Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Model VER
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components
may be hot enough to cause pain or injury. Allow
time for cooling before servicing.
CAUTION
Precaution should be taken in explosive
atmospheres.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces or
chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
VersiVent Energy Recovery Unit
1
Receiving
Upon receiving the product, check to make sure
all items are accounted for by referencing the bill
of lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. A Carrier Inspection Report should be filled out
by the carrier upon arrival and the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle each piece in such a manner as to keep from
scratching or chipping the coating. Damaged finish
may reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to
prevent deterioration of the unit during storage.
The user assumes responsibility of the unit and
accessories while in storage. The manufacturer will
not be responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
Inspection and Maintenance during
Storage
While in storage, inspect units once per month. Keep
a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate all moving components by hand
ten to fifteen revolutions to distribute lubricant on
motor and bearings. If paint deterioration begins,
consideration should be given to touch-up or
repainting. Units with special coatings may require
special techniques for touch-up or repair.
Machined parts coated with rust preventive should
be restored to good condition promptly if signs of
rust occur. Immediately remove the original rust
preventive coating with petroleum solvent and clean
with lint-free cloths. Polish any remaining rust from
surface with crocus cloth or fine emery paper and oil.
Do not destroy the continuity of the surfaces. Wipe
clean thoroughly with Tectyl® 506 (Ashland Inc.) or
the equivalent. For hard to reach internal surfaces or
for occasional use, consider using Tectyl® 511M Rust
Preventive or WD-40® or the equivalent.
Special Owner’s Information for
Units with Packaged DX
The following summary highlights some important
notes to help avoid premature failure and possible
voidance of warranty.
Product Overview
Greenheck VER Models integrated with a complete
refrigerant system are designed with the purpose of
being a self-contained source for heating and cooling
in both commercial and institutional applications. This
is done in a highly efficient manner through the use of
a total enthalpy recovery wheel. The wheel allows the
compressors and cooling equipment to be downsized
in the unit, therefore being more cost effective to
operate. The DX system comes fully charged from the
factory with refrigerant and is ready for installation
upon arrival.
Units above seven (7) tons come standard with two
compressors. This allows for staging of compressors
to meet a wider range of outdoor air loads while
reducing the amount of cycles per compressor.
Integral Components
All units are provided with an expansion valve,
hermetic scroll compressor(s), liquid line filter drier,
high pressure manual reset cutout, low pressure autoreset cutout, time delays for compressor protection,
service/ charging valves, moisture indicating sight
glass, and hot gas bypass. The compressors also
come standard with a crankcase heater for additional
protection.
Shutdown Operation
The scroll compressors in this unit are designed
to compress gas refrigerant only. To prevent liquid
refrigerant from migrating into and damaging the
compressors, each compressor is supplied with a
crankcase heater. Prior to starting the compressors,
the heaters must have power to them for 24 hours.
Power should never be cut to these units unless the
complete shutdown procedure is followed.
Proper shutdown procedure:
1. Turn off main power supply to the unit
2. Turn thermostat controls to “off” position
3. Restore main power supply to the unit
4. Wait 24 hours prior to turning the thermostat
control to the “on” position.
VersiVent Energy Recovery Unit
2
Low Ambient Operation
Low ambient operation can cause damage to the
refrigerant system. A factory-installed temperature
sensor in the outdoor air intake prevents refrigerant
system operation at ambient conditions below 55ºF.
Crankcase heaters will still be engaged provided the
main power has not been disconnected. If cooling
is desired at ambient temperatures below 55ºF,
economizer operation (wheel start/stop or wheel
modulation) should be employed.
Reduced Airflow
Pumping Oil and Liquid Refrigerant
Lack of maintenance will lead to filters, condensing
coils, and evaporator coils building up with dirt and
debris. As this occurs, the airflow through the unit
will decrease. Cooling coils are sized to handle a
particular airflow volume. A reduction in airflow can
cause the cooling coils to get too cold and may
result in excessive liquid refrigerant return to the
compressors. The liquid refrigerant buildup in the
compressors will displace the necessary oil required
for proper lubrication. The combination of these
two events will significantly reduce the life of the
compressors.
To maintain the proper airflow and system efficiency,
follow all procedures in the Maintenance section.
Safety Listing
The VER units are listed per ANSI/UL 1995, Heating
and Cooling Equipment, and bear the ETL label.
Environmental Concerns
When working with Greenheck’s fully charged
refrigerant system, it is strongly recommended that
caution is undertaken during installation, operation,
and routine maintenance. This caution will help ensure
that minimal amounts of refrigerant are leaked into
the atmosphere. To comply to the U.S. Clean Air
Act, anytime there is residual refrigerant, the proper
equipment shall be used and methods should be
followed to reclaim the refrigerant so that it can be
recycled, reprocessed, or destroyed.
IMPORTANT
Do not release refrigerant to the atmosphere! If
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified EPA Certified Technician.
Table of Contents
Basic Operation . . . . . . . . . . . . . . 4
Installation
Installation Concerns. . . . . . . . . . . . 4
Lifting . . . . . . . . . . . . . . . . . . 5
Recommended Roof Openings . . . . . . . 5
Unit Weights and Dimensions . . . . . . . . 6
Rail and Roof Curb Mounting
Rail Mounting and Layout . . . . . . . . . . 7
Roof Curb Mounting . . . . . . . . . . . . 7
Curb Dimensions and Weights . . . . . . . . 8
Electrical Information
General Electrical Information . . . . . . . . 9
Control Center Components . . . . . . . . . 10
Electric Heater Application/Operation . . . . . 10
Unit Accessories. . . . . . . . . . . . . . 10
Service Clearances . . . . . . . . . . . . 11
Access Panel Description. . . . . . . . . . 12
Component Location . . . . . . . . . . . . 13
Coil Applications . . . . . . . . . . . . . 14
Drain Trap Information . . . . . . . . . . . 15
Ductwork Connections . . . . . . . . . . . 15
Optional Accessories
Frost Control Application/Operation . . . . . 16
Economizer Application/Operation . . . . . . 17
Variable Frequency Drives and Wiring . . . .18 -19
Sensors and Lights . . . . . . . . . . . . 20
Sensors Mounted by Factory . . . . . . . . 21
Remote Control Panel and Wiring . . . . . . 22
Typical Wiring Diagram . . . . . . . . . 23-24
Sequence of Operation . . . . . . . . . . . 25
Start-Up
Unit . . . . . . . . . . . . . . . . . 26-28
Optional Accessories . . . . . . . . . . . 29
Fan . . . . . . . . . . . . . . . . . 30-31
Energy Recovery Wheel . . . . . . . . . . 31
Refrigeration System . . . . . . . . . . 32-33
Routine Maintenance Checklist
General . . . . . . . . . . . . . . . . . 34
Belts . . . . . . . . . . . . . . . . 34-35
Motors . . . . . . . . . . . . . . . . . 35
Fan Wheel and Fasteners . . . . . . . . . . 35
Fan Bearings . . . . . . . . . . . . . . . 35
Filters . . . . . . . . . . . . . . . . . . 36
Coil Maintenance . . . . . . . . . . . 36-37
Energy Recovery Wheel Maintenance
Accessing Energy Recovery Wheel . . . . . 37
Removing Wheel Segments . . . . . . . . 37
Cleaning Wheel Segments . . . . . . . . 37
Wheel Belts . . . . . . . . . . . . . . 37
Wheel Bearings . . . . . . . . . . . . . 37
Troubleshooting – Airflow . . . . . . . . . . 38
Troubleshooting – Unit . . . . . . . . . 39-40
Troubleshooting – Refrigeration Circuit . .41-45
Maintenance Log . . . . . . . . . . . 46-47
Warranty . . . . . . . . . . . . . Backcover
VersiVent Energy Recovery Unit
3
Basic Operation
Installation
The VER units bring in fresh, outdoor air and remove
stale, exhaust air. Prior to discharging the exhaust air,
the energy recovery wheel transfers energy from the
exhaust air to the outdoor air at an efficiency of 7080%. Simply put, this unit preconditions the outdoor
air to save money on heating and cooling costs. These
particular units also have cooling and heating options
available after the recovery wheel to further condition
the fresh air.
Supplemental Installation,
Operation and Maintenance
Manuals
Refer to the following Installation, Operation and
Maintenance Manuals for additional details:
Part #463687 — Centrifugal Fan
Part #461006 — Indirect Gas-Fired Furnaces for
Energy Recovery Units, Model PVF
Part #469690 — Microprocessor Controller
Installation, Operation and Maintenance Manuals can
be found online at www.greenheck.com
General Installation, Operation and
Maintenance (IOM) Information
The VER model energy recovery unit is designed with
semi-custom versatility in mind. This quality allows for
the selection of several component options. Please
be aware that this IOM is comprehensive and includes
information for all the potential options offered for
this product line. Included options will vary on each
unit. Please pay special attention to the specific unit
in question when reviewing the information in this
manual.
The system design and installation should follow
accepted industry practice, such as described in the
ASHRAE Handbook.
Adequate space should be left around the unit for
piping coils and drains, filter replacement, and
maintenance. Sufficient space should be provided on
the side of the unit for routine service and component
removal should that become necessary.
See Service Clearances/Access Panel Locations
section for more details.
Installation Concerns for Units with
Packaged DX
Unobstructed airflow to the condensing section
must be maintained at all times to ensure proper
operating efficiency and capacity of the cooling
system. Unit placement should allow proper airflow
over the condensing section. The unit may not operate
properly and damage may occur to the system if there
is coil starvation (lack of air over condenser) or warm
air recirculating back through the condensing coil.
Recirculating air is caused when the unit is placed
near obstacles that can redirect exhaust air from
the condensing fans, back around to the coil inlet.
Overhangs or walls near the condensing section are
two examples.
Another consideration when placing the unit is
prevailing wind direction. The condensing coil
operation can be significantly affected when winds are
blowing continuously and directly at the condensing
coil. On hot days, the wind will help the system by
providing extra flow over the coil. But on cooler days,
that same wind may overcool the refrigerant, and
cause hot gas bypass to operate more frequently,
causing higher operating costs. Therefore, avoiding
direct winds will provide a more stable operation of
the system throughout the cooling season.
Lack of air over the coil can reduce efficiencies and
affect system operation. Do not allow debris (such as
leaves and trash), to accumulate on or near the unit.
Keeping debris clear of the unit will ensure minimal
obstruction to the coils, keeping efficiencies and
operation closer to design. The unit typically should
not operate when snow is present. In the event this
is possible, make sure all snow is clear of the coil and
condensing fans prior to operating the unit.
If more than one unit is being installed, make
provisions so discharge air from either the condensing
fans or exhaust fan of the unit do not discharge
towards another unit’s intake. Also, OA intake and
condensing sections should be spaced as too allow
proper airflow to each unit helping ensure the units
operate as intended.
VersiVent Energy Recovery Unit
4
Where the supply or warm air duct passes thru a
E
G
H
F
A
B
C
D
Return Air Intake
Supply Air
Discharge
combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.
Handling Concerns for Units with
Packaged DX
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation. Exercise extreme
caution to prevent any damage from occurring to
the refrigerant system. This unit contains a system
pressurized with refrigerant that if damaged, could
leak into the atmosphere or cause bodily harm due
to the extreme cold nature of expanding refrigerant.
Use protective equipment such as gloves and safety
glasses to minimize or prevent injury in case of a
system leak during installation.
Lifting
1. Before lifting, be sure that all shipping material
has been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Unit Weights &
Dimensions section on page 6.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach
to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
Recommended Roof Opening
Refer to weight and dimension data to determine the
exact location of the section containing the outdoor
air discharge opening. If the unit is equipped with
an Indirect Gas Heater (IG) section the outdoor air
discharge opening will be in that section; if not, it will
be in the blower section. The return air intake will
be consistent for all units. The dimensions of these
openings and their locations are illustrated below.
All dimensions are in inches.
IG = Indirect Gas Furnace; PDX = Packaged DX Cooling
1 = Any unit without IG and PDX.
Blower Module is at the end of the unit.
2 = Any unit with IG that does not have PDX.
3 = Any unit with IG and PDX
4 = Any unit without IG and with PDX
When cutting only duct openings, cut opening one inch
(25 mm) larger than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof is
constructed of combustible materials, area within the
roof curb must be ventilated, left open, or covered with
non-combustible material which has an “R” value of at
least five. If area within curb is open, higher radiated
sound levels may result.
Where the supply or warm air duct passes thru a
combustible roof, a clearance of one inch must be
6. Always test-lift the unit to check for proper
balance and rigging before hoisting to desired
location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing has been applied
to the curb prior to lifting the unit and setting on
curb.
11. Do not use fork lifts for handling unit.
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A. Position the unit roof opening such that
the supply discharge and exhaust inlet of the unit will
line up with the corresponding ductwork. Be sure to
allow for the recommended service clearances when
positioning opening (see Service Clearances). Do not
face the outdoor air intake of the unit into prevailing
wind and keep the intake away from any other exhaust
fans. Likewise, position the exhaust discharge opening
away from outdoor air intakes of any other equipment.
All dimensions shown in inches.
*L Sum the lengths of the appropriate modules to get the total length of the unit.
^Weight: The weights shown are a worse case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal
weights added together with the largest fans, coils and heaters for the unit.
D1D2D3D4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
ABC
(lbs.)
4900
VersiVent Energy Recovery Unit
6
Rail and Roof Curb Mounting
AB CD
Return Air
Intake
Supply Air
Discharge
Rails are positioned in random places.
See table for proper location
beyond the unit a minimum of 12 inches on each
side.
• Setunitonrails.
Isometric View
Roof Curb Mounting
Roof curb details, including duct location dimensions,
are available on VER roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1. Factory Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a
knockdown kit (includes duct adapter) and require
field assembly (by others). Assembly instructions
are included with the curb.
2. Install Curb
Locate curb over roof opening and fasten in place.
(Refer to Recommended Roof Openings). Check
that the diagonal dimensions are within ±1/8 inch of
each other and adjust as necessary. For proper coil
drainage and unit operation, it is important that the
installation be level. Shim as required to level.
3. Install Ductwork
Installation of all ducts should be done in
accordance with SMACNA and AMCA guidelines.
Duct adapter provided to support ducts prior to
setting the unit.
4. Set the Unit
Lift unit to a point directly above the curb and duct
openings. Guide unit while lowering to align with
duct openings. Roof curbs fit inside the unit base.
Make sure the unit is properly seated on the curb
and is level.
Side View
Unit SizeABCD
VER-4553.316
VER-6558.116
VER-90 105.316
All dimensions shown in inches.
IG = Indirect Gas
CS = Condensing Section
33.8 w/IG
27 w/o IG
31.0 w/IG
30 w/o IG
33.8 w/IG
34 w/o IG
9.2 IG w/o CS; 37.1 IG w/CS
5.2 w/o IG and CS
33.1 w/o IG and w/ CS
9 IG w/o CS; 36.9 IG w/CS
4.6 w/o IG and CS
32.5 w/o IG and w/ CS
9.2 IG w/o CS; 37.1 IG w/CS
3.7 w/o IG and CS
31.6 w/o IG and w/ CS
VersiVent Energy Recovery Unit
7
4-inch Final Filters
2-inch Filters
2-inch Filters
Wheel Cassette
Outdoor Air Hood
Intake
Section
Wheel
Section
Optional
Coil Section
Blower
Section
Optional
IG Heater Section
Optional
Condensing Section
Condensing Coil
Drain Pan ConnectionIG Gas Connection
ABC*D
L*
EF
Curb Outside Dimensions and Weights
Side of Unit
Recommended
2-inches of
Insulation
Roof Curb
1 in .
1 in .
2½ in.
1.195 in.
1 in .
W - 3.75 inches
L* - 3.75 inches
Elevation View
Subtract 3.75 inches from dimensions
W & L* to get the outside curb dimensions.
All dimensions shown in inches.
L* — Sum up the applicable section dimensions (A–F) for your unit to get the overall length.
^ — Curb weights shown are for the worst case scenario (largest curb) possible for each size unit.
C* Coil Module Options
C1C2C3C4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
DX + EH + HGRH
HW = Hot WaterEH = Electric Heat
CW = Chilled WaterHP = Wrap-around Heat Pipe
DX = Direct ExpansionHGRH = Hot Gas Reheat
Curb Cap Details
VersiVent Energy Recovery Unit
8
Electrical Information
The unit must be electrically grounded in accordance
with the current National Electrical Code, ANSI/NFPA
70. In Canada, use current CSA Standard C22.1,
Canadian Electrical Code, Part 1. In addition, the
installer should be aware of any local ordinances or
electrical company requirements that might apply.
System power wiring must be properly fused and
conform to the local and national electrical codes.
System power wiring is to the unit main disconnect
(door interlocking disconnect switch standard on most
units) or distribution block and must be compatible
with the ratings on the nameplate: supply power
voltage, phase, and amperage (Minimum Circuit
Amps - MCA; Maximum Overcurrent Protection MOP). All wiring beyond this point has been done by
the manufacturer and cannot be modified without
affecting the unit’s agency / safety certification.
If field installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and
size according to the rating plate.
Field Power Connection: All power and control
connections should be run through the floor or side
panel.
CAUTION
The VersiVent Roof lining contains high voltage
wiring. To prevent electrocution do not puncture the
interior or exterior panel of the roof.
If power supply is desired through bottom of unit, run
the wiring through the curb, cut a hole in the cabinet
bottom, and wire to the disconnect switch. Seal
penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent
requirements for the system to operate properly.
Voltage supply and voltage imbalance between
phases should be within the following tolerances.
If the power is not within these voltage tolerances,
contact the power company prior to operating the
system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at
all line disconnect switches. Readings must fall within
the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive
voltage imbalance between phases will cause motors
to overheat and eventually fail. Maximum allowable
imbalance is 2%. To determine voltage imbalance, use
recorded voltage measurements in this formula.
Key:V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with wiring material having a temperature rating of
at least 105ºC.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the
power supply, turn off the gas.
Most factory supplied electrical components are
pre-wired. To determine what electrical accessories
require additional field wiring, refer to the unit specific
wiring diagram located on the inside of the unit
control center access door. The low voltage control
circuit is 24 VAC and control wiring should not exceed
0.75 ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft.18
200 ft.16
300 ft.14
450 ft.12
Minimum
Wire Gauge
Control wires should not be run inside the same
conduit as that carrying the supply power. Make sure
that field supplied conduit does not interfere with
access panel operation.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit
control center and wired in place of the remote
switch (typically between terminal blocks R and G
on the terminal strip (refer to Typical Control Center
Components). The relay must be rated for at least
5 amps and have a 24 VAC coil. Failure to comply
with these guidelines may cause motor starters to
“chatter” or not pull in which can cause contactor
failures and/or motor failures.
Note: Standard factory installed electric post-
heaters have their own disconnect separate
from the unit disconnect. Thus, each electric
post-heater requires its own separate power
connection.
VersiVent Energy Recovery Unit
9
Control Center Components
1
8
7
5
6
18
9
2
3419
17
16
11
12
10
13
15
14
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter - Exhaust Air Fan
3. Motor Starter - Supply Air Fan
4. Motor Contactor - Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors*
8. Grounding lug
9. Distributor block*
10. Compressor fuse blocks*
11. Compressor contactors*
12. Condensing fan contactors*
13. Compressor relay*
14. Terminal block*
15. Compressor cycle timers*
Optional Control Center Components
16. DDC controller*
17. Dirty filter pressure switches*
18. Terminal block
19. Energy recovery wheel VFD*
*Not always provided
Electric Heater Application/Operation
Factory installed electric heaters can be provided for
preheat and/or post-heat. An electric preheater warms
the outdoor air prior to the energy recovery wheel to
prevent frosting on the wheel. An electric post-heater
warms the air leaving the energy recovery wheel to a
user specified discharge temperature. Electric heaters
are available in 208, 230, or 460 VAC (refer to heater
nameplate for voltage).
Preheaters: Preheaters are standard as two-stage
step control. Step control heaters are designed with
multiple stages made up of equal increments of
heating capability. For example a 10 kW heater with
two stages will be composed of two 5 kW stages.
Preheaters are single point wired at the factory.
A temperature sensor (with field adjustable set
point) is mounted in the outdoor airstream after the
preheater to turn the preheater on. See Frost Control
Application/Operation for typical set points. If the
temperature falls below the set point and the wheel
pressure drop sensor is triggered, the first stage of the
preheater will turn on. If the first stage does not satisfy
the set point, the second stage will also turn on.
The pre-heater is single point wired to the VER control
center. Access to the preheater control panel is
through the outdoor air intake.
Post-heaters: Post-heaters are standard as SCR
control. Post-heaters are not single point wired (see
Electrical Connections). A temperature sensor (with
field adjustable set point) is mounted in the outdoor
airstream after the post-heater. A SCR heater provides
an infinitely modulating control of the heat to provide
an accurate discharge temperature. A call for heat is
required to turn the post-heater on.
The post-heater is not single point wired to the VER
control center. Separate power must be supplied to
the post-heater disconnect located in the unit control
center.
10
VersiVent Energy Recovery Unit
Unit Accessories
Outdoor Air Weatherhood
Outdoor air weatherhood will be
factory mounted.
Exhaust Weatherhood
The exhaust weatherhood is shipped
separately as a kit with its own
instructions.
Dampers
Backdraft dampers are always
included as an integral part of the
exhaust hood assemblies. Motorized
outdoor air and exhaust air dampers
are optional and are factory mounted
(and wired) at the intake.
Service Clearances
TL
TRTR
TL
TR
TL
TR
TL
TRTR
TL
TL
TR
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
A
B
C
D
VER-90
ONLY
VER-45, 65 and 90 units require minimum clearances
for access on all sides for routine maintenance. Filter
replacement, drain pan inspection and cleaning,
energy wheel cassette inspection, fan bearing
lubrication and belt adjustment are examples of
routine maintenance that must be performed. Blower
and motor assemblies, energy recovery wheel
cassette, coil and filter sections are always provided
with a service door or panel for proper component
access. Clearances for component removal may be
greater than the service clearances, refer to drawings
for these dimensions.
Additional clearances for units with
packaged DX
Clearances must be maintained on all sides of
this unit. This especially is true with the top of
this unit. Hot air is being discharged through the
condensing fans during operation, and the more
clearance available, the better the chance of avoiding
recirculation or coil starvation. This unit should never
be placed under an overhang or inside a building. A
minimum of 48 inches over the condensing fans is
recommended.
Minimum 48 inches
clearance
Minimum 24 inches
Condensing Coil Intake
clearance
Keep this area clear
Unit Clearances
Unit SizeABCD
VER-4565423624
VER-6570423624
VER-9065426524
All dimensions shown in inches.
Access Panels may change depending on options
selected.
VersiVent Energy Recovery Unit
11
Access Panel Descriptions and
Locations
Following is a list of items accessible through the
access doors shown on the diagrams. Some items are
optional and may not have been provided.
#8 – Supply Blower
#9 – Compressors
8
#6 – Control Panel
#2 – OA Intake Damper
and Electric Preheat
2
3
4
1
9
9
#7 – IG Furnace
Control Center
1. Aluminum mesh filters (intake hood)
2. Outdoor air intake damper
Electric pre-heater
3. Exhaust blower, motor, and drives
4. Energy recovery wheel, motor, belt, and seals
Exhaust air filters
Exhaust air intake damper (optional)
Outdoor air filters
Frost control sensors (optional)
Economizer sensors (optional)
Coil Application Recommendation
for Units with Heating or Cooling
Options
Factory installed cooling and heating components
are mounted in the coil section of the unit. The coil
section is downstream of the energy wheel on the
supply air side of the unit.
Note the coil connection
locations on the picture.
Coil connections are
located external to
the unit as shown.
Coil connections that
are not external have
been ordered from the
factory with interior coil
connections.
Note: DX coil liquid
connection is internal to
units.
Water Coils
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Water connections are
male NPT iron pipe. When installing couplings,
do not apply undue stress to the connection
extending through the unit. Use a backup pipe
wrench to avoid breaking the weld between coil
connection and header.
2. Connect the water supply to the bottom
connection on the air leaving side and the water
return to the top connection on the air entering
side. To insure proper venting, an external air
vent in the piping is recommended. Connecting
the supply and/or return in any other manner
will result in very poor performance. Be sure to
replace factory installed grommets around coil
connections if removed for piping. Failure to
replace grommets will result in water leakage into
the unit and altered performance.
3. The air vent at the uppermost point should be
temporarily opened during system start-up to
release all of the air from the coil. To maintain heat
transfer capacity, periodically vent any air in coil.
4. Water coils are not normally recommended for
use with entering air temperatures below 40ºF;
however, the energy recovery wheel maintains
a pre-coil temperature higher than 40ºF. No
control system can be depended on to be 100%
safe against freeze-up with water coils. Glycol
solutions or brines are the only safe media for
operation of water coils with low entering air
conditions.
Continuous water circulation through the coil at all
times is highly recommended.
5. Pipe sizes for the system must be selected on the
Water
Coil
Connections
basis of the head (pressure) available from the
circulation pump. The velocity should not exceed
6 feet per second and the friction loss should be
approximately 3 feet of water column per 100 feet
of pipe.
6. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. Refer to Drain Trap
section.
Direct Expansion (DX) Coils for units with a split
DX System
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should
not be applied at the connection to coil headers.
2. When connecting suction and liquid connections,
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage.
Be sure to replace factory installed grommets
around coil connections if removed for piping.
Direct Expansion (DX) Coil for units with
Packaged DX System
1. The condensate drain pipe should be sized
adequately to ensure the condensate drains
properly. Refer to Drain Trap section.
VersiVent Energy Recovery Unit
14
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Length of Straight Duct
GOOD
POOR
GOODPOOR
Turning
Vanes
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
Drain Trap
4 in.
2 in.
Ductwork Connections
Cooling coils are provided with a stainless steel drain
pan with 1-inch male NPT drain connection. A drain
trap must be connected to the drain connection to
allow excess water to flow out of the drain pan. More
importantly, though, due to the negative internal static
of the cooling coil compartment, installing the drain
trap prevents outdoor air from being pulled into the
drain pan and consequently forcing water out of the
pan and into the unit.
To ensure the drain trap works properly, the trap
height must account for the difference in static
pressure between ambient conditions outside the
unit and the internal negative pressure of the cooling
coil compartment. For energy recovery units, an
assumption of 3.0 in. wg differential will be sufficient.
This would require a trap design as shown. If the
internal static is believed to be higher, consult factory.
Supply Fan:
The supply fan in this unit is a plenum style fan. The
discharge opening dimensions are provided. For
proper fan performance, match the duct size to the
dimensions listed. Installation of all ducts should be
done in accordance with SMACNA.
Supply Fan Discharge Opening Dimensions
Supply Air
Model
Discharge Location
TopEndBottom
VER-45 38.5 x 30 41.8 x 27
VER-6550 x 3150 x 31
VER-9062 x 3459.7 x 35
All dimensions shown in inches.
See diagram in Recommended Roof Openings section (page 5)
*
for the Bottom Discharge opening sizes.
*
*
*
Length of
Straight Duct
(Supply Fan)
48
60
60
Exhaust Fan
The exhaust fan in this unit is a forward curved fan.
Good and Poor fan-to-duct connections are shown
below. Airflow out of the fan should be directed strait
or curved the same direction as the fan wheel rotates.
Poor duct installation will result in low airflow and
other system effects.
Refer to local codes to determine drainage
requirements. If draining onto to roof, place a drip
pad below drain to protect roof. If draining onto roof
is not acceptable, a drain line must be attached to
the trap. The drain line must be pitched away from
the unit at least 1/8-in. per foot. On longer runs, an
air break should be used to ensure proper drainage.
Local codes may require drainage into a waste water
system.
Drainage problems not only occur from improper drain
trap design, but also from lack of maintenance of the
cooling coil compartment. Algae can form in the drain
pan and trap and cause reduced water flow, which
can in turn result in backup into the system. Regular
maintenance will prevent this from occurring. If the
drains have a clean-out opening, be sure to close the
opening after cleaning.
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project. Refer
to plans for appropriate job specific duct size and/or velocity
limitations.