Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
VersiVent - Model VER
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
CAUTION
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electric Code (CEC) in Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
Precaution should be taken in explosive atmospheres.
Upon receiving the product check to make sure all items
are accounted for by referencing the bill of lading to
ensure all items were received. Inspect each crate for
shipping damage before accepting delivery. Notify the
carrier if any damage is noticed. The carrier will make
notification on the delivery receipt acknowledging any
damage to the product. All damage should be noted on
all the copies of the bill of lading which is countersigned
by the delivering carrier. A Carrier Inspection Report
should be filled out by the carrier upon arrival and
reported to the Traffic Department. If damaged upon
arrival, file claim with carrier. Any physical damage to
the unit after acceptance is not the responsibility of
manufacturer.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C)
and 110°F (43°C) (wide temperature swings may
cause condensation and “sweating” of metal parts).
All accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels, and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all unit parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl
hard to reach internal surfaces or for occasional use,
consider using Tectyl
or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
®
511M Rust Preventive or WD-40®
VersiVent Energy Recovery Ventilator
3
Product Overview
The VER units bring in fresh, outdoor air and remove
stale, exhaust air. Prior to discharging the exhaust air,
the energy recovery wheel transfers energy from the
exhaust air to the outdoor air at an efficiency of 7080%. Simply put, this unit preconditions the outdoor
air to save money on heating and cooling costs. These
particular units also have cooling and heating options
available after the recovery wheel to further condition
the fresh air.
Optional Subassemblies
Dampers
Backdraft dampers are always included as an integral
part of the exhaust hood assemblies. Motorized outdoor
air and return air dampers are optional and are factorymounted (and wired) at the intake.
Hot Water / Chilled Water Coils
Water coils can be used for a single purpose such
as heating or cooling, or their function can be
alternated between heating and cooling by changing
the temperature of the water flowing through the coil.
Depending on the application, it may be necessary to
use a glycol mixture to prevent the liquid from freezing.
The water coils are engineered to operate at pressures
up to 250 PSIG and temperatures up to 300°F, but
ancillary equipment such as valves and pumps will often
dictate lower operating temperatures. All water coils
are pressure tested at the factory with 450 PSIG of dry
nitrogen.
Electric Post-Heaters
The optional post-heater is used as a heat source for
the building and is integrated into the supply airstream.
A temperature sensor (with a field-adjustable set point)
is mounted in the supply airstream after the post-heater
to turn the post-heater on. A SCR heater allows for
an infinite amount of modulating control of the heat to
provide an accurate discharge temperature during the
call for heat.
As standard, the post-heater control panel is not single
point wired to the unit control center. Separate power
must be supplied to the post-heater disconnect (located
in unit control center). Electric heaters are available in
208, 230, 460, or 575 VAC (refer to heater nameplate for
voltage).
Indirect Gas Furnace
An optional indirect gas furnace may be installed and
provides supplementary heat to the building. Refer to
the PVF/PVG Indirect Gas-Fired Heat manuals provided
with the unit. A unit-specific wiring diagram is located
inside the furnace housing access door.
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory-mounted.
Exhaust Air Weatherhood
The exhaust weatherhood is shipped separately as a
kit with its own instructions. Backdraft dampers are
always included as an integral part of the exhaust hood
assemblies.
Packaged Direct Expansion (PDX)
The DX system comes fully charged from the factory
with refrigerant and is ready for installation upon arrival.
All units come standard with two compressors. This
allows for staging of compressors to meet a wider range
of outdoor air loads while reducing the amount of cycles
per compressor.
Integral Components
All units are provided with an expansion valve, hermetic
scroll compressor(s), liquid line filter drier, high pressure
manual reset cutout, low pressure auto-reset cutout,
time delays for compressor protection, service/charging
valves, moisture indicating sight glass, and optional hot
gas bypass. The compressors also come standard with
a crankcase heater for additional protection.
Split DX
The unit can be equipped with two evaporator coils
that will be connected to a separate condensing unit
(provided by others). Depending on controlling options,
the condensing unit will be controlled by others or could
receive a call for stage 1 and stage 2 of cooling with the
integral microprocessor controller. The microprocessor
controller will only provide a call for cooling, it will not
send a digital control signal to the compressors. Piping
components such as thermostatic expansion valve, filter
drier, sight glass, etc., shall be field-provided.
All dimensions shown in inches.
*L Sum the lengths of the appropriate modules to get the total length of the unit.
^Weight: The weights shown are a worse case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal
ABC
weights added together with the largest fans, coils and heaters for the unit.
D1D2D3D4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
D1D2D3D4
D* Coil Module Options
D
DX + EH + HGRH
EFGH IWL*
HW = Hot Water
CW = Chilled Water
DX = Direct Expansion
EH = Electric Heat
HP = Wrap-around Heat Pipe
HGRH = Hot Gas Reheat
^Weight
see
note
(lbs.)
4900
VersiVent Energy Recovery Ventilator
5
Curb Outside Dimensions and Weights
Outdoor Air Weatherhood
Intake
Section
2-inch Filters
Wheel
Section
Wheel Cassette
2-inch Filters
Optional
Coil Section
4-inch Final Filters
Blower
Section
IG Heater Section
Optional
Optional
Condensing Section
Condensing Coil
L* - 3.75 inches
W - 3.75 inches
ABC*D
Drain Pan ConnectionIG Gas Connection
L*
EF
Subtract 3.75 inches from dimensions
W & L* to get the outside curb dimensions.
All dimensions shown in inches.
L* — Sum up the applicable section dimensions (A–F) for your unit to get the overall length.
^ — Curb weights shown are for the worst case scenario (largest curb) possible for each size unit.
C* Coil Module Options
C1C2C3C4
HWHW + DXCW + HPHW + CW + HP
CWHW + CWDX + HPHW + DX + HP
DXEH + CWDX + HGRHEH + DX + HP
EHEH + DXDX + HW + HGRHEH + CW + HP
DX + EH + HGRH
HW = Hot WaterEH = Electric Heat
CW = Chilled WaterHP = Wrap-around Heat Pipe
DX = Direct ExpansionHGRH = Hot Gas Reheat
Most factory-supplied electrical components are prewired. To determine what electrical accessories require
additional field wiring, refer to the unit-specific wiring
diagram located on the inside of the unit control center
access door. The low voltage control circuit is 24 VAC
and control wiring should not exceed 0.75ohms.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that fieldsupplied conduit does not interfere with access panel
operation.
Curb Weight^
(lbs.)
447
see
note
If wire resistance exceeds 0.75 ohms, an industrial-style
plug-in relay should be added to the unit control center
Side of Unit
1 in.
2½ in.
1.195 in.
1 in.
and wired in lieu of the remote switch (typically between
terminal blocks R and G on the terminal strip (refer to
Typical Control Center Components). The relay must be
rated for at least 5 amps and have a 24 VAC coil. Failure
1 in.
to comply with these guidelines may cause motor
starters to “chatter” or not pull in which can cause
contactor failures and/or motor failures.
Note: Standard factory-installed electric post-heaters
have their own disconnect separate from the
unit disconnect. Thus, each electric post-heater
requires its own separate power connection.
Roof Curb
Recommended
2-inches of
Insulation
Curb Cap Details
VersiVent Energy Recovery Ventilator
6
Service Clearances
VER-45, 65 and 90 units require minimum clearances
for access on all sides for routine maintenance. Filter
replacement, drain pan inspection and cleaning, energy
wheel cassette inspection, fan bearing lubrication and
belt adjustment are examples of routine maintenance
that must be performed. Blower and motor assemblies,
energy recovery wheel cassette, coil and filter sections
are always provided with a service door or panel for
proper component access. Clearances for component
removal may be greater than the service clearances,
refer to drawings for these dimensions.
Additional clearances for units with packaged DX
Clearances must be maintained on all sides of this unit.
This especially is true with the top of this unit. Hot air is
being discharged through the condensing fans during
operation, and the more clearance available, the better
the chance of avoiding recirculation or coil starvation.
This unit should never be placed under an overhang
or inside a building. A minimum of 48 inches over the
condensing fans is recommended.
Minimum 48 inches
clearance
ACCESS
PANEL
C
ACCESS
PANEL
VER-90
ONLY
B
ACCESS
PANEL
ACCESS
PANEL
TL
A
ACCESS
PANEL
TL
TL
TRTR
Minimum 24 inches
clearance
Condensing Coil Intake
Keep this area clear
Unit Clearances
Unit SizeABCD
VER-4565423624
VER-6570423624
VER-9065426524
All dimensions shown in inches.
ACCESS
PANEL
ACCESS
PANEL
TL
TRTR
ACCESS
PANEL
TL
TR
ACCESS
TL
TR
TR
PANEL
ACCESS
PANEL
D
Access Panels may change depending on options
selected.
VersiVent Energy Recovery Ventilator
7
Access Panel Descriptions and Locations
Following is a list of items accessible through the
access doors shown on the diagrams. Some items are
optional and may not have been provided.
#8 – Supply Fan
#9 – Compressors
8
#6 – Control Panel
#2 – OA Intake Damper
and Electric Preheat
2
3
4
1
9
9
#7 – IG Furnace
Control Center
#5 – Packaged DX
Coil and Final Filter
1. Aluminum mesh filters (intake hood)
2. Outdoor air intake damper
Electric pre-heater
3. Exhaust fan, motor, and drives
4. Energy recovery wheel, motor, belt, and seals
Exhaust air filters
Return air intake damper (optional)
Outdoor air filters
Frost control sensors (optional)
Economizer sensors (optional)
6. Control center
All electrical controls
VFD for energy recovery wheel (optional)
7. Indirect gas furnace control center
8. Supply air fan, motor, and drives
(with indirect gas furnace)
Electric post-heater control center (optional)
9. Compressor(s) –
(optional)
#3 – Exhaust Fan
VersiVent Energy Recovery Ventilator
8
Recommended Roof Opening
A
Refer to weight and dimension data to determine the
exact location of the section containing the outdoor
air discharge opening. If the unit is equipped with
an Indirect Gas Heater (IG) section, the outdoor air
discharge opening will be in that section; if not, it will
be in the blower section. The return air intake will
be consistent for all units. The dimensions of these
openings and their locations are illustrated below.
All dimensions are in inches.
IG = Indirect Gas Furnace; PDX = Packaged DX Cooling
1 = Any unit without IG and PDX.
Blower Module is at the end of the unit.
2 = Any unit with IG that does not have PDX.
3 = Any unit with IG and PDX
4 = Any unit without IG and with PDX
D
E
G
Handling
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation. Exercise extreme
caution to prevent any damage from occurring to the
refrigerant system. This unit could contain a system
pressurized with refrigerant that, if damaged, could
leak into the atmosphere or cause bodily harm due to
the extreme cold nature of expanding refrigerant. Use
protective equipment such as gloves and safety glasses
to minimize or prevent injury in case of a system leak
during installation.
F
The system design and installation should follow
accepted industry practice, such as described in
H
the ASHRAE Handbook. Adequate space should be
left around the unit for piping coils and drains, filter
replacement, and maintenance. Sufficient space should
be provided on the side of the unit for routine service
and component removal should that become necessary.
Lifting
1. Before lifting, be sure that all shipping material has
been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Unit Weights &
Dimensions section.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach to
unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
When cutting only duct openings, cut opening oneinch
(25 mm) larger than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof is
constructed of combustible materials, area within the
roof curb must be ventilated, left open, or covered with
non-combustible material which has an “R” value of at
least five. If area within curb is open, higher radiated
sound levels may result.
Where the supply or warm air duct passes thru a
combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A. Position the unit roof opening such that
the supply discharge and exhaust inlet of the unit will
line up with the corresponding ductwork. Be sure to
allow for the recommended service clearances when
positioning opening (see Service Clearances). Do not
face the outdoor air intake of the unit into prevailing
wind and keep the intake away from any other exhaust
fans. Likewise, position the exhaust discharge opening
away from outdoor air intakes of any other equipment.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to lifting
the unit and setting on curb.
11. Do not use fork lifts for handling unit.
VersiVent Energy Recovery Ventilator
9
Roof Curb Mounting
Roof curb details, including duct location dimensions,
are available on VER roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1. Factory-Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a
knockdown kit (includes duct adapter) and require
field-assembly (by others). Assembly instructions are
included with the curb.
2. Install Curb
Locate curb over roof opening and fasten in place.
Check that the diagonal dimensions are within
±1/8 inch of each other and adjust as necessary.
For proper coil drainage and unit operation, it is
important that the installation be level. Shim as
required to level.
3. Install Ductwork
Installation of all ducts should be done in
accordance with SMACNA and AMCA guidelines.
Duct adapter provided to support ducts prior to
setting the unit.
4. Set the Unit
Lift unit to a point directly above the curb and duct
openings. Guide unit while lowering to align with duct
openings. Roof curbs fit inside the unit base. Make
sure the unit is properly seated on the curb and is
level.
Rail Mounting and Layout
• Rails designed to handle the weight of the VER
should be positioned as shown on the diagram (rails
by others).
• Make sure that rail positioning does not interfere with
the supply air discharge opening or the return air
intake opening on the VER unit.
• Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
• Set unit on rails.
Rails are positioned in random places.
See table for proper location
Isometric View
Return Air
Intake
ABCD
Side View
UnitABCD
VER-4553.316
VER-6558.116
VER-90 105.316
All dimensions shown in inches.
IG = Indirect Gas
CS = Condensing Section
33.8 w/IG
27 w/o IG
31.0 w/IG
30 w/o IG
33.8 w/IG
34 w/o IG
Supply Air
Discharge
9.2 IG w/o CS; 37.1 IG w/CS
5.2 w/o IG and CS
33.1 w/o IG and w/ CS
9 IG w/o CS; 36.9 IG w/CS
4.6 w/o IG and CS
32.5 w/o IG and w/ CS
9.2 IG w/o CS; 37.1 IG w/CS
3.7 w/o IG and CS
31.6 w/o IG and w/ CS
VersiVent Energy Recovery Ventilator
10
Ductwork Connections
Supply Fan
The supply fan in this unit is a plenum style fan. The
discharge opening dimensions are provided. For proper
fan performance, match the duct size to the dimensions
listed. Installation of all ducts should be done in
accordance with SMACNA.
Supply Fan Discharge Opening Dimensions
Supply Air
Unit
Discharge Location
TopEndBottom
VER-45 38.5 x 30 41.8 x 27
VER-6550 x 3150 x 31
VER-9062 x 3459.7 x 35
All dimensions shown in inches.
See diagram in Recommended Roof Openings section for the
*
Bottom Discharge opening sizes.
*
*
*
Exhaust Fan
The exhaust fan in this unit is a forward-curved fan.
Good and poor fan-to-duct connections are shown.
Airflow out of the fan should be
directed straight or curved the
same direction as the
fan wheel rotates. Poor
duct installation will
n
o
i
t
a
t
o
R
result in low airflow and
other system effects.
Length of
Straight Duct
(Supply Fan)
48
60
60
POOR
n
o
i
t
a
t
o
R
Length of Straight Duct
GOOD
Recommended Exhaust Fan Discharge Duct Size
Length of
Straight Duct
(Exhaust Fan)
UnitDuct Size
Exhaust
Blower Size
VER-4520 x 201248
VER-6528 x 281560
VER-9032 x 321860
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project. Refer
to plans for appropriate job specific duct size and/or velocity
limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
VersiVent Energy Recovery Ventilator
11
Electrical Installation
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the power
supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest
edition of the National Electrical Code ANSI/NFPA70
and any local codes that may apply. In Canada, wiring
should be done in accordance with the Canadian
Electrical Code.
IMPORTANT
The equipment must be properly grounded and
bonded. Any wiring running through the unit in the
airstream must be protected by metal conduit, metal
clad cable or raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105°C, except for an
energy cut-off or sensor lead wire which must be rated
to 150°C.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
WARNING
If unit is equipped with a microprocessor, terminals Y1,
Y2 and W1 cannot be wired to a thermostat. Wiring to
these terminals will bypass unit’s internal safeties.
1. Determine the Size of the Main Power Lines
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.
2. Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate
power supply. The power connection should
be made to the factory-provided electric heater
disconnect and must be compatible with the ratings
on the nameplate, supply power voltage, phase and
amperage. Consult ANSI/NFPA 70 and CSA C22.1
for proper conductor sizing.
3. Provide the Opening(s) for the Electrical
Connections
Electrical openings vary by unit size and arrangement
and are field-supplied.
4. Connect the Power Supplies
Connect the main power lines and electric heater
power lines to the disconnect switches or terminal
blocks and main grounding lug(s). Torque field
connections to manufacturer’s recommendations.
5. Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V
power supply circuit. The circuit must include short
circuit protection which may need to be supplied by
others.
6. Connect Field-Wired Low Voltage Components
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field-wiring, refer to the unitspecific wiring diagram located on the inside of the
control center access door.
If unit is equipped with a microprocessor, terminals Y1,
Y2 and W1 cannot be wired to a thermostat. Wiring to
these terminals will bypass unit’s internal safeties.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that
field-supplied conduit does not interfere with access
panel operation. All low voltage wiring should be run in
conduit wherever it may be exposed to the weather.
The low voltage control circuit is 24 VAC and control
wiring should not exceed 0.75 ohms. If wire resistance
exceeds 0.75 ohms, an isolation relay should be added
to the unit control center and wired in place of the
remote switch (typically between terminal blocks R
and G on the terminal strip). The relay must be rated
for at least 5 amps and have a 24 VAC coil. Failure to
comply with these guidelines may cause motor starters
to “chatter” or not pull in which can cause contactor
failures and/or motor failures.
VersiVent Energy Recovery Ventilator
12
Field-Provided Disconnect
If field-installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
Discharge Air Temperature Sensor
Without Indirect Gas Furnace
For units without an indirect gas furnace, the discharge
air temperature sensor is factory-mounted in the blower
discharge section of the unit behind the blower cut off
plate.
WARNING
Discharge air temperature sensor is to be fieldinstalled prior to unit start-up on units with an indirect
gas furnace.
With Indirect Gas Furnace
For units with an indirect gas furnace, the discharge
air temperature sensor is to be
field-installed prior to unit start
up at least three duct diameters
downstream of the heat exchanger
or where good mixed average
temperature occurs in the ductwork.
The discharge air sensor is shipped
loose and can be found in the unit’s
control center. See the unit-specific
wiring diagram for connection locations.
Typical Control Center Components
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter - Exhaust Air Fan
3. Motor Starter - Supply Air Fan
4. Motor Contactor - Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors*
8. Grounding lug
9. Distributor block*
10. Compressor fuse blocks*
11. Compressor contactors*
12. Condensing fan contactors*
13. Compressor relay*
14. Terminal block*
15. Compressor cycle timers*
Optional Control Center Components
16. DDC controller*
17. Dirty filter pressure switches*
18. Terminal block
19. Energy recovery wheel VFD*
*Not always provided
1
8
5
6
7
18
9
2
10
11
3419
12
13
15
17
16
14
VersiVent Energy Recovery Ventilator
13
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of different
alarm lights and switches to control the unit. The remote
panel ships loose and requires mounting and wiring in
the field. The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• On/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
• Wheel rotation sensor light
Unit Interfacing Terminals
Heating/Cooling Switches and Night Setback Switch/
Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
UNIT ON/OFF
S1
COOL STAGE 1 / ECONOMIZER
S6
COOL STAGE 2
S7
HEAT
S4
C
G
Y1
Y2
W1
6
7
12
7-Day Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
BLACKBLUE
RED
(CAPPED)
TIMER
C
G
Y1
Y2
W1
6
7
12
On/Off/Auto Switch & Indictor Light Wiring
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
UNIT ON/OFF
FROST CONTROL
ECONOMIZER
WHEEL ROTATION
ON
OFF
AUTO
* -- BMS, TIMECLOCK,
TSTAT, RTU, ETC.
*
R
C
G
Y1
Y2
W1
6
7
12
UNOCCUPIED RECIRCULATION
S5
Dirty Filter Indicator
(Powered by others)
HOTCOMMON
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
NC
NC
A
C
NO
C
NO
DIRTY FILTER
C
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
ON/OFF/AUTO SWITCH ALLOWS THREE MODES OF OPERATION
"ON" - UNIT IS TURNED ON MANUALLY
"OFF" - UNIT IS TURNED OFF MANUALLY
"AUTO" - UNIT IS CONTROLLED VIA SCHEDULER OF BMS, TIMECLOCK, TSAT, ETC.
VersiVent Energy Recovery Ventilator
14
NC
NC
NO
C
NO
DIRTY FILTER
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.