coil. The valve should begin to open
when the suction pressure drops to approximately
58 PSIG (the valve will feel warm to the touch).
Adjustments are made by first removing the cap
on the valve and then turning the adjusting stem
counterclockwise to decrease the pressure. Allow
several minutes between adjustments for system to
stabilize. When adjustment is complete, replace the
cap on the valve.
Reversing Valve
Each compressor is equipped with a reversing valve
to reverse the direction of refrigerant flow. The valve is
electrically actuated.
Access Ports
For easy measurement and charging access, several
ports are provided throughout the system. These can be
used to measure system pressures and also charge or
evacuate the system.
Model ERCH-HP Energy Recovery Unit
24
Heat Pump Controls
Each unit is factory provided with a Unit Protection
Module (UPM) that controls compressor operation and
monitors the safety controls that protect the unit. The
UPM is a printed circuit board and is found in the heat
pump module.
Safety controls include the following:
• High pressure switch located in the refrigerant
discharge line and wired across the HPC terminals
on the UPM.
• Low pressure switch located in the unit refrigerant
suction line and wired across terminals LPC1 and
LPC2 on the UPM.
The UPM includes the following features:
Anti-Short Cycle Timer
Five minute delay on break timer to prevent compressor
short cycling.
Random Start
Each controller has a unique random start delay ranging
from 270 to 300 seconds to reduce the chances
of multiple units simultaneously starting after initial
power up or after a power interruption, creating a large
electrical spike.
Low Pressure Bypass Timer
The low pressure switch is bypassed for 120 seconds
after compressor start-up to prevent nuisance low
pressure lockouts during cold start-up in the heating
mode. If the low pressure switch remains opened after
120 seconds, the unit enters a soft lock.
Brownout/Surge/Power Interruption Protection
The brownout protection in the UPM board will shut
down the unit if the incoming power falls below 18VAC.
The unit will remain off until a minimal incoming power
of 18 VAC is detected. Once proper power is restored,
the unit will start-up within the random start time period.
Malfunction Output
The controller has a set of wet contacts for remote fault
indication or dry contacts for communication with a
DDC controller or BMS. The fault output will depend on
the dip switch setting for “ALARM”. If set to “CONST”, a
constant signal will be produced to indicate a fault has
occurred and the unit requires inspection to determine
the type of fault. If it is set to “PULSE”, a pulse signal
is produced and a fault code is detected by a remote
device indicating the fault. The remote device must have
a malfunction detection capability when the UPM board
is set to “PULSE”.
Test Dip Switch
A test dip switch is provided to reduce all time delay
settings to five seconds during troubleshooting or
verification of unit operation. Note that operation of the
unit while in test mode can lead to accelerated wear and
premature failure of the unit. The “TEST” switch must be
set back to “NO” for normal operation.
Freeze Sensor
This is optional and can be set to ignore or monitor a
freeze sensor. There are two configurable freeze points,
35°F and 15°F. The unit will enter a soft lockout until the
temperature climbs above the set point and the antishort cycle time delay has expired.
NOTE
If unit is employing a fresh water system (no antifreeze protection), it is extremely important to have
the “Freeze” switch set to 35°F in order to shutdown
the unit at the appropriate leaving water temperature
and protect your heat pump from freezing if a freeze
sensor is included.
Crankcase Heater
A crankcase heater is installed around the base of each
compressor in the unit to boil-off any liquid refrigerant
that may be absorbed into the oil during idle periods. It
is recommended the heater operate 24 hours prior to
the compressors being started.
Before Airside CoilHot Vapor130°F250 PSIG50°F Superheat
Heating
Mode /
Refrigerant
Properties
After Airside CoilWarm Liquid65°F250 PSIG15°F Subcool
After Thermostatic
Expansion Valve
After water-to-refrigerant
heat exchanger
Water entering the coaxial heat exchanger is cooled because of the heat being absorbed by the refrigerant and
leaves about 6°F warmer.
Hot Vapor150°F330 PSIG50°F Superheat
Warm Liquid85°F330 PSIG15°F Subcool
Saturated LiquidVapor mix
Saturated LiquidVapor mix
Cold Vapor45°F120 PSIG10°F Superheat
-45°F144 PSIG
-35°F120 PSIG
Model ERCH-HP Energy Recovery Unit
26
Unit Protection Module (UPM)
Fault Indications
Each unit includes one Unit Protection Module (UPM)
printed circuit board and each UPM has two LED
indictor lights.
LED
Color
Green
Power LED indicates 18-30 VAC present at
the board
Dual or
Single
Compressor
Dual
Compressor
LED Fault Indication
# of
blinks
High pressure lockout
1
Compressor 1
Low pressure lockout
2
Compressor 1
High pressure lockout
3
Compressor 2
Low pressure lockout
4
Compressor 2
Freeze sensor lockout
5
(optional item)
Status
Condensate overflow
Red
6
in coil drain pan
(optional item)
Brownout AC voltage
7
to R and C terminal
below 18 VAC
1High pressure lockout
2Low pressure lockout
Freeze sensor lockout
3
(optional item)
Single
Compressor
Condensate overflow
4
in coil drain pan
(optional item)
Brownout AC voltage
5
to R and C terminals
below 18 VAC
Lockout Reset
A hard lockout can be reset by turning the unit
thermostat off and then back on when the “RESET” dip
switch is set to “Y” or by shutting off unit power at the
circuit breaker when the “RESET” dip switch is set to
“R”.
Your UPM board will come
from the factory with the
following default settings:
Default Settings
FreezeNO
Temp35°
Lockout2
ResetT
AlarmCONT
TestNO
Hot/Dry AlarmHOT
Intelligent Reset
If a fault condition is initiated, the five minute delay
on break time period and the random start timer is
initiated and the unit will restart after these delays
expire. During this period the fault LED will indicate
the cause of the fault. If the fault condition occurs 2 or
4 times (depending on 2 or 4 setting for Lockout dip
switch) before 60 minutes, the unit will go into a hard
lockout and requires a manual lockout reset. A single
condensate overflow fault will cause the unit to go into
a hard lockout immediately, and will require a manual
lockout reset.
Model ERCH-HP Energy Recovery Unit
27
Troubleshooting - Controller Alarms
The first step in troubleshooting the unit is to check
the on-board alarm indicators. Several of the electronic
controls in the unit monitor the system for faults and will
go into alarm, shutting down the unit or a single function
within the unit.
DDC Controller
Check the screen on the DDC for an alarm condition. If
the DDC is
in an alarm
condition, a
message will
show on the
DDC screen.
The DDC is located in the main control center. If the
DDC is in alarm condition, the alarm button will blink
red. Press the alarm button to see the specific condition
or to reset the DDC. Refer to the DDC Installation
Operations and Maintenance manual for detailed
information on fault codes and see the unit-specific
wiring diagram.
Phase Monitor
The phase monitor has two
LED indicator lights, one
red and one green. Green
indicates proper operational
status, red indicates the unit
has detected a fault and is in
alarm condition.
Variable Frequency Drive (VFD)
Variable frequency drives have a
display screen that will show an
alarm condition. If a fault such
as a voltage spike occurs, the
VFD will go into alarm and will
not reset until a hard restart is
performed. See the unit-specific
manufacturer’s manual supplied
with the unit. VFDs are located in
the main control center.
FX05 Furnace Controller
Present only if an indirect gas-fired furnace option is
present.
The FX05 furnace controller will display an alarm
condition if present. The controller will be found in the
furnace control cneter. See the
furnace installation, operation
and maintenance manual and
the controller manufacturer’s
unit-specific manul for further
information.
Model ERCH-HP Energy Recovery Unit
28
Troubleshooting – Airflow
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,
prior to contacting the factory, please determine the following information:
Unit #1Unit #2Unit #3Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Outdoor Air Fan Horsepower
Design Airflow
Outdoor Air
Measured Airflow
Outdoor Air
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Outdoor Air Fan Amp Draw
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in accordance
with SMACNA and AMCA guidelines.
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.Replace fuse or reset circuit breaker and check amps.
Defective motor or capacitor.Replace.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.
Motor starter overloaded.Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the
coil.
Check for On/Off switches. Check for correct supply
voltage.
Check for broken or loose belts. Tighten loose
pulleys.
Shorten wiring run to mechanical room or install a
relay which will turn unit on/off. Consult Factory for
relay information. Increase wire gauge size so that
resistance is .075 ohms or less.
Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.
Model ERCH-HP Energy Recovery Unit
29
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
CFM too high.Check cfm and adjust drives if needed.
Motor over amps
Low airflow (cfm)
Static pressures are higher or lower than design.
Blower rotation is incorrect.Check rotation and reverse if necessary.
Motor voltage incorrect.Check motor nameplate versus supplied voltage.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.Check for correct drives and rpm with catalog data.
Fan wheels are operating backwards.
Dirty filter.
Leaks in ductwork.Repair.
Elbows or other obstructions may be obstructing
fan outlet.
Belt slippage.Adjust belt tension.
Blower fan speed too high.
If higher, ductwork should be improved.
If lower, fan rpm should be lower.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Improve ductwork to eliminate losses using good
duct practices.
For 3-phase, direction can be reversed by
interchanging any two of the three electrical leads.
Follow cleaning procedures in Routine Maintenance
section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed if
necessary.
High airflow (cfm)
Excessive noise
or vibration
Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.
Loose motor or blower sheave.Tighten sheave setscrew.
Belts too loose.Adjust belt tension after 24 hours of operation.
Belts too tight.
Worn belt.Replace.
Motor base or blower loose.Tighten mounting bolts.
Buildup of material on wheel.Clean wheel and housing.
Bearing and drive misaligned.Realign.
Noise being transmitted by duct.
Induce Ps into system ductwork. Make sure grilles
and access doors are installed. Decrease fan speed if
necessary.
Adjust wheel and/or inlet cone. Tighten wheel hub or
bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.
Loosen to maintain a 3/8 inch deflection per foot of
span between sheaves.
Make sure ductwork is supported properly. Make
sure ductwork metal thickness is sized for proper
stiffness. Check duct size at discharge to ensure that
air velocities are not too high.
Model ERCH-HP Energy Recovery Unit
30
Troubleshooting – Refrigeration Circuit
TROUBLESHOOTING NOTE
IMPORTANT
Do not release refrigerant to the atmosphere! If
Before any components are changed on the
refrigeration system, the cause of the failure must be
identified. Further problems will exist unless the true
cause or problem is identified and corrected.
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by an EPA Certified Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.
SymptomPossible CauseCorrective Action
Open disconnect switch or circuit breaker.Close switch and / or breaker.
Check voltage to contactor coil, transformer, slave
relay, system. Replace parts as necessary.
Check for reason and repair. Replace fuse after
correcting problem.
Check line voltage. If more than 10% from
compressor marking, correcting is necessary.
Motor thermal protector automatically resets.
Allow time (2 hrs.) for compressor to cool down so
protector will reset. Restart and check for reason
overheat occurred.
Check motor for open circuit, short circuit,
grounded windings or burn out.
Compressor may be seized; check refrigerant.
If necessary, replace compressor.
Compressor
will not run
or
does not
try to start
Compressor contactor not closing.
Blown fuse or tripped breaker.
Low line voltage.
Compressor motor protector open.
Compressor defective.
If manual reset (high pressure), reset switch.
(Switch opens at 600 psi and will not reset above
High or low pressure switch open or defective.
Open room thermostat or control
(no cooling required).
Loose wiring.Check all wire terminals and tighten as necessary.
Defective high or low pressure control.Check high or low pressure switch.
Liquid floodback.Possible tight bearings.
Compressor
short cycles
Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.
Defective expansion valve.Check thermal expansion valve and superheat.
Poor air distribution.Check ductwork for recirculating.
High discharge pressure.See “High discharge pressure”.
Leaking discharge valves in compressor.See “High suction pressure”.
Low airflow at evaporator(s).Check blower operation and airstream restrictions.
Incorrect unit selection (oversized).Contact factory.
Check condenser controls and reset to obtain
desired condensing temperature.
Model ERCH-HP Energy Recovery Unit
34
Troubleshooting – Refrigeration Circuit
SymptomPossible CauseCorrective Action
Low or no
oil pressure
Compressor
loses oil
Low oil level (trapped oil in evaporator or suction
line).
Excessive liquid refrigerant in the crankcase.
Worn oil pump.Replace the oil pump.
Worn compressor bearings.Replace the compressor.
Loose fitting on oil line or pump housing gasket
leaking.
Compressor short cycling.Check low pressure control setting.
Refrigerant leak.
Short cycling.Check low pressure control settings.
Refrigerant flood back.
Improper piping or traps.Verify proper piping slopes.
Reheat flush cycle inadequate.Contact factory.
Refrigeration undercharged.Check subcooling.
Thoroughly defrost evaporator. After defrost,
observe level, add oil. Check for leaks. Check lines
for proper slope and traps.
Adjust expansion valve for higher superheat. Check
crankcase heater.
Check and tighten system. Check bottom plate or
compressor.
Check system for leaks. Repair leaks and add
refrigerant.
Check thermal expansion valve setting. Check for
refrigerant overcharge.
Running cycle is
too long or unit
operates
continuously
Liquid line
is too hot
Liquid line is
frosted or wet
Suction line
is frosting
Dirty filter or evaporator coil.Check filter, coil and airflow.
Dirty or clogged condenser coil.Check coil and airflow.
Air or other non-condensables in system.
Defective compressor.See “High suction pressure”.
Restriction in suction and liquid line.Check for restrictions in refrigerant circuit.
Control contacts stuck.Check wiring.
Excessive load.Add more equipment or reduce room load.
Too low of a system thermostat setting or
defective thermostat.
Refrigerant undercharge.Adjust the charge by subcooling.
High discharge pressure.See “High discharge pressure”.
Restriction in liquid line.Clear restriction upstream of point of frosting.
Insufficient evaporator airflow.
Restriction in suction or liquid line.Restriction upstream of point of frosting.
Check equalized high side pressure with equivalent
outdoor temperature.
Adjust or replace thermostat.
Check airflow, check filters, check drive for loose
parts or belts.
Malfunctioning or defective expansion valve.Check bulb of thermal expansion valve.
Frost on
evaporator coil
Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.
Hot gas bypass valve not functioning properly.Check valve. If defective, replace.
Manual hot gas bypass valve closed.Open valve.
Model ERCH-HP Energy Recovery Unit
35
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
This unit requires minimal maintenance to operate
properly. To ensure proper operation and longevity, the
following items should be completed. The items in this
list assume a relatively clean air environment, and may
require attention more frequently in a dirty or dusty
area. If this unit contains an indirect gas heater, refer
to the Installation, Operation and Maintenance Manual
provided with the unit for maintenance purposes. A
Certified Technician should complete all refrigerant
systems checks.
Maintenance Frequency:
Monthly
1. External Filter
Check for cleanliness – clean if required
2. Internal Filter
Check for cleanliness – replace if required
3. Condensate Drain (if applicable)
Inspect and clean – rell with water
4. Bearings
Lubricate per the schedule in the Fan Bearings
section
Semiannually
1. Fan Belts
Check for wear, tension, alignment
2. Check for belt wear
Check pulley, bearings, and motor
3. Bearings
Lubricate per the schedule in the Fan Bearings
section
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit startup checklist provided in the manual to ensure the
refrigeration system operates in the intended matter.
1. Lubrication
Apply lubrication where required
2. Dampers
Check for unobstructed operation
3. Motors
Check for cleanliness
4. Fan Belts
Check for wear, tension, alignment
5. Blower Wheel & Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
6. Bearings
Lubricate per the schedule in the Fan Bearings
section
7. Door Seal
Check if intact and pliable
8. Wiring Connections
Check all connections for tightness
9. Inspect all coils for cleanliness. Clean if required.
10. Inspect exterior and interior of entire unit for
surface rust. If rust is found, remove rust and coat
the blemished area with an appropriate protectant.
Heat Pump
An annual inspection of the heat pump system by a
licensed refrigeration mechanic is recommended.
1. Inspect entire heat pump for cleanliness.
2. Record performance data for volts, amps and water
temperature differences (both heating and cooling).
3. Compare annual data to recorded start-up data.
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication.
Apply lubrication where required. Any components
showing excessive wear should be replaced to maintain
the integrity of the unit and ensure proper operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Fan Belts
Belts must be checked on a regular basis for wear,
tension, alignment, and dirt accumulation. Premature
or frequent belt failures can be caused by improper
belt tension (either too loose or too tight) or misaligned
sheaves. Abnormally high belt tension or drive
misalignment will cause excessive bearing loads and
may result in failure of the fan and/or motor bearings.
Conversely, loose belts will cause squealing on start-up,
excessive belt flutter, slippage, and overheated sheaves.
Both loose and tight belts can cause fan vibration.
Model ERCH-HP Energy Recovery Unit
36
When replacing belts on multiple groove drives, all belts
should be changed to provide uniform drive loading. Do
not pry belts on or off the sheave. Loosen belt tension
until belts can be removed by simply lifting the belts off
the sheaves. After replacing belts, insure that slack in
each belt is on the same side of the drive. Belt dressing
should never be used.
Do not install new belts on worn sheaves. If the sheaves
have grooves worn in them, they must be replaced
before new belts are installed.
The proper belt setting is the lowest tension at which
the belts will not slip under peak load operation. For
initial tensioning, set the belt deflection at 1/64-inch
for each inch of belt span (measured half-way between
sheave centers). For example, if the belt span is 64
inches, the belt deflection should be 1 inch (using
moderate thumb pressure at mid-point of the drive).
Check belt tension two times during the first 24hours of
operation and periodically thereafter.
Deflection =
Belt Span
Belt Span
64
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper motor cooling. Never
wash-down motor with high pressure spray. Greasing
of motors is only intended when fittings are provided.
Many fractional motors are permanently lubricated for
life and require no further lubrication.
Fan Wheel and Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Fan Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively clean
environment. Some bearings are relubricatable and will
need to be regreased depending on fan use. Check your
bearings for grease zerk fittings to find out what type
of bearing you have. If your fan is not being operated
under normal use, bearings should be checked monthly
for lubrication. Shaft bearings are the most critical
moving part of a fan. Therefore, special attention
should be given to keeping the bearings clean and well
lubricated. Proper lubrication provides for reduction in
friction and wear, transmission and dissipation of heat,
extended bearing life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper
grease applied at regular intervals is required. Refer to
the recommended bearing lubrication schedule:
In addition to lubricating the bearings at specified
intervals, set screws in the bearing collars should be
checked for tightness. A bearing collar which has
loosened will cause premature failure of the fan shaft.
Fasteners attaching the bearings to the drive frame
should also be checked.
Shaft Diameter in Inches
Model ERCH-HP Energy Recovery Unit
37
Internal Filter Maintenance
The unit will typically be provided with 2-inch, pleated
filters in the supply airstream. These filters should
be checked per a routine maintenance schedule
and replaced as necessary to ensure proper airflow
through the unit. Replacement filters shall be of same
performance and quality as factory installed filters. Filter
type must be pleated design with integral metal grid.
Two acceptable filter replacements are Aerostat Series
400 or Farr 30/30®.
Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the
access side of the unit.
Refer to Subassemblies/Filters section for additional
information on filter locations.
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate make-up air ventilator without the
filters and birdscreens installed. They prevent the entry
of foreign objects such as leaves, birds, etc.
Do not remove access panels or other unit
components while standing on a ladder or other
unsteady base. Access panels and unit components
are heavy and serious injury may occur.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
purchased). Filters should be checked and cleaned
on a regular basis for best efficiency. The frequency of
cleaning depends upon the cleanliness of the incoming
air. These filters should be cleaned by rinsing with a mild
detergent in warm water prior to start-up.
Filters upstream of the coil should be checked
regularly. If the filters are dirty, they should be cleaned
or replaced. It is important that the coils stay clean to
maintain desired airflow.
Coil Maintenance
Coils must be cleaned to obtain maximum performance.
Check once a year under normal operating conditions
and if dirty, brush or vacuum clean. Soiled fins reduce
the capacity of the coil, demand more energy from the
fan, and create an environment for odor and bacteria to
grow and spread through the conditioned zone. High
pressure water (700 psi or less) may be used to clean
coils with fin thickness over 0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil
to determine if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Many coil
cleaners contain harsh chemicals, so they must be used
with caution by qualified personnel only. Care must be
taken not to damage the coils, including the fins, while
cleaning. Caution: Fin edges are sharp.
WARNING
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel.
Drain pans in any air conditioning unit will have some
moisture in them, therefore, algae and other organisms
will grow due to airborne spores and bacteria. Periodic
cleaning is necessary to prevent this buildup from
plugging the drain and causing the drain pan to
overflow. Inspect twice a year to avoid the possibility
of overflow. Also, drain pans should be kept clean to
prevent the spread of disease. Cleaning should be
performed by qualified personnel.
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one
year from the shipment date. The energy recovery wheel is warranted to be free from defects in material and
workmanship for a period of five years from the shipment date. Any units or parts which prove defective during
the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors
are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service station.
Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Greenheck Catalog Energy Recovery Ventilator with Integral
Water Source Heat Pump, Model ERCH-HP, provides
additional information describing the equipment, fan
performance, available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at: www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.