Greenheck VER-65 Installation Manual

Page 1
®
Part #471849
Energy Recovery – VersiVent
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Model VER
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electric Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to the unit while it is running.
VersiVent Energy Recovery Unit
1
Page 2
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle each piece in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
Inspection and Maintenance during Storage
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate all moving components by hand ten to fifteen revolutions to distribute lubricant on motor and bearings. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
Special Owner’s Information for Units with Packaged DX
The following summary highlights some important notes to help avoid premature failure and possible voidance of warranty.
Product Overview
Greenheck VER Models integrated with a complete refrigerant system are designed with the purpose of being a self-contained source for heating and cooling in both commercial and institutional applications. This is done in a highly efficient manner through the use of a total enthalpy recovery wheel. The wheel allows the compressors and cooling equipment to be downsized in the unit, therefore being more cost effective to operate. The DX system comes fully charged from the factory with refrigerant and is ready for installation upon arrival.
Units above seven (7) tons come standard with two compressors. This allows for staging of compressors to meet a wider range of outdoor air loads while reducing the amount of cycles per compressor.
Integral Components
All units are provided with an expansion valve, hermetic scroll compressor(s), liquid line filter drier, high pressure manual reset cutout, low pressure auto­reset cutout, time delays for compressor protection, service/ charging valves, moisture indicating sight glass, and hot gas bypass. The compressors also come standard with a crankcase heater for additional protection.
Shutdown Operation
The scroll compressors in this unit are designed to compress gas refrigerant only. To prevent liquid refrigerant from migrating into and damaging the compressors, each compressor is supplied with a crankcase heater. Prior to starting the compressors, the heaters must have power to them for 24 hours. Power should never be cut to these units unless the complete shutdown procedure is followed.
Proper shutdown procedure:
1. Turn off main power supply to the unit
2. Turn thermostat controls to “off” position
3. Restore main power supply to the unit
4. Wait 24 hours prior to turning the thermostat control to the “on” position.
VersiVent Energy Recovery Unit
2
Page 3
Low Ambient Operation
Low ambient operation can cause damage to the refrigerant system. A factory-installed temperature sensor in the outdoor air intake prevents refrigerant system operation at ambient conditions below 55ºF. Crankcase heaters will still be engaged provided the main power has not been disconnected. If cooling is desired at ambient temperatures below 55ºF, economizer operation (wheel start/stop or wheel modulation) should be employed.
Reduced Airflow Pumping Oil and Liquid Refrigerant
Lack of maintenance will lead to filters, condensing coils, and evaporator coils building up with dirt and debris. As this occurs, the airflow through the unit will decrease. Cooling coils are sized to handle a particular airflow volume. A reduction in airflow can cause the cooling coils to get too cold and may result in excessive liquid refrigerant return to the compressors. The liquid refrigerant buildup in the compressors will displace the necessary oil required for proper lubrication. The combination of these two events will significantly reduce the life of the compressors.
To maintain the proper airflow and system efficiency, follow all procedures in the Maintenance section.
Safety Listing
The VER units are listed per ANSI/UL 1995, Heating and Cooling Equipment, and bear the ETL label.
Environmental Concerns
When working with Greenheck’s fully charged refrigerant system, it is strongly recommended that caution is undertaken during installation, operation, and routine maintenance. This caution will help ensure that minimal amounts of refrigerant are leaked into the atmosphere. To comply to the U.S. Clean Air Act, anytime there is residual refrigerant, the proper equipment shall be used and methods should be followed to reclaim the refrigerant so that it can be recycled, reprocessed, or destroyed.
IMPORTANT
Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be performed by a qualified EPA Certified Technician.
Table of Contents
Basic Operation . . . . . . . . . . . . . . 4
Installation
Installation Concerns. . . . . . . . . . . . 4
Lifting . . . . . . . . . . . . . . . . . . 5
Recommended Roof Openings . . . . . . . 5
Unit Weights and Dimensions . . . . . . . . 6
Rail and Roof Curb Mounting
Rail Mounting and Layout . . . . . . . . . . 7
Roof Curb Mounting . . . . . . . . . . . . 7
Curb Dimensions and Weights . . . . . . . . 8
Electrical Information
General Electrical Information . . . . . . . . 9
Control Center Components . . . . . . . . . 10
Electric Heater Application/Operation . . . . . 10
Unit Accessories. . . . . . . . . . . . . . 10
Service Clearances . . . . . . . . . . . . 11
Access Panel Description. . . . . . . . . . 12
Component Location . . . . . . . . . . . . 13
Coil Applications . . . . . . . . . . . . . 14
Drain Trap Information . . . . . . . . . . . 15
Ductwork Connections . . . . . . . . . . . 15
Optional Accessories
Frost Control Application/Operation . . . . . 16
Economizer Application/Operation . . . . . . 17
Variable Frequency Drives and Wiring . . . .18 -19
Sensors and Lights . . . . . . . . . . . . 20
Sensors Mounted by Factory . . . . . . . . 21
Remote Control Panel and Wiring . . . . . . 22
Typical Wiring Diagram . . . . . . . . . 23-24
Sequence of Operation . . . . . . . . . . . 25
Start-Up
Unit . . . . . . . . . . . . . . . . . 26-28
Optional Accessories . . . . . . . . . . . 29
Fan . . . . . . . . . . . . . . . . . 30-31
Energy Recovery Wheel . . . . . . . . . . 31
Refrigeration System . . . . . . . . . . 32-33
Routine Maintenance Checklist
General . . . . . . . . . . . . . . . . . 34
Belts . . . . . . . . . . . . . . . . 34-35
Motors . . . . . . . . . . . . . . . . . 35
Fan Wheel and Fasteners . . . . . . . . . . 35
Fan Bearings . . . . . . . . . . . . . . . 35
Filters . . . . . . . . . . . . . . . . . . 36
Coil Maintenance . . . . . . . . . . . 36-37
Energy Recovery Wheel Maintenance
Accessing Energy Recovery Wheel . . . . . 37
Removing Wheel Segments . . . . . . . . 37
Cleaning Wheel Segments . . . . . . . . 37
Wheel Belts . . . . . . . . . . . . . . 37
Wheel Bearings . . . . . . . . . . . . . 37
Troubleshooting – Airflow . . . . . . . . . . 38
Troubleshooting – Unit . . . . . . . . . 39-40
Troubleshooting – Refrigeration Circuit . .41-45
Maintenance Log . . . . . . . . . . . 46-47
Warranty . . . . . . . . . . . . . Backcover
VersiVent Energy Recovery Unit
3
Page 4
Basic Operation
Installation
The VER units bring in fresh, outdoor air and remove stale, exhaust air. Prior to discharging the exhaust air, the energy recovery wheel transfers energy from the exhaust air to the outdoor air at an efficiency of 70­80%. Simply put, this unit preconditions the outdoor air to save money on heating and cooling costs. These particular units also have cooling and heating options available after the recovery wheel to further condition the fresh air.
Supplemental Installation, Operation and Maintenance Manuals
Refer to the following Installation, Operation and Maintenance Manuals for additional details:
Part #463687 — Centrifugal Fan
Part #461006 — Indirect Gas-Fired Furnaces for Energy Recovery Units, Model PVF
Part #469690 — Microprocessor Controller
Installation, Operation and Maintenance Manuals can be found online at www.greenheck.com
General Installation, Operation and Maintenance (IOM) Information
The VER model energy recovery unit is designed with semi-custom versatility in mind. This quality allows for the selection of several component options. Please be aware that this IOM is comprehensive and includes information for all the potential options offered for this product line. Included options will vary on each unit. Please pay special attention to the specific unit in question when reviewing the information in this manual.
The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook.
Adequate space should be left around the unit for piping coils and drains, filter replacement, and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.
See Service Clearances/Access Panel Locations section for more details.
Installation Concerns for Units with Packaged DX
Unobstructed airflow to the condensing section must be maintained at all times to ensure proper operating efficiency and capacity of the cooling system. Unit placement should allow proper airflow over the condensing section. The unit may not operate properly and damage may occur to the system if there is coil starvation (lack of air over condenser) or warm air recirculating back through the condensing coil. Recirculating air is caused when the unit is placed near obstacles that can redirect exhaust air from the condensing fans, back around to the coil inlet. Overhangs or walls near the condensing section are two examples.
Another consideration when placing the unit is prevailing wind direction. The condensing coil operation can be significantly affected when winds are blowing continuously and directly at the condensing coil. On hot days, the wind will help the system by providing extra flow over the coil. But on cooler days, that same wind may overcool the refrigerant, and cause hot gas bypass to operate more frequently, causing higher operating costs. Therefore, avoiding direct winds will provide a more stable operation of the system throughout the cooling season.
Lack of air over the coil can reduce efficiencies and affect system operation. Do not allow debris (such as leaves and trash), to accumulate on or near the unit. Keeping debris clear of the unit will ensure minimal obstruction to the coils, keeping efficiencies and operation closer to design. The unit typically should not operate when snow is present. In the event this is possible, make sure all snow is clear of the coil and condensing fans prior to operating the unit.
If more than one unit is being installed, make provisions so discharge air from either the condensing fans or exhaust fan of the unit do not discharge towards another unit’s intake. Also, OA intake and condensing sections should be spaced as too allow proper airflow to each unit helping ensure the units operate as intended.
VersiVent Energy Recovery Unit
4
Page 5
Where the supply or warm air duct passes thru a
E
G
H
F
A
B
C
D
Return Air Intake
Supply Air Discharge
combustible roof, a clearance of one inch must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A.
Handling Concerns for Units with Packaged DX
While this unit was constructed with quality and dependability in mind, damage still may occur during handling of the unit for installation. Exercise extreme caution to prevent any damage from occurring to the refrigerant system. This unit contains a system pressurized with refrigerant that if damaged, could leak into the atmosphere or cause bodily harm due to the extreme cold nature of expanding refrigerant. Use protective equipment such as gloves and safety glasses to minimize or prevent injury in case of a system leak during installation.
Lifting
1. Before lifting, be sure that all shipping material has been removed from unit.
2. To assist in determining rigging requirements, weights are provided in the Unit Weights & Dimensions section on page 6.
3. Unit must be lifted by all lifting lugs provided on base structure.
4. Rigger to use suitable mating hardware to attach to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent damage to the cabinet by the lift cables.
Recommended Roof Opening
Refer to weight and dimension data to determine the exact location of the section containing the outdoor air discharge opening. If the unit is equipped with an Indirect Gas Heater (IG) section the outdoor air discharge opening will be in that section; if not, it will be in the blower section. The return air intake will be consistent for all units. The dimensions of these openings and their locations are illustrated below.
VER-45 A B C D E F G H
1 56.9 4.7 51.5 15.9 26.9 42.7 3.3 11.8 2 56.9 4.7 51.5 15.9 33.8 34.1 7.4 14.4 3 56.9 4.7 51.5 15.9 33.8 34.1 35.3 14.4 4 56.9 4.7 51.5 15.9 26.9 42.7 31.2 11.8
VER-65 A B C D E F G H
1 59.9 6.3 56.1 15.9 29.9 51.9 2.7 10.3 2 59.9 6.3 56.1 15.9 30.9 49.9 7.3 7.1 3 59.9 6.3 56.1 15.9 30.9 49.9 35.2 7.1 4 59.9 6.3 56.1 15.9 29.9 51.9 30.6 10.3
VER-90 A B C D E F G H
1 77.9 4.7 99.2 15.9 33.8 61.9 2.0 12.7 2 77.9 4.7 99.2 15.9 33.8 51.9 7.5 17.7 3 77.9 4.7 99.2 15.9 33.8 51.9 35.3 17.7 4 77.9 4.7 99.2 15.9 33.8 61.9 29.9 12.7
All dimensions are in inches. IG = Indirect Gas Furnace; PDX = Packaged DX Cooling 1 = Any unit without IG and PDX.
Blower Module is at the end of the unit. 2 = Any unit with IG that does not have PDX. 3 = Any unit with IG and PDX 4 = Any unit without IG and with PDX
When cutting only duct openings, cut opening one inch (25 mm) larger than duct size to allow clearance for installation. Area enclosed by roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R” value of at least five. If area within curb is open, higher radiated sound levels may result.
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
10. Check to be sure that gasketing has been applied to the curb prior to lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A. Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the corresponding ductwork. Be sure to allow for the recommended service clearances when positioning opening (see Service Clearances). Do not face the outdoor air intake of the unit into prevailing wind and keep the intake away from any other exhaust fans. Likewise, position the exhaust discharge opening away from outdoor air intakes of any other equipment.
VersiVent Energy Recovery Unit
5
Page 6
Unit Weights & Dimensions
A
W
I
B CD*
L*
EF G
Condensing Coil
Electrical Box
4-inch Final Filters
2-inch Filters
2-inch Filters
Wheel Cassette
Outdoor Air Intake
Exhaust Air Discharge
Return Air Intake
Supply Air Discharge
A
W
I
H
B CD*
L*
EF G
Condensing Coil
Electrical Box
4-inch Final Filters
4-inch Final Filters
2-inch Filters
2-inch Filters
2-inch Filters
2-inch Filters
Wheel Cassette
Wheel Cassette
Outdoor Air Intake
Outdoor Air Hood
Exhaust Air Discharge
Return Air Intake
Supply Air Discharge
Intake
Section
Wheel
Section
Optional
Coil Section
Blower
Section
Optional
IG Heater Section
Optional
Condensing Section
Condensing Coil
Drain Pan Connection
IG Gas Connection
Plan View
Elevation View
D*
D1 D2 D3 D4
D* Coil Module Options
DX + EH + HGRH
E F G H I W L*
HW = Hot Water
CW = Chilled Water
DX = Direct Expansion
EH = Electric Heat
HP = Wrap-around Heat Pipe
HGRH = Hot Gas Reheat
^Weight
see
note
Unit Size
VER-45 16.381 28.146 44.627 30.159 36.159 44.159 50.275 36.312 47.571 63.964 65.851 18.780 69.987
VER-65 16.381 30.825 46.597 30.159 36.159 44.159 50.275 38.124 47.571 65.958 72.098 23.358 76.246 6300
VER-90 16.381 34.825 85.658 30.159 36.159 44.159 50.275 41.312 47.571 65.958 65.851 23.358 91.010 7250
All dimensions shown in inches. *L Sum the lengths of the appropriate modules to get the total length of the unit. ^Weight: The weights shown are a worse case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal
weights added together with the largest fans, coils and heaters for the unit.
D1 D2 D3 D4
HW HW + DX CW + HP HW + CW + HP
CW HW + CW DX + HP HW + DX + HP
DX EH + CW DX + HGRH EH + DX + HP
EH EH + DX DX + HW + HGRH EH + CW + HP
A B C
(lbs.)
4900
VersiVent Energy Recovery Unit
6
Page 7
Rail and Roof Curb Mounting
AB CD
Return Air
Intake
Supply Air Discharge
Rails are positioned in random places. See table for proper location
Rail Mounting and Layout
• RailsdesignedtohandletheweightoftheVER
should be positioned as shown on the diagram (rails by others).
• Makesurethatrailpositioningdoesnotinterfere
with the supply air discharge opening or the return air intake opening on the VER unit.
• Railsshouldrunthewidthoftheunitandextend
beyond the unit a minimum of 12 inches on each side.
• Setunitonrails.
Isometric View
Roof Curb Mounting
Roof curb details, including duct location dimensions, are available on VER roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a knockdown kit (includes duct adapter) and require field assembly (by others). Assembly instructions are included with the curb.
2. Install Curb Locate curb over roof opening and fasten in place. (Refer to Recommended Roof Openings). Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper coil drainage and unit operation, it is important that the installation be level. Shim as required to level.
3. Install Ductwork
Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
4. Set the Unit
Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.
Side View
Unit Size A B C D
VER-45 53.3 16
VER-65 58.1 16
VER-90 105.3 16
All dimensions shown in inches. IG = Indirect Gas
CS = Condensing Section
33.8 w/IG 27 w/o IG
31.0 w/IG 30 w/o IG
33.8 w/IG 34 w/o IG
9.2 IG w/o CS; 37.1 IG w/CS
5.2 w/o IG and CS
33.1 w/o IG and w/ CS
9 IG w/o CS; 36.9 IG w/CS
4.6 w/o IG and CS
32.5 w/o IG and w/ CS
9.2 IG w/o CS; 37.1 IG w/CS
3.7 w/o IG and CS
31.6 w/o IG and w/ CS
VersiVent Energy Recovery Unit
7
Page 8
4-inch Final Filters
2-inch Filters
2-inch Filters
Wheel Cassette
Outdoor Air Hood
Intake
Section
Wheel
Section
Optional
Coil Section
Blower Section
Optional
IG Heater Section
Optional
Condensing Section
Condensing Coil
Drain Pan Connection IG Gas Connection
ABC* D
L*
E F
Curb Outside Dimensions and Weights
Side of Unit
Recommended 2-inches of Insulation
Roof Curb
1 in .
1 in .
2½ in.
1.195 in.
1 in .
W - 3.75 inches
L* - 3.75 inches
Elevation View
Subtract 3.75 inches from dimensions W & L* to get the outside curb dimensions.
Unit Size
A B
C1 C2 C3 C4
VER-45 28.146 44.627 30.159 36.159 44.159 50.275 36.312 47.571 27.909 69.987
VER-65 30.825 46.597 30.159 36.159 44.159 50.275 38.124 47.571 27.909 76.246 473
C*
D E F W L*
see
note
Curb Weight^
(lbs.)
447
VER-90 34.825 85.658 30.159 36.159 44.159 50.275 41.312 47.571 27.909 91.010 621
All dimensions shown in inches. L* — Sum up the applicable section dimensions (A–F) for your unit to get the overall length. ^ — Curb weights shown are for the worst case scenario (largest curb) possible for each size unit.
C* Coil Module Options
C1 C2 C3 C4
HW HW + DX CW + HP HW + CW + HP
CW HW + CW DX + HP HW + DX + HP
DX EH + CW DX + HGRH EH + DX + HP
EH EH + DX DX + HW + HGRH EH + CW + HP
DX + EH + HGRH
HW = Hot Water EH = Electric Heat
CW = Chilled Water HP = Wrap-around Heat Pipe
DX = Direct Expansion HGRH = Hot Gas Reheat
Curb Cap Details
VersiVent Energy Recovery Unit
8
Page 9
Electrical Information
The unit must be electrically grounded in accordance with the current National Electrical Code, ANSI/NFPA
70. In Canada, use current CSA Standard C22.1, Canadian Electrical Code, Part 1. In addition, the installer should be aware of any local ordinances or electrical company requirements that might apply. System power wiring must be properly fused and conform to the local and national electrical codes. System power wiring is to the unit main disconnect (door interlocking disconnect switch standard on most units) or distribution block and must be compatible with the ratings on the nameplate: supply power voltage, phase, and amperage (Minimum Circuit Amps - MCA; Maximum Overcurrent Protection ­MOP). All wiring beyond this point has been done by the manufacturer and cannot be modified without affecting the unit’s agency / safety certification.
If field installing an additional disconnect switch, it is recommended that there is at least four feet of service room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect, use dual element time delay fuses and size according to the rating plate.
Field Power Connection: All power and control connections should be run through the floor or side panel.
CAUTION
The VersiVent Roof lining contains high voltage wiring. To prevent electrocution do not puncture the interior or exterior panel of the roof.
If power supply is desired through bottom of unit, run the wiring through the curb, cut a hole in the cabinet bottom, and wire to the disconnect switch. Seal penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent requirements for the system to operate properly. Voltage supply and voltage imbalance between phases should be within the following tolerances.
If the power is not within these voltage tolerances, contact the power company prior to operating the system.
Voltage Supply: See voltage use range on the rating plate. Measure and record each supply leg voltage at all line disconnect switches. Readings must fall within the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive voltage imbalance between phases will cause motors to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded voltage measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
CAUTION
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105ºC.
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect switch open.
For units with a gas furnace, if you turn off the power supply, turn off the gas.
Most factory supplied electrical components are pre-wired. To determine what electrical accessories require additional field wiring, refer to the unit specific wiring diagram located on the inside of the unit control center access door. The low voltage control circuit is 24 VAC and control wiring should not exceed
0.75 ohms.
Refer to Field Control Wiring Length/Gauge table for wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft. 18 200 ft. 16 300 ft. 14 450 ft. 12
Minimum
Wire Gauge
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field supplied conduit does not interfere with access panel operation.
If wire resistance exceeds 0.75 ohms, an industrial­style, plug-in relay should be added to the unit control center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip (refer to Typical Control Center Components). The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
Note: Standard factory installed electric post-
heaters have their own disconnect separate from the unit disconnect. Thus, each electric post-heater requires its own separate power connection.
VersiVent Energy Recovery Unit
9
Page 10
Control Center Components
1
8
7
5
6
18
9
2
3 4 19
17
16
11
12
10
13
15
14
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter - Exhaust Air Fan
3. Motor Starter - Supply Air Fan
4. Motor Contactor - Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors*
8. Grounding lug
9. Distributor block*
10. Compressor fuse blocks*
11. Compressor contactors*
12. Condensing fan contactors*
13. Compressor relay*
14. Terminal block*
15. Compressor cycle timers*
Optional Control Center Components
16. DDC controller*
17. Dirty filter pressure switches*
18. Terminal block
19. Energy recovery wheel VFD*
*Not always provided
Electric Heater Application/Operation
Factory installed electric heaters can be provided for preheat and/or post-heat. An electric preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. An electric post-heater warms the air leaving the energy recovery wheel to a user specified discharge temperature. Electric heaters are available in 208, 230, or 460 VAC (refer to heater nameplate for voltage).
Preheaters: Preheaters are standard as two-stage step control. Step control heaters are designed with multiple stages made up of equal increments of heating capability. For example a 10 kW heater with two stages will be composed of two 5 kW stages. Preheaters are single point wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the outdoor airstream after the preheater to turn the preheater on. See Frost Control Application/Operation for typical set points. If the temperature falls below the set point and the wheel pressure drop sensor is triggered, the first stage of the preheater will turn on. If the first stage does not satisfy the set point, the second stage will also turn on.
The pre-heater is single point wired to the VER control center. Access to the preheater control panel is through the outdoor air intake.
Post-heaters: Post-heaters are standard as SCR control. Post-heaters are not single point wired (see Electrical Connections). A temperature sensor (with field adjustable set point) is mounted in the outdoor airstream after the post-heater. A SCR heater provides an infinitely modulating control of the heat to provide an accurate discharge temperature. A call for heat is required to turn the post-heater on.
The post-heater is not single point wired to the VER control center. Separate power must be supplied to the post-heater disconnect located in the unit control center.
10
VersiVent Energy Recovery Unit
Unit Accessories
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory mounted.
Exhaust Weatherhood
The exhaust weatherhood is shipped separately as a kit with its own instructions.
Dampers
Backdraft dampers are always included as an integral part of the exhaust hood assemblies. Motorized outdoor air and exhaust air dampers are optional and are factory mounted (and wired) at the intake.
Page 11
Service Clearances
TL
TRTR
TL
TR
TL
TR
TL
TRTR
TL
TL
TR
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
ACCESS
PANEL
A
B
C
D
VER-90
ONLY
VER-45, 65 and 90 units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances, refer to drawings for these dimensions.
Additional clearances for units with packaged DX
Clearances must be maintained on all sides of this unit. This especially is true with the top of this unit. Hot air is being discharged through the condensing fans during operation, and the more clearance available, the better the chance of avoiding recirculation or coil starvation. This unit should never be placed under an overhang or inside a building. A minimum of 48 inches over the condensing fans is recommended.
Minimum 48 inches clearance
Minimum 24 inches
Condensing Coil Intake
clearance
Keep this area clear
Unit Clearances
Unit Size A B C D
VER-45 65 42 36 24
VER-65 70 42 36 24
VER-90 65 42 65 24
All dimensions shown in inches.
Access Panels may change depending on options selected.
VersiVent Energy Recovery Unit
11
Page 12
Access Panel Descriptions and Locations
Following is a list of items accessible through the access doors shown on the diagrams. Some items are optional and may not have been provided.
#8 – Supply Blower
#9 – Compressors
8
#6 – Control Panel
#2 – OA Intake Damper
and Electric Preheat
2
3
4
1
9
9
#7 – IG Furnace
Control Center
1. Aluminum mesh filters (intake hood)
2. Outdoor air intake damper Electric pre-heater
3. Exhaust blower, motor, and drives
4. Energy recovery wheel, motor, belt, and seals Exhaust air filters Exhaust air intake damper (optional) Outdoor air filters Frost control sensors (optional) Economizer sensors (optional)
5. Coil access / drain pan / final filters Bypass damper (optional)
#5 – Packaged DX
Coil and Final Filter
5
6
7
#3 – Exhaust Blower
#4 – Filter & Wheel
6. Control center All electrical controls VFD for energy recovery wheel (optional)
7. Indirect gas furnace control center
8. Outdoor air blower, motor, and drives (with indirect gas furnace) Electric post-heater control center (optional)
9. Compressor(s) – refer to Refrigeration System Section for components in compressor compartment (optional)
VersiVent Energy Recovery Unit
12
Page 13
Component Location
3
12
2
1
6
7
8
9
4
5
11
10
1. Supply blower
 •Plenumfan   •Adjustablemotormountforbelttensioning   •Adjustablesheavesforspeedcontrol
2. Removable energy recovery wheel segments
3. Energy recovery wheel cassette
 •OnewheelformodelVER-45andVER-65   •TwowheelsformodelVER-90
4. Optional supply weatherhood with 2 inch aluminum mesh filter
5. Optional Electric Preheat Frost Control
6. Optional supply and exhaust air filter racks for 2-inch MERV 8, 30% efficient
7. Optional Final Filters
 •2-inchMERV8 30%efficient   •4-inchMERV11 65%efficient   •4-inchMERV13 85%efficient
8. Coil section optional equipment.
Not all items depicted above.
 •PackagedorsplitDXcoolingcoil–DX   •Hotgasreheatcoil–HGRH   •Chilledwatercoil–CW   •Wraparoundheatpipe–HP   •Hotwatercoil–HW   •Electricheat–EH   •Indirectgasfurnace–IG;locateddownstream
of Plenum Supply Fan
9. Vibration isolators (quantity 4 per blower)
 •SpringIsolators—SupplyFan   •NeopreneIsolators—ExhaustFan(not shown)
10. Compressor(s)
11. Condensing coil
12. Condensing fans
VersiVent Energy Recovery Unit
13
Page 14
Coil Application Recommendation for Units with Heating or Cooling Options
Factory installed cooling and heating components are mounted in the coil section of the unit. The coil section is downstream of the energy wheel on the supply air side of the unit.
Note the coil connection locations on the picture. Coil connections are located external to the unit as shown. Coil connections that are not external have been ordered from the factory with interior coil connections.
Note: DX coil liquid connection is internal to units.
Water Coils
1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Water connections are male NPT iron pipe. When installing couplings, do not apply undue stress to the connection extending through the unit. Use a backup pipe wrench to avoid breaking the weld between coil connection and header.
2. Connect the water supply to the bottom connection on the air leaving side and the water return to the top connection on the air entering side. To insure proper venting, an external air vent in the piping is recommended. Connecting the supply and/or return in any other manner will result in very poor performance. Be sure to replace factory installed grommets around coil connections if removed for piping. Failure to replace grommets will result in water leakage into the unit and altered performance.
3. The air vent at the uppermost point should be temporarily opened during system start-up to release all of the air from the coil. To maintain heat transfer capacity, periodically vent any air in coil.
4. Water coils are not normally recommended for use with entering air temperatures below 40ºF; however, the energy recovery wheel maintains a pre-coil temperature higher than 40ºF. No control system can be depended on to be 100% safe against freeze-up with water coils. Glycol solutions or brines are the only safe media for operation of water coils with low entering air conditions.
Continuous water circulation through the coil at all
times is highly recommended.
5. Pipe sizes for the system must be selected on the
Water
Coil
Connections
basis of the head (pressure) available from the circulation pump. The velocity should not exceed 6 feet per second and the friction loss should be approximately 3 feet of water column per 100 feet of pipe.
6. For chilled water coils, the condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Drain Trap section.
Direct Expansion (DX) Coils for units with a split DX System
1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Undue stress should not be applied at the connection to coil headers.
2. When connecting suction and liquid connections, make sure the coil is free from all foreign material. Make sure all joints are tight and free of leakage. Be sure to replace factory installed grommets around coil connections if removed for piping.
Direct Expansion (DX) Coil for units with Packaged DX System
1. The condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Drain Trap section.
VersiVent Energy Recovery Unit
14
Page 15
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Length of Straight Duct
GOOD
POOR
GOODPOOR
Tu rning
Vanes
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Tu rning
Vanes
Drain Trap
4 in.
2 in.
Ductwork Connections
Cooling coils are provided with a stainless steel drain pan with 1-inch male NPT drain connection. A drain trap must be connected to the drain connection to allow excess water to flow out of the drain pan. More importantly, though, due to the negative internal static of the cooling coil compartment, installing the drain trap prevents outdoor air from being pulled into the drain pan and consequently forcing water out of the pan and into the unit.
To ensure the drain trap works properly, the trap height must account for the difference in static pressure between ambient conditions outside the unit and the internal negative pressure of the cooling coil compartment. For energy recovery units, an assumption of 3.0 in. wg differential will be sufficient. This would require a trap design as shown. If the internal static is believed to be higher, consult factory.
Supply Fan:
The supply fan in this unit is a plenum style fan. The discharge opening dimensions are provided. For proper fan performance, match the duct size to the dimensions listed. Installation of all ducts should be done in accordance with SMACNA.
Supply Fan Discharge Opening Dimensions
Supply Air
Model
Discharge Location
Top End Bottom
VER-45 38.5 x 30 41.8 x 27
VER-65 50 x 31 50 x 31
VER-90 62 x 34 59.7 x 35
All dimensions shown in inches.
See diagram in Recommended Roof Openings section (page 5)
*
for the Bottom Discharge opening sizes.
*
*
*
Length of
Straight Duct
(Supply Fan)
48
60
60
Exhaust Fan
The exhaust fan in this unit is a forward curved fan. Good and Poor fan-to-duct connections are shown below. Airflow out of the fan should be directed strait or curved the same direction as the fan wheel rotates. Poor duct installation will result in low airflow and other system effects.
Refer to local codes to determine drainage requirements. If draining onto to roof, place a drip pad below drain to protect roof. If draining onto roof is not acceptable, a drain line must be attached to the trap. The drain line must be pitched away from the unit at least 1/8-in. per foot. On longer runs, an air break should be used to ensure proper drainage. Local codes may require drainage into a waste water system.
Drainage problems not only occur from improper drain trap design, but also from lack of maintenance of the cooling coil compartment. Algae can form in the drain pan and trap and cause reduced water flow, which can in turn result in backup into the system. Regular maintenance will prevent this from occurring. If the drains have a clean-out opening, be sure to close the opening after cleaning.
Recommended Exhaust Fan Discharge Duct Size
Length of
Straight Duct
(Exhaust Fan)
Model Duct Size
Exhaust
Blower Size
VER-45 20 x 20 12 48
VER-65 28 x 28 15 60
VER-90 32 x 32 18 60
All dimensions shown in inches.
• Recommendedductsizesarebasedonvelocitiesacrossthe
cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.
• Straightductlengthswerecalculatedbasedon100%effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
VersiVent Energy Recovery Unit
15
Page 16
A1 B1 15
16 18 A2
0.20
0.41.0
0.60.8
0.20
0.41.0
0.60.8
T1
T2
T21 MIN
T11 MIN
Timer Scale
Dip Switch
Optional Accessories
Frost Control Application/Operation
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:
1. Timed Exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control All of these options are provided with a thermostat
(with probe) mounted in the outdoor air intake compartment and a pressure sensor to monitor pressure drop across the wheel.
Frost Threshold Temperatures
Indoor RH @ 70°F Frost Threshold Temp
20% -10º F
30% -5º F
40% 0º F
The typical temperature setting corresponds to the indoor air relative humidity as shown in the Frost Threshold Temperatures Table and represents when frost can occur. An increase in pressure drop would indicate that frost is occurring. Both the pressure sensor AND the outdoor air temperature sensor must trigger in order to initiate frost control. The two sensors together insure that frost control is only initiated during a real frost condition. Field wiring of a light (or other alarm) between 6 & C in the control center will notify personnel when unit is in frost control mode (refer to Remote Panel Wiring schematics section for wiring details). The following explains the three options in more detail.
Timed exhaust frost control includes a timer in addition to the thermostat and wheel pressure sensor. When timed exhaust frost control is initiated, the timer will turn the supply blower on and off to allow the warm exhaust air to defrost the energy recovery wheel. Default factory settings are 5 minutes off and 30 minutes on. Use the following test procedure for troubleshooting.
Testing (refer to Timer Faceplate drawing below)
• Jumperthewheelpressureswitchintheunit
control center. Set the Timer Scale for T1 and T2 to 1 minute. Set the Timer Settings for T1 and T2 to
1.0. Set the dip switch to the down position. (normal position)
• Turnthetemperature
sensor up as high as possible. The supply blower should cycle on for one minute, then turn off for one minute.
VersiVent Energy Recovery Unit
16
• Aftertesting,settheTimerScaleasfollows: T1 = 10 minutes, T2 = 1 hour
• SettheTimerSettingsasfollows: T1 = 0.5, T2 = 0.5 The timer is now set for 5 minutes off and 30 minutes on. Remember to remove the jumper.
Electric preheat frost control includes an electric heater (at outdoor air intake) and an airflow pressure switch (located at the preheater) in addition to the thermostat and pressure sensor on wheel. (Refer to Electric Heater Application/Operation for electric preheater location). When electric preheat frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel to avoid frosting. Use the following test procedure for troubleshooting.
Testing:
• Turnthethermostatashighasitwillgoand
jumper the wheel pressure sensor. The heater should turn on.
• Ifitdoesn’t,eitherputtheoutdoorairsidedoors
on or temporarily jumper the airflow pressure switch in the preheater control center to avoid nuisance tripping of the pressure switch. Also check the airflow switch pressure tap located at the supply discharge blower to ensure the tubing is connected and the tap is not blocked.
Remember to remove the jumpers.
Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure sensor. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed of the wheel. Reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air condition from reaching saturation, thus, eliminating condensation and frosting. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The temperature and pressure differential set points are set at the factory, but are field-adjustable (refer to VFD section for more information). The variable frequency drive will be fully programmed at the factory.
Page 17
Economizer Application/Operation
The energy recovery wheel operation can be altered to take advantage of economizer operation (free cooling). Two modes are available:
1. De-energizing the wheel
2. Modulating the wheel
Both modes above require a field supplied call for cool (R to Y1) in order to be activated.
De-energizing the wheel is accomplished with a signal from a Temperature or Enthalpy sensor mounted in the air intake compartment. This primary sensor will de-energize the energy wheel when the outdoor air temperature (factory default is 65ºF) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable set point. An Override temperature sensor is also furnished in the outdoor air intake compartment to deactivate economizer mode. The Override (with field adjustable set point) is set at some temperature lower than the primary sensor (factory default is 50ºF). Effectively, the two sensors create a deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned.
Testing
Temperature Sensor with Override
• TurnbothTemperatureand
Override thermostats down as low as they go. The wheel should be rotating.
• TurntheTemperatureSensor
up as high as it goes, and keep the Override sensor as low as it will go. The wheel should stop rotating.
• Turnbothsensorsashighastheywillgo.The
wheel should start rotating.
• SettheTemperatureSensoratdesiredpoint
for economizer operation to begin. Set the Override sensor at desired point for economizer operation to end (factory default is 65ºF and 50ºF, respectively).
Enthalpy Sensor with Override
• Turnunitpoweroff.Disconnect
C7400 Solid State Enthalpy Sensor from terminal So on the enthalpy controller. Also, disconnect the
620 ohm resistor from terminal Sr on the enthalpy controller. Turn unit power on. The LED on the enthalpy controller should light and the energy recovery wheel should not rotate.
•Turnunitpoweroff.Reconnect620
ohm resistor to terminal Sr on the
Enthalpy
enthalpy controller. Turn unit power
Controller
Temperature
Sensor with
Override
Enthalpy
Sensor with
Override
on. The LED on the enthalpy controller should not light and the energy recovery wheel should energize and rotate.
If these steps provide the results described, the enthalpy economizer is working properly.
• Turnunitpoweroff.ReconnectC7400solidstate
enthalpy sensor to terminal So.
Modulating the Wheel
In applications in which an internal heat gain is present in the space, the rotational speed of the energy wheel may be modulated (via variable frequency drive) to avoid overheating the space during the winter. The speed of the energy wheel will be controlled in response to the discharge temperature set point.
Sequence of Operation: The variable frequency drive is fully programmed at the factory (refer to VFD section for more information). A “call for cool” must be field wired to the unit (terminals provided in unit - refer to wiring diagram in unit control center) to allow for initiation of economizer mode. When the space calls for cooling, factory supplied controls will drive the following wheel operations:
TAO > T
TAO < T
and
TAO > T
TAO < T
and
TAO < T
RA
RA
SA
RA
SA
Wheel runs at full speed.
(maximum energy recovery)
Wheel is stopped.
(no energy recovery)
Wheel will modulate to maintain
discharge temperature.
Where (TOA) is the outdoor air temperature set point, (TRA) is the return air temperature set point, and (TSA) is the supply air discharge thermostat set point.
VersiVent Energy Recovery Unit
17
Page 18
Variable Frequency Drives for Energy Recovery Blowers
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
MPACAMAC+VA2A1PCP2P1
IGS-S+R-R+
V1000
MA MB MCACAMAC+VA1SCS5S4S3S2S1
J1000
OPTION 1 - 0-10 VDC CONTROL
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
USER TO PROVIDE ISOLATION AS REQUIRED
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
WIRED TO A1 (+) AND AC (COMMON)
0-10 VDC CONTROL SIGNAL (BY OTHERS)
10 VDC=60 Hz
0 VDC=30 Hz
A1 AC
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4 SC
NEITHER S4 OR S5 CONTACT CLOSED DRIVE SPEED = 60 Hz.
DRIVE SPEED = 40 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
S5 TO SC CONTACT CLOSED (BY OTHERS) DRIVE SPEED = 30 Hz.
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER n01 CHANGE TO 1
PARAMETER n22 FOR NEW 40Hz SETTING
PARAMETER n21 FOR NEW 60Hz SETTING
PARAMETER n23 FOR NEW 30Hz SETTING PARAMETER n01 CHANGE TO 0
USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided for modulating or multi-speed control of the blowers. One VFD is provided for each blower (supply air and
exhaust).TheVFD’sprovidedareeitherYaskawamodelV1000orJ1000.Refertothetablesinthissectionfor
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an example wiring diagram has been provided in this manual for reference). When making adjustments outside of the factory set points, refer to Yaskawa VFD instruction manual, which can be found online at www.drives.com. For technical support, contact Yaskawa direct at 1-800-927-5292.
18
VersiVent Energy Recovery Unit
Factory Set Points
Variable Frequency Drives (VFDs) for the blowers are factory setup to operate in one of the three following modes:
Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30 and 60Hz
Multi-speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
 •SCtoS4-Driverunsat40Hz  •SCtoS5-Driverunsat30Hz
CO2 Sensor: A digital contact closure from an
optional factory provided CO2 sensor sends the VFD to high or low speed depending on CO2 ppm levels at the sensor.
The terminal locations for Modulating (option 1) and Multi-speed (option 2) are shown on the left. Most of the set points in the VFDs are Yaskawa factory defaults. However, a few set points are changed at Greenheck and are shown in the tables on the next page. These settings are based on the VFD mode selected.
To gain access to change set points on the V1000 and
J1000drives,parameterA1-01needstobesetat“2”.
To prevent access or tampering with drive settings on either drive, change parameter A1-01 to “0”.
Drive Operation
SC to S1 contact for On/Off
A1 (0-10 VDC) referenced to AC. Can use +15 VDC
from +V
Page 19
Factory Set Points - continued
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory defaults go to parameter A1-01 and set it to “2”. Then go to A1-03 and change it to “1110” and press enter. The drive is now reset back to the settings programmed at Greenheck. This option is not
availableontheJ1000.
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
A1-01 Access Level 2 2
b1-17 VFD Start-Up Setting 1 1 C1-01 Acceleration Time 30 sec. 30 sec. C1-02 Deceleration Time 30 sec. 30 sec. C6-02 Carrier Frequency 1 1
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H3-04 Terminal A1 Bias 50% 50% A1-01 Access Level 0 0
MULTI-SPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
A1-01 Access Level 2 2
b1-01 Reference Source (Frequency) 0 0
b1-17 VFD Start-Up Setting 1 1
C1-01 Acceleration Time 30 sec. 30 sec.
C1-02 Deceleration Time 30 sec. 30 sec.
C6-02 Carrier Frequency 1 1
d1-01 Frequency Reference 1 60 Hz 60 Hz
d1-02 Frequency Reference 2 40 Hz 40 Hz
d1-03 Frequency Reference 3 30 Hz 30 Hz
d1-04 Frequency Reference 4 60 Hz 60 Hz
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H1-04
H1-05
H1-06
H3-10 A2 Not Used F NA
A1-01 Access Level 0 0
Multi-Function Input Sel 4
(Terminal S4)
Multi-Function Input Sel 5
(Terminal S5)
Multi-Function Input Sel 6
(Terminal S6)
Setting
V1000 J1000
Motor
FLA
V1000 J1000
Motor
FLA
3 3
4 4
5 NA
Motor
FLA
Setting
Motor
FLA
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C02 DROPS bELOW 700 PPM)
(FULL SPEED WHEN C02 RISES AbOVE 800 PPM)
Parameter
A1-01 Access Level 2 2
b1-01 Reference Source (Frequency) 0 0
b1-17 VFD Start-Up Setting 1 1
C1-01 Acceleration Time 30 sec. 30 sec.
C1-02 Deceleration Time 30 sec. 30 sec.
C6-02 Carrier Frequency 1 1
d1-01 Frequency Reference 1 60 Hz 30 Hz
d1-02 Frequency Reference 2 30 Hz 60 Hz
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H3-10 A2 Not Used F NA
A1-01 Access Level 0 0
Setting
V1000 J1000
Motor
FLA
Motor
FLA
Variable Frequency Drives for Energy Recovery Wheel
Optional factory installed VFD for the energy recovery wheel is programmed at the factory per the settings shown below for economizer and frost control modes.
TheVFDprovidedisaYaskawamodelJ1000.Refer
to the VFD instruction manual that ships with the unit when making adjustments.
Parameter Setting–J1000 A1-01 Access Level 2 b1-17 VFD Auto Start 1 C6-02 Carrier Frequency 2 d2-01 Ref Upper Limit 100% or 66%* d2-02 Ref Lower Limit 5% E2-01 Motor Rated FLA Motor FLA
E2-03 Motor No-Load Current
H1-02
H2-01
Multi-Function Input
(Terminal S2)
Multi-Function Output
(MA, MB, MC)
Economizer Signal Source (0-10 VDC)
H3-03
H3-04
L1-01 Elect Thermal Overload 2 L4-01 Frequency Detection Level 20 A1-01 Access Level 0
*36 inch wheel is 66% (40 Hz). All other wheels are 100% (60 Hz).
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
Must be less than
FLA
6
5
Setting
Honeywell
Module
0 100
99 0
Carel
Controller
VersiVent Energy Recovery Unit
19
Page 20
Rotation Sensor
The rotation sensor monitors energy recovery wheel rotation. If the wheel should stop rotating, the sensor will close a set of contacts in the unit control center. Field wiring of a light (or other alarm) between terminals R & 12 in the unit control center will notify maintenance personnel when a failure has occurred (refer to Remote Panel Wiring Schematics section for wiring details).
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the outdoor air filters, exhaust air filters or both. If the pressure drop across the filters exceeds the set point, the sensor will close a set of contacts in the unit control center. Field wiring of a light (or other alarm) to these contacts will notify maintenance personnel when filters need to be replaced.
The switch has not been set at the factory due to external system losses that will affect the switch. This switch will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to the unit control center or in unit control center.
To adjust the switch, the unit must be running with all of the access doors in place, except for the compartment where the switch is located (exhaust intake compartment). The adjusting screw is located on the top of the switch. Open the filter compartment and place a sheet of plastic or cardboard over 50% of the filter media. Replace the filter compartment door. Check to see if there is power at the alert signal leads (refer to electrical diagram). Whether there is power or not, turn the adjustment screw on the dirty filter gauge (clockwise if you did not have power, counterclockwise if you did have power) until the power comes on or just before the power goes off. Open the filter compartment and remove the obstructing material. Replace the door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for operation.
Setscrew (on front of switch) must be manually adjusted after the system is in operation.
Negative pressure connection is toward the ‘front or top’ of the switch. (senses blower side
of filters)
DDC Temperature Control Package
Temperature control package allows for stand-alone operation of energy recovery units provided with supplemental cooling and heating. Controller can be ordered for discharge or room control. Room control would require a room thermostat (or other call for heat or cool) be wired to the controller. A remote panel option is also available to allow set points and other controller parameters to be adjusted from a remote location. For additional information, refer to the controls catalog and Installation, Operation and Maintenance Manual.
CO2 Sensor
This accessory is often used to provide a modulating control signal to a variable frequency drive to raise and lower airflow in relationship to the CO2 levels in the space. This strategy is often referred to as Demand Control Ventilation and provides further energy savings to the system. Follow instructions supplied with sensor for installation and wiring details.
Service Outlet
120 VAC GFCI service outlet ships loose for field installation. Requires separate power source so power is available when unit main disconnect is turned off for servicing.
Vapor Tight Lights
Vapor tight lights provide light in the energy recovery unit. The lights are wired to a junction box mounted on the outside of the unit. The switch to turn the lights on is located in the unit control center. The switch requires a separate power source to allow for power to the lights when the unit main disconnect is off for servicing.
Positive pressure connection is toward the ‘back or bottom’ of the switch. (senses air inlet side of filters)
VersiVent Energy Recovery Unit
20
Page 21
Sensors Mounted by Factory
OAF-P
OAI
FROM
OUTSIDE
OA
FILTER
OAW-P
OAAW
COOL
COIL
ACC
HEAT COIL
OAF-A
SUPPLY
BLOWER
OAD
TO
INSIDE
TO
OUTSIDE
EF-A
EXHAUST
BLOWER
EAW
EW-P
RAI
RAF-P
RA
FILTER
FROM INSIDE
ENERGY WHEEL
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for the controls contractor to connect the Building Management System for monitoring purposes.
Temperature Sensors - 1K Ohm RTD
Drawing Labels Terminal Strip Labels
OAI OA/Supply Inlet Temp OAAW OA After Wheel ACC After Cooling Coil Temp OAD Supply Discharge Temp EAW Exhaust After Wheel Temp
Pressure Sensors (analog or digital)
Drawing Labels Terminal Strip Labels
OAF-P OA/Supply Filter Pressure OAW-P Outdoor Air Wheel Pressure RAF-P RA/Exhaust Filter Pressure EW-P Exhaust Wheel Pressure
Amp - Current Sensors (analog or digital)
Drawing Labels Terminal Strip Labels
OAF-A Supply Fan Amps EF-A Exhaust Fan Amps
VersiVent Energy Recovery Unit
21
Page 22
Remote Control Panel and Wiring
A
W1
12
7
6
Y2
Y1
G
C
R
Unit On/Off
Econ/First Stage Cooling
Second Stage Cooling
Heat
Night Setback Timer
Night Setback Switch
Terminal Block
in unit
Control Center
G
C
R
7-Day Timer
S1 - Unit On/Off
Terminal Block
in Unit
Control Center
G
C
R
On Off
BMS
Auto
Terminal Block
in unit
Control Center
C
NC
NO
C
NC NO
12
6
7
W1
Y1
Y2
G
R
C
Dirty Filter
Rotation Sensor
Frost Control
Unit On/Off
Economizer
PS2
PS3
NC
C
NO
NC
C
NO
Dirty Filter
PS2
PS3
Hot
L1
Schematics
The remote panel is available with a number of different alarm lights and switches to control the unit. The remote panel ships loose and requires mounting and wiring in the field.
The remote panel is available with the following options:
 • Uniton/offswitch  • Uniton/offlight  • 7-daytimeclock  • Hand/off/autoswitch  • Dirtylterlight  • Economizerlight  • Frostcontrollight  • Wheelrotationsensorlight
Refer to Electrical Connections section for Field Control Wiring recommendations.
Indicator Lights powered by the VER Unit
7-Day Timer or On/Off Switch
Dirty Filter Indicator (power by others)
For 7-Day Timer, use blue and black wires. Red wires should be capped off.
Refer to Pressure Switch for voltage and load ratings.
Hand/Off/Auto Switch
Heating/Cooling Switch & Night Setback Switch/Timer
Hand/Off/Auto Switch allows the unit to “Off” - off “On” - Manual Operation “Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.
VersiVent Energy Recovery Unit
22
Page 23
Wiring Diagram
ENERGY WHEEL
FA CTORY SUPPLIED AND WIRED
G
MULTI-VOLTAGE PRIMARY 24 SECONDARY
TR1
C
TO UNIT
MAIN POWER
L3
L2
L1
DS1
SUPPLY DAMPER
D2
ENERGY WHEEL
R1
R
4
S1
PS1
NO C COM NO
TS1
6
FROST CONTROL
A1T1A2
B1
16
15
T1
R1
LEGEND
C1 COOLING STAGE 1 RELAY C2 COOLING STAGE 2 RELAY CC COMPRESSOR CONTACTOR CF CONDENSING FAN CONTACTOR CH COMPRESSOR SUMP HEATER D DAMPER DB POWER DISTRIBUTION BLOCK DL DAMPER LIMIT SWITCH DS DISCONNECT SWITCH EC ECONOMIZER CONTROLLER FCS CONDENSOR F A N CYCLE SWITCH FU FUSES FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II) FZ1 FREEZE PROTECTION HG HOT GAS REHEAT VA L V E HPS HIGH PRESSURE SWITCH (MANUAL RESET) LPS LOW PRESSURE SWITCH PS1 WHEEL FROST PRESSURE SWITCH PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH R1 ENERGY WHEEL RELAY/CONTACTOR R2 OCCUPIED/UNOCCUPIED RELAY R3 EXHAUST BLOWER VFD RELAY R4 SUPPLY BLOWER VFD RELAY R5 MODULATING WHEEL FROST CONTROL RELAY R6 ECONOMIZER RELAY R7 COMPRESSOR INTERLOCK RELAY R8 EVAP RELAY (INDIRECT) R9 EVAP RELAY (DIRECT) R10 UNIT RELAY R11 POST HEAT RELAY R12 DEHUMIDIFICATION RELAY R13 ROOM CALL FOR HEAT RELAY R14 ROT A T ION SENSOR RELAY R15 ROT A T ION SENSOR RELAY S1 FAN SWITCH S2 ROTA T ION SENSOR (LOCATED BY WHEEL) S3 ROTA T ION SENSOR (LOCATED BY WHEEL) S4 CALL FOR HEAT SWITCH S5 OCC/UNOCC SWITCH - CLOSED=OCCUPIED/OPEN=UNOCCUPIED S6 CALL FOR COOL SWITCH (FIRST STAGE) S7 CALL FOR COOL SWITCH (SECOND STAGE) S8 CALL FOR DEHUMIDIFICATION SWITCH ST MOTOR STARTER T1 FROST CONTROL TIMER TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN. T4 ECONOMIZER WHEEL JOG TIMER TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC. T5 EVAP DELAY OFF TIMER T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) TR TRANSFORMER TS1 FROST CONTROL THERMOST A T (JUMPER - HEAT) CLOSES ON TEMP. DECREASE TYPICAL SETTING 5°F. TS2 ECONOMIZER LOW LIMIT THERMOST A T (JUMPER - HEAT) OPENS ON TEMP . DECREASE TYP. SETTING 20° OFFSET OR 50°F> TS3 ECONOMIZER UPPER LIMIT THERMOST A T (JUMPER - HEAT) CLOSES ON TEMP. DECREASE TYP. SETTING 65°F./2° DIFF. TS4 ROOM OVERRIDE SENSOR TS5 INLET AIR POST HEATER LOCKOUT THERMOST A T (AFTER WHEEL) CLOSES ON TEMP. DECREASE TYPICAL SETTING 65°F. TS6 INLET AIR COMPRESSOR LOCKOUT THERMOST A T (JUMPER-HEAT) OPENS ON TEMP . DECREASE TYPICAL SETTING 60°F./2° DIFF.
A2 A1
o FIELD WIRED
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM. IF RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY. USE 14 GAUGE MINIMUM WIRE THICKNESS FOR CONTROL WIRING.
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA
CAUTION:
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C. POWER MUST BE OFF WHILE SERVICING.
**
*
*
o
*
* *
*
* *
*
*
*
D1
EXHAUST DAMPER
GROUND
FROST CONTROL INDICAT OR
6 C
ROTA TION INDICA T OR
12 C
USER INTERFACE CONNECTIONS:
USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICA T OR DEVICES.
EXHAUST FA N
SUPPLY FAN
ST2
O.L.
MOTOR
MOTOR
ST1
O.L.
MOTOR(S)
ST1 O.L.
95 96
ST2 O.L.
95 96
ST1
A2 A1
ST2
A2 A1
SUPPLY FAN
EXHAUST FA N
ST2
13 14
54
CC2-NO
55
FCS1
(LOCATED IN CONDENSING FAN)
(LOCATED IN CONDENSING FAN)
56
1P2
CF2 O.L.
2P22P1
1P1
ST1-NO
CC1-NO
S7
Y2
51
COM NC
TS6
52
LPS1 HPS1
CF1 O.L.
53
21 24
11
R17
14
R7
T7
3
3
T6
CF2
CF1
A1A1A2
A2
CONDENSING FA N 2
CONDENSING FA N 1
COMPRESSOR INTERLOCKS
R7
CC2
CC1
A1
1
1
A2
COMPRESSOR 2
COMPRESSOR 1
COMPRESSOR 1
COMPRESSOR 2
CONDENSING FAN 1
CONDENSING FAN 2
CC1
CC2
CF1
CF2
CH1 CH2
DB1
*
*
*
*
o o
*
*
*
*
*
*
*
RETURN AIR SENSOR
620 OHM RESISTOR OR
S6
OUTDOOR AIR
SENSOR
3
SO+
SR+ SO
SR
Y1
1
TR
COM
4
2
5
TR1
6
NC
TS2
7
ECONOMIZER
ECONOMIZER CONTROL
R6
A1 A2
*
*
*
ECONOMIZER INDICAT OR
7 C
R6
21
12
EC
THERMOSTA T(S) TS1, TS2, TS6
24 VA C
THERMOSTAT CONTROLLER(S)
OA-SENSOR
SENSOR
COM
R14
21 12
S2
12
ROTATION SENSOR
R14
A2
A1
ROTATION SENSOR
BLUE
PINK
LT. BLUE
ORANGE
LT. BLUE
ORANGE
PURPLE
PURPLE
LT. BLUE
YELLOW
YELLOW
YELLOW
ORANGE
RED RED
REDRED
BROWN
RED RED
BROWN
BLACK BLACK BLACK
WHITE
YELLOW
5958
LPS2
57
HPS2
COMPRESSOR INTERLOCKS
R17
BLACK
A1 A2
CIRCUIT 1
CIRCUIT 2
FCS2
Following are several examples of typical wiring diagrams located in the unit control center. These wiring diagrams include a legend highlighting which accessories were provided with the unit. Factory wiring and field wiring are also indicated.
The example below includes:
 • FactoryControlsforEconomizerOperation  • EnergyRecoveryWheelRotationSensor  • MotorizedOutdoorAirandExhaustAirIntakeDampers  • TimedExhaustFrostControl  • PackagedDXControlandSafetyCircuit
Many other factory installed and wired accessories are available.
VersiVent Energy Recovery Unit
23
Page 24
ENERGY WHEEL
ENERGY RECOVERY
FACTORY SUPPLIED AND WIRED
G
MULTI-VOLTAGE PRIMARY 24 SECONDARY
TR1
C
TO UNIT
MAIN POWER
L3
L2
L1
DS1
SUPPLY DAMPER
D2
R
4
S1
R1
LEGEND
C1 COOLING STAGE 1 RELAY C2 COOLING STAGE 2 RELAY CC COMPRESSOR CONTACTOR CF CONDENSING FAN CONTACTOR CH COMPRESSOR SUMP HEATER D DAMPER DB POWER DISTRIBUTION BLOCK DL DAMPER LIMIT SWITCH DS DISCONNECT SWITCH EC ECONOMIZER CONTROLLER FCS CONDENSOR FAN CYCLE SWITCH FU FUSES FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II) FZ1 FREEZE PROTECTION HG HOT GAS REHEAT VALVE HPS HIGH PRESSURE SWITCH (MANUAL RESET) LPS LOW PRESSURE SWITCH PS1 WHEEL FROST PRESSURE SWITCH PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH R1 ENERGY WHEEL RELAY/CONTACTOR R2 OCCUPIED/UNOCCUPIED RELAY R3 EXHAUST BLOWER VFD RELAY R4 SUPPLY BLOWER VFD RELAY R5 MODULATING WHEEL FROST CONTROL RELAY R6 ECONOMIZER RELAY R7 COMPRESSOR INTERLOCK RELAY R8 EVAP RELAY (INDIRECT) R9 EVAP RELAY (DIRECT) R10 UNIT RELAY R11 POST HEAT RELAY R12 ROOM CALL FOR COOL RELAY R13 ROOM CALL FOR HEAT RELAY R14 ROTATION SENSOR RELAY R15 ENERGY WHEEL RELAY R16 HOT GAS REHEAT RELAY S1 FAN SWITCH S2 ROTATION SENSOR (LOCATED BY WHEEL) S3 ROTATION SENSOR (LOCATED BY WHEEL) S4 CALL FOR HEAT SWITCH S5 OCC/UNOCC SWITCH - CLOSED=UNOCCUPIED/OPEN=OCCUPIED S6 CALL FOR COOL SWITCH (FIRST STAGE) S7 CALL FOR COOL SWITCH (SECOND STAGE) S8 CALL FOR DEHUMIDIFICATION SWITCH S9 ROOM RESET SWITCH ST MOTOR STARTER T1 FROST CONTROL TIMER TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN. T2 ROTATION SENSOR TIMER T3 ROTATION SENSOR TIMER T4 ECONOMIZER WHEEL JOG TIMER TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC. T5 EVAP DELAY OFF TIMER T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) T8 COMPRESSOR MINIMUM ON TIMER (TYP. 5 MIN.) TR TRANSFORMER TS4 ROOM OVERRIDE SENSOR
o FIELD WIRED
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75
OHM. IF RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY.
USE 14 GAUGE MINIMUM WIRE THICKNESS FOR CONTROL WIRING.
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA
CAUTION:
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C. POWER MUST BE OFF WHILE SERVICING.
**
*
*
*
o
*
* *
*
*
*
*
*
D1
EXHAUST DAMPER
GROUND
EXHAUST FAN
SUPPLY FAN
ST2
O.L.
MOTOR
MOTOR
ST1
O.L.
MOTOR(S)
TO L1 AND L3 ON
CR IN IG FURNACE
ST1 O.L.
95 96
ST2 O.L.
95 96
ST1
A2 A1
ST2
A2 A1
SUPPLY FAN
EXHAUST FAN
ST2
13 14
A2
A1
R14
ROTATION SENSOR
R11
TO "A" AND "RH"
IN IG FURNACE
POST HEAT
*
14
21
A1
A2
G
NO1
NO2
NO3
13 14
ST1
4
C4
NO5
NO6
J13
J12
GO
J1
C1
G
NO4
12
NO7
C7
J14
VG
Y2
Y3
Y1
Y4
VG0
J4
IDC1
ID8
ID7
ID6
ID5
ID1
ID4
ID3
ID2
J5
BC5
B5
BC4
B4
+VDC
B3
B2
B1
J2
J3
DDC
CONTROLLER
NO8
NC8
C8
J15
R14
21 12
USER INTERFACE
ALARM NO/NC CONTACTS
ALARM
12
NOC
PS2
PS1
NO C
ST1-AUX
NO C
W1
TO NC ON T2
IN IG FURNACE
GND
TO NO ON T2
IN IG FURNACE
G
DDC SETUP CODE
X 0Y 1 1
R15
3 4
ENERGY WHEEL RELAY
S2
OAI
ACC
OAD
X
R15
1 2R1A2 A1
ENERGY WHEEL
*
R
PINK
LT. BLUE
PINK
YELLOW
BROWN
ORANGE
PURPLE
BLUE
YELLOW
ORANGE
YELLOWBROWN
LT. BLUE
BROWN
PURPLE
ORANGE
RED
ORANGE
YELLOW
PINK
BLUE
WHITE
BROWN
R8
11
RED
14
R7
11 14
RED
BROWN
CC2
CC1
COMPRESSOR 1
COMPRESSOR 2
CONDENSING FAN 1
COMPRESSOR 2
COMPRESSOR 1
CONDENSING FAN 2
CC1
CC2
CF1
CF2
CH1 CH2
DB1
RED
RED
CC2-NO
CC1-NO
HPS1LPS1
52 53
CONDENSING FAN 2
CONDENSING FAN 1
COMPRESSOR INTERLOCKS
A1
54
A1
A1
A2
CF2
A2
A2
CF1
R7
* * *
*
*
* *
*
* *
LPS2 HPS2
57
COMPRESSOR INTERLOCKS
58
A1 A2
R8
R7
21 24 2421
R8
2
FCS2
FCS1
55 56
Wiring Diagram
The wiring diagram below includes a Factory Mounted DDC controller. The DDC controller operates the unit based on a built-in program. Additional features shown are:
 • EnergyRecoveryWheelRotationSensor • IGFurnacePowerandControlOutput  • PackagedDXControlandSafetyCircuit • TemperatureandPressureSensors
The DDC setup code can be cross-referenced with the DDC Controller IOM (Part #469690) for specific control information.
24
VersiVent Energy Recovery Unit
Page 25
Sequence of Operation
Basic Unit
The VER units are pre-wired such that when a call for outside air is made (via field supplied 24 VAC control signal wired to unit control center), the supply fan, exhaust fan and energy wheel are energized and optional motorized dampers open. The VER units can be supplied with or without heating coils. Controls can be supplied by Greenheck or by the controls contractor. If supplied by the controls contractor, they would provide, mount, and wire any temperature controllers and temperature or relative humidity sensors required for the unit to discharge air at the desired conditions. However, temperature, pressure, and current sensors can be provided by Greenheck for purposes of monitoring via the Building Management System (see Optional Accessories section).
Summer Operation
Outdoor air is preconditioned (temperature and moisture levels are decreased) by the transfer of energy from the cooler, drier, exhaust air via the energy recovery wheel. Units supplied with cooling coils can further cool the air coming off the wheel and strip out moisture to levels at or below room design. A heating coil downstream of the cooling coil can reheat the air to a more comfortable discharge temperature to the space.
The VER model can be supplied with a wrap around heatpipe for additional precooling of the outdoor air prior to entering the cooling coil. The heatpipe also provides reheat after the cooling coil for applications where the outdoor needs to be provided at a space neutral condition.
Standard DX Sequence of Operation:
Unit without economizer
Ambient temperatures above 55ºF
• Firstcallforcool,theunitwillturnontherst
compressor.
• Onthesecondcallforcool,theunitwillturnon
the second compressor if available. (seven (7) or larger tonnage system).
Ambient temperatures below 55ºF
• DXsystemlockedoutandwillnotoperate.
Unit with economizer
With economizer conditions available and ambient temperature above 55ºF
• Firstcallforcool-theunitwillcheckifitcan
use economizer air. If it can, the wheel will shut off or modulate and the cooling coil will be de­energized.
• Secondcallforcool-theunitwillturnona
compressor to provide the space with further cooling.
With economizer conditions available and ambient temperature below 55ºF
• Firstcallforcool-theunitwillengageeconomizer
allowing free cooling down to minimum set point, factory set at 50ºF.
• Secondcallforcool-theDXsystemislockedout,
not allowing compressors to run below 55ºF. First stage of cooling will still operate unless ambient temperature drops below economizer set point.
Without economizer conditions available and ambient temperature above 55ºF
• Firstcallforcool-theunitwillturnoncompressor
one.
• Secondcallforcool-theunitwillturnonthe
second compressor if available. (10 or larger tonnage system).
Economizer Operation: Refer to Economizer Application/Operation section.
Winter Operation
Outdoor air is preconditioned (temperature and moisture levels are increased) by the transfer of energy from the warmer, more humid exhaust air via the energy recovery wheel. Units supplied with heating coils can further heat the air coming off the wheel to levels at or above room design.
Frost Control Operation: Refer to Frost Control Application/Operation section.
Rotation Sensor: Refer to Optional Accessories section
Dirty Filter Sensor: Refer to Optional Accessories section
CO2 Sensor: Refer to Optional Accessories section
DX Safety and General Control Sequence: To
prevent damage to the system, there is a safety loop incorporated into the controls. This loop includes a check to make sure the supply fan starter is pulled in, ambient temperature is above 55ºF, and the low­and high-pressure switches are not tripped out. After this loop is verified, a relay then pulls in to start the anti-cycle timer. (Typical setting is 3 minutes). Once the timer has counted down, only then can the compressor contact pull in. Once the compressor contact pulls in, the first stage of condensing fans turns on. If pressure in the condensing coil increases to a point at which more heat needs to be removed from the system, the fan cycle switch will close and the second stage of condensing fans turns on.
VersiVent Energy Recovery Unit
25
Page 26
Start-Up
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
Do not operate energy recovery ventilator without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to internal components may result and void warranty.
General factory information:
• Unitwasfactorytested.Allblowers,fans,
and compressors are set-up to run correct when supplied power. If any one fan is running backwards or the compressor is making loud noises, immediately turn off the power. Switch two leads on the incoming power to the disconnect. This will ensure proper operation of the unit. Failure to comply may damage the compressors and void the warranty.
• Donotjumperanysafetydeviceswhenoperating
the unit. This may damage components within or cause serious injury or death.
• Donotoperatecompressorwhentheoutdoor
temperature is below 40ºF.
• Donotshort-cyclethecompressor.Allow
5 minutes between “on” cycles to prevent compressor damage.
• Priortostartinguptheunit,powermustbe
energized for 24 hours without a call for cool to allow the compressor crankcase heaters time to boil off any liquid refrigerant present in the compressor.
• DXsystemischargedwithrefrigerant.Start-up
must be performed by EPA Certified Technician.
General Start-Up Information
Every installation requires a comprehensive start­up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed.
Unit Model Number _______________________________
(e.g. VER-65)
Unit Serial Number _______________________________
(e.g. 04C99999 or 10111000)
Energy Wheel Date Code __________________________
(e.g. 0450)
Compressor 1 Model Number ______________________
(e.g. ZR36-XXXXX)
Compressor 2 Model Number ______________________
(e.g. ZR36-XXXXX)
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check as items are
completed.
o Disconnect and lock-out all power switches
o Remove any foreign objects that are located in the
energy recovery unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and accessories for tightness.
o Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing. If rubbing occurs, refer to Start-Up section for more information.
o Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more information).
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood (refer to Routine Maintenance section).
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify control wire gauge (refer to the Electrical
Connections section).
o Verify diameter seal settings on the energy
recovery wheel (refer to Start-Up section for more information).
VersiVent Energy Recovery Unit
26
Page 27
oVerify proper drain trap installation (refer to Drain
Trap section).
oLook over the piping system. Inspect for oil at
all tubing connections. Oil typically highlights a leak in the system. If a leak is present, refer to the Maintenance section in this manual.
oInspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully straighten fins with a fin comb.
oIf there is an indirect gas-fired furnace in this unit,
refer to the PVF IOM provided with this unit for Pre Start-Up information.
For plenum or backward inclined fans, check the radial gap and overlap. Adjust if necessary.
Additional Information for Units with Packaged DX
oCheck condensing fans for any damage or
misalignment. Spin the blades and make sure they don’t contact any parts and are free turning without any resistance.
o This unit contains a crankcase heater for each
compressor which needs power supplied to it 24 hours prior to start-up. If start-up is scheduled in 24 hours, unlock the disconnect power and energize unit.
SPECIAL TOOLS REQUIRED
• VoltageMeter(withwireprobes)
• AmperageMeter
• PressureGauges–R410aRefrigerant
• TemperatureGaugescapableofmeasuringpipe
temperature
• Thermometer
• Inclinemanometerorequivalent
Start-Up Checklist
The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must be collected while the unit is running. In order to measure volts & amps, the control center door must be open, and the unit energized using a crescent wrench to turn the disconnect handle.
Start-Up Procedure
 • MakesurePreStart-Upchecklistiscomplete.  • JumperRtoG,RtoY1,andRtoY2onthe
control board.
 • Turnthedisconnecton.Ifyourunitcontains
compressors (optional), after 3 minutes they will energize. Make sure all fans and compressors are rotating in the correct direction.
WARNING
All motor(s) / compressor(s) have been checked for rotation. If blower rotation is incorrect, wiring must be changed at the disconnect to ensure all motor(s) / compressors are corrected.
Operation of scroll compressor(s) in this unit are directional and will be damaged if run with the wrong direction.
 • IfyourunitcontainsaPackagedDXsystem
(optional), allow the unit to run until the refrigerant system stabilizes. Approximately 1-2 minutes.
 • Takethefollowingmeasurementswhiletheunitis
running to ensure proper operation.
Additional Information for Units with Packaged DX
 • Turnthedisconnecton.After3minutes
compressors will come on. Make sure all fans and compressors are rotating the correct direction.
 • Allowtheunittorununtiltherefrigerantsystem
stabilizes. Approximately 1-2 minutes.
Start-Up Checklist
Check line voltage at unit disconnect _______ L1-L2 volts _______ L2-L3 volts _______ L1-L3 volts
Motor Amp Draw
  •SupplyFan •ExhaustFan
_______ L1 amps ______ L1 amps _______ L2 amps ______ L2 amps _______ L3 amps ______ L3 amps
Fan RPM _______ Supply Fan ______ Exhaust Fan
Correct fan rotation direction Supply Fan Yes / No Exhaust Fan Yes / No
Energy Wheel Motor _______ L1 amps _______ L2 amps _______ L3 amps
Electric Post-Heater Voltage _______ L1-L2 volts _______ L2-L3 volts _______ L1-L3 volts
VersiVent Energy Recovery Unit
27
Page 28
Start-Up Checklist (Units with Packaged DX)
Outdoor Air Temperature ________Deg. F.
Return Air Temperature ________Deg. F.
Outdoor Air Relative Temperature _________% RH
Return Air Relative Temperature _________% RH
CIRCUIT A
oCompressor: _______ L1 amps _______ L2 amps _______ L3 amps
_______ Crankcase Heater
Superheat _______Deg. F.
Should be between 8º and 12ºF.
Subcooling _______Deg. F.
Should be between 12º and 17ºF.
Discharge Pressure ________% RH
Should be between 300 and 500 PSIG
Suction Line Pressure ________ % RH
Should be between 100 and 135 PSIG
Liquid Line Temperature _______ Deg. F.
Suction Line Temperature _______ Deg. F.
Moisture Indicating Sight Glass Liquid Visible Yes / No Color of Center Dot Green / Yellow
Oil in Compressor Sight Glass Yes / No
Hot Gas Bypass Operational Yes / No
oCondensing Fan 1: _______ L1 amps _______ L2 amps _______ L3 amps
oCondensing Fan 2: _______ L1 amps _______ L2 amps _______ L3 amps.
CIRCUIT B
oCompressor: _______ L1 amps _______ L2 amps _______ L3 amps
_______ Crankcase Heater
Superheat _______Deg. F.
Should be between 8º and 12ºF.
Subcooling _______Deg. F.
Should be between 12º and 17ºF.
Discharge Pressure ________% RH
Should be between 300 and 500 PSIG
Suction Line Pressure ________ % RH
Should be between 100 and 135 PSIG
Liquid Line Temperature _______ Deg. F.
Suction Line Temperature _______ Deg. F.
Moisture Indicating Sight Glass Liquid Visible Yes / No Color of Center Dot Green / Yellow
Oil in Compressor Sight Glass Yes / No
Packaged DX units are provided fully charged with R410a refrigerant
VersiVent Energy Recovery Unit
28
Page 29
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit? Frost Control Application / Operation section: Setting Factory Default
Yes No Frost Control set point 5ºF
Differential 2ºF Timer Refer to IOM
Yes No Frost Control Modulating Refer to IOM
Economizer Application / Operation section:
Yes No Economizer (temperature)
Set point 65ºF
Offset 20ºF
Differential 2ºF
Yes No Economizer (enthalpy)
Set point D
Yes No Economizer (modulating) Refer to IOM
Optional Accessories section: Operational
Yes No Wheel Rotation Sensor Yes No N/A
Yes No OA Dirty Filter Sensor Yes No N/A
Yes No EA Dirty Filter Sensor Yes No N/A
Yes No CO2 Sensor Yes No N/A
Yes No Service Outlet Yes No N/A
Yes No Vapor Tight Lights Yes No N/A
Yes No Remote Control Panel Yes No N/A
Variable Frequency Drives section: Operational
Yes No Blower VFDs Yes No N/A
Yes No Wheel VFD Yes No N/A
Damper section: Operational
Yes No Outdoor Air Damper Yes No N/A
Yes No Exhaust Air Damper Yes No N/A
Yes No Night Setback Damper Yes No N/A
Yes No Indirect Gas Furnace (refer to the PVF IOM, Part #461006 for start-up information)
VersiVent Energy Recovery Unit
29
Page 30
Unit Start-Up
Belt Span
Deflection =
Belt Span
64
WRONG WRONG
WRONG CORRECT
WRONG WRONG
WRONG CORRECT
MOTOR
FA N
MOTOR
Overlap
Radial
Gap
A
Refer to Component section for component locations.
Fans
The VER models contain a plenum supply fan and a forward curved exhaust fan. The fans should be checked for free rotation. If any binding occurs, check for concealed damage and foreign objects in the fan housing. Be sure to check the belt drives per the start­up recommendations in the following section.
When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult Greenheck to determine if the unit can operate safely at the new conditions.
Supply Fan (Plenum Type)
The model VER contains one plenum supply fan located on the end of the unit opposite the outdoor air intake (see beginning of Unit Start-Up section for diagram of unit layout). Efficient fan performance can be maintained by having the correct radial gap and overlap. These items should be checked before start­up and after the fan has been in operation for 24 hours.
Radial Gap: Radial gap is adjusted by loosening the inlet cone/ring on the wheel. If additional adjustment is required to maintain a constant radial gap, loosening the bearing bolts and centering the wheel is acceptable as a secondary option.
Overlap: Proper overlap is obtained by loosening the wheel hub from the shaft and adjusting the wheel to maintain an “A” dimension.
Refer to Part #463687 ­Centrifugal Fan IOM for additional start-up and maintenance information regarding the QEP Plenum Supply Fan.
Exhaust Fans (Forward Curved Type)
The model VER contains one forward curved exhaust fan located on either side of the unit (see Basic Unit Operation). The forward curved fan should be checked for free rotation. If any binding occurs, check for concealed damage and foreign objects in the fan
VersiVent Energy Recovery Unit
30
Supply Fan
CAUTION
Plenum
Forward Curved
Radial Gap
and Overlap
“A” Dimension
Model
VER-45
VER-65
VER-90
Supply
Fan
QEP-15 5 ±1/8
QEP-18 6 3/8 ±1/8
QEP-18 6 3/8 ±1/8
QEP-20 7 ±3/16
QEP-20 7 ±3/16
QEP-24 8 5/8 ±1/4
Exhaust Fan
A Dimension
± Tolerance
(inches)
housing. Be sure to check the belt drives per the Belt Drive Installation section (Unit Start-Up) and per the Fan Belts section (Routine Maintenance).
Fan Performance Modifications
Due to job specification revisions, it may be necessary to adjust or change the sheave or pulley to obtain the desired airflow at the time of installation. Start-up technician must check blower amperage to ensure that the amperage listed on the motor nameplate is not exceeded. Amperage to be tested with access doors closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by Greenheck, have been carefully selected for the unit’s specific operating condition. Utilizing different components than those supplied could result in unsafe operating conditions which may cause personal injury or failure of the following components:
 •FanShaft • Bearings •Motor  •FanWheel • Belt
Tighten all fasteners and set screws securely and realign drive pulleys after adjustment. Check pulleys and belts for proper alignment to avoid unnecessary belt wear, noise, vibration and power loss. Motor and drive shafts must be parallel and pulleys in line (see diagrams in this section).
Belt Drive Installation
1. Remove the protective coating from the end of the fan shaft and assure that it is free of nicks and burrs.
2. Check fan and motor shafts for parallel and angular alignment.
3. Slide sheaves on shafts. Do not drive sheaves on as this may result in bearing damage.
4. Align fan and motor sheaves with a straight-edge or string and tighten.
5. Place belts over sheaves. Do not pry or force belts, as this could result in damage to the cords in the belts.
6. With the fan off, adjust the belt tension by moving the motor base. (See belt tensioning procedures in the Routine Maintenance section of this manual). When in operation, the tight side of the belts should be in a straight line from sheave to sheave with a slight bow on the slack side.
Page 31
Direction of Fan Wheel Rotation
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Airflow
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Forward Curved
Blower access is labeled on unit. Check for proper wheel rotation by momentarily energizing the fan. Rotation is determined by viewing the wheel from the drive side and should match the rotation decal affixed to the fan housing (see Rotation Direction figures). If the wheel is rotating the wrong way, direction can be reversed by interchanging any two of the three electrical leads. Check for unusual noise, vibration, or
overheating of bearings. Refer to the Troubleshooting section of this manual if a problem develops.
Fan RPM
Supply fan and exhaust fan will have an adjustable motor pulley (on 15 HP and below) preset at the factory to the customer specified RPM. Fan speed can be increased or decreased by adjusting the pitch diameter of the motor pulley. Multi-groove variable pitch pulleys must be adjusted an equal number of turns open or closed. Any increase in fan speed represents a substantial increase in load on the motor. Always check the motor amperage reading and compare it to the amperage rating shown on the motor nameplate when changing fan RPM. All access doors must be installed except the control center door. Do not operate units with access doors open or
without proper ductwork in place as the fan motors will overload.
Vibration
Excessive vibration may be experienced during initial start-up. Left unchecked, excessive vibration can cause a multitude of problems, including structural and/or component failure. The most common sources of vibration are listed.
Many of these conditions can be discovered by careful
Wheel Unbalance Drive Pulley Misalignment Incorrect Belt Tension Bearing Misalignment Mechanical Looseness Faulty Belts Drive Component Unbalance Poor Inlet/Outlet Conditions Foundation Stiffness
consulted. If the problem is wheel unbalance, in-place balancing can be done.
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To eliminate this undesirable effect, the use of heavy canvas connectors is recommended.
observation. Refer to the Troubleshooting section of this manual for corrective actions. If observation cannot locate the source of vibration, a qualified technician using vibration analysis equipment should be
Spring Vibration Isolators
Two to four securing bolts prevent unwanted fan and isolator movement during shipping. Proper unit operation requires the removal of these bolts.
Remove the 5/16 in. hex head bolts from each corner of the fan sub-frame.
Coils
Leak test thermal system to insure tight connections. Check for properly trapped condensate drain.
Energy Recovery Wheel
The VER models contain a total energy recovery wheel. The wheels are inspected for proper mechanical operation at the factory. However, during shipping and handling, shifting can occur that may affect wheel operation. The wheel is accessible through the access door marked “Energy Wheel Cassette Access”. To access seals in VER units, pull the cassettes out following the instructions in the Energy Recovery Wheel Maintenance section.
Turn the energy recovery
Adjustable Air Seals
Bearing Support
wheels by hand to verify free operation. The wheel should rotate smoothly and should not wobble.
Drive Belt
Drive Pulley
Label showing cassette serial # and date code
Drive Belt
Inspect the drive belt. Make sure the belt rides smoothly through the pulley and over the wheel rim.
Air Seals
Check that the air seals located around the outside of the wheel and across the center (both sides of wheel) are secure and in good condition. Air seal clearance is determined by placing a sheet of paper, to act as a feeler gauge, against the wheel face. To access seals in VER units, pull the cassettes out following the instructions in the Energy Recovery Wheel Maintenance section. To adjust the air seals, loosen all eight seal retaining screws. These screws are located on the bearing support that spans the length of the cassette through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper.
Replace cassette into unit, plug in wheel drive, replace access door and apply power. Observe by opening door slightly (remove filters if necessary to view wheel). The wheel should rotate freely at about 50-60 rpm.
VersiVent Energy Recovery Unit
31
Page 32
Factory Installed Refrigeration System Components for Units with Packaged DX (optional)
TYPICAL REFRIGERATION CIRCUIT
(HOT GAS BYPASS SHALL BE PROVIDED ON CIRCUIT A)
CHARGING
PORT
EQUALIZER
LINE
CONDENSER COIL
COMPRESSOR(S)
HOT GAS BYPASS VALVE
(HGBV)
DISCHARGE
SUCTION GAS
LIQUID
HEAD PRESSURE
FAN CONTROL
(LOW AMBIENT)
HIGH PRESSURE
600 / 420 PSI
OPEN / RESET SWITCH
LOW PRESSURE
50 / 90 PSI
OPEN / RESET SWITCH
HIGH PRESSURE
ACCESS PORT
LOW PRESSURE
ACCESS PORT
TXV
SIGHT GLASS
LIQUID LINE FILTER DRIER
SOLENOID VALV E
SCHRAEDER VALV EMANUAL VALV E THERMAL EXPANSION VALVE (TXV)
HOT GAS BYPASS VALVE (HGPB)
1. Thermostatic Expansion Valve (TXV) - each unit is equipped with a thermal expansion valve. The valve controls the flow of liquid refrigerant entering the evaporator coil by maintaining a constant, factory set superheat of 10ºF. The valve is located on the side of the evaporator coil and can be accessed through the exhaust airstream, through the coil panel access door.
2. Refrigerant Distributor - attached to the TXV is a refrigerant distributor. The refrigerant distributor evenly distributes the refrigerant to each circuit of the evaporator coil to provide optimum performance.
3. Evaporator Coil - each unit contains a multiple circuit evaporator coil. The coil is located in the outdoor airstream, directly after the energy wheel. In the DX system, the liquid refrigerant is expanded in the TXV, and then flows through the evaporator coil. The refrigerant enters the coil as low temp liquid/gas where it eventually boils into a low temp, low pressure gas prior to going to the compressor. To ensure proper operation, the coil surface must be cleaned so that air movement over the coil provides the necessary heat transfer.
4. Low Limit Pressure Switch - the unit includes a low limit pressure switch (located in the compressor compartment). The switch is installed
VersiVent Energy Recovery Unit
32
in the suction line and shuts off the DX system when the suction pressure drops to 50 psi for R410a. The switch has a built in auto-reset, which will close the circuit and allow the system to run when the pressure increases back to 90 psi for R410a.
5. Compressors - each unit includes 1, 2 or more efficiency scroll type compressors depending on needed capacity. Scroll type compressors are essentially maintenance free since they are a self-contained, self-cooling design. The scroll compresses the refrigerant in the gaseous state to a high temperature, high pressure gas.
Compressor protective devices:
Thermal Overload - each compressor is equipped
with an auto reset thermal overload
High Temp Protection - internal devices within
the compressor protect it against excessively high discharge gas temperatures
Crankcase Heater - Liquid refrigerant is
incompressible. Therefore, a crankcase heater is installed around each compressor in the unit to boil any liquid refrigerant that may be absorbed into the oil during idle periods. System power energizes the heater; it is recommended the heater is allowed to run 24 hours prior to compressors being started.
Page 33
6. Condensing Coil - each unit contains a multiple circuit condensing coil mounted on the exterior of the unit. High temperature, high pressure gas from the compressor enters the coil and is eventually cooled into a high temperature, high pressure liquid. The condensing fans move air over the coil which pulls the heat out of the refrigerant. To ensure proper operation, the coil must be cleaned so that air movement over the coil provides the necessary heat transfer.
7. Condenser Fans - the unit is equipped with two direct-drive condensing fans. The fans provide the necessary airflow to cool the refrigerant in the condensing coil. Depending on head pressure, one fan may not be running, which is normal operation for this unit and does not highlight a problem. The motors are equipped with sling protection to guard against water penetration, and are thermally protected. The thermal overloads shut down the condensing fans.
8. High Limit Pressure Switch - to safely shutdown the DX system, in case of an increase in refrigerant pressure, a high limit pressure switch is included (located in compressor compartment). The switch is located in the compressor compartment. It trips when refrigerant pressure increase to 600 psi for R410a in the liquid line, and can only be manually reset when the pressure drops below 420 psi. Typically if the high limit switch trips, a failure in the system has occurred and more investigation is needed to determine the underlying problem.
9. Head Pressure Cycle Switch - to maintain proper refrigerant pressures, a Fan-Cycle switch that operates on head pressure is installed in the liquid line. When liquid line refrigerant pressure increases to 400 psi for R410a, the switch closes and turns on an additional condensing fan to aid in cooling the refrigerant. After turning on, the fan will run until liquid line pressure drops down to 300 psi for R410a where it cycles off. The switch is located in the compressor compartment.
10. Liquid Line Filter Drier - the liquid line filter drier prevents moisture and foreign matter from entering the thermal expansion valve. It is mounted in the compressor compartment.
11. Moisture Indicating Sight Glass - moisture in a DX system can cause great harm and break down the refrigerant. Located in the compressor compartment is a moisture indicating sight glass. During normal operating conditions, the sight glass should typically be liquid. Some gas is acceptable, but excessive bubbles may indicate improper charge or a leak in the system. A green dot means moisture is below a safe operation level in the refrigerant, while a yellow dot indicates moisture has been introduced into the system and needs to be addressed.
12. Hot Gas Bypass Valve - on units equipped with hot bypass, hot gas from the compressor
is injected into the liquid line of the evaporator coil after the TXV. This process starts to occur when suction gas temperatures drop below 28ºF, which is 32º–34ºF coil surface temperature. Hot gas helps prevent the evaporator coil from freezing up and the compressor from cycling. The valve is factory set, but can be adjusted to exact specifications once installed in the field.
13. Access Ports - for easy measurement and charging access, several ports are provided throughout the system. These can be used to measure system pressures and also charge or evacuate the system. Most ports are located in the compressor compartment for easy access.
Valve Adjustment To adjust the valve, connect a pressure gauge to
the suction line and block the entering air to the evaporator coil. The Valve should begin to open when the suction pressure drops to approximately 115 PSIG for R410a (the valve will feel warm to the touch). Adjustments are made by first removing the cap on the valve and then turning the adjusting stem clockwise to increase the setting pressure and counterclockwise to decrease the setting pressure. Allow several minutes between adjustments for system to stabilize. When adjustment is complete, replace the cap on the valve.
VersiVent Energy Recovery Unit
33
Page 34
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
This unit requires minimal maintenance to operate properly. To ensure proper operation and longevity, the following items should be completed. The items in this list assume a relatively clean air environment, and may require attention more frequently in a dirty or dusty area. If this unit contains an Indirect Gas Heater, refer to the Installation, Operation and Maintenance Manual provided with the unit for maintenance purposes. A Certified Technician should complete all refrigerant systems checks.
Maintenance Frequency:
Monthly
1. External Filter Check for cleanliness – clean if required
2. Internal Filter Check for cleanliness – replace if required
3. Condensate Drain (if applicable) Inspect and clean – refill with water
4. Bearings Lubricate per the schedule in the Fan Bearings section
Semi-Annually
1. Fan Belts Check for wear, tension, alignment
2. Energy Recovery Wheel Check for cleanliness – clean if required
3. Check for belt wear Check pulley, bearings, and motor
4. Bearings Lubricate per the schedule in the Fan Bearings section
Annually
It is recommended that the annual inspection and maintenance occur at the start of the cooling season. After completing the checklist, follow the unit start­up checklist provided in the manual to ensure the refrigeration system operates in the intended matter.
1. Lubrication Apply lubrication where required
2. Dampers Check for unobstructed operation
3. Motors Check for cleanliness
4. Fan Belts Check for wear, tension, alignment
5. Motors Check for cleanliness
6. Blower Wheel & Fasteners Check for cleanliness Check all fasteners for tightness Check for fatigue, corrosion, wear
7. Bearings Lubricate per the schedule in the Fan Bearings section
8. Energy Recovery Wheel Check for cleanliness – clean if required Check belt for wear Check pulley, bearings, and motor
9. Door Seal Check if intact and pliable
10. Wiring Connections Check all connections for tightness
Units with Packaged DX
1. Evaporator Coil Maintenance Check for cleanliness – clean if required
2. Condenser Coil Maintenance Check for cleanliness – clean if required
3. Condensate Drain Inspect and clean – refill with water
4. Condensing Fan Blades and Motor Check for cleanliness Check all fasteners for tightness Check for fatigues, corrosion, and wear
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication. Apply lubrication where required. Any components showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation.
Dampers
Check all dampers to ensure they open and close properly and without binding. Backdraft dampers can be checked by hand to determine if blades open and close freely. Apply power to motorized dampers to ensure the actuator opens and closes the damper as designed.
Fan Belts
Belts must be checked on a regular basis for wear, tension, alignment, and dirt accumulation. Premature or frequent belt failures can be caused by improper belt tension (either too loose or too tight) or misaligned sheaves. Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result in failure of the fan and/or motor bearings. Conversely, loose belts will cause squealing on start-up, excessive belt flutter, slippage, and overheated sheaves. Both loose and tight belts can cause fan vibration.
VersiVent Energy Recovery Unit
34
Page 35
Belt Span
Deflection =
Belt Span
64
When replacing belts on multiple groove drives, all belts should be changed to provide uniform drive loading. Do not pry belts on or off the sheave. Loosen belt tension until belts can be removed by simply lifting the belts off the sheaves. After replacing belts, insure that slack in each belt is on the same side of the drive. Belt dressing should never be used.
Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced before new belts are installed.
The proper belt setting is the lowest tension at which the belts will not slip under peak load operation. For initial tensioning, set the belt deflection at 1/64-inch for each inch of belt span (measured half-way between sheave centers). For example, if the belt span is 64 inches, the belt deflection should be 1 inch (using moderate thumb pressure at mid-point of the drive). Check belt tension two times during the first 24 hours of operation and periodically thereafter.
Fan Motors
Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only. Removing dust and grease buildup on the motor housing assists proper motor cooling. Never wash-down motor with high pressure spray. Greasing of motors is only intended when fittings are provided. Many fractional motors are permanently lubricated for life and require no further lubrication.
Fan Wheel and Fasteners
Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe operation. Inspect fan impeller and housing for fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness. A proper maintenance program will help preserve the performance and reliability designed into the fan.
Fan Bearings
Most bearings are permanently lubricated and require no further lubrication under normal use. Normal use being considered -20ºF to 120ºF and in a relatively clean environment. Some bearings are re-lubricatable and will need to be re-greased depending on fan use. Check your bearings for grease zerk fittings to find out what type of bearing you have. If your fan is not being operated under normal use, bearings should be checked monthly for lubrication. Shaft bearings are the most critical moving part of a fan. Therefore, special attention should be given to keeping the bearings clean and well lubricated. Proper lubrication provides for reduction in friction and wear, transmission and dissipation of heat, extended bearing life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper grease applied at regular intervals is required. Refer to the recommended bearing lubrication schedule:
Bearing Lubrication Schedule
for Plenum Fans on VER Models
(Relubrication Schedule in Months)
Fan
RPM
To 250 6 6 6 6
500 6 6 6 5
750 6 5 4 3 1000 6 4 3 2 1250 5 3 2 1 1500 5 2 1 1 2000 5 1 1 .5 2500 4 .5 .5 .25 3000 4 .5 .25 .25 4000 3 .25 .25 .25 5000 2 .25 .25 .25
1
2 to 1 11⁄8 to 11⁄2 15⁄8 to 17⁄8 115⁄16 to 23⁄16
If unusual conditions exist—temperatures below 32ºF or above 200ºF, moisture or contaminants—more frequent lubrication is required.
With the unit running, add grease very slowly with a manual grease gun until a slight bead of grease forms at the seal.
Be careful not to unseat the seal by over lubricating or using excessive pressure. A guide to the amount of grease to be used is to fill 30% to 60% of available space in the bearing and housing.
A high quality lithium based grease conforming to NLGI Grade 2 consistency, such as those listed below should be used:
Mobil 532 Texaco Premium #2 B Shell Alvania #2 Mobilux #2 Texaco Multifak #2 Unirex 2
In addition to lubricating the bearings at specified intervals, set screws in the bearing collars should be checked for tightness. A bearing collar which has loosened will cause premature failure of the fan shaft. Fasteners attaching the bearings to the drive frame should also be checked. See bearing lubrication schedule.
Shaft Diameter in Inches
VersiVent Energy Recovery Unit
35
Page 36
Internal Filter Maintenance
The VER units will typically be provided with 2-inch, pleated filters in the supply air and exhaust airstream. These filters should be checked per a routine maintenance schedule and replaced as necessary to ensure proper airflow through the unit. See table below for pleated filter size and quantity for each unit. Replacement filters shall be of same performance and quality as factory installed filters. Filter type must be pleated design with integral metal grid. Two acceptable filter replacements are Aerostat Series 400 or Farr 30/30®.
Located downstream of the energy wheel in the VER, is an optional final filter section. Either MERV 8, 11 or 13 filters are available in 2 or 4-inch depth. An acceptable replacement filter is an AmAir® 1100 or similar model.
Filter Size and Quantities
Model
VER-45 (4) 16x25x2 (4) 16x25x2 (4) 16x25x2 (4) 16x25x4
VER-65 (6) 16x25x2 (6) 16x25x2 (6) 16x25x2 (6) 16x25x4
VER-90 (6) 20x25x2 (6) 20x25x2 (8) 20x20x2 (8) 20x20x4
Wheel
Supply
Wheel
Exhaust
Final 2 inch
(optional)
Final 4 inch
(optional)
Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the access side of the unit.
Exhaust Air Filters: Access to the exhaust air filters is through the door labeled as “Filter Access” on the access side of the unit.
Refer to Access Door Descriptions section for additional information on filter locations.
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate energy recovery ventilator without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.
Do not remove access panels or other unit components while standing on a ladder or other unsteady base. Access panels and unit components are heavy and serious injury may occur.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the supply weatherhood (if the weatherhood option was purchased). Filters should be checked and cleaned on a regular basis for best efficiency. The frequency of cleaning depends upon the cleanliness of the incoming air. These filters should be cleaned prior to start-up.
To access these filters, remove bottom bolt in the access door on the side of the weatherhood. Slide the access door up and then pull bottom out to remove door. Then, slide the filters out.
Outdoor air
intake hood
mesh filter
access
Clean filters by rinsing with a mild detergent in warm water.
Filters upstream of the coil should be checked regularly. If the filters are dirty, they should be cleaned or replaced. It is important that the coils stay clean to maintain desired airflow. See Filter Maintenance section for additional information.
Coil Maintenance
Units with Optional Heating or Cooling
Coils must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more energy from the fan, and create an environment for odor and bacteria to grow and spread through the conditioned zone. High pressure water (700 psi or less) may be used to clean coils with fin thickness over 0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil cleaners contain harsh chemicals, so they must be used with caution by qualified personnel only. Care must be taken not to damage the coils, including the fins, while cleaning. Caution: Fin edges are sharp.
WARNING
Biological hazard. May cause disease. Cleaning should be performed by qualified personnel.
Drain pans in any air conditioning unit will have some moisture in them, therefore, algae and other organisms will grow due to airborne spores and bacteria. Periodic cleaning is necessary to prevent this buildup from plugging the drain and causing the drain pan to overflow. Inspect twice a year to avoid the possibility of overflow. Also, drain pans should be kept clean to prevent the spread of disease. Cleaning should be performed by qualified personnel.
Winterizing Coils
Coil freeze-up can be caused by such things as air stratification and failure of outdoor air dampers and/ or preheat coils. Routine draining of water cooling coils for winter shutdown cannot be depended upon as insurance against freeze-up. Severe coil damage may result. It is recommended that all coils be drained as thoroughly as possible and then treated in the following manner.
Fill each coil independently with an antifreeze solution using a small circulating pump and again thoroughly drain. Check freezing point of antifreeze before proceeding to next coil. Due to a small amount of water always remaining in each coil, there will be a diluting effect. The small amount of antifreeze solution remaining in the coil must always be concentrated enough to prevent freeze-up.
VersiVent Energy Recovery Unit
36
Page 37
Bracket Segment Retainer
Lift away from segment
Catch Segment Retainer
Push toward center
Center of Wheel
Spoke
Inside of wheel rim
Note: Carefully read instructions for mixing antifreeze solution used. Some products will have a higher freezing point in their natural state than when mixed with water.
WARNING
Disconnect power to the unit before performing any type of service.
Energy Recovery Wheel Maintenance
Annual inspection of the energy recovery wheel is recommended. Units ventilating smoking lounges and other non-clean air spaces should have energy recovery wheel inspections more often based upon need. Inspections for smoke ventilation applications are recommended bimonthly to quarterly until a regular schedule can be established.
Accessing the Energy Recovery Wheel
Access to the wheels on all VER models is provided by a wheel access door. The cassettes can be serviced and inspected by simply sliding them out of the unit as far as is needed. Be sure to disconnect the power wires to the motor before sliding the cassette. The VER-45 and the VER-65 have one wheel. The VER-90 has two wheels which are accessed on opposite sides of the unit.
Removing the Energy Recovery Wheel Segments
Steel retainers are located on the inside of the wheel rim. Push the retainer toward center of wheel, then lift up and away to release segments (see below).
Important! Place retainers back in the original position before rotating the energy recovery wheel, otherwise damage to retainer will occur.
Wheel
Removal
Cleaning the Energy Recovery Wheel
If the wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only excessive buildup of foreign material needs to be removed. Discoloration and staining of energy recovery wheel does not affect its performance.
Thoroughly spray wheel matrix with household cleaner such as Fantastik® or equivalent. Gently rinse with warm water and using a soft brush remove any heavier accumulation. A detergent/water solution can also be used. Avoid aggressive organic solvents, such as acetone. The energy recovery wheel segments can be soaked in the above solution overnight for stubborn dirt or accumulation.
After cleaning is complete, shake the excess water from the wheel or segments. Dry wheel or segments before placing them back into the cassette. Place wheel or segments back into cassette by reversing removal procedures.
CAUTION
Do not clean energy recovery wheel segments with water in excess of 140ºF (60ºC).
Do not dry energy recovery wheel segments in air in excess of 140ºF (60ºC).
The use of a pressure washer to clean segments is not recommended. Damage could result.
Energy Recovery Wheel Belt
Inspect belts each time filters are replaced. Belts that look chewed up or are leaving belt dust near the motor pulley may indicate a problem with the wheel. Be sure to inspect wheel for smooth and unrestricted rotation. If a belt requires replacement, contact the local Greenheck
Wheel Belt & Pulley
representative. Instructions for replacement will ship with the new belt.
Energy Recovery Wheel Bearings
In the unlikely event that a wheel bearing fails, access is available through the outdoor air filter door and through a removable plate in the divider in the unit (accessed through the exhaust air filter door). Contact the local Greenheck representative for detailed instructions
Wheel Bearing
on how to replace the bearing.
VersiVent Energy Recovery Unit
37
Page 38
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low, prior to contacting the factory, please determine the following information:
Unit #1 Unit #2 Unit #3 Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Pressure Drop Across Energy Recovery Wheel
Outdoor Air Side
Exhaust Side
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in accordance with SMACNA and AMCA guidelines.
VersiVent Energy Recovery Unit
38
Page 39
Troubleshooting – Unit
Symptom Possible Cause Corrective Action
Blown fuse or open circuit breaker.
Defective motor or capacitor. Replace.
Replace fuse or reset circuit breaker and check amps.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Motor starter overloaded. Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long (resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated. Voltage supplied to starter coil must be within +10% / -15% of nominal voltage stated on the coil.
CFM too high. Check cfm and adjust drives if needed.
Static pressures are higher or lower than design.
Blower rotation is incorrect. Check rotation and reverse if necessary.
Motor voltage incorrect. Check motor nameplate versus supplied voltage.
Motor horsepower too low.
Shorted windings in motor. Replace motor.
Check for On/Off switches. Check for correct supply voltage.
Check for broken or loose belts. Tighten loose pulleys.
Shorten wiring run to mechanical room or install a relay which will turn unit on/off. Consult Factory for relay information. Increase wire gauge size so that resistance is .075 ohms or less.
Need to increase supply power or use a special control transformer which is sized for the actual supply power.
If higher, ductwork should be improved. If lower, fan rpm should be lower.
See specifications and catalog for fan curves to determine if horsepower is sufficient.
Unit damper not fully open. Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Low airflow (cfm)
Dirty filter or energy wheel.
Leaks in ductwork. Repair.
Elbows or other obstructions may be obstructing fan outlet.
Belt slippage. Adjust belt tension.
Blower fan speed too high.
High airflow (cfm)
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Filter(s) not in place. Install filters.
Insufficient static pressure (Ps) (airflow resistance).
Improve ductwork to eliminate losses using good duct practices.
Check for correct drives and rpm with catalog data.
For 3-phase, see Direction of Fan Wheel Rotation under Unit Start-Up section.
Follow cleaning procedures in Routine Maintenance section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed if necessary.
Induce Ps into system ductwork. Make sure grilles and access doors are installed. Decrease fan speed if necessary.
VersiVent Energy Recovery Unit
39
Page 40
Troubleshooting – Unit
Symptom Possible Cause Corrective Action
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Exhaust Only frost control sensors are tripping.
Adjust frost temperature sensor set point as needed.
Energy wheel does
NOT turn
Energy wheel runs
intermittently
Air seals are too tight.
“Economizer” sensors are operating.
No power to wheel motor.
Wheel drive belt.
VFD overload. (OL1 on readout)
Wheel motor overloads are tripping, due to rubbing between wheel and air seals.
Fan wheel rubbing on inlet.
Bearings.
Wheel out of balance. Replace or rebalance.
Loose wheel on shaft. Tighten wheel setscrew.
Loose motor or blower sheave. Tighten sheave setscrew.
See Energy Recovery Wheel under Unit Start-Up section.
Adjust temperature or enthalpy set points as needed.
Make sure wheel drive is plugged in. Verify power is available.
Check for loose or broken belts. Replace belts (consult factory).
Refer to VFD section. Compare motor amp rating to setting in VFD. Adjust accordingly.
Recheck air seals, make sure they are not too tight. See Energy Recovery Wheel under Unit Start-Up Section.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Belts too loose. Adjust belt tension after 24 hours of operation.
Excessive noise
or vibration
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Belts too tight.
Worn belt. Replace.
Motor base or blower loose. Tighten mounting bolts.
Buildup of material on wheel. Clean wheel and housing.
Bearing and drive misaligned. Realign.
Noise being transmitted by duct.
Loosen to maintain a 3/8 inch deflection per foot of span between sheaves.
Make sure ductwork is supported properly. Make sure ductwork metal thickness is sized for proper stiffness. Check duct size at discharge to ensure that air velocities are not too high.
VersiVent Energy Recovery Unit
40
Page 41
Troubleshooting – Refrigeration Circuit (optional)
TROUBLESHOOTING NOTE
IMPORTANT
Do not release refrigerant to the atmosphere! If Before any components are changed on the refrigeration system, the cause of the failure must be identified. Further problems will exist unless the true cause or problem is identified and corrected.
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified HVAC Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.
Symptom Possible Cause Corrective Action
Open disconnect switch or circuit breaker. Close switch and / or breaker.
Check voltage to contactor coil, transformer, slave relay, system. Replace parts as necessary.
Check for reason and repair. Replace fuse after correcting problem.
Check line voltage. If more than 10% from compressor marking, correcting is necessary.
Motor thermal protector automatically resets. Allow time (2 hrs.) for compressor to cool down so protector will reset. Restart and check for reason overheat occurred.
Check motor for open circuit, short circuit, grounded windings or burn out. Compressor may be seized; check refrigerant. If necessary, replace compressor.
Compressor
will not run
or
does not
try to start
Compressor contactor not closing.
Blown fuse or tripped breaker.
Low line voltage.
Compressor motor protector open.
Compressor defective.
If manual reset (high pressure), reset switch. (Switch opens at 600 psi and will not reset above
High or low pressure switch open or defective.
Open room thermostat or control (no cooling required).
Loose wiring.
Low refrigerant charge. Check refrigerant pressures.
Compressor starts
but cuts out on low
pressure
Low pressure
switch activates
at 50 psig for R410a
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Airflow restricted.
Restriction in refrigerant line.
Defective low pressure switch. Replace.
420 psi for R410a. If auto reset (low pressure) does not reset and everything else is OK, replace switch.
Check room temperature. If temperature is proper, wait for thermostat to close.
Check all wire terminals and tighten as necessary.
Check for dirty evaporator coil, dirty filters, dampers closed, iced evaporator coil, improper belt, check motor amps, check duct design.
Check refrigerant pressure, check and adjust thermal expansion valve. If not functioning properly, check for pressure drop across the filter drier.
VersiVent Energy Recovery Unit
41
Page 42
Troubleshooting – Refrigeration Circuit (optional)
Symptom Possible Cause Corrective Action
Refrigerant overcharge. Check pressures, charge by subcooling.
Condenser fan motor defective. Check fan motor.
Compressor starts
but cuts out on high
pressure switch
High pressure
activates at
600 psig for R410a
Condenser coil inlet obstructed or dirty. Check coil and inlet clearances.
Air or non-condensables in system.
Defective high pressure switch. Replace.
Restriction in discharge or liquid line.
Condensing fan relay not pulling in. Replace.
Low voltage. Check voltage.
Sustained high discharge pressure.
Check high side equalized pressure reading with equivalent outdoor temperature.
Check refrigerant line pressures, check thermal expansion valves.
Check running amperage and conditions described under ‘Low suction pressure’ symptoms.
Compressor cuts out
on thermal overload
Compressor hums,
but will not start
High suction and discharge pressures.
Defective compressor overload.
Improper refrigerant charge. Check subcooling.
Improperly wired. Review wiring schematics.
Loose wiring. Check all connections and wires.
Defective start relay. Replace relay.
Motor windings damaged. Verify amp draw.
Improperly wired. Review wiring schematics.
Low line voltage. Check voltage.
Loose wiring. Check all connections.
Defective start or run capacitor.
Defective relay start. Replace relay.
Check thermal expansion valve setting, check for air in system.
If compressor is hot, allow compressor to cool for two hours. Recheck for open circuit.
Check run capacitor for compressor and fan motor.
Motor winding damaged. Verify amp draws.
Internal compressor mechanical damage. Replace.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
VersiVent Energy Recovery Unit
42
Page 43
Troubleshooting – Refrigeration Circuit (optional)
Symptom Possible Cause Corrective Action
Refrigerant overcharge. Check pressures and subcooling.
Compressor noisy
or vibrating
High suction
pressure
Liquid floodback.
Tubing rattle.
Scroll compressor rotating in reverse (3 phase). Rewire for opposite rotation.
Worn or damaged compressor. Replace the compressor.
Improper mounting on unit base. Check that compressor is properly isolated.
Excessive load on evaporator coil.
Compressor is unloaded.
Expansion valve not secured to suction line.
Check thermal expansion valve setting. Check for refrigerant overcharge.
Dampen tubing vibration by taping or clamping. Carefully bend tubing away from contact where possible.
Check for high entering wet bulb temperature. Check for excessive air.
Check head pressure, check thermal expansion valve if not functioning properly, check pressure drop across filter drier.
Check the thermal expansion valve, ensure bulb is insulated.
Check superheat. If superheat is high, then valve is out of control and pegged wide open.
•Checkbulbforcontact. •Adjustvalveforsuperheat. •Replacevalvepowerheadorvalve.
High discharge
pressure
Thermostatic expansion valve pressure limit feature incorrect or inoperative. Overfeeding.
Room load too large. Reduce the load or add more equipment.
Overcharged. Check pressures and subcooling.
Thermal expansion valve setting.
Air inlet to condenser dirty or obstructed.
Condenser fan motor defective. Check condenser fan motor and capacitor.
Too much refrigerant. Remove excess refrigerant.
Non-condensable in system. Remove non-condensable from system.
Dirty condenser coil. Clean condenser coil.
Condenser fan not running or running backwards.
Discharge service valve partially closed. Open valve.
High load conditions. Add more equipment or reduce load.
Check bulb location and clamping. Adjust superheat. Replace expansion valve power head.
Check thermal expansion setting and calibrate superheat.
Check for proper clearances and possible air recirculating.
Check electrical circuit and fuse. Check fan cycling controls.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
VersiVent Energy Recovery Unit
43
Page 44
Troubleshooting – Refrigeration Circuit (optional)
Symptom Possible Cause Corrective Action
Refrigerant undercharge. Check pressures and subcooling.
Low suction
pressure
Low discharge
pressure
Blower running backward.
Loose blower, pulley or belts. Check drive pulley alignment, belt tension.
Low entering air temperature (low load condition).
Refrigerant leak.
Evaporator dirty or iced up or airflow restricted.
Plugged liquid line filter-drier. Replace filter-drier.
Improper suction pressure regulator setting. Check setting and correct as required.
Expansion valve defective, superheat too high, or valve too small.
Moisture in system. Reclaim refrigerant, check for leaks, recharge.
Insufficient refrigerant charge.
Defective or improperly adjusted expansion valve.
Low suction pressure. See “Low suction pressure”.
Interchange any two wires from 3 phase disconnect.
Check entering air wet bulb conditions.
Check system for leaks. Repair leaks and add refrigerant.
Check defrost system. Clean the coil. Check fan operation. Check airflow.
Adjust valve for proper superheat or replace the expansion valve if too small or defective.
Check subcooling, check for leak. Repair leak and add refrigerant.
Check superheating and adjust thermal expansion valve.
Faulty condenser temperature controls.
Thermostat location or malfunction.
Improper refrigerant charge. Check subcooling, verify superheat.
Defective high or low pressure control. Check high or low pressure switch.
Liquid floodback. Possible tight bearings, see above.
Compressor short cycles
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Defective expansion valve. Check thermal expansion valve and superheat.
Poor air distribution. Check ductwork for recirculating.
High discharge pressure. See “High discharge pressure”.
Leaking discharge valves in compressor. See “High suction pressure”.
Low airflow at evaporator(s).
Incorrect unit selection (oversized). Contact factory.
Check condenser controls and reset to obtain desired condensing temperature.
Check thermostat, check heat anticipator setting.
Check blower operation and airstream restrictions.
VersiVent Energy Recovery Unit
44
Page 45
Troubleshooting – Refrigeration Circuit (optional)
Symptom Possible Cause Corrective Action
Thoroughly defrost evaporator. After defrost, observe level, add oil. Check for leaks. Check lines for proper slope and traps.
Adjust expansion valve for higher superheat. Check crankcase heater.
Low or no
oil pressure
Low oil level (trapped oil in evaporator or suction line).
Excessive liquid refrigerant in the crankcase.
Worn oil pump. Replace the oil pump.
Worn compressor bearings. Replace the compressor.
Compressor
loses oil
Running cycle is
too long or unit
operates
continuously
Loose fitting on oil line or pump housing gasket leaking.
Compressor short cycling. Check low pressure control setting.
Refrigerant leak.
Short cycling. Check low pressure control settings.
Refrigerant flood back.
Improper piping or traps. Verify proper piping slopes.
Refrigeration undercharged. Check subcooling.
Dirty filter or evaporator coil. Check filter, coil and airflow.
Dirty or clogged condenser coil. Check coil and airflow.
Air or other non-condensables in system.
Defective compressor. See “High suction pressure”.
Restriction in suction and liquid line. Check for restrictions in refrigerant circuit.
Control contacts stuck. Check wiring.
Check and tighten system. Check bottom plate or compressor.
Check system for leaks. Repair leaks and add refrigerant.
Check thermal expansion valve setting. Check for refrigerant overcharge.
Check equalized high side pressure with equivalent outdoor temperature.
Excessive load. Add more equipment or reduce room load.
Too low of a system thermostat setting or defective thermostat.
Liquid line
is too hot
Liquid line is
frosted or wet
Suction line
is frosting
Frost on
evaporator coil
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Refrigerant undercharge. Adjust the charge by subcooling.
High discharge pressure. See “High discharge pressure”.
Restriction in liquid line. Clear restriction upstream of point of frosting.
Insufficient evaporator airflow.
Restriction in suction or liquid line. Restriction upstream of point of frosting.
Malfunctioning or defective expansion valve. Check bulb of thermal expansion valve.
Hot gas bypass valve not functioning properly. Check valve. If defective, replace.
Manual hot gas bypass valve closed. Open valve.
Adjust or replace thermostat.
Check airflow, check filters, check drive for loose parts or belts.
VersiVent Energy Recovery Unit
45
Page 46
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
VersiVent Energy Recovery Unit
46
Page 47
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
VersiVent Energy Recovery Unit
47
Page 48
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Greenheck Catalog VersiVent provides additional information describing the equipment, fan performance, available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at: www.amca.org.
Phone:(715)359-6171•Fax:(715)355-2399•E-mail:gfcinfo@greenheck.com•Web site: www.greenheck.com
471849 • Model VER IOM, Rev. 1, February 2009 Copyright 2009 © Greenheck Fan Corp.
48
Loading...