Greenheck VER Installation Manual

Document 471849
Energy Recovery Ventilator
®
VersiVent
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
VersiVent - Model VER
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electric Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to the unit while it is running.
Precaution should be taken in explosive atmospheres.
VersiVent Energy Recovery Ventilator
Table of Contents
General Safety Information ...................1
Receiving, Handling and Storage ..............3
Product Overview ...........................4
Optional Subassemblies ......................4
Installation
Unit Dimensions and Weights ..................5
Curb Outside Dimensions and Weights ...........6
Service Clearances ..........................7
Access Panel Descriptions and Locations ........8
Recommended Roof Openings .................9
Handling ...................................9
Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Roof Curb Mounting ........................10
Rail Mounting/Layout ........................10
Duct Connections ..........................11
Electrical Installation
Warnings .................................12
Procedure .................................12
Field-Provided Disconnect ....................13
Discharge Air Temperature Sensor .............13
Typical Control Center Components ............13
Optional Accessory Wiring Schematics ..........14
Piping Installation
Optional Gas Piping .........................15
Gas Connections ...........................15
Optional Coil Piping .........................15
Water Coils ..............................15
Direct Expansion .........................15
Condensate Drain Trap ....................16
Unit Overview
Basic Unit .................................17
Optional Component Overview
Economizer ...............................17
Frost Control ..............................18
Variable Frequency Drive .....................18
CO2 Sensor ...............................18
Phase Monitor .............................18
Rotation Sensor ............................18
Dirty Filter Sensor ..........................18
Microprocessor Controller ....................19
Unoccupied Recirculation Damper .............19
Service Outlet ..............................19
Vapor Tight Lights ..........................19
Hot Gas Bypass Valve .......................19
Hot Gas Reheat Valve .......................19
Digital Scroll Compressor ....................19
Cooling System Overview
Packaged DX ..............................20
Start-Up
Warnings .................................21
Special Tools Required ......................21
Start-Up Procedure .........................21
Voltage Imbalance ..........................21
Pre-Start-Up Checklist .......................22
Start-Up Checklist .......................
Optional Accessories Checklist ................24
22-23
Start-Up Components
Energy Wheel ..............................25
Fans - Supply and Exhaust ................25-26
Vibration ..................................26
Hot Gas Bypass Valve .......................26
Optional Components Start-Up
Dirty Filter Sensor ..........................27
Economizer ...............................27
Frost Control ..............................28
Variable Frequency Drives ................29-30
Routine Maintenance
Maintenance Frequency ......................31
Units with Packaged DX .....................31
Maintenance Procedures
Lubrication ..............................32
Dampers ................................32
Gas Furnace .............................32
Fan Belts ...............................32
Fan Motors ..............................32
Fan Wheel and Fasteners ..................32
Bearings ................................32
Internal Filter ............................32
External Filter ............................33
Coils ...................................33
Door Seals ..............................33
Energy Wheel ............................34
Troubleshooting
Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Refrigeration Circuit ......................36-39
Energy Wheel ..............................39
Controller Alarms ...........................40
Rotation Sensor ............................40
Digital Scroll Compressor ....................40
Economizer ...............................41
Reference
Technical Assistance Information ..............41
Additional Installation, Operation and
Maintenance Manuals .....................41
Component Location ........................42
Maintenance Log ...........................43
Our Commitment ....................Backcover
VersiVent Energy Recovery Ventilator
Receiving
Upon receiving the product check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and reported to the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The fan should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated on an adequate number of wooden blocks so that it is above water and snow levels, and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance during Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. Every three months, the fan motor should be energized. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl hard to reach internal surfaces or for occasional use, consider using Tectyl or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation.
Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
®
511M Rust Preventive or WD-40®
VersiVent Energy Recovery Ventilator
Product Overview
The VER units bring in fresh, outdoor air and remove stale, exhaust air. Prior to discharging the exhaust air, the energy recovery wheel transfers energy from the exhaust air to the outdoor air at an efficiency of 70­80%. Simply put, this unit preconditions the outdoor air to save money on heating and cooling costs. These particular units also have cooling and heating options available after the recovery wheel to further condition the fresh air.
Optional Subassemblies
Dampers
Backdraft dampers are always included as an integral part of the exhaust hood assemblies. Motorized outdoor air and return air dampers are optional and are factory­mounted (and wired) at the intake.
Hot Water / Chilled Water Coils
Water coils can be used for a single purpose such as heating or cooling, or their function can be alternated between heating and cooling by changing the temperature of the water flowing through the coil. Depending on the application, it may be necessary to use a glycol mixture to prevent the liquid from freezing. The water coils are engineered to operate at pressures up to 250 PSIG and temperatures up to 300°F, but ancillary equipment such as valves and pumps will often dictate lower operating temperatures. All water coils are pressure tested at the factory with 450 PSIG of dry nitrogen.
Electric Post-Heaters
The optional post-heater is used as a heat source for the building and is integrated into the supply airstream.
A temperature sensor (with a field-adjustable set point) is mounted in the supply airstream after the post-heater to turn the post-heater on. A SCR heater allows for an infinite amount of modulating control of the heat to provide an accurate discharge temperature during the call for heat.
As standard, the post-heater control panel is not single point wired to the unit control center. Separate power must be supplied to the post-heater disconnect (located in unit control center). Electric heaters are available in 208, 230, 460, or 575 VAC (refer to heater nameplate for voltage).
Indirect Gas Furnace
An optional indirect gas furnace may be installed and provides supplementary heat to the building. Refer to the PVF/PVG Indirect Gas-Fired Heat manuals provided with the unit. A unit-specific wiring diagram is located inside the furnace housing access door.
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory-mounted.
Exhaust Air Weatherhood
The exhaust weatherhood is shipped separately as a kit with its own instructions. Backdraft dampers are always included as an integral part of the exhaust hood assemblies.
Packaged Direct Expansion (PDX)
The DX system comes fully charged from the factory with refrigerant and is ready for installation upon arrival. All units come standard with two compressors. This allows for staging of compressors to meet a wider range of outdoor air loads while reducing the amount of cycles per compressor.
Integral Components
All units are provided with an expansion valve, hermetic scroll compressor(s), liquid line filter drier, high pressure manual reset cutout, low pressure auto-reset cutout, time delays for compressor protection, service/charging valves, moisture indicating sight glass, and optional hot gas bypass. The compressors also come standard with a crankcase heater for additional protection.
Split DX
The unit can be equipped with two evaporator coils that will be connected to a separate condensing unit (provided by others). Depending on controlling options, the condensing unit will be controlled by others or could receive a call for stage 1 and stage 2 of cooling with the integral microprocessor controller. The microprocessor controller will only provide a call for cooling, it will not send a digital control signal to the compressors. Piping components such as thermostatic expansion valve, filter drier, sight glass, etc., shall be field-provided.
VersiVent Energy Recovery Ventilator
Installation
Unit Weights & Dimensions
A
W
I
Plan View
BC D*L*EF G
Electrical Box
Wheel Cassette
Exhaust Air Discharge
Wheel
Section
2-inch Filters
4-inch Final Filters
Return Air Intake
Optional
Coil Section
Blower
Section
Optional
IG Heater Section
Supply Air Discharge
Optional
Condensing Section
2-inch Filters
Outdoor Air Intake
Intake
Section
Condensing Coil
H
Outdoor Air Hood
2-inch Filters
Wheel Cassette
2-inch Filters
Drain Pan Connection
4-inch Final Filters
Condensing Coil
IG Gas Connection
Elevation View
*
Unit Size
VER-45 16.381 28.146 44.627 30.159 36.159 44.159 50.275 36.312 47.571 63.964 65.851 18.780 69.987
VER-65 16.381 30.825 46.597 30.159 36.159 44.159 50.275 38.124 47.571 65.958 72.098 23.358 76.246 6300
VER-90 16.381 34.825 85.658 30.159 36.159 44.159 50.275 41.312 47.571 65.958 65.851 23.358 91.010 7250
All dimensions shown in inches. *L Sum the lengths of the appropriate modules to get the total length of the unit. ^Weight: The weights shown are a worse case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal
ABC
weights added together with the largest fans, coils and heaters for the unit.
D1 D2 D3 D4
HW HW + DX CW + HP HW + CW + HP
CW HW + CW DX + HP HW + DX + HP
DX EH + CW DX + HGRH EH + DX + HP
EH EH + DX DX + HW + HGRH EH + CW + HP
D1 D2 D3 D4
D* Coil Module Options
D
DX + EH + HGRH
EFGH IWL*
HW = Hot Water
CW = Chilled Water
DX = Direct Expansion
EH = Electric Heat
HP = Wrap-around Heat Pipe
HGRH = Hot Gas Reheat
^Weight
see
note
(lbs.)
4900
VersiVent Energy Recovery Ventilator
Curb Outside Dimensions and Weights
Outdoor Air Weatherhood
Intake
Section
2-inch Filters
Wheel
Section
Wheel Cassette
2-inch Filters
Optional
Coil Section
4-inch Final Filters
Blower Section
IG Heater Section
Optional
Optional
Condensing Section
Condensing Coil
L* - 3.75 inches
W - 3.75 inches
A B C* D
Drain Pan Connection IG Gas Connection
L*
EF
Subtract 3.75 inches from dimensions W & L* to get the outside curb dimensions.
Elevation View
Unit Size
AB
C1 C2 C3 C4
C*
DEFWL*
VER-45 28.146 44.627 30.159 36.159 44.159 50.275 36.312 47.571 27.909 69.987
VER-65 30.825 46.597 30.159 36.159 44.159 50.275 38.124 47.571 27.909 76.246 473
VER-90 34.825 85.658 30.159 36.159 44.159 50.275 41.312 47.571 27.909 91.010 621
All dimensions shown in inches. L* — Sum up the applicable section dimensions (A–F) for your unit to get the overall length. ^ — Curb weights shown are for the worst case scenario (largest curb) possible for each size unit.
C* Coil Module Options
C1 C2 C3 C4
HW HW + DX CW + HP HW + CW + HP
CW HW + CW DX + HP HW + DX + HP
DX EH + CW DX + HGRH EH + DX + HP
EH EH + DX DX + HW + HGRH EH + CW + HP
DX + EH + HGRH
HW = Hot Water EH = Electric Heat
CW = Chilled Water HP = Wrap-around Heat Pipe
DX = Direct Expansion HGRH = Hot Gas Reheat
Most factory-supplied electrical components are pre­wired. To determine what electrical accessories require additional field wiring, refer to the unit-specific wiring diagram located on the inside of the unit control center access door. The low voltage control circuit is 24 VAC and control wiring should not exceed 0.75ohms.
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field­supplied conduit does not interfere with access panel operation.
Curb Weight^
(lbs.)
447
see
note
If wire resistance exceeds 0.75 ohms, an industrial-style plug-in relay should be added to the unit control center
Side of Unit
1 in.
2½ in.
1.195 in. 1 in.
and wired in lieu of the remote switch (typically between terminal blocks R and G on the terminal strip (refer to Typical Control Center Components). The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure
1 in.
to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
Note: Standard factory-installed electric post-heaters
have their own disconnect separate from the unit disconnect. Thus, each electric post-heater requires its own separate power connection.
Roof Curb
Recommended 2-inches of Insulation
Curb Cap Details
VersiVent Energy Recovery Ventilator
Service Clearances
VER-45, 65 and 90 units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances, refer to drawings for these dimensions.
Additional clearances for units with packaged DX
Clearances must be maintained on all sides of this unit. This especially is true with the top of this unit. Hot air is being discharged through the condensing fans during operation, and the more clearance available, the better the chance of avoiding recirculation or coil starvation. This unit should never be placed under an overhang or inside a building. A minimum of 48 inches over the condensing fans is recommended.
Minimum 48 inches clearance
ACCESS
PANEL
C
ACCESS
PANEL
VER-90
ONLY
B
ACCESS
PANEL
ACCESS
PANEL
TL
A
ACCESS
PANEL
TL
TL
TRTR
Minimum 24 inches clearance
Condensing Coil Intake
Keep this area clear
Unit Clearances
Unit Size A B C D
VER-45 65 42 36 24
VER-65 70 42 36 24
VER-90 65 42 65 24
All dimensions shown in inches.
ACCESS
PANEL
ACCESS
PANEL
TL
TRTR
ACCESS
PANEL
TL
TR
ACCESS
TL
TR
TR
PANEL
ACCESS
PANEL
D
Access Panels may change depending on options selected.
VersiVent Energy Recovery Ventilator
Access Panel Descriptions and Locations
Following is a list of items accessible through the access doors shown on the diagrams. Some items are optional and may not have been provided.
#8 – Supply Fan
#9 – Compressors
8
#6 – Control Panel
#2 – OA Intake Damper
and Electric Preheat
2
3
4
1
9
9
#7 – IG Furnace
Control Center
#5 – Packaged DX
Coil and Final Filter
1. Aluminum mesh filters (intake hood)
2. Outdoor air intake damper Electric pre-heater
3. Exhaust fan, motor, and drives
4. Energy recovery wheel, motor, belt, and seals Exhaust air filters Return air intake damper (optional) Outdoor air filters Frost control sensors (optional) Economizer sensors (optional)
5. Coil access / drain pan / final filters Bypass damper (optional)
5
6
7
#4 – Filter & Wheel
6. Control center All electrical controls VFD for energy recovery wheel (optional)
7. Indirect gas furnace control center
8. Supply air fan, motor, and drives (with indirect gas furnace) Electric post-heater control center (optional)
9. Compressor(s) –
(optional)
#3 – Exhaust Fan
VersiVent Energy Recovery Ventilator
Recommended Roof Opening
A
Refer to weight and dimension data to determine the exact location of the section containing the outdoor air discharge opening. If the unit is equipped with an Indirect Gas Heater (IG) section, the outdoor air discharge opening will be in that section; if not, it will be in the blower section. The return air intake will be consistent for all units. The dimensions of these openings and their locations are illustrated below.
Return Air Intake
Supply Air Discharge
B
C
VER-45 A B C D E F G H
1 56.9 4.7 51.5 15.9 26.9 42.7 3.3 11.8 2 56.9 4.7 51.5 15.9 33.8 34.1 7.4 14.4 3 56.9 4.7 51.5 15.9 33.8 34.1 35.3 14.4 4 56.9 4.7 51.5 15.9 26.9 42.7 31.2 11.8
VER-65 A B C D E F G H
1 59.9 6.3 56.1 15.9 29.9 51.9 2.7 10.3 2 59.9 6.3 56.1 15.9 30.9 49.9 7.3 7.1 3 59.9 6.3 56.1 15.9 30.9 49.9 35.2 7.1 4 59.9 6.3 56.1 15.9 29.9 51.9 30.6 10.3
VER-90 A B C D E F G H
1 77.9 4.7 99.2 15.9 33.8 61.9 2.0 12.7 2 77.9 4.7 99.2 15.9 33.8 51.9 7.5 17.7 3 77.9 4.7 99.2 15.9 33.8 51.9 35.3 17.7 4 77.9 4.7 99.2 15.9 33.8 61.9 29.9 12.7
All dimensions are in inches. IG = Indirect Gas Furnace; PDX = Packaged DX Cooling 1 = Any unit without IG and PDX.
Blower Module is at the end of the unit. 2 = Any unit with IG that does not have PDX. 3 = Any unit with IG and PDX 4 = Any unit without IG and with PDX
D
E
G
Handling
While this unit was constructed with quality and dependability in mind, damage still may occur during handling of the unit for installation. Exercise extreme caution to prevent any damage from occurring to the refrigerant system. This unit could contain a system pressurized with refrigerant that, if damaged, could leak into the atmosphere or cause bodily harm due to the extreme cold nature of expanding refrigerant. Use protective equipment such as gloves and safety glasses to minimize or prevent injury in case of a system leak during installation.
F
The system design and installation should follow accepted industry practice, such as described in
H
the ASHRAE Handbook. Adequate space should be left around the unit for piping coils and drains, filter replacement, and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.
Lifting
1. Before lifting, be sure that all shipping material has been removed from unit.
2. To assist in determining rigging requirements, weights are provided in the Unit Weights & Dimensions section.
3. Unit must be lifted by all lifting lugs provided on base structure.
4. Rigger to use suitable mating hardware to attach to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent damage to the cabinet by the lift cables.
When cutting only duct openings, cut opening oneinch (25 mm) larger than duct size to allow clearance for installation. Area enclosed by roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R” value of at least five. If area within curb is open, higher radiated sound levels may result.
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A. Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the corresponding ductwork. Be sure to allow for the recommended service clearances when positioning opening (see Service Clearances). Do not face the outdoor air intake of the unit into prevailing wind and keep the intake away from any other exhaust fans. Likewise, position the exhaust discharge opening away from outdoor air intakes of any other equipment.
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by others) has been applied to the curb prior to lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
VersiVent Energy Recovery Ventilator
Roof Curb Mounting
Roof curb details, including duct location dimensions, are available on VER roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory-Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a knockdown kit (includes duct adapter) and require field-assembly (by others). Assembly instructions are included with the curb.
2. Install Curb
Locate curb over roof opening and fasten in place. Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper coil drainage and unit operation, it is important that the installation be level. Shim as required to level.
3. Install Ductwork
Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
4. Set the Unit
Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.
Rail Mounting and Layout
• Rails designed to handle the weight of the VER should be positioned as shown on the diagram (rails by others).
• Make sure that rail positioning does not interfere with the supply air discharge opening or the return air intake opening on the VER unit.
• Rails should run the width of the unit and extend beyond the unit a minimum of 12 inches on each side.
• Set unit on rails.
Rails are positioned in random places. See table for proper location
Isometric View
Return Air
Intake
AB CD
Side View
Unit A B C D
VER-45 53.3 16
VER-65 58.1 16
VER-90 105.3 16
All dimensions shown in inches. IG = Indirect Gas
CS = Condensing Section
33.8 w/IG 27 w/o IG
31.0 w/IG 30 w/o IG
33.8 w/IG 34 w/o IG
Supply Air Discharge
9.2 IG w/o CS; 37.1 IG w/CS
5.2 w/o IG and CS
33.1 w/o IG and w/ CS
9 IG w/o CS; 36.9 IG w/CS
4.6 w/o IG and CS
32.5 w/o IG and w/ CS
9.2 IG w/o CS; 37.1 IG w/CS
3.7 w/o IG and CS
31.6 w/o IG and w/ CS
VersiVent Energy Recovery Ventilator
10
Ductwork Connections
Supply Fan
The supply fan in this unit is a plenum style fan. The discharge opening dimensions are provided. For proper fan performance, match the duct size to the dimensions listed. Installation of all ducts should be done in accordance with SMACNA.
Supply Fan Discharge Opening Dimensions
Supply Air
Unit
Discharge Location
Top End Bottom
VER-45 38.5 x 30 41.8 x 27
VER-65 50 x 31 50 x 31
VER-90 62 x 34 59.7 x 35
All dimensions shown in inches.
See diagram in Recommended Roof Openings section for the
*
Bottom Discharge opening sizes.
*
*
*
Exhaust Fan
The exhaust fan in this unit is a forward-curved fan. Good and poor fan-to-duct connections are shown. Airflow out of the fan should be directed straight or curved the same direction as the fan wheel rotates. Poor duct installation will
n
o
i
t
a
t
o
R
result in low airflow and other system effects.
Length of
Straight Duct
(Supply Fan)
48
60
60
POOR
n
o
i
t
a
t
o
R
Length of Straight Duct
GOOD
Recommended Exhaust Fan Discharge Duct Size
Length of
Straight Duct
(Exhaust Fan)
Unit Duct Size
Exhaust
Blower Size
VER-45 20 x 20 12 48
VER-65 28 x 28 15 60
VER-90 32 x 32 18 60
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.
• Straight duct lengths were calculated based on 100% effective duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
VersiVent Energy Recovery Ventilator
11
Electrical Installation
WARNING
The roof lining contains high voltage wiring. To prevent electrocution, do not puncture the interior or exterior panels of the roof.
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect switch open.
For units with a gas furnace, if you turn off the power supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached on the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest edition of the National Electrical Code ANSI/NFPA70 and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded and bonded. Any wiring running through the unit in the airstream must be protected by metal conduit, metal clad cable or raceways.
CAUTION
If replacement wire is required, it must have a temperature rating of at least 105°C, except for an energy cut-off or sensor lead wire which must be rated to 150°C.
DANGER
High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or property damage. Manufacturer is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.
WARNING
If unit is equipped with a microprocessor, terminals Y1, Y2 and W1 cannot be wired to a thermostat. Wiring to these terminals will bypass unit’s internal safeties.
1. Determine the Size of the Main Power Lines The unit’s nameplate states the voltage and the unit’s MCA. The main power lines to the unit should be sized accordingly. The nameplate is located on the outside of the unit on the control panel side.
2. Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate power supply. The power connection should be made to the factory-provided electric heater disconnect and must be compatible with the ratings on the nameplate, supply power voltage, phase and amperage. Consult ANSI/NFPA 70 and CSA C22.1 for proper conductor sizing.
3. Provide the Opening(s) for the Electrical Connections
Electrical openings vary by unit size and arrangement and are field-supplied.
4. Connect the Power Supplies Connect the main power lines and electric heater power lines to the disconnect switches or terminal blocks and main grounding lug(s). Torque field connections to manufacturer’s recommendations.
5. Wire the Optional Convenience Outlet The convenience outlet requires a separate 115V power supply circuit. The circuit must include short circuit protection which may need to be supplied by others.
6. Connect Field-Wired Low Voltage Components Most factory-supplied electrical components are prewired. To determine what electrical accessories require additional field-wiring, refer to the unit­specific wiring diagram located on the inside of the control center access door.
If unit is equipped with a microprocessor, terminals Y1, Y2 and W1 cannot be wired to a thermostat. Wiring to these terminals will bypass unit’s internal safeties.
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field-supplied conduit does not interfere with access panel operation. All low voltage wiring should be run in conduit wherever it may be exposed to the weather.
The low voltage control circuit is 24 VAC and control wiring should not exceed 0.75 ohms. If wire resistance exceeds 0.75 ohms, an isolation relay should be added to the unit control center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip). The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
VersiVent Energy Recovery Ventilator
12
Field-Provided Disconnect
If field-installing an additional disconnect switch, it is recommended that there is at least four feet of service room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect, use dual element time delay fuses and size according to the rating plate.
Discharge Air Temperature Sensor
Without Indirect Gas Furnace
For units without an indirect gas furnace, the discharge air temperature sensor is factory-mounted in the blower discharge section of the unit behind the blower cut off plate.
WARNING
Discharge air temperature sensor is to be field­installed prior to unit start-up on units with an indirect gas furnace.
With Indirect Gas Furnace
For units with an indirect gas furnace, the discharge air temperature sensor is to be field-installed prior to unit start up at least three duct diameters downstream of the heat exchanger or where good mixed average temperature occurs in the ductwork. The discharge air sensor is shipped loose and can be found in the unit’s control center. See the unit-specific wiring diagram for connection locations.
Typical Control Center Components
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter - Exhaust Air Fan
3. Motor Starter - Supply Air Fan
4. Motor Contactor - Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors*
8. Grounding lug
9. Distributor block*
10. Compressor fuse blocks*
11. Compressor contactors*
12. Condensing fan contactors*
13. Compressor relay*
14. Terminal block*
15. Compressor cycle timers*
Optional Control Center Components
16. DDC controller*
17. Dirty filter pressure switches*
18. Terminal block
19. Energy recovery wheel VFD*
*Not always provided
1
8
5
6
7
18
9
2
10
11
3 4 19
12
13
15
17
16
14
VersiVent Energy Recovery Ventilator
13
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of different alarm lights and switches to control the unit. The remote panel ships loose and requires mounting and wiring in the field. The remote panel is available with the following options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• On/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
• Wheel rotation sensor light
Unit Interfacing Terminals
Heating/Cooling Switches and Night Setback Switch/ Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
UNIT ON/OFF
S1
COOL STAGE 1 / ECONOMIZER
S6
COOL STAGE 2
S7
HEAT
S4
C
G
Y1
Y2
W1
6
7
12
7-Day Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
BLACK BLUE
RED
(CAPPED)
TIMER
C
G
Y1
Y2
W1
6
7
12
On/Off/Auto Switch & Indictor Light Wiring
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
UNIT ON/OFF
FROST CONTROL
ECONOMIZER
WHEEL ROTATION
ON
OFF
AUTO
* -- BMS, TIMECLOCK,
TSTAT, RTU, ETC.
*
R
C
G
Y1
Y2
W1
6
7
12
UNOCCUPIED RECIRCULATION
S5
Dirty Filter Indicator
(Powered by others)
HOT COMMON
SUPPLY DIRTY FILTER SWITCH
EXHAUST DIRTY FILTER SWITCH
NC
NC
A
C
NO
C
NO
DIRTY FILTER
C
SUPPLY DIRTY FILTER SWITCH
EXHAUST DIRTY FILTER SWITCH
ON/OFF/AUTO SWITCH ALLOWS THREE MODES OF OPERATION "ON" - UNIT IS TURNED ON MANUALLY "OFF" - UNIT IS TURNED OFF MANUALLY "AUTO" - UNIT IS CONTROLLED VIA SCHEDULER OF BMS, TIMECLOCK, TSAT, ETC.
VersiVent Energy Recovery Ventilator
14
NC
NC
NO
C
NO
DIRTY FILTER
Loading...
+ 30 hidden pages