Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Model VER
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components
may be hot enough to cause pain or injury. Allow
time for cooling before servicing.
CAUTION
Precaution should be taken in explosive
atmospheres.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces or
chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
VersiVent Energy Recovery Unit
1
Page 2
Receiving
Upon receiving the product, check to make sure
all items are accounted for by referencing the bill
of lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. A Carrier Inspection Report should be filled out
by the carrier upon arrival and the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle each piece in such a manner as to keep from
scratching or chipping the coating. Damaged finish
may reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to
prevent deterioration of the unit during storage.
The user assumes responsibility of the unit and
accessories while in storage. The manufacturer will
not be responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
Inspection and Maintenance during
Storage
While in storage, inspect units once per month. Keep
a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate all moving components by hand
ten to fifteen revolutions to distribute lubricant on
motor and bearings. If paint deterioration begins,
consideration should be given to touch-up or
repainting. Units with special coatings may require
special techniques for touch-up or repair.
Machined parts coated with rust preventive should
be restored to good condition promptly if signs of
rust occur. Immediately remove the original rust
preventive coating with petroleum solvent and clean
with lint-free cloths. Polish any remaining rust from
surface with crocus cloth or fine emery paper and oil.
Do not destroy the continuity of the surfaces. Wipe
clean thoroughly with Tectyl® 506 (Ashland Inc.) or
the equivalent. For hard to reach internal surfaces or
for occasional use, consider using Tectyl® 511M Rust
Preventive or WD-40® or the equivalent.
Special Owner’s Information for
Units with Packaged DX
The following summary highlights some important
notes to help avoid premature failure and possible
voidance of warranty.
Product Overview
Greenheck VER Models integrated with a complete
refrigerant system are designed with the purpose of
being a self-contained source for heating and cooling
in both commercial and institutional applications. This
is done in a highly efficient manner through the use of
a total enthalpy recovery wheel. The wheel allows the
compressors and cooling equipment to be downsized
in the unit, therefore being more cost effective to
operate. The DX system comes fully charged from the
factory with refrigerant and is ready for installation
upon arrival.
Units above seven (7) tons come standard with two
compressors. This allows for staging of compressors
to meet a wider range of outdoor air loads while
reducing the amount of cycles per compressor.
Integral Components
All units are provided with an expansion valve,
hermetic scroll compressor(s), liquid line filter drier,
high pressure manual reset cutout, low pressure autoreset cutout, time delays for compressor protection,
service/ charging valves, moisture indicating sight
glass, and hot gas bypass. The compressors also
come standard with a crankcase heater for additional
protection.
Shutdown Operation
The scroll compressors in this unit are designed
to compress gas refrigerant only. To prevent liquid
refrigerant from migrating into and damaging the
compressors, each compressor is supplied with a
crankcase heater. Prior to starting the compressors,
the heaters must have power to them for 24 hours.
Power should never be cut to these units unless the
complete shutdown procedure is followed.
Proper shutdown procedure:
1. Turn off main power supply to the unit
2. Turn thermostat controls to “off” position
3. Restore main power supply to the unit
4. Wait 24 hours prior to turning the thermostat
control to the “on” position.
VersiVent Energy Recovery Unit
2
Page 3
Low Ambient Operation
Low ambient operation can cause damage to the
refrigerant system. A factory-installed temperature
sensor in the outdoor air intake prevents refrigerant
system operation at ambient conditions below 55ºF.
Crankcase heaters will still be engaged provided the
main power has not been disconnected. If cooling
is desired at ambient temperatures below 55ºF,
economizer operation (wheel start/stop or wheel
modulation) should be employed.
Reduced Airflow
Pumping Oil and Liquid Refrigerant
Lack of maintenance will lead to filters, condensing
coils, and evaporator coils building up with dirt and
debris. As this occurs, the airflow through the unit
will decrease. Cooling coils are sized to handle a
particular airflow volume. A reduction in airflow can
cause the cooling coils to get too cold and may
result in excessive liquid refrigerant return to the
compressors. The liquid refrigerant buildup in the
compressors will displace the necessary oil required
for proper lubrication. The combination of these
two events will significantly reduce the life of the
compressors.
To maintain the proper airflow and system efficiency,
follow all procedures in the Maintenance section.
Safety Listing
The VER units are listed per ANSI/UL 1995, Heating
and Cooling Equipment, and bear the ETL label.
Environmental Concerns
When working with Greenheck’s fully charged
refrigerant system, it is strongly recommended that
caution is undertaken during installation, operation,
and routine maintenance. This caution will help ensure
that minimal amounts of refrigerant are leaked into
the atmosphere. To comply to the U.S. Clean Air
Act, anytime there is residual refrigerant, the proper
equipment shall be used and methods should be
followed to reclaim the refrigerant so that it can be
recycled, reprocessed, or destroyed.
IMPORTANT
Do not release refrigerant to the atmosphere! If
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified EPA Certified Technician.
Table of Contents
Basic Operation . . . . . . . . . . . . . . 4
Installation
Installation Concerns. . . . . . . . . . . . 4
Lifting . . . . . . . . . . . . . . . . . . 5
Recommended Roof Openings . . . . . . . 5
Unit Weights and Dimensions . . . . . . . . 6
Rail and Roof Curb Mounting
Rail Mounting and Layout . . . . . . . . . . 7
Roof Curb Mounting . . . . . . . . . . . . 7
Curb Dimensions and Weights . . . . . . . . 8
Electrical Information
General Electrical Information . . . . . . . . 9
Control Center Components . . . . . . . . . 10
Electric Heater Application/Operation . . . . . 10
Unit Accessories. . . . . . . . . . . . . . 10
Service Clearances . . . . . . . . . . . . 11
Access Panel Description. . . . . . . . . . 12
Component Location . . . . . . . . . . . . 13
Coil Applications . . . . . . . . . . . . . 14
Drain Trap Information . . . . . . . . . . . 15
Ductwork Connections . . . . . . . . . . . 15
Optional Accessories
Frost Control Application/Operation . . . . . 16
Economizer Application/Operation . . . . . . 17
Variable Frequency Drives and Wiring . . . .18 -19
Sensors and Lights . . . . . . . . . . . . 20
Sensors Mounted by Factory . . . . . . . . 21
Remote Control Panel and Wiring . . . . . . 22
Typical Wiring Diagram . . . . . . . . . 23-24
Sequence of Operation . . . . . . . . . . . 25
Start-Up
Unit . . . . . . . . . . . . . . . . . 26-28
Optional Accessories . . . . . . . . . . . 29
Fan . . . . . . . . . . . . . . . . . 30-31
Energy Recovery Wheel . . . . . . . . . . 31
Refrigeration System . . . . . . . . . . 32-33
Routine Maintenance Checklist
General . . . . . . . . . . . . . . . . . 34
Belts . . . . . . . . . . . . . . . . 34-35
Motors . . . . . . . . . . . . . . . . . 35
Fan Wheel and Fasteners . . . . . . . . . . 35
Fan Bearings . . . . . . . . . . . . . . . 35
Filters . . . . . . . . . . . . . . . . . . 36
Coil Maintenance . . . . . . . . . . . 36-37
Energy Recovery Wheel Maintenance
Accessing Energy Recovery Wheel . . . . . 37
Removing Wheel Segments . . . . . . . . 37
Cleaning Wheel Segments . . . . . . . . 37
Wheel Belts . . . . . . . . . . . . . . 37
Wheel Bearings . . . . . . . . . . . . . 37
Troubleshooting – Airflow . . . . . . . . . . 38
Troubleshooting – Unit . . . . . . . . . 39-40
Troubleshooting – Refrigeration Circuit . .41-45
Maintenance Log . . . . . . . . . . . 46-47
Warranty . . . . . . . . . . . . . Backcover
VersiVent Energy Recovery Unit
3
Page 4
Basic Operation
Installation
The VER units bring in fresh, outdoor air and remove
stale, exhaust air. Prior to discharging the exhaust air,
the energy recovery wheel transfers energy from the
exhaust air to the outdoor air at an efficiency of 7080%. Simply put, this unit preconditions the outdoor
air to save money on heating and cooling costs. These
particular units also have cooling and heating options
available after the recovery wheel to further condition
the fresh air.
Supplemental Installation,
Operation and Maintenance
Manuals
Refer to the following Installation, Operation and
Maintenance Manuals for additional details:
Part #463687 — Centrifugal Fan
Part #461006 — Indirect Gas-Fired Furnaces for
Energy Recovery Units, Model PVF
Part #469690 — Microprocessor Controller
Installation, Operation and Maintenance Manuals can
be found online at www.greenheck.com
General Installation, Operation and
Maintenance (IOM) Information
The VER model energy recovery unit is designed with
semi-custom versatility in mind. This quality allows for
the selection of several component options. Please
be aware that this IOM is comprehensive and includes
information for all the potential options offered for
this product line. Included options will vary on each
unit. Please pay special attention to the specific unit
in question when reviewing the information in this
manual.
The system design and installation should follow
accepted industry practice, such as described in the
ASHRAE Handbook.
Adequate space should be left around the unit for
piping coils and drains, filter replacement, and
maintenance. Sufficient space should be provided on
the side of the unit for routine service and component
removal should that become necessary.
See Service Clearances/Access Panel Locations
section for more details.
Installation Concerns for Units with
Packaged DX
Unobstructed airflow to the condensing section
must be maintained at all times to ensure proper
operating efficiency and capacity of the cooling
system. Unit placement should allow proper airflow
over the condensing section. The unit may not operate
properly and damage may occur to the system if there
is coil starvation (lack of air over condenser) or warm
air recirculating back through the condensing coil.
Recirculating air is caused when the unit is placed
near obstacles that can redirect exhaust air from
the condensing fans, back around to the coil inlet.
Overhangs or walls near the condensing section are
two examples.
Another consideration when placing the unit is
prevailing wind direction. The condensing coil
operation can be significantly affected when winds are
blowing continuously and directly at the condensing
coil. On hot days, the wind will help the system by
providing extra flow over the coil. But on cooler days,
that same wind may overcool the refrigerant, and
cause hot gas bypass to operate more frequently,
causing higher operating costs. Therefore, avoiding
direct winds will provide a more stable operation of
the system throughout the cooling season.
Lack of air over the coil can reduce efficiencies and
affect system operation. Do not allow debris (such as
leaves and trash), to accumulate on or near the unit.
Keeping debris clear of the unit will ensure minimal
obstruction to the coils, keeping efficiencies and
operation closer to design. The unit typically should
not operate when snow is present. In the event this
is possible, make sure all snow is clear of the coil and
condensing fans prior to operating the unit.
If more than one unit is being installed, make
provisions so discharge air from either the condensing
fans or exhaust fan of the unit do not discharge
towards another unit’s intake. Also, OA intake and
condensing sections should be spaced as too allow
proper airflow to each unit helping ensure the units
operate as intended.
VersiVent Energy Recovery Unit
4
Page 5
Where the supply or warm air duct passes thru a
E
G
H
F
A
B
C
D
Return Air Intake
Supply Air
Discharge
combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.
Handling Concerns for Units with
Packaged DX
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation. Exercise extreme
caution to prevent any damage from occurring to
the refrigerant system. This unit contains a system
pressurized with refrigerant that if damaged, could
leak into the atmosphere or cause bodily harm due
to the extreme cold nature of expanding refrigerant.
Use protective equipment such as gloves and safety
glasses to minimize or prevent injury in case of a
system leak during installation.
Lifting
1. Before lifting, be sure that all shipping material
has been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Unit Weights &
Dimensions section on page 6.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach
to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
Recommended Roof Opening
Refer to weight and dimension data to determine the
exact location of the section containing the outdoor
air discharge opening. If the unit is equipped with
an Indirect Gas Heater (IG) section the outdoor air
discharge opening will be in that section; if not, it will
be in the blower section. The return air intake will
be consistent for all units. The dimensions of these
openings and their locations are illustrated below.
All dimensions are in inches.
IG = Indirect Gas Furnace; PDX = Packaged DX Cooling
1 = Any unit without IG and PDX.
Blower Module is at the end of the unit.
2 = Any unit with IG that does not have PDX.
3 = Any unit with IG and PDX
4 = Any unit without IG and with PDX
When cutting only duct openings, cut opening one inch
(25 mm) larger than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof is
constructed of combustible materials, area within the
roof curb must be ventilated, left open, or covered with
non-combustible material which has an “R” value of at
least five. If area within curb is open, higher radiated
sound levels may result.
Where the supply or warm air duct passes thru a
combustible roof, a clearance of one inch must be
6. Always test-lift the unit to check for proper
balance and rigging before hoisting to desired
location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing has been applied
to the curb prior to lifting the unit and setting on
curb.
11. Do not use fork lifts for handling unit.
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A. Position the unit roof opening such that
the supply discharge and exhaust inlet of the unit will
line up with the corresponding ductwork. Be sure to
allow for the recommended service clearances when
positioning opening (see Service Clearances). Do not
face the outdoor air intake of the unit into prevailing
wind and keep the intake away from any other exhaust
fans. Likewise, position the exhaust discharge opening
away from outdoor air intakes of any other equipment.
All dimensions shown in inches.
*L Sum the lengths of the appropriate modules to get the total length of the unit.
^Weight: The weights shown are a worse case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal
weights added together with the largest fans, coils and heaters for the unit.
D1D2D3D4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
ABC
(lbs.)
4900
VersiVent Energy Recovery Unit
6
Page 7
Rail and Roof Curb Mounting
AB CD
Return Air
Intake
Supply Air
Discharge
Rails are positioned in random places.
See table for proper location
beyond the unit a minimum of 12 inches on each
side.
• Setunitonrails.
Isometric View
Roof Curb Mounting
Roof curb details, including duct location dimensions,
are available on VER roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1. Factory Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a
knockdown kit (includes duct adapter) and require
field assembly (by others). Assembly instructions
are included with the curb.
2. Install Curb
Locate curb over roof opening and fasten in place.
(Refer to Recommended Roof Openings). Check
that the diagonal dimensions are within ±1/8 inch of
each other and adjust as necessary. For proper coil
drainage and unit operation, it is important that the
installation be level. Shim as required to level.
3. Install Ductwork
Installation of all ducts should be done in
accordance with SMACNA and AMCA guidelines.
Duct adapter provided to support ducts prior to
setting the unit.
4. Set the Unit
Lift unit to a point directly above the curb and duct
openings. Guide unit while lowering to align with
duct openings. Roof curbs fit inside the unit base.
Make sure the unit is properly seated on the curb
and is level.
Side View
Unit SizeABCD
VER-4553.316
VER-6558.116
VER-90 105.316
All dimensions shown in inches.
IG = Indirect Gas
CS = Condensing Section
33.8 w/IG
27 w/o IG
31.0 w/IG
30 w/o IG
33.8 w/IG
34 w/o IG
9.2 IG w/o CS; 37.1 IG w/CS
5.2 w/o IG and CS
33.1 w/o IG and w/ CS
9 IG w/o CS; 36.9 IG w/CS
4.6 w/o IG and CS
32.5 w/o IG and w/ CS
9.2 IG w/o CS; 37.1 IG w/CS
3.7 w/o IG and CS
31.6 w/o IG and w/ CS
VersiVent Energy Recovery Unit
7
Page 8
4-inch Final Filters
2-inch Filters
2-inch Filters
Wheel Cassette
Outdoor Air Hood
Intake
Section
Wheel
Section
Optional
Coil Section
Blower
Section
Optional
IG Heater Section
Optional
Condensing Section
Condensing Coil
Drain Pan ConnectionIG Gas Connection
ABC*D
L*
EF
Curb Outside Dimensions and Weights
Side of Unit
Recommended
2-inches of
Insulation
Roof Curb
1 in .
1 in .
2½ in.
1.195 in.
1 in .
W - 3.75 inches
L* - 3.75 inches
Elevation View
Subtract 3.75 inches from dimensions
W & L* to get the outside curb dimensions.
All dimensions shown in inches.
L* — Sum up the applicable section dimensions (A–F) for your unit to get the overall length.
^ — Curb weights shown are for the worst case scenario (largest curb) possible for each size unit.
C* Coil Module Options
C1C2C3C4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
DX + EH + HGRH
HW = Hot WaterEH = Electric Heat
CW = Chilled WaterHP = Wrap-around Heat Pipe
DX = Direct ExpansionHGRH = Hot Gas Reheat
Curb Cap Details
VersiVent Energy Recovery Unit
8
Page 9
Electrical Information
The unit must be electrically grounded in accordance
with the current National Electrical Code, ANSI/NFPA
70. In Canada, use current CSA Standard C22.1,
Canadian Electrical Code, Part 1. In addition, the
installer should be aware of any local ordinances or
electrical company requirements that might apply.
System power wiring must be properly fused and
conform to the local and national electrical codes.
System power wiring is to the unit main disconnect
(door interlocking disconnect switch standard on most
units) or distribution block and must be compatible
with the ratings on the nameplate: supply power
voltage, phase, and amperage (Minimum Circuit
Amps - MCA; Maximum Overcurrent Protection MOP). All wiring beyond this point has been done by
the manufacturer and cannot be modified without
affecting the unit’s agency / safety certification.
If field installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and
size according to the rating plate.
Field Power Connection: All power and control
connections should be run through the floor or side
panel.
CAUTION
The VersiVent Roof lining contains high voltage
wiring. To prevent electrocution do not puncture the
interior or exterior panel of the roof.
If power supply is desired through bottom of unit, run
the wiring through the curb, cut a hole in the cabinet
bottom, and wire to the disconnect switch. Seal
penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent
requirements for the system to operate properly.
Voltage supply and voltage imbalance between
phases should be within the following tolerances.
If the power is not within these voltage tolerances,
contact the power company prior to operating the
system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at
all line disconnect switches. Readings must fall within
the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive
voltage imbalance between phases will cause motors
to overheat and eventually fail. Maximum allowable
imbalance is 2%. To determine voltage imbalance, use
recorded voltage measurements in this formula.
Key:V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with wiring material having a temperature rating of
at least 105ºC.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the
power supply, turn off the gas.
Most factory supplied electrical components are
pre-wired. To determine what electrical accessories
require additional field wiring, refer to the unit specific
wiring diagram located on the inside of the unit
control center access door. The low voltage control
circuit is 24 VAC and control wiring should not exceed
0.75 ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft.18
200 ft.16
300 ft.14
450 ft.12
Minimum
Wire Gauge
Control wires should not be run inside the same
conduit as that carrying the supply power. Make sure
that field supplied conduit does not interfere with
access panel operation.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit
control center and wired in place of the remote
switch (typically between terminal blocks R and G
on the terminal strip (refer to Typical Control Center
Components). The relay must be rated for at least
5 amps and have a 24 VAC coil. Failure to comply
with these guidelines may cause motor starters to
“chatter” or not pull in which can cause contactor
failures and/or motor failures.
Note: Standard factory installed electric post-
heaters have their own disconnect separate
from the unit disconnect. Thus, each electric
post-heater requires its own separate power
connection.
VersiVent Energy Recovery Unit
9
Page 10
Control Center Components
1
8
7
5
6
18
9
2
3419
17
16
11
12
10
13
15
14
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter - Exhaust Air Fan
3. Motor Starter - Supply Air Fan
4. Motor Contactor - Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors*
8. Grounding lug
9. Distributor block*
10. Compressor fuse blocks*
11. Compressor contactors*
12. Condensing fan contactors*
13. Compressor relay*
14. Terminal block*
15. Compressor cycle timers*
Optional Control Center Components
16. DDC controller*
17. Dirty filter pressure switches*
18. Terminal block
19. Energy recovery wheel VFD*
*Not always provided
Electric Heater Application/Operation
Factory installed electric heaters can be provided for
preheat and/or post-heat. An electric preheater warms
the outdoor air prior to the energy recovery wheel to
prevent frosting on the wheel. An electric post-heater
warms the air leaving the energy recovery wheel to a
user specified discharge temperature. Electric heaters
are available in 208, 230, or 460 VAC (refer to heater
nameplate for voltage).
Preheaters: Preheaters are standard as two-stage
step control. Step control heaters are designed with
multiple stages made up of equal increments of
heating capability. For example a 10 kW heater with
two stages will be composed of two 5 kW stages.
Preheaters are single point wired at the factory.
A temperature sensor (with field adjustable set
point) is mounted in the outdoor airstream after the
preheater to turn the preheater on. See Frost Control
Application/Operation for typical set points. If the
temperature falls below the set point and the wheel
pressure drop sensor is triggered, the first stage of the
preheater will turn on. If the first stage does not satisfy
the set point, the second stage will also turn on.
The pre-heater is single point wired to the VER control
center. Access to the preheater control panel is
through the outdoor air intake.
Post-heaters: Post-heaters are standard as SCR
control. Post-heaters are not single point wired (see
Electrical Connections). A temperature sensor (with
field adjustable set point) is mounted in the outdoor
airstream after the post-heater. A SCR heater provides
an infinitely modulating control of the heat to provide
an accurate discharge temperature. A call for heat is
required to turn the post-heater on.
The post-heater is not single point wired to the VER
control center. Separate power must be supplied to
the post-heater disconnect located in the unit control
center.
10
VersiVent Energy Recovery Unit
Unit Accessories
Outdoor Air Weatherhood
Outdoor air weatherhood will be
factory mounted.
Exhaust Weatherhood
The exhaust weatherhood is shipped
separately as a kit with its own
instructions.
Dampers
Backdraft dampers are always
included as an integral part of the
exhaust hood assemblies. Motorized
outdoor air and exhaust air dampers
are optional and are factory mounted
(and wired) at the intake.
Page 11
Service Clearances
TL
TRTR
TL
TR
TL
TR
TL
TRTR
TL
TL
TR
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
A
B
C
D
VER-90
ONLY
VER-45, 65 and 90 units require minimum clearances
for access on all sides for routine maintenance. Filter
replacement, drain pan inspection and cleaning,
energy wheel cassette inspection, fan bearing
lubrication and belt adjustment are examples of
routine maintenance that must be performed. Blower
and motor assemblies, energy recovery wheel
cassette, coil and filter sections are always provided
with a service door or panel for proper component
access. Clearances for component removal may be
greater than the service clearances, refer to drawings
for these dimensions.
Additional clearances for units with
packaged DX
Clearances must be maintained on all sides of
this unit. This especially is true with the top of
this unit. Hot air is being discharged through the
condensing fans during operation, and the more
clearance available, the better the chance of avoiding
recirculation or coil starvation. This unit should never
be placed under an overhang or inside a building. A
minimum of 48 inches over the condensing fans is
recommended.
Minimum 48 inches
clearance
Minimum 24 inches
Condensing Coil Intake
clearance
Keep this area clear
Unit Clearances
Unit SizeABCD
VER-4565423624
VER-6570423624
VER-9065426524
All dimensions shown in inches.
Access Panels may change depending on options
selected.
VersiVent Energy Recovery Unit
11
Page 12
Access Panel Descriptions and
Locations
Following is a list of items accessible through the
access doors shown on the diagrams. Some items are
optional and may not have been provided.
#8 – Supply Blower
#9 – Compressors
8
#6 – Control Panel
#2 – OA Intake Damper
and Electric Preheat
2
3
4
1
9
9
#7 – IG Furnace
Control Center
1. Aluminum mesh filters (intake hood)
2. Outdoor air intake damper
Electric pre-heater
3. Exhaust blower, motor, and drives
4. Energy recovery wheel, motor, belt, and seals
Exhaust air filters
Exhaust air intake damper (optional)
Outdoor air filters
Frost control sensors (optional)
Economizer sensors (optional)
Coil Application Recommendation
for Units with Heating or Cooling
Options
Factory installed cooling and heating components
are mounted in the coil section of the unit. The coil
section is downstream of the energy wheel on the
supply air side of the unit.
Note the coil connection
locations on the picture.
Coil connections are
located external to
the unit as shown.
Coil connections that
are not external have
been ordered from the
factory with interior coil
connections.
Note: DX coil liquid
connection is internal to
units.
Water Coils
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Water connections are
male NPT iron pipe. When installing couplings,
do not apply undue stress to the connection
extending through the unit. Use a backup pipe
wrench to avoid breaking the weld between coil
connection and header.
2. Connect the water supply to the bottom
connection on the air leaving side and the water
return to the top connection on the air entering
side. To insure proper venting, an external air
vent in the piping is recommended. Connecting
the supply and/or return in any other manner
will result in very poor performance. Be sure to
replace factory installed grommets around coil
connections if removed for piping. Failure to
replace grommets will result in water leakage into
the unit and altered performance.
3. The air vent at the uppermost point should be
temporarily opened during system start-up to
release all of the air from the coil. To maintain heat
transfer capacity, periodically vent any air in coil.
4. Water coils are not normally recommended for
use with entering air temperatures below 40ºF;
however, the energy recovery wheel maintains
a pre-coil temperature higher than 40ºF. No
control system can be depended on to be 100%
safe against freeze-up with water coils. Glycol
solutions or brines are the only safe media for
operation of water coils with low entering air
conditions.
Continuous water circulation through the coil at all
times is highly recommended.
5. Pipe sizes for the system must be selected on the
Water
Coil
Connections
basis of the head (pressure) available from the
circulation pump. The velocity should not exceed
6 feet per second and the friction loss should be
approximately 3 feet of water column per 100 feet
of pipe.
6. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. Refer to Drain Trap
section.
Direct Expansion (DX) Coils for units with a split
DX System
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should
not be applied at the connection to coil headers.
2. When connecting suction and liquid connections,
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage.
Be sure to replace factory installed grommets
around coil connections if removed for piping.
Direct Expansion (DX) Coil for units with
Packaged DX System
1. The condensate drain pipe should be sized
adequately to ensure the condensate drains
properly. Refer to Drain Trap section.
VersiVent Energy Recovery Unit
14
Page 15
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Length of Straight Duct
GOOD
POOR
GOODPOOR
Turning
Vanes
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
Drain Trap
4 in.
2 in.
Ductwork Connections
Cooling coils are provided with a stainless steel drain
pan with 1-inch male NPT drain connection. A drain
trap must be connected to the drain connection to
allow excess water to flow out of the drain pan. More
importantly, though, due to the negative internal static
of the cooling coil compartment, installing the drain
trap prevents outdoor air from being pulled into the
drain pan and consequently forcing water out of the
pan and into the unit.
To ensure the drain trap works properly, the trap
height must account for the difference in static
pressure between ambient conditions outside the
unit and the internal negative pressure of the cooling
coil compartment. For energy recovery units, an
assumption of 3.0 in. wg differential will be sufficient.
This would require a trap design as shown. If the
internal static is believed to be higher, consult factory.
Supply Fan:
The supply fan in this unit is a plenum style fan. The
discharge opening dimensions are provided. For
proper fan performance, match the duct size to the
dimensions listed. Installation of all ducts should be
done in accordance with SMACNA.
Supply Fan Discharge Opening Dimensions
Supply Air
Model
Discharge Location
TopEndBottom
VER-45 38.5 x 30 41.8 x 27
VER-6550 x 3150 x 31
VER-9062 x 3459.7 x 35
All dimensions shown in inches.
See diagram in Recommended Roof Openings section (page 5)
*
for the Bottom Discharge opening sizes.
*
*
*
Length of
Straight Duct
(Supply Fan)
48
60
60
Exhaust Fan
The exhaust fan in this unit is a forward curved fan.
Good and Poor fan-to-duct connections are shown
below. Airflow out of the fan should be directed strait
or curved the same direction as the fan wheel rotates.
Poor duct installation will result in low airflow and
other system effects.
Refer to local codes to determine drainage
requirements. If draining onto to roof, place a drip
pad below drain to protect roof. If draining onto roof
is not acceptable, a drain line must be attached to
the trap. The drain line must be pitched away from
the unit at least 1/8-in. per foot. On longer runs, an
air break should be used to ensure proper drainage.
Local codes may require drainage into a waste water
system.
Drainage problems not only occur from improper drain
trap design, but also from lack of maintenance of the
cooling coil compartment. Algae can form in the drain
pan and trap and cause reduced water flow, which
can in turn result in backup into the system. Regular
maintenance will prevent this from occurring. If the
drains have a clean-out opening, be sure to close the
opening after cleaning.
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project. Refer
to plans for appropriate job specific duct size and/or velocity
limitations.
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
VersiVent Energy Recovery Unit
15
Page 16
A1B1 15
1618 A2
0.20
0.41.0
0.60.8
0.20
0.41.0
0.60.8
T1
T2
T21 MIN
T11 MIN
Timer
Scale
Dip
Switch
Optional Accessories
Frost Control Application/Operation
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the energy
recovery wheel. Frost control is an optional feature
that will prevent/control wheel frosting. Three options
are available:
1. Timed Exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control
All of these options are provided with a thermostat
(with probe) mounted in the outdoor air intake
compartment and a pressure sensor to monitor
pressure drop across the wheel.
Frost Threshold Temperatures
Indoor RH @ 70°FFrost Threshold Temp
20%-10º F
30%-5º F
40%0º F
The typical temperature setting corresponds to the
indoor air relative humidity as shown in the Frost
Threshold Temperatures Table and represents when
frost can occur. An increase in pressure drop would
indicate that frost is occurring. Both the pressure
sensor AND the outdoor air temperature sensor
must trigger in order to initiate frost control. The
two sensors together insure that frost control is only
initiated during a real frost condition. Field wiring of
a light (or other alarm) between 6 & C in the control
center will notify personnel when unit is in frost control
mode (refer to Remote Panel Wiring schematics
section for wiring details). The following explains the
three options in more detail.
Timed exhaust frost control includes a timer in
addition to the thermostat and wheel pressure sensor.
When timed exhaust frost control is initiated, the
timer will turn the supply blower on and off to allow
the warm exhaust air to defrost the energy recovery
wheel. Default factory settings are 5 minutes off and
30 minutes on. Use the following test procedure for
troubleshooting.
Testing (refer to Timer Faceplate drawing below)
• Jumperthewheelpressureswitchintheunit
control center. Set the Timer Scale for T1 and T2
to 1 minute. Set the Timer
Settings for T1 and T2 to
1.0. Set the dip switch
to the down position.
(normal position)
• Turnthetemperature
sensor up as high as
possible. The supply
blower should cycle on
for one minute, then turn
off for one minute.
• SettheTimerSettingsasfollows:T1 = 0.5, T2 = 0.5
The timer is now set for 5 minutes off and 30
minutes on. Remember to remove the jumper.
Electric preheat frost control includes an electric
heater (at outdoor air intake) and an airflow pressure
switch (located at the preheater) in addition to the
thermostat and pressure sensor on wheel. (Refer
to Electric Heater Application/Operation for electric
preheater location). When electric preheat frost
control is initiated, the electric preheater will turn
on and warm the air entering the energy wheel to
avoid frosting. Use the following test procedure for
troubleshooting.
Testing:
• Turnthethermostatashighasitwillgoand
jumper the wheel pressure sensor. The heater
should turn on.
on or temporarily jumper the airflow pressure
switch in the preheater control center to avoid
nuisance tripping of the pressure switch. Also
check the airflow switch pressure tap located
at the supply discharge blower to ensure the
tubing is connected and the tap is not blocked.
Remember to remove the jumpers.
Modulating wheel frost control includes a variable
frequency drive in addition to the thermostat and
pressure sensor. When modulating wheel frost control
is initiated, the variable frequency drive will reduce the
speed of the wheel. Reducing the speed of the energy
wheel reduces its effectiveness, which keeps the
exhaust air condition from reaching saturation, thus,
eliminating condensation and frosting. If the outdoor
air temperature is greater than the frost threshold
temperature OR the pressure differential is less than
the set point, the wheel will run at full speed. If the
outdoor air temperature is less than the frost threshold
temperature AND the pressure differential is greater
than the set point, the wheel will run at reduced speed
until the pressure differential falls below the set point.
The temperature and pressure differential set points
are set at the factory, but are field-adjustable (refer
to VFD section for more information). The variable
frequency drive will be fully programmed at the
factory.
Page 17
Economizer Application/Operation
The energy recovery wheel operation can be altered to
take advantage of economizer operation (free cooling).
Two modes are available:
1. De-energizing the wheel
2. Modulating the wheel
Both modes above require a field supplied call for cool
(R to Y1) in order to be activated.
De-energizing the wheel is accomplished with a signal
from a Temperature or Enthalpy sensor mounted
in the air intake compartment. This primary sensor
will de-energize the energy wheel when the outdoor
air temperature (factory default is 65ºF) or enthalpy
(factory default is the ‘D’ setting) is below the field
adjustable set point. An Override temperature
sensor is also furnished in the outdoor air intake
compartment to deactivate economizer mode. The
Override (with field adjustable set point) is set at some
temperature lower than the primary sensor (factory
default is 50ºF). Effectively, the two sensors create a
deadband where the energy recovery wheel will not
operate and free cooling from outside can be brought
into the building unconditioned.
Testing
Temperature Sensor with Override
• TurnbothTemperatureand
Override thermostats down as
low as they go. The wheel should
be rotating.
• TurntheTemperatureSensor
up as high as it goes, and keep
the Override sensor as low as it
will go. The wheel should stop
rotating.
for economizer operation to begin. Set the
Override sensor at desired point for economizer
operation to end (factory default is 65ºF and 50ºF,
respectively).
Enthalpy Sensor with Override
• Turnunitpoweroff.Disconnect
C7400 Solid State Enthalpy Sensor
from terminal So on the enthalpy
controller. Also, disconnect the
620 ohm resistor from
terminal Sr on the
enthalpy controller.
Turn unit power on. The
LED on the enthalpy
controller should light
and the energy recovery wheel should
not rotate.
•Turnunitpoweroff.Reconnect620
ohm resistor to terminal Sr on the
Enthalpy
enthalpy controller. Turn unit power
Controller
Temperature
Sensor with
Override
Enthalpy
Sensor with
Override
on. The LED on the enthalpy controller should
not light and the energy recovery wheel should
energize and rotate.
If these steps provide the results described, the
enthalpy economizer is working properly.
In applications in which an internal heat gain is
present in the space, the rotational speed of the
energy wheel may be modulated (via variable
frequency drive) to avoid overheating the space during
the winter. The speed of the energy wheel will be
controlled in response to the discharge temperature
set point.
Sequence of Operation: The variable frequency
drive is fully programmed at the factory (refer to VFD
section for more information). A “call for cool” must be
field wired to the unit (terminals provided in unit - refer
to wiring diagram in unit control center) to allow for
initiation of economizer mode. When the space calls
for cooling, factory supplied controls will drive the
following wheel operations:
TAO > T
TAO < T
and
TAO > T
TAO < T
and
TAO < T
RA
RA
SA
RA
SA
Wheel runs at full speed.
(maximum energy recovery)
Wheel is stopped.
(no energy recovery)
Wheel will modulate to maintain
discharge temperature.
Where (TOA) is the outdoor air temperature set point,
(TRA) is the return air temperature set point, and (TSA)
is the supply air discharge thermostat set point.
VersiVent Energy Recovery Unit
17
Page 18
Variable Frequency Drives for Energy Recovery Blowers
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
MPACAMAC+VA2A1PCP2P1
IGS-S+R-R+
V1000
MA MB MCACAMAC+VA1SCS5S4S3S2S1
J1000
OPTION 1 - 0-10 VDC CONTROL
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
USER TO PROVIDE ISOLATION AS REQUIRED
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
WIRED TO A1 (+) AND AC (COMMON)
0-10 VDC CONTROL SIGNAL (BY OTHERS)
10 VDC=60 Hz
0 VDC=30 Hz
A1 AC
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4SC
NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.
DRIVE SPEED = 40 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER n01 CHANGE TO 1
PARAMETER n22 FOR NEW 40Hz SETTING
PARAMETER n21 FOR NEW 60Hz SETTING
PARAMETER n23 FOR NEW 30Hz SETTING
PARAMETER n01 CHANGE TO 0
USER TO PROVIDE CONTACTS AND ISOLATION
AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided
for modulating or multi-speed control of the blowers. One VFD is provided for each blower (supply air and
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an
example wiring diagram has been provided in this manual for reference). When making adjustments outside of
the factory set points, refer to Yaskawa VFD instruction manual, which can be found online at www.drives.com.
For technical support, contact Yaskawa direct at 1-800-927-5292.
18
VersiVent Energy Recovery Unit
Factory Set Points
Variable Frequency Drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:
Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30
and 60Hz
Multi-speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
optional factory provided CO2 sensor sends the VFD
to high or low speed depending on CO2 ppm levels
at the sensor.
The terminal locations for Modulating (option 1) and
Multi-speed (option 2) are shown on the left. Most
of the set points in the VFDs are Yaskawa factory
defaults. However, a few set points are changed at
Greenheck and are shown in the tables on the next
page. These settings are based on the VFD mode
selected.
To gain access to change set points on the V1000 and
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.
Drive Operation
SC to S1 contact for On/Off
A1 (0-10 VDC) referenced to AC. Can use +15 VDC
from +V
Page 19
Factory Set Points - continued
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”.
Then go to A1-03 and change it to “1110” and press
enter. The drive is now reset back to the settings
programmed at Greenheck. This option is not
availableontheJ1000.
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
A1-01Access Level22
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec. 30 sec.
C6-02Carrier Frequency11
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H3-04Terminal A1 Bias50%50%
A1-01Access Level00
MULTI-SPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
A1-01Access Level22
b1-01Reference Source (Frequency)00
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec.30 sec.
C6-02Carrier Frequency11
d1-01Frequency Reference 160 Hz60 Hz
d1-02Frequency Reference 240 Hz40 Hz
d1-03Frequency Reference 330 Hz30 Hz
d1-04Frequency Reference 460 Hz60 Hz
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H1-04
H1-05
H1-06
H3-10A2 Not UsedFNA
A1-01Access Level00
Multi-Function Input Sel 4
(Terminal S4)
Multi-Function Input Sel 5
(Terminal S5)
Multi-Function Input Sel 6
(Terminal S6)
Setting
V1000J1000
Motor
FLA
V1000J1000
Motor
FLA
33
44
5NA
Motor
FLA
Setting
Motor
FLA
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C02 DROPS bELOW 700 PPM)
(FULL SPEED WHEN C02 RISES AbOVE 800 PPM)
Parameter
A1-01Access Level22
b1-01Reference Source (Frequency)00
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec.30 sec.
C6-02Carrier Frequency11
d1-01Frequency Reference 160 Hz30 Hz
d1-02Frequency Reference 230 Hz60 Hz
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H3-10A2 Not UsedFNA
A1-01Access Level00
Setting
V1000J1000
Motor
FLA
Motor
FLA
Variable Frequency Drives for Energy
Recovery Wheel
Optional factory installed VFD for the energy recovery
wheel is programmed at the factory per the settings
shown below for economizer and frost control modes.
TheVFDprovidedisaYaskawamodelJ1000.Refer
to the VFD instruction manual that ships with the unit
when making adjustments.
ParameterSetting–J1000
A1-01Access Level2
b1-17VFD Auto Start1
C6-02Carrier Frequency2
d2-01Ref Upper Limit100% or 66%*
d2-02Ref Lower Limit5%
E2-01Motor Rated FLAMotor FLA
*36 inch wheel is 66% (40 Hz). All other wheels are 100% (60 Hz).
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
Must be less than
FLA
6
5
Setting
Honeywell
Module
0100
990
Carel
Controller
VersiVent Energy Recovery Unit
19
Page 20
Rotation Sensor
The rotation sensor monitors energy recovery wheel
rotation. If the wheel should stop rotating, the sensor
will close a set of contacts in the unit control center.
Field wiring of a light (or other alarm) between
terminals R & 12 in the unit control center will notify
maintenance personnel when a failure has occurred
(refer to Remote Panel Wiring Schematics section for
wiring details).
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit
control center. Field wiring of a light (or other alarm)
to these contacts will notify maintenance personnel
when filters need to be replaced.
The switch has not been set at the factory due to
external system losses that will affect the switch. This
switch will need minor field adjustments after the
unit has been installed with all ductwork complete.
The dirty filter switch is mounted in the exhaust inlet
compartment next to the unit control center or in unit
control center.
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located
on the top of the switch. Open the filter compartment
and place a sheet of plastic or cardboard over 50%
of the filter media. Replace the filter compartment
door. Check to see if there is power at the alert
signal leads (refer to electrical diagram). Whether
there is power or not, turn the adjustment screw on
the dirty filter gauge (clockwise if you did not have
power, counterclockwise if you did have power) until
the power comes on or just before the power goes
off. Open the filter compartment and remove the
obstructing material. Replace the door and check to
make sure that you do not have power at the alert
signal leads. The unit is now ready for operation.
Setscrew (on front of switch)
must be manually adjusted after
the system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (senses blower side
of filters)
DDC Temperature Control Package
Temperature control package allows for stand-alone
operation of energy recovery units provided with
supplemental cooling and heating. Controller can be
ordered for discharge or room control. Room control
would require a room thermostat (or other call for
heat or cool) be wired to the controller. A remote
panel option is also available to allow set points and
other controller parameters to be adjusted from a
remote location. For additional information, refer to
the controls catalog and Installation, Operation and
Maintenance Manual.
CO2 Sensor
This accessory is often used to provide a modulating
control signal to a variable frequency drive to raise
and lower airflow in relationship to the CO2 levels
in the space. This strategy is often referred to as
Demand Control Ventilation and provides further
energy savings to the system. Follow instructions
supplied with sensor for installation and wiring details.
Service Outlet
120 VAC GFCI service outlet ships
loose for field installation. Requires
separate power source so power is
available when unit main disconnect is
turned off for servicing.
Vapor Tight Lights
Vapor tight lights provide light in the energy recovery
unit. The lights are wired to a
junction box mounted on the
outside of the unit. The switch to
turn the lights on is located in the
unit control center. The switch
requires a separate power source
to allow for power to the lights
when the unit main disconnect is
off for servicing.
Positive pressure connection is toward the ‘back or
bottom’ of the switch. (senses air inlet side of filters)
VersiVent Energy Recovery Unit
20
Page 21
Sensors Mounted by Factory
OAF-P
OAI
FROM
OUTSIDE
OA
FILTER
OAW-P
OAAW
COOL
COIL
ACC
HEAT
COIL
OAF-A
SUPPLY
BLOWER
OAD
TO
INSIDE
TO
OUTSIDE
EF-A
EXHAUST
BLOWER
EAW
EW-P
RAI
RAF-P
RA
FILTER
FROM
INSIDE
ENERGY WHEEL
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for
the controls contractor to connect the Building Management System for monitoring purposes.
Temperature Sensors - 1K Ohm RTD
Drawing Labels Terminal Strip Labels
OAIOA/Supply Inlet Temp
OAAWOA After Wheel
ACCAfter Cooling Coil Temp
OADSupply Discharge Temp
EAWExhaust After Wheel Temp
The remote panel is available with a number of
different alarm lights and switches to control the unit.
The remote panel ships loose and requires mounting
and wiring in the field.
The remote panel is available with the following
options:
Refer to Electrical Connections section for Field Control
Wiring recommendations.
Indicator Lights powered by the VER Unit
7-Day Timer or On/Off Switch
Dirty Filter Indicator (power by others)
For 7-Day Timer, use blue and black wires.
Red wires should be capped off.
Refer to Pressure Switch for voltage and load ratings.
Hand/Off/Auto Switch
Heating/Cooling Switch & Night Setback
Switch/Timer
Hand/Off/Auto Switch allows the unit to
“Off” - off
“On” - Manual Operation
“Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.
VersiVent Energy Recovery Unit
22
Page 23
Wiring Diagram
ENERGY WHEEL
FA CTORY SUPPLIED AND WIRED
G
MULTI-VOLTAGE PRIMARY
24 SECONDARY
TR1
C
TO UNIT
MAIN POWER
L3
L2
L1
DS1
SUPPLY DAMPER
D2
ENERGY WHEEL
R1
R
4
S1
PS1
NO CCOM NO
TS1
6
FROST CONTROL
A1T1A2
B1
16
15
T1
R1
LEGEND
C1 COOLING STAGE 1 RELAY
C2 COOLING STAGE 2 RELAY
CC COMPRESSOR CONTACTOR
CF CONDENSING FAN CONTACTOR
CH COMPRESSOR SUMP HEATER
D DAMPER
DB POWER DISTRIBUTION BLOCK
DL DAMPER LIMIT SWITCH
DS DISCONNECT SWITCH
EC ECONOMIZER CONTROLLER
FCS CONDENSOR F A N CYCLE SWITCH
FU FUSES
FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II)
FZ1 FREEZE PROTECTION
HG HOT GAS REHEAT VA L V E
HPS HIGH PRESSURE SWITCH (MANUAL RESET)
LPS LOW PRESSURE SWITCH
PS1 WHEEL FROST PRESSURE SWITCH
PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH
PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH
R1 ENERGY WHEEL RELAY/CONTACTOR
R2 OCCUPIED/UNOCCUPIED RELAY
R3 EXHAUST BLOWER VFD RELAY
R4 SUPPLY BLOWER VFD RELAY
R5 MODULATING WHEEL FROST CONTROL RELAY
R6 ECONOMIZER RELAY
R7 COMPRESSOR INTERLOCK RELAY
R8 EVAP RELAY (INDIRECT)
R9 EVAP RELAY (DIRECT)
R10 UNIT RELAY
R11 POST HEAT RELAY
R12 DEHUMIDIFICATION RELAY
R13 ROOM CALL FOR HEAT RELAY
R14 ROT A T ION SENSOR RELAY
R15 ROT A T ION SENSOR RELAY
S1 FAN SWITCH
S2 ROTA T ION SENSOR (LOCATED BY WHEEL)
S3 ROTA T ION SENSOR (LOCATED BY WHEEL)
S4 CALL FOR HEAT SWITCH
S5 OCC/UNOCC SWITCH - CLOSED=OCCUPIED/OPEN=UNOCCUPIED
S6 CALL FOR COOL SWITCH (FIRST STAGE)
S7 CALL FOR COOL SWITCH (SECOND STAGE)
S8 CALL FOR DEHUMIDIFICATION SWITCH
ST MOTOR STARTER
T1 FROST CONTROL TIMER
TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN.
T4 ECONOMIZER WHEEL JOG TIMER
TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC.
T5 EVAP DELAY OFF TIMER
T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)
T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)
TR TRANSFORMER
TS1 FROST CONTROL THERMOST A T (JUMPER - HEAT)
CLOSES ON TEMP. DECREASE TYPICAL SETTING 5°F.
TS2 ECONOMIZER LOW LIMIT THERMOST A T (JUMPER - HEAT)
OPENS ON TEMP . DECREASE TYP. SETTING 20° OFFSET OR 50°F>
TS3 ECONOMIZER UPPER LIMIT THERMOST A T (JUMPER - HEAT)
CLOSES ON TEMP. DECREASE TYP. SETTING 65°F./2° DIFF.
TS4 ROOM OVERRIDE SENSOR
TS5 INLET AIR POST HEATER LOCKOUT THERMOST A T (AFTER WHEEL)
CLOSES ON TEMP. DECREASE TYPICAL SETTING 65°F.
TS6 INLET AIR COMPRESSOR LOCKOUT THERMOST A T (JUMPER-HEAT)
OPENS ON TEMP . DECREASE TYPICAL SETTING 60°F./2° DIFF.
A2A1
o FIELD WIRED
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM.
IF RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY.
USE 14 GAUGE MINIMUM WIRE THICKNESS FOR CONTROL WIRING.
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA
CAUTION:
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
**
*
*
o
*
*
*
*
*
*
*
*
*
D1
EXHAUST DAMPER
GROUND
FROST CONTROL INDICAT OR
6C
ROTA TION INDICA T OR
12C
USER INTERFACE CONNECTIONS:
USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICA T OR DEVICES.
EXHAUST FA N
SUPPLY FAN
ST2
O.L.
MOTOR
MOTOR
ST1
O.L.
MOTOR(S)
ST1 O.L.
95 96
ST2 O.L.
95 96
ST1
A2A1
ST2
A2A1
SUPPLY FAN
EXHAUST FA N
ST2
13 14
54
CC2-NO
55
FCS1
(LOCATED IN CONDENSING FAN)
(LOCATED IN CONDENSING FAN)
56
1P2
CF2 O.L.
2P22P1
1P1
ST1-NO
CC1-NO
S7
Y2
51
COM NC
TS6
52
LPS1HPS1
CF1 O.L.
53
21 24
11
R17
14
R7
T7
3
3
T6
CF2
CF1
A1A1A2
A2
CONDENSING FA N 2
CONDENSING FA N 1
COMPRESSOR INTERLOCKS
R7
CC2
CC1
A1
1
1
A2
COMPRESSOR 2
COMPRESSOR 1
COMPRESSOR 1
COMPRESSOR 2
CONDENSING FAN 1
CONDENSING FAN 2
CC1
CC2
CF1
CF2
CH1 CH2
DB1
*
*
*
*
o
o
*
*
*
*
*
*
*
RETURN AIR SENSOR
620 OHM RESISTOR OR
S6
OUTDOOR AIR
SENSOR
3
SO+
SR+
SO
SR
Y1
1
TR
COM
4
2
5
TR1
6
NC
TS2
7
ECONOMIZER
ECONOMIZER CONTROL
R6
A1A2
*
*
*
ECONOMIZER INDICAT OR
7C
R6
21
12
EC
THERMOSTA T(S) TS1, TS2, TS6
24 VA C
THERMOSTAT CONTROLLER(S)
OA-SENSOR
SENSOR
COM
R14
21 12
S2
12
ROTATION SENSOR
R14
A2
A1
ROTATION SENSOR
BLUE
PINK
LT. BLUE
ORANGE
LT. BLUE
ORANGE
PURPLE
PURPLE
LT. BLUE
YELLOW
YELLOW
YELLOW
ORANGE
REDRED
REDRED
BROWN
REDRED
BROWN
BLACKBLACKBLACK
WHITE
YELLOW
5958
LPS2
57
HPS2
COMPRESSOR INTERLOCKS
R17
BLACK
A1A2
CIRCUIT 1
CIRCUIT 2
FCS2
Following are several examples of typical wiring diagrams located in the unit control center. These wiring
diagrams include a legend highlighting which accessories were provided with the unit. Factory wiring and field
wiring are also indicated.
Many other factory installed and wired accessories are available.
VersiVent Energy Recovery Unit
23
Page 24
ENERGY WHEEL
ENERGY RECOVERY
FACTORY SUPPLIED AND WIRED
G
MULTI-VOLTAGE PRIMARY
24 SECONDARY
TR1
C
TO UNIT
MAIN POWER
L3
L2
L1
DS1
SUPPLY DAMPER
D2
R
4
S1
R1
LEGEND
C1 COOLING STAGE 1 RELAY
C2 COOLING STAGE 2 RELAY
CC COMPRESSOR CONTACTOR
CF CONDENSING FAN CONTACTOR
CH COMPRESSOR SUMP HEATER
D DAMPER
DB POWER DISTRIBUTION BLOCK
DL DAMPER LIMIT SWITCH
DS DISCONNECT SWITCH
EC ECONOMIZER CONTROLLER
FCS CONDENSOR FAN CYCLE SWITCH
FU FUSES
FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II)
FZ1 FREEZE PROTECTION
HG HOT GAS REHEAT VALVE
HPS HIGH PRESSURE SWITCH (MANUAL RESET)
LPS LOW PRESSURE SWITCH
PS1 WHEEL FROST PRESSURE SWITCH
PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH
PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH
R1 ENERGY WHEEL RELAY/CONTACTOR
R2 OCCUPIED/UNOCCUPIED RELAY
R3 EXHAUST BLOWER VFD RELAY
R4 SUPPLY BLOWER VFD RELAY
R5 MODULATING WHEEL FROST CONTROL RELAY
R6 ECONOMIZER RELAY
R7 COMPRESSOR INTERLOCK RELAY
R8 EVAP RELAY (INDIRECT)
R9 EVAP RELAY (DIRECT)
R10 UNIT RELAY
R11 POST HEAT RELAY
R12 ROOM CALL FOR COOL RELAY
R13 ROOM CALL FOR HEAT RELAY
R14 ROTATION SENSOR RELAY
R15 ENERGY WHEEL RELAY
R16 HOT GAS REHEAT RELAY
S1 FAN SWITCH
S2 ROTATION SENSOR (LOCATED BY WHEEL)
S3 ROTATION SENSOR (LOCATED BY WHEEL)
S4 CALL FOR HEAT SWITCH
S5 OCC/UNOCC SWITCH - CLOSED=UNOCCUPIED/OPEN=OCCUPIED
S6 CALL FOR COOL SWITCH (FIRST STAGE)
S7 CALL FOR COOL SWITCH (SECOND STAGE)
S8 CALL FOR DEHUMIDIFICATION SWITCH
S9 ROOM RESET SWITCH
ST MOTOR STARTER
T1 FROST CONTROL TIMER
TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN.
T2 ROTATION SENSOR TIMER
T3 ROTATION SENSOR TIMER
T4 ECONOMIZER WHEEL JOG TIMER
TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC.
T5 EVAP DELAY OFF TIMER
T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)
T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.)
T8 COMPRESSOR MINIMUM ON TIMER (TYP. 5 MIN.)
TR TRANSFORMER
TS4 ROOM OVERRIDE SENSOR
o FIELD WIRED
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75
OHM. IF RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY.
USE 14 GAUGE MINIMUM WIRE THICKNESS FOR CONTROL WIRING.
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA
CAUTION:
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
**
*
*
*
o
*
*
*
*
*
*
*
*
D1
EXHAUST DAMPER
GROUND
EXHAUST FAN
SUPPLY FAN
ST2
O.L.
MOTOR
MOTOR
ST1
O.L.
MOTOR(S)
TO L1 AND L3 ON
CR IN IG FURNACE
ST1 O.L.
95 96
ST2 O.L.
95 96
ST1
A2A1
ST2
A2A1
SUPPLY FAN
EXHAUST FAN
ST2
13 14
A2
A1
R14
ROTATION SENSOR
R11
TO "A" AND "RH"
IN IG FURNACE
POST HEAT
*
14
21
A1
A2
G
NO1
NO2
NO3
13 14
ST1
4
C4
NO5
NO6
J13
J12
GO
J1
C1
G
NO4
12
NO7
C7
J14
VG
Y2
Y3
Y1
Y4
VG0
J4
IDC1
ID8
ID7
ID6
ID5
ID1
ID4
ID3
ID2
J5
BC5
B5
BC4
B4
+VDC
B3
B2
B1
J2
J3
DDC
CONTROLLER
NO8
NC8
C8
J15
R14
21 12
USER INTERFACE
ALARM NO/NC CONTACTS
ALARM
12
NOC
PS2
PS1
NO C
ST1-AUX
NO C
W1
TO NC ON T2
IN IG FURNACE
GND
TO NO ON T2
IN IG FURNACE
G
DDC SETUP CODE
X0Y1 1
R15
34
ENERGY WHEEL RELAY
S2
OAI
ACC
OAD
X
R15
1 2R1A2A1
ENERGY WHEEL
*
R
PINK
LT. BLUE
PINK
YELLOW
BROWN
ORANGE
PURPLE
BLUE
YELLOW
ORANGE
YELLOWBROWN
LT. BLUE
BROWN
PURPLE
ORANGE
RED
ORANGE
YELLOW
PINK
BLUE
WHITE
BROWN
R8
11
RED
14
R7
11 14
RED
BROWN
CC2
CC1
COMPRESSOR 1
COMPRESSOR 2
CONDENSING FAN 1
COMPRESSOR 2
COMPRESSOR 1
CONDENSING FAN 2
CC1
CC2
CF1
CF2
CH1 CH2
DB1
RED
RED
CC2-NO
CC1-NO
HPS1LPS1
5253
CONDENSING FAN 2
CONDENSING FAN 1
COMPRESSOR INTERLOCKS
A1
54
A1
A1
A2
CF2
A2
A2
CF1
R7
*
*
*
*
*
*
*
*
*
*
LPS2HPS2
57
COMPRESSOR INTERLOCKS
58
A1A2
R8
R7
21 242421
R8
2
FCS2
FCS1
5556
Wiring Diagram
The wiring diagram below includes a Factory Mounted DDC controller. The DDC controller operates the unit
based on a built-in program. Additional features shown are:
The DDC setup code can be cross-referenced with the DDC Controller IOM (Part #469690) for specific control
information.
24
VersiVent Energy Recovery Unit
Page 25
Sequence of Operation
Basic Unit
The VER units are pre-wired such that when a call for
outside air is made (via field supplied 24 VAC control
signal wired to unit control center), the supply fan,
exhaust fan and energy wheel are energized and
optional motorized dampers open. The VER units can
be supplied with or without heating coils. Controls
can be supplied by Greenheck or by the controls
contractor. If supplied by the controls contractor,
they would provide, mount, and wire any temperature
controllers and temperature or relative humidity
sensors required for the unit to discharge air at the
desired conditions. However, temperature, pressure,
and current sensors can be provided by Greenheck for
purposes of monitoring via the Building Management
System (see Optional Accessories section).
Summer Operation
Outdoor air is preconditioned (temperature and
moisture levels are decreased) by the transfer of
energy from the cooler, drier, exhaust air via the
energy recovery wheel. Units supplied with cooling
coils can further cool the air coming off the wheel and
strip out moisture to levels at or below room design. A
heating coil downstream of the cooling coil can reheat
the air to a more comfortable discharge temperature
to the space.
The VER model can be supplied with a wrap around
heatpipe for additional precooling of the outdoor air
prior to entering the cooling coil. The heatpipe also
provides reheat after the cooling coil for applications
where the outdoor needs to be provided at a space
neutral condition.
second compressor if available. (10 or larger
tonnage system).
Economizer Operation: Refer to Economizer
Application/Operation section.
Winter Operation
Outdoor air is preconditioned (temperature and
moisture levels are increased) by the transfer of
energy from the warmer, more humid exhaust air via
the energy recovery wheel. Units supplied with heating
coils can further heat the air coming off the wheel to
levels at or above room design.
Frost Control Operation: Refer to Frost Control
Application/Operation section.
Rotation Sensor: Refer to Optional Accessories
section
Dirty Filter Sensor: Refer to Optional Accessories
section
CO2 Sensor: Refer to Optional Accessories section
DX Safety and General Control Sequence: To
prevent damage to the system, there is a safety loop
incorporated into the controls. This loop includes a
check to make sure the supply fan starter is pulled
in, ambient temperature is above 55ºF, and the lowand high-pressure switches are not tripped out.
After this loop is verified, a relay then pulls in to start
the anti-cycle timer. (Typical setting is 3 minutes).
Once the timer has counted down, only then can the
compressor contact pull in. Once the compressor
contact pulls in, the first stage of condensing fans
turns on. If pressure in the condensing coil increases
to a point at which more heat needs to be removed
from the system, the fan cycle switch will close and
the second stage of condensing fans turns on.
VersiVent Energy Recovery Unit
25
Page 26
Start-Up
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit
to OFF at disconnect switch(es). Unit may have
multiple power supplies.
WARNING
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Do not operate energy recovery ventilator without
the filters and birdscreens installed. They prevent
the entry of foreign objects such as leaves, birds,
etc.
CAUTION
Do not run unit during construction phase. Damage
to internal components may result and void
warranty.
General factory information:
• Unitwasfactorytested.Allblowers,fans,
and compressors are set-up to run correct
when supplied power. If any one fan is running
backwards or the compressor is making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect.
This will ensure proper operation of the unit.
Failure to comply may damage the compressors
and void the warranty.
the unit. This may damage components within or
cause serious injury or death.
• Donotoperatecompressorwhentheoutdoor
temperature is below 40ºF.
• Donotshort-cyclethecompressor.Allow
5 minutes between “on” cycles to prevent
compressor damage.
• Priortostartinguptheunit,powermustbe
energized for 24 hours without a call for cool to
allow the compressor crankcase heaters time
to boil off any liquid refrigerant present in the
compressor.
Every installation requires a comprehensive startup to ensure proper operation of the unit. As part
of that process, the following checklist must be
completed and information recorded. Starting up
the unit in accordance with this checklist will not
only ensure proper operation, but will also provide
valuable information to personnel performing future
maintenance. Should an issue arise which requires
factory assistance, this completed document will
allow unit experts to provide quicker resolve. Qualified
personnel should perform start-up to ensure safe and
proper practices are followed.
Unit Model Number _______________________________
(e.g. VER-65)
Unit Serial Number _______________________________
(e.g. 04C99999 or 10111000)
Energy Wheel Date Code __________________________
(e.g. 0450)
Compressor 1 Model Number ______________________
(e.g. ZR36-XXXXX)
Compressor 2 Model Number ______________________
(e.g. ZR36-XXXXX)
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check as items are
completed.
o Disconnect and lock-out all power switches
o Remove any foreign objects that are located in the
energy recovery unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
o Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing. If
rubbing occurs, refer to Start-Up section for more
information.
o Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more
information).
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood
(refer to Routine Maintenance section).
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify control wire gauge (refer to the Electrical
Connections section).
o Verify diameter seal settings on the energy
recovery wheel (refer to Start-Up section for more
information).
VersiVent Energy Recovery Unit
26
Page 27
oVerify proper drain trap installation (refer to Drain
Trap section).
oLook over the piping system. Inspect for oil at
all tubing connections. Oil typically highlights a
leak in the system. If a leak is present, refer to the
Maintenance section in this manual.
oInspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully
straighten fins with a fin comb.
oIf there is an indirect gas-fired furnace in this unit,
refer to the PVF IOM provided with this unit for Pre
Start-Up information.
For plenum or backward inclined fans, check the
radial gap and overlap. Adjust if necessary.
Additional Information for Units with
Packaged DX
oCheck condensing fans for any damage or
misalignment. Spin the blades and make sure they
don’t contact any parts and are free turning without
any resistance.
o This unit contains a crankcase heater for each
compressor which needs power supplied to it 24
hours prior to start-up. If start-up is scheduled in 24
hours, unlock the disconnect power and energize
unit.
SPECIAL TOOLS REQUIRED
• VoltageMeter(withwireprobes)
• AmperageMeter
• PressureGauges–R410aRefrigerant
• TemperatureGaugescapableofmeasuringpipe
temperature
• Thermometer
• Inclinemanometerorequivalent
Start-Up Checklist
The unit will be in operational mode during start-up.
Use necessary precautions to avoid injury. All data
must be collected while the unit is running. In order to
measure volts & amps, the control center door must
be open, and the unit energized using a crescent
wrench to turn the disconnect handle.
compressors (optional), after 3 minutes they will
energize. Make sure all fans and compressors are
rotating in the correct direction.
WARNING
All motor(s) / compressor(s) have been checked for
rotation. If blower rotation is incorrect, wiring must
be changed at the disconnect to ensure all motor(s) /
compressors are corrected.
Operation of scroll compressor(s) in this unit are
directional and will be damaged if run with the wrong
direction.
• IfyourunitcontainsaPackagedDXsystem
(optional), allow the unit to run until the
refrigerant system stabilizes. Approximately
1-2 minutes.
Moisture Indicating Sight Glass
Liquid Visible Yes / No
Color of Center Dot Green / Yellow
Oil in Compressor Sight Glass Yes / No
Packaged DX units are provided fully charged with R410a refrigerant
VersiVent Energy Recovery Unit
28
Page 29
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit? Frost Control Application / Operation section:SettingFactory Default
YesNoFrost Control set point5ºF
Differential2ºF
TimerRefer to IOM
YesNoFrost Control ModulatingRefer to IOM
Economizer Application / Operation section:
YesNoEconomizer (temperature)
Set point65ºF
Offset20ºF
Differential2ºF
YesNoEconomizer (enthalpy)
Set pointD
YesNoEconomizer (modulating)Refer to IOM
Optional Accessories section: Operational
YesNo Wheel Rotation SensorYes No N/A
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesNo CO2 SensorYes No N/A
YesNo Service OutletYes No N/A
YesNo Vapor Tight LightsYes No N/A
YesNo Remote Control PanelYes No N/A
Variable Frequency Drives section: Operational
YesNo Blower VFDsYes No N/A
YesNo Wheel VFDYes No N/A
Damper section: Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
YesNo Night Setback DamperYes No N/A
YesNoIndirect Gas Furnace (refer to the PVF IOM, Part #461006 for start-up information)
VersiVent Energy Recovery Unit
29
Page 30
Unit Start-Up
Belt Span
Deflection =
Belt Span
64
WRONGWRONG
WRONGCORRECT
WRONGWRONG
WRONGCORRECT
MOTOR
FAN
MOTOR
Overlap
Radial
Gap
A
Refer to Component section for component locations.
Fans
The VER models
contain a plenum
supply fan and a
forward curved
exhaust fan. The
fans should be
checked for free rotation. If any binding occurs, check
for concealed damage and foreign objects in the fan
housing. Be sure to check the belt drives per the startup recommendations in the following section.
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.),
consult Greenheck to determine if the unit can
operate safely at the new conditions.
Supply Fan (Plenum Type)
The model VER contains one plenum supply fan
located on the end of the unit opposite the outdoor
air intake (see beginning of Unit Start-Up section for
diagram of unit layout). Efficient fan performance can
be maintained by having the correct radial gap and
overlap. These items should be checked before startup and after the fan has been in operation for 24 hours.
Radial Gap: Radial gap is
adjusted by loosening the
inlet cone/ring on the wheel.
If additional adjustment
is required to maintain
a constant radial gap,
loosening the bearing bolts
and centering the wheel is
acceptable as a secondary
option.
Overlap: Proper overlap is
obtained by loosening
the wheel hub from the
shaft and adjusting the
wheel to maintain an “A”
dimension.
Refer to Part #463687 Centrifugal Fan IOM for
additional start-up and
maintenance information
regarding the QEP
Plenum Supply Fan.
Exhaust Fans (Forward Curved Type)
The model VER contains one forward curved exhaust
fan located on either side of the unit (see Basic Unit
Operation). The forward curved fan should be checked
for free rotation. If any binding occurs, check for
concealed damage and foreign objects in the fan
VersiVent Energy Recovery Unit
30
Supply Fan
CAUTION
Plenum
Forward Curved
Radial Gap
and Overlap
“A” Dimension
Model
VER-45
VER-65
VER-90
Supply
Fan
QEP-155±1/8
QEP-18 6 3/8 ±1/8
QEP-18 6 3/8 ±1/8
QEP-207±3/16
QEP-207±3/16
QEP-24 8 5/8±1/4
Exhaust Fan
A Dimension
± Tolerance
(inches)
housing. Be sure to check the belt drives per the Belt
Drive Installation section (Unit Start-Up) and per the
Fan Belts section (Routine Maintenance).
Fan Performance Modifications
Due to job specification revisions, it may be necessary
to adjust or change the sheave or pulley to obtain
the desired airflow at the time of installation. Start-up
technician must check blower amperage to ensure
that the amperage listed on the motor nameplate is
not exceeded. Amperage to be tested with access
doors closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by
Greenheck, have been carefully selected for the
unit’s specific operating condition. Utilizing different
components than those supplied could result in
unsafe operating conditions which may cause
personal injury or failure of the following components:
•FanShaft• Bearings•Motor
•FanWheel• Belt
Tighten all fasteners and set screws securely and
realign drive pulleys after adjustment. Check pulleys
and belts for proper alignment to avoid unnecessary
belt wear, noise, vibration and power loss. Motor and
drive shafts must be parallel and pulleys in line (see
diagrams in this section).
Belt Drive Installation
1. Remove the protective coating from the end of
the fan shaft and assure that it is free of nicks and
burrs.
2. Check fan and motor shafts for parallel and
angular alignment.
3. Slide sheaves on shafts. Do not drive sheaves on
as this may result in bearing damage.
4. Align fan and motor sheaves with
a straight-edge or string and
tighten.
5. Place belts over sheaves.
Do not pry or force belts, as
this could result in damage
to the cords in the belts.
6. With the fan off, adjust the belt tension by moving
the motor base. (See belt tensioning procedures in
the Routine Maintenance section of this manual).
When in operation, the tight side of the belts
should be in a straight line from sheave to sheave
with a slight bow on the slack side.
Page 31
Direction of Fan Wheel Rotation
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Airflow
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Forward Curved
Blower access is labeled on unit. Check for proper
wheel rotation by momentarily energizing the fan.
Rotation is determined by viewing the wheel from the
drive side and should match the rotation decal affixed
to the fan housing (see Rotation Direction figures).
If the wheel is rotating the wrong way, direction can
be reversed by interchanging any two of the three
electrical leads. Check for unusual noise, vibration, or
overheating of bearings. Refer to the Troubleshooting
section of this manual if a problem develops.
Fan RPM
Supply fan and exhaust fan will have an adjustable
motor pulley (on 15 HP and below) preset at the
factory to the customer specified RPM. Fan speed
can be increased or decreased by adjusting the pitch
diameter of the motor pulley. Multi-groove variable
pitch pulleys must be adjusted an equal number
of turns open or closed. Any increase in fan speed
represents a substantial increase in load on the
motor. Always check the motor amperage reading
and compare it to the amperage rating shown on the
motor nameplate when changing fan RPM. All access
doors must be installed except the control center
door. Do not operate units with access doors open or
without proper ductwork in place as the fan motors
will overload.
Vibration
Excessive vibration may be experienced during initial
start-up. Left unchecked, excessive vibration can
cause a multitude of problems, including structural
and/or component failure. The most common sources
of vibration are listed.
Many of these conditions can be discovered by careful
consulted. If the problem is wheel unbalance, in-place
balancing can be done.
Generally, fan vibration and noise is transmitted
to other parts of the building by the ductwork. To
eliminate this undesirable effect, the use of heavy
canvas connectors is recommended.
observation. Refer to
the Troubleshooting
section of this manual
for corrective actions.
If observation cannot
locate the source of
vibration, a qualified
technician using
vibration analysis
equipment should be
Spring Vibration Isolators
Two to four securing bolts prevent unwanted fan
and isolator movement during shipping. Proper unit
operation requires the removal of these bolts.
Remove the 5/16 in. hex head bolts from each corner
of the fan sub-frame.
Coils
Leak test thermal system to insure tight connections.
Check for properly trapped condensate drain.
Energy Recovery Wheel
The VER models contain a total energy recovery
wheel. The wheels are inspected for proper
mechanical operation at the factory. However, during
shipping and handling, shifting can occur that may
affect wheel operation. The wheel is accessible
through the access door marked “Energy Wheel
Cassette Access”. To access seals in VER units, pull
the cassettes out following the instructions in the
Energy Recovery Wheel Maintenance section.
Turn the
energy
recovery
Adjustable
Air Seals
Bearing
Support
wheels by
hand to
verify free
operation.
The wheel
should rotate
smoothly and
should not
wobble.
Drive Belt
Drive Pulley
Label
showing
cassette
serial #
and date
code
Drive Belt
Inspect the drive belt. Make sure the belt rides
smoothly through the pulley and over the wheel rim.
Air Seals
Check that the air seals located around the outside of
the wheel and across the center (both sides of wheel)
are secure and in good condition. Air seal clearance
is determined by placing a sheet of paper, to act as
a feeler gauge, against the wheel face. To access
seals in VER units, pull the cassettes out following
the instructions in the Energy Recovery Wheel
Maintenance section. To adjust the air seals, loosen all
eight seal retaining screws. These screws are located
on the bearing support that spans the length of the
cassette through the wheel center. Tighten the screws
so the air seals tug slightly on the sheet of paper.
Replace cassette into unit, plug in wheel drive, replace
access door and apply power. Observe by opening
door slightly (remove filters if necessary to view
wheel). The wheel should rotate freely at about 50-60
rpm.
VersiVent Energy Recovery Unit
31
Page 32
Factory Installed Refrigeration System Components for Units with Packaged DX (optional)
1. Thermostatic Expansion Valve (TXV) - each
unit is equipped with a thermal expansion valve.
The valve controls the flow of liquid refrigerant
entering the evaporator coil by maintaining a
constant, factory set superheat of 10ºF. The valve
is located on the side of the evaporator coil and
can be accessed through the exhaust airstream,
through the coil panel access door.
2. Refrigerant Distributor - attached to the TXV is
a refrigerant distributor. The refrigerant distributor
evenly distributes the refrigerant to each circuit
of the evaporator coil to provide optimum
performance.
3. Evaporator Coil - each unit contains a multiple
circuit evaporator coil. The coil is located in
the outdoor airstream, directly after the energy
wheel. In the DX system, the liquid refrigerant is
expanded in the TXV, and then flows through the
evaporator coil. The refrigerant enters the coil as
low temp liquid/gas where it eventually boils into
a low temp, low pressure gas prior to going to the
compressor. To ensure proper operation, the coil
surface must be cleaned so that air movement
over the coil provides the necessary heat transfer.
4. Low Limit Pressure Switch - the unit includes
a low limit pressure switch (located in the
compressor compartment). The switch is installed
VersiVent Energy Recovery Unit
32
in the suction line and shuts off the DX system
when the suction pressure drops to 50 psi for
R410a. The switch has a built in auto-reset, which
will close the circuit and allow the system to run
when the pressure increases back to 90 psi for
R410a.
5. Compressors - each unit includes 1, 2 or more
efficiency scroll type compressors depending
on needed capacity. Scroll type compressors
are essentially maintenance free since they are
a self-contained, self-cooling design. The scroll
compresses the refrigerant in the gaseous state to
a high temperature, high pressure gas.
Compressor protective devices:
Thermal Overload - each compressor is equipped
with an auto reset thermal overload
High Temp Protection - internal devices within
the compressor protect it against excessively high
discharge gas temperatures
Crankcase Heater - Liquid refrigerant is
incompressible. Therefore, a crankcase heater
is installed around each compressor in the
unit to boil any liquid refrigerant that may be
absorbed into the oil during idle periods. System
power energizes the heater; it is recommended
the heater is allowed to run 24 hours prior to
compressors being started.
Page 33
6. Condensing Coil - each unit contains a multiple
circuit condensing coil mounted on the exterior of
the unit. High temperature, high pressure gas from
the compressor enters the coil and is eventually
cooled into a high temperature, high pressure
liquid. The condensing fans move air over the
coil which pulls the heat out of the refrigerant. To
ensure proper operation, the coil must be cleaned
so that air movement over the coil provides the
necessary heat transfer.
7. Condenser Fans - the unit is equipped with two
direct-drive condensing fans. The fans provide
the necessary airflow to cool the refrigerant in the
condensing coil. Depending on head pressure,
one fan may not be running, which is normal
operation for this unit and does not highlight a
problem. The motors are equipped with sling
protection to guard against water penetration, and
are thermally protected. The thermal overloads
shut down the condensing fans.
8. High Limit Pressure Switch - to safely shutdown
the DX system, in case of an increase in refrigerant
pressure, a high limit pressure switch is included
(located in compressor compartment). The switch
is located in the compressor compartment. It trips
when refrigerant pressure increase to 600 psi for
R410a in the liquid line, and can only be manually
reset when the pressure drops below 420 psi.
Typically if the high limit switch trips, a failure in
the system has occurred and more investigation is
needed to determine the underlying problem.
9. Head Pressure Cycle Switch - to maintain
proper refrigerant pressures, a Fan-Cycle switch
that operates on head pressure is installed in the
liquid line. When liquid line refrigerant pressure
increases to 400 psi for R410a, the switch closes
and turns on an additional condensing fan to aid
in cooling the refrigerant. After turning on, the fan
will run until liquid line pressure drops down to
300 psi for R410a where it cycles off. The switch is
located in the compressor compartment.
10. Liquid Line Filter Drier - the liquid line filter
drier prevents moisture and foreign matter
from entering the thermal expansion valve. It is
mounted in the compressor compartment.
11. Moisture Indicating Sight Glass - moisture in
a DX system can cause great harm and break
down the refrigerant. Located in the compressor
compartment is a moisture indicating sight glass.
During normal operating conditions, the sight
glass should typically be liquid. Some gas is
acceptable, but excessive bubbles may indicate
improper charge or a leak in the system. A green
dot means moisture is below a safe operation
level in the refrigerant, while a yellow dot indicates
moisture has been introduced into the system and
needs to be addressed.
12. Hot Gas Bypass Valve - on units equipped
with hot bypass, hot gas from the compressor
is injected into the liquid line of the evaporator
coil after the TXV. This process starts to occur
when suction gas temperatures drop below
28ºF, which is 32º–34ºF coil surface temperature.
Hot gas helps prevent the evaporator coil from
freezing up and the compressor from cycling. The
valve is factory set, but can be adjusted to exact
specifications once installed in the field.
13. Access Ports - for easy measurement and
charging access, several ports are provided
throughout the system. These can be used to
measure system pressures and also charge or
evacuate the system. Most ports are located in the
compressor compartment for easy access.
Valve Adjustment
To adjust the valve, connect a pressure gauge to
the suction line and block the entering air to the
evaporator coil. The Valve should begin to open
when the suction pressure drops to approximately
115 PSIG for R410a (the valve will feel warm to the
touch). Adjustments are made by first removing
the cap on the valve and then turning the
adjusting stem clockwise to increase the setting
pressure and counterclockwise to decrease the
setting pressure. Allow several minutes between
adjustments for system to stabilize. When
adjustment is complete, replace the cap on the
valve.
VersiVent Energy Recovery Unit
33
Page 34
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death. Before
attempting to perform any service or maintenance,
turn the electrical power to unit to OFF at disconnect
switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit
components, especially while standing on a ladder or
other potentially unsteady base. Access panels and unit
components can be heavy and serious injury may occur.
This unit requires minimal maintenance to operate
properly. To ensure proper operation and longevity, the
following items should be completed. The items in this
list assume a relatively clean air environment, and may
require attention more frequently in a dirty or dusty
area. If this unit contains an Indirect Gas Heater, refer
to the Installation, Operation and Maintenance Manual
provided with the unit for maintenance purposes. A
Certified Technician should complete all refrigerant
systems checks.
Maintenance Frequency:
Monthly
1. External Filter
Check for cleanliness – clean if required
2. Internal Filter
Check for cleanliness – replace if required
3. Condensate Drain (if applicable)
Inspect and clean – refill with water
4. Bearings
Lubricate per the schedule in the Fan
Bearings section
Semi-Annually
1. Fan Belts
Check for wear, tension, alignment
2. Energy Recovery Wheel
Check for cleanliness – clean if required
3. Check for belt wear
Check pulley, bearings, and motor
4. Bearings
Lubricate per the schedule in the Fan
Bearings section
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit startup checklist provided in the manual to ensure the
refrigeration system operates in the intended matter.
1. Lubrication
Apply lubrication where required
2. Dampers
Check for unobstructed operation
3. Motors
Check for cleanliness
4. Fan Belts
Check for wear, tension, alignment
5. Motors
Check for cleanliness
6. Blower Wheel & Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
7. Bearings
Lubricate per the schedule in the Fan
Bearings section
8. Energy Recovery Wheel
Check for cleanliness – clean if required
Check belt for wear
Check pulley, bearings, and motor
9. Door Seal
Check if intact and pliable
10. Wiring Connections
Check all connections for tightness
Units with Packaged DX
1. Evaporator Coil Maintenance
Check for cleanliness – clean if required
2. Condenser Coil Maintenance
Check for cleanliness – clean if required
3. Condensate Drain
Inspect and clean – refill with water
4. Condensing Fan Blades and Motor
Check for cleanliness
Check all fasteners for tightness
Check for fatigues, corrosion, and wear
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication.
Apply lubrication where required. Any components
showing excessive wear should be replaced to
maintain the integrity of the unit and ensure proper
operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Fan Belts
Belts must be checked on a regular basis for
wear, tension, alignment, and dirt accumulation.
Premature or frequent belt failures can be caused by
improper belt tension (either too loose or too tight)
or misaligned sheaves. Abnormally high belt tension
or drive misalignment will cause excessive bearing
loads and may result in failure of the fan and/or motor
bearings. Conversely, loose belts will cause squealing
on start-up, excessive belt flutter, slippage, and
overheated sheaves. Both loose and tight belts can
cause fan vibration.
VersiVent Energy Recovery Unit
34
Page 35
Belt Span
Deflection =
Belt Span
64
When replacing belts on multiple groove drives, all
belts should be changed to provide uniform drive
loading. Do not pry belts on or off the sheave. Loosen
belt tension until belts can be removed by simply
lifting the belts off the sheaves. After replacing belts,
insure that slack in each belt is on the same side of
the drive. Belt dressing should never be used.
Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.
The proper belt setting is the lowest tension at which
the belts will not slip under peak load operation. For
initial tensioning, set the belt deflection at 1/64-inch
for each inch of belt span (measured half-way
between sheave centers). For example, if the belt
span is 64 inches, the belt deflection should be 1 inch
(using moderate thumb pressure at mid-point of the
drive). Check belt tension two times during the first 24
hours of operation and periodically thereafter.
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper motor cooling. Never
wash-down motor with high pressure spray. Greasing
of motors is only
intended when fittings
are provided. Many
fractional motors
are permanently
lubricated for life and
require no further
lubrication.
Fan Wheel and Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Fan Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively
clean environment. Some bearings are re-lubricatable
and will need to be re-greased depending on fan
use. Check your bearings for grease zerk fittings to
find out what type of bearing you have. If your fan
is not being operated under normal use, bearings
should be checked monthly for lubrication. Shaft
bearings are the most critical moving part of a fan.
Therefore, special attention should be given to
keeping the bearings clean and well lubricated. Proper
lubrication provides for reduction in friction and
wear, transmission and dissipation of heat, extended
bearing life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper
grease applied at regular intervals is required. Refer to
the recommended bearing lubrication schedule:
If unusual conditions exist—temperatures below 32ºF
or above 200ºF, moisture or contaminants—more
frequent lubrication is required.
With the unit running, add grease very slowly with a
manual grease gun until a slight bead of grease forms
at the seal.
Be careful not to unseat the seal by over lubricating
or using excessive pressure. A guide to the amount
of grease to be used is to fill 30% to 60% of available
space in the bearing and housing.
A high quality lithium based grease conforming to
NLGI Grade 2 consistency, such as those listed below
should be used:
In addition to lubricating the bearings at specified
intervals, set screws in the bearing collars should be
checked for tightness. A bearing collar which has
loosened will cause premature failure of the fan shaft.
Fasteners attaching the bearings to the drive frame
should also be checked. See bearing lubrication
schedule.
Shaft Diameter in Inches
VersiVent Energy Recovery Unit
35
Page 36
Internal Filter Maintenance
The VER units will typically be provided with 2-inch,
pleated filters in the supply air and exhaust airstream.
These filters should be checked per a routine
maintenance schedule and replaced as necessary
to ensure proper airflow through the unit. See table
below for pleated filter size and quantity for each unit.
Replacement filters shall be of same performance
and quality as factory installed filters. Filter type
must be pleated design with integral metal grid. Two
acceptable filter replacements are Aerostat Series 400
or Farr 30/30®.
Located downstream of the energy wheel in the VER,
is an optional final filter section. Either MERV 8, 11
or 13 filters are available in 2 or 4-inch depth. An
acceptable replacement filter is an AmAir® 1100 or
similar model.
Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the
access side of the unit.
Exhaust Air Filters: Access to the exhaust air filters
is through the door labeled as “Filter Access” on the
access side of the unit.
Refer to Access Door Descriptions section for
additional information on filter locations.
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate energy recovery ventilator without
the filters and birdscreens installed. They prevent the
entry of foreign objects such as leaves, birds, etc.
Do not remove access panels or other unit
components while standing on a ladder or other
unsteady base. Access panels and unit components
are heavy and serious injury may occur.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
purchased). Filters should be checked and cleaned on
a regular basis for best efficiency.
The frequency of cleaning depends
upon the cleanliness of the
incoming air. These filters should be
cleaned prior to start-up.
To access these filters, remove
bottom bolt in the access door on
the side of the weatherhood. Slide
the access door up and then pull
bottom out to remove door. Then,
slide the filters out.
Outdoor air
intake hood
mesh filter
access
Clean filters by rinsing with a mild detergent in warm
water.
Filters upstream of the coil should be checked
regularly. If the filters are dirty, they should be cleaned
or replaced. It is important that the coils stay clean
to maintain desired airflow. See Filter Maintenance
section for additional information.
Coil Maintenance
Units with Optional Heating or Cooling
Coils must be cleaned to obtain maximum
performance. Check once a year under normal
operating conditions and if dirty, brush or vacuum
clean. Soiled fins reduce the capacity of the coil,
demand more energy from the fan, and create an
environment for odor and bacteria to grow and spread
through the conditioned zone. High pressure water
(700 psi or less) may be used to clean coils with
fin thickness over 0.0095 inches thick. TEST THE
SPRAY PRESSURE over a small corner of the coil to
determine if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Many coil
cleaners contain harsh chemicals, so they must be
used with caution by qualified personnel only. Care
must be taken not to damage the coils, including the
fins, while cleaning. Caution: Fin edges are sharp.
WARNING
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel.
Drain pans in any air conditioning unit will have
some moisture in them, therefore, algae and other
organisms will grow due to airborne spores and
bacteria. Periodic cleaning is necessary to prevent
this buildup from plugging the drain and causing the
drain pan to overflow. Inspect twice a year to avoid
the possibility of overflow. Also, drain pans should be
kept clean to prevent the spread of disease. Cleaning
should be performed by qualified personnel.
Winterizing Coils
Coil freeze-up can be caused by such things as air
stratification and failure of outdoor air dampers and/
or preheat coils. Routine draining of water cooling
coils for winter shutdown cannot be depended upon
as insurance against freeze-up. Severe coil damage
may result. It is recommended that all coils be drained
as thoroughly as possible and then treated in the
following manner.
Fill each coil independently with an antifreeze solution
using a small circulating pump and again thoroughly
drain. Check freezing point of antifreeze before
proceeding to next coil. Due to a small amount of
water always remaining in each coil, there will be a
diluting effect. The small amount of antifreeze solution
remaining in the coil must always be concentrated
enough to prevent freeze-up.
VersiVent Energy Recovery Unit
36
Page 37
Bracket Segment
Retainer
Lift away from
segment
Catch Segment
Retainer
Push toward center
Center of Wheel
Spoke
Inside of wheel rim
Note: Carefully read instructions for mixing antifreeze
solution used. Some products will have a higher
freezing point in their natural state than when mixed
with water.
WARNING
Disconnect power to the unit before performing any
type of service.
Energy Recovery Wheel Maintenance
Annual inspection of the energy recovery wheel is
recommended. Units ventilating smoking lounges
and other non-clean air spaces should have energy
recovery wheel inspections more often based upon
need. Inspections for smoke ventilation applications
are recommended bimonthly to quarterly until a
regular schedule can be established.
Accessing the Energy Recovery
Wheel
Access to the wheels on all VER
models is provided by a wheel access
door. The cassettes can be serviced
and inspected by simply sliding them
out of the unit as far as is needed. Be
sure to disconnect the power wires to
the motor before sliding the cassette.
The VER-45 and the VER-65 have one
wheel. The VER-90 has two wheels
which are accessed on opposite sides
of the unit.
Removing the Energy Recovery
Wheel Segments
Steel retainers are located on the inside of the wheel
rim. Push the retainer toward center of wheel, then lift
up and away to release segments (see below).
Important! Place retainers back in the original
position before rotating the energy recovery wheel,
otherwise damage to retainer will occur.
Wheel
Removal
Cleaning the Energy Recovery Wheel
If the wheel appears excessively dirty, it should be
cleaned to ensure maximum operating efficiency.
Only excessive buildup of foreign material needs to
be removed. Discoloration and staining of energy
recovery wheel does not affect its performance.
Thoroughly spray wheel matrix with household
cleaner such as Fantastik® or equivalent. Gently rinse
with warm water and using a soft brush remove any
heavier accumulation. A detergent/water solution can
also be used. Avoid aggressive organic solvents, such
as acetone. The energy recovery wheel segments
can be soaked in the above solution overnight for
stubborn dirt or accumulation.
After cleaning is complete, shake the excess water
from the wheel or segments. Dry wheel or segments
before placing them back into the cassette. Place
wheel or segments back into cassette by reversing
removal procedures.
CAUTION
Do not clean energy recovery wheel segments with
water in excess of 140ºF (60ºC).
Do not dry energy recovery wheel segments in air in
excess of 140ºF (60ºC).
The use of a pressure washer to clean segments is
not recommended. Damage could result.
Energy Recovery Wheel Belt
Inspect belts each time
filters are replaced. Belts
that look chewed up
or are leaving belt dust
near the motor pulley
may indicate a problem
with the wheel. Be sure
to inspect wheel for
smooth and unrestricted
rotation. If a belt requires
replacement, contact
the local Greenheck
Wheel Belt & Pulley
representative. Instructions
for replacement will ship with the new belt.
Energy Recovery Wheel Bearings
In the unlikely event
that a wheel bearing
fails, access is available
through the outdoor air
filter door and through
a removable plate in
the divider in the unit
(accessed through
the exhaust air filter
door). Contact the local
Greenheck representative
for detailed instructions
Wheel Bearing
on how to replace the
bearing.
VersiVent Energy Recovery Unit
37
Page 38
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,
prior to contacting the factory, please determine the following information:
Unit #1Unit #2Unit #3Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Pressure Drop Across Energy Recovery Wheel
Outdoor Air Side
Exhaust Side
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in
accordance with SMACNA and AMCA guidelines.
VersiVent Energy Recovery Unit
38
Page 39
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.
Defective motor or capacitor.Replace.
Replace fuse or reset circuit breaker and check
amps.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Motor starter overloaded.Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the coil.
CFM too high.Check cfm and adjust drives if needed.
Static pressures are higher or lower than design.
Blower rotation is incorrect.Check rotation and reverse if necessary.
Motor voltage incorrect.Check motor nameplate versus supplied voltage.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Check for On/Off switches. Check for correct
supply voltage.
Check for broken or loose belts. Tighten loose
pulleys.
Shorten wiring run to mechanical room or
install a relay which will turn unit on/off. Consult
Factory for relay information. Increase wire
gauge size so that resistance is .075 ohms or
less.
Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.
If higher, ductwork should be improved.
If lower, fan rpm should be lower.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Low airflow (cfm)
Dirty filter or energy wheel.
Leaks in ductwork.Repair.
Elbows or other obstructions may be
obstructing fan outlet.
Belt slippage.Adjust belt tension.
Blower fan speed too high.
High airflow (cfm)
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Improve ductwork to eliminate losses using
good duct practices.
Check for correct drives and rpm with catalog
data.
For 3-phase, see Direction of Fan Wheel
Rotation under Unit Start-Up section.
Follow cleaning procedures in Routine
Maintenance section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed if
necessary.
Induce Ps into system ductwork. Make sure
grilles and access doors are installed. Decrease
fan speed if necessary.
VersiVent Energy Recovery Unit
39
Page 40
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Exhaust Only frost control sensors are tripping.
Adjust frost temperature sensor set point as
needed.
Energy wheel does
NOT turn
Energy wheel runs
intermittently
Air seals are too tight.
“Economizer” sensors are operating.
No power to wheel motor.
Wheel drive belt.
VFD overload. (OL1 on readout)
Wheel motor overloads are tripping, due to
rubbing between wheel and air seals.
Fan wheel rubbing on inlet.
Bearings.
Wheel out of balance.Replace or rebalance.
Loose wheel on shaft.Tighten wheel setscrew.
Loose motor or blower sheave.Tighten sheave setscrew.
See Energy Recovery Wheel under Unit Start-Up
section.
Adjust temperature or enthalpy set points as
needed.
Make sure wheel drive is plugged in. Verify
power is available.
Check for loose or broken belts. Replace belts
(consult factory).
Refer to VFD section. Compare motor amp
rating to setting in VFD. Adjust accordingly.
Recheck air seals, make sure they are not too
tight. See Energy Recovery Wheel under Unit
Start-Up Section.
Adjust wheel and/or inlet cone. Tighten wheel
hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.
Belts too loose.Adjust belt tension after 24 hours of operation.
Excessive noise
or vibration
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Belts too tight.
Worn belt.Replace.
Motor base or blower loose.Tighten mounting bolts.
Buildup of material on wheel.Clean wheel and housing.
Bearing and drive misaligned.Realign.
Noise being transmitted by duct.
Loosen to maintain a 3/8 inch deflection per foot
of span between sheaves.
Make sure ductwork is supported properly.
Make sure ductwork metal thickness is sized for
proper stiffness. Check duct size at discharge to
ensure that air velocities are not too high.
Do not release refrigerant to the atmosphere! If
Before any components are changed on the
refrigeration system, the cause of the failure must be
identified. Further problems will exist unless the true
cause or problem is identified and corrected.
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified HVAC Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.
SymptomPossible CauseCorrective Action
Open disconnect switch or circuit breaker.Close switch and / or breaker.
Check voltage to contactor coil, transformer,
slave relay, system. Replace parts as necessary.
Check for reason and repair. Replace fuse after
correcting problem.
Check line voltage. If more than 10% from
compressor marking, correcting is necessary.
Motor thermal protector automatically resets.
Allow time (2 hrs.) for compressor to cool down
so protector will reset. Restart and check for
reason overheat occurred.
Check motor for open circuit, short circuit,
grounded windings or burn out.
Compressor may be seized; check refrigerant.
If necessary, replace compressor.
Compressor
will not run
or
does not
try to start
Compressor contactor not closing.
Blown fuse or tripped breaker.
Low line voltage.
Compressor motor protector open.
Compressor defective.
If manual reset (high pressure), reset switch.
(Switch opens at 600 psi and will not reset above
High or low pressure switch open or defective.
Open room thermostat or control
(no cooling required).
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Airflow restricted.
Restriction in refrigerant line.
Defective low pressure switch.Replace.
420 psi for R410a.
If auto reset (low pressure) does not reset and
everything else is OK, replace switch.
Check room temperature. If temperature is
proper, wait for thermostat to close.
Check all wire terminals and tighten as
necessary.
Check for dirty evaporator coil, dirty filters,
dampers closed, iced evaporator coil, improper
belt, check motor amps, check duct design.
Check refrigerant pressure, check and adjust
thermal expansion valve. If not functioning
properly, check for pressure drop across the
filter drier.
Refrigerant overcharge.Check pressures, charge by subcooling.
Condenser fan motor defective.Check fan motor.
Compressor starts
but cuts out on high
pressure switch
High pressure
activates at
600 psig for R410a
Condenser coil inlet obstructed or dirty.Check coil and inlet clearances.
Air or non-condensables in system.
Defective high pressure switch.Replace.
Restriction in discharge or liquid line.
Condensing fan relay not pulling in.Replace.
Low voltage.Check voltage.
Sustained high discharge pressure.
Check high side equalized pressure reading with
equivalent outdoor temperature.
Check refrigerant line pressures, check thermal
expansion valves.
Check running amperage and conditions
described under ‘Low suction pressure’
symptoms.
Compressor cuts out
on thermal overload
Compressor hums,
but will not start
High suction and discharge pressures.
Defective compressor overload.
Improper refrigerant charge.Check subcooling.
Improperly wired.Review wiring schematics.
Loose wiring.Check all connections and wires.
Defective start relay.Replace relay.
Motor windings damaged.Verify amp draw.
Improperly wired.Review wiring schematics.
Low line voltage.Check voltage.
Loose wiring.Check all connections.
Defective start or run capacitor.
Defective relay start.Replace relay.
Check thermal expansion valve setting, check
for air in system.
If compressor is hot, allow compressor to cool
for two hours. Recheck for open circuit.
Check run capacitor for compressor and fan
motor.
Motor winding damaged.Verify amp draws.
Internal compressor mechanical damage.Replace.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Thermostatic expansion valve pressure limit
feature incorrect or inoperative. Overfeeding.
Room load too large.Reduce the load or add more equipment.
Overcharged.Check pressures and subcooling.
Thermal expansion valve setting.
Air inlet to condenser dirty or obstructed.
Condenser fan motor defective.Check condenser fan motor and capacitor.
Too much refrigerant.Remove excess refrigerant.
Non-condensable in system.Remove non-condensable from system.
Dirty condenser coil.Clean condenser coil.
Condenser fan not running or running
backwards.
Discharge service valve partially closed.Open valve.
High load conditions.Add more equipment or reduce load.
Check bulb location and clamping. Adjust
superheat. Replace expansion valve power
head.
Check thermal expansion setting and calibrate
superheat.
Check for proper clearances and possible air
recirculating.
Check electrical circuit and fuse. Check fan
cycling controls.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Defective high or low pressure control.Check high or low pressure switch.
Liquid floodback.Possible tight bearings, see above.
Compressor
short cycles
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Defective expansion valve.Check thermal expansion valve and superheat.
Poor air distribution.Check ductwork for recirculating.
High discharge pressure.See “High discharge pressure”.
Leaking discharge valves in compressor.See “High suction pressure”.
Low airflow at evaporator(s).
Incorrect unit selection (oversized).Contact factory.
Check condenser controls and reset to obtain
desired condensing temperature.
Check thermostat, check heat anticipator
setting.
Check blower operation and airstream
restrictions.
Thoroughly defrost evaporator. After defrost,
observe level, add oil. Check for leaks. Check
lines for proper slope and traps.
Adjust expansion valve for higher superheat.
Check crankcase heater.
Low or no
oil pressure
Low oil level (trapped oil in evaporator or
suction line).
Excessive liquid refrigerant in the crankcase.
Worn oil pump.Replace the oil pump.
Worn compressor bearings.Replace the compressor.
Compressor
loses oil
Running cycle is
too long or unit
operates
continuously
Loose fitting on oil line or pump housing gasket
leaking.
Compressor short cycling.Check low pressure control setting.
Refrigerant leak.
Short cycling.Check low pressure control settings.
Refrigerant flood back.
Improper piping or traps.Verify proper piping slopes.
Refrigeration undercharged.Check subcooling.
Dirty filter or evaporator coil.Check filter, coil and airflow.
Dirty or clogged condenser coil.Check coil and airflow.
Air or other non-condensables in system.
Defective compressor.See “High suction pressure”.
Restriction in suction and liquid line.Check for restrictions in refrigerant circuit.
Control contacts stuck.Check wiring.
Check and tighten system. Check bottom plate
or compressor.
Check system for leaks. Repair leaks and add
refrigerant.
Check thermal expansion valve setting. Check
for refrigerant overcharge.
Check equalized high side pressure with
equivalent outdoor temperature.
Excessive load.Add more equipment or reduce room load.
Too low of a system thermostat setting or
defective thermostat.
Liquid line
is too hot
Liquid line is
frosted or wet
Suction line
is frosting
Frost on
evaporator coil
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Refrigerant undercharge.Adjust the charge by subcooling.
High discharge pressure.See “High discharge pressure”.
Restriction in liquid line.Clear restriction upstream of point of frosting.
Insufficient evaporator airflow.
Restriction in suction or liquid line.Restriction upstream of point of frosting.
Malfunctioning or defective expansion valve.Check bulb of thermal expansion valve.
Hot gas bypass valve not functioning properly.Check valve. If defective, replace.
Manual hot gas bypass valve closed.Open valve.
Adjust or replace thermostat.
Check airflow, check filters, check drive for
loose parts or belts.
VersiVent Energy Recovery Unit
45
Page 46
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
VersiVent Energy Recovery Unit
46
Page 47
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
VersiVent Energy Recovery Unit
47
Page 48
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a
period of five years from the purchase date. Any units or parts which prove defective during the warranty period will
be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor
manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they
should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal
or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck Catalog VersiVent provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at: www.amca.org.