Greenheck Vektor Laboratory Exhaust User Manual

Document 476072
®
Vektor
®
with Variable Geometry Nozzle (VGN) Technology
Laboratory Exhaust
Electrical Controls Information
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
Table of Contents
General Safety Information ......................1
Receiving, Handling and Storage .................2
VFD Controller Nozzle Controller
Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces, or chemicals. Replace cord immediately if damaged.
3. Verify the power source is compatible with the equipment.
DANGER
Always disconnect power before working on or near a unit. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, variable frequency drives (VFD) may be hot enough to cause pain or injury. Allow motor to cool before servicing.
Component Checklist - Electrical ...............2
System Components ...........................3
Wiring Installation .............................3
Fan Operation - Single Fan
Set Point and Minimum Variables ...............4
Defined Modes .............................4
VGN Technology Control Flow Chart ............5
Fan Operation - Multiple Fans, No Staging
Set Point and Minimum Variables ...............6
Defined Modes ........................... 6-7
VGN Technology Control Flow Chart ............8
Fan Operation - Multiple Fans, With Staging
Set Point and Minimum Variables ...............9
Defined Modes ............................10
VGN Technology Control Flow Chart ...........11
Factory-Supplied Variable Frequency Drive
System Diagram .............................12
Wiring Diagram ..............................13
Communication BACnet® and LonWorks® Protocol . 14
Start-Up Procedure - Electrical Controls ..........15
System Test and Balance for VGN ...............16
Nozzle Velocity Adjustment .....................16
Customer-Supplied Variable Frequency Drive
System Diagram .............................18
Wiring Diagram ..............................19
VGN Nozzle Controller Intro. and Tutorial ....... 20-22
Communication ..............................23
Start-Up Procedure - Electrical Controls ..........24
System Test and Balance for VGN ...............25
Nozzle Velocity Adjustment .....................25
Troubleshooting ..............................26
Maintenance ................................27
Electrical Replacement Parts ...................27
Our Commitment .............................28
®
VGN Technology
1
General Electrical Controls Information
Receiving
Upon receiving the product, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Greenheck Representative. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Component Checklist - Electrical
Check off the following system components to verify all components are received.
ABB Eclipse Variable Frequency Drive (VFD) with
bypass mode and internal wiring kit. (VGN with factory-supplied VFD)
VGN nozzle controller
(VGN customer-supplied VFD)
Transducer/terminal enclosure with Sure Aire™
pressure transducer and system terminals in NEMA3R enclosure
24 volt VGN nozzle with modulating actuator
0/2-10 VDC with feedback
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing; report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
atmosphere. Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts, allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to eliminate any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection. The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
Inspection and Maintenance during Storage
While in storage, inspect equipment once per month. Keep a record of inspection and maintenance performed. If moisture or dirt accumulations are found on parts, the source should be located and eliminated.
Removed From Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, and accessories for tightness.
Handling
Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR - The ideal environment for the storage of
units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry
VGN Technology
2
®
General Electrical Controls Information
System Components
System Components (supplied by Greenheck)
Quantity Description
1 Pressure transducer with adjustable pressure
range and VDC signal
1 VFD with bypass mode and integrated controller
(VGN with factory-supplied VFD)
1 VGN nozzle controller.
(VGN, customer-supplied VFD)
1 to 4 Actuator motor(s) (nozzle)
24 volts, modulating VDC signal with feedback
Varies Actuator motor (bypass damper), if provided by
manufacturer
Varies Actuator motor (isolation damper) 24 volts,
open/close. Quantity will be zero if isolation
damper actuator is supplied by others or if gravity style isolation damper is used.
System Components (customer-supplied)
Quantity Description
Varies Wiring, conduit, miscellaneous fittings
1 Building control system with required
communication wiring and shielding Varies Pressure transducer for duct pressure Varies Actuator motor (bypass damper) if provided by
others
1 Actuator motor (isolation damper), if provided
by others. Quantity will be zero if gravity style
isolation damper is used.
Varies 1/4 inch tubing. Connection from Sure-Aire
termination plate mounted on fan to mounting
location of transducer/terminal enclosure.
1 Fan motor VFD.
(VGN, customer-supplied VFD)
Wiring Installation
NOTE
All field installation and wiring of electrical equipment must be done to meet NEC and local codes.
NOTE
Be sure to use appropriately sized wire for the full load amp draw.
The following items are a list of requirements necessary to install the controls for the VGN Technology system.
1. Mount variable frequency drive in the desired location; indoors or outdoors. Maximum distance from fan is 100 feet (30.5 meters).
2. Mount transducer/terminal enclosure at fan or bypass air plenum (BAP).
3. Run main power wiring from building breaker panel to variable frequency drive. By others.
4. Run motor power wiring from service disconnect switch to variable frequency drive. Wire length to be less than 100 feet. By others.
5. Connect control wiring pigtail (by factory) from VGN nozzle actuator(s) to transducer/terminal enclosure. (See wiring diagram).
Optional: Connect wiring from isolation damper
actuator(s) to transducer/terminal enclosure. By others.
6. Run control wiring from transducer/terminal enclosure to variable frequency drive or nozzle controller terminal strip. Wire length to be less than 100 feet (See wiring diagram).
7a. Run communication cable from variable frequency
drive to Building Management System (BMS). See VFD manual for type and maximum length. By others. (VGN with factory-supplied VFD).
7b. Run VGN nozzle controller system wiring from main
control panel to Building Management System (BMS). By others. (Customer-supplied VFD).
8. Run nozzle actuator feedback control wire from transducer/terminal enclosure at the fan to BMS controls.
9. Install 1/4 inch pressure tubing (by others) from transducer/terminal enclosure to Sure-Aire connection plate on fan. By others.
10. Install BMS with duct pressure control system. By others.
11. For specific device installation reference the appropriate component cut sheet or IOM. Also reference the following system and wiring diagrams on pages 4 and 7 for more detail.
®
VGN Technology
3
General Electrical Controls Information
Fan Operation - Single Fan
Set point and minimum variables
1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of the fan, based on the airflow monitoring station. Building Management System (BMS) to monitor nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity.
2. Fan to run at BMS defined operation for speed and bypass mode. Mode reference will be determined by minimum fan speed and by minimum nozzle actuator feedback.
a. If the BMS speed is equal to the minimum specific
fan speed and nozzle feedback is minimum for a set time period (user-defined) the BMS will begin to modulate the bypass damper open to assist with pressure control.
b. If the bypass damper is at full closed for a set time
period, the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control.
c. The PID sequence to be programmed at the BMS
for bypass damper operation. The BMS to provide fan enable and VFD speed reference.
Definition of typical operation modes:
Mode #1: Unoccupied. Defined as no one inside the
lab(s), all lab hoods are closed.
1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. BMS to monitor nozzle actuator feedback and keep fan speed above the minimum required to maintain velocity.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period.
4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system.
Mode #2: Occupied; no lab hoods being used.
Defined as people entering the lab(s), no work being done at the hoods.
1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. BMS to monitor nozzle actuator feedback and keep fan speed above the minimum required to maintain velocity.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period (user-defined).
4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system.
VGN Technology
4
Mode #3: Occupied; some or all lab hoods being used. Defined as people in the lab(s), lab hood sashes
being used.
A. Sashes opening in the lab
1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. Typical system response should be to increase fan speed and increase nozzle open area.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS.
3. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system.
B. Sashes closing in the lab
1. Fan will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan. Typical system response should be to decrease fan speed and decrease nozzle open area.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper as required if system speed is equal to the minimum fan speed and nozzle actuator is at minimum for a time period (user­defined).
4. VFD speed, duct pressure control and bypass damper operation is provided by the BMS system.
Mode #4: Fault mode. Defined as safety mode; the system has an issue and needs to default to VFD bypass.
1. VFD failure detected, automatically or manually put
into VFD bypass if available, by operator or BMS.
2. Nozzle area to increase proportional to fan airflow
which will increase as fan speed is at maximum.
3. Sure-Aire will measure airflow of the fan. VFD or the
nozzle controller will report this value to BMS.
4. Duct pressure control will modulate bypass damper
as required if system is in alarm mode. Duct pressure control is provided and programmed by the BMS system.
5. System manually to be reset and placed back in VFD
auto mode.
®
General Electrical Controls Information
VGN Technology Control Flow Chart - Single Fan
Positive Pressure Fault
Negative Pressure Fault
Max. VFD
Monitor
Time
Above Setpoint
(more positive)
VFD
No
at Full Speed
Yes
Yes
BMS Control
Drive
Fault Bypass
Mode
No
Static
Pressure
Valve
Static
Pressure =
Setpoint
No
Static
Pressure
Value
Drive Fault
Yes
Below Setpoint
(more negative)
Feedback at
Minimum
No
No
Minimum
Alarm
Nozzle
VFD at
Speed
Yes
Yes
Min. VFD
Monitor
Time
Fan at
Full Speed
Yes
Required
Nozzle Area
Increase
Fan Speed
Send to BMS
Controller
Time Period
Met?
Yes
Positive
Pressure
Alarm
No
Reset at
Fault CLR
Decrease
Fan Speed
Above Setpoint
(more positive)
Close
Bypass
Damper
Bypass
Feedback
= Mimimum
VDC
Yes
Yes
Yes
Time Period
Met?
Yes
BMS Control
Bypass Damper
PID
Static
Pressure
Value
Static
Pressure =
Setpoint
No
Static
Pressure
Value
No
Reset by
BMS
Below Setpoint
(more negative)
Bypass
Damper
Yes
Feedback
= Maximum
Open
Bypass
VDC
Damper Position Monitor
NoNo
Time
Yes
Time Period
Met?
Reset by
BMS
®
No No
Time Period
Met?
Yes
Negative Pressure
Alarm
Reset at
Fault CLR
Send to BMS
Controller
VGN Technology
5
General Electrical Controls Information
Fan Operation - Multiple Fans, No Staging
Set point and minimum variables
1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of each fan, based on the airflow monitoring station. Building Management System (BMS) to monitor each fan nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity.
2. Each fan to run at BMS defined operation for fan on or off, and event timing, as required per system airflow requirements. BMS is also required to control fan speed for all fans. Bypass damper mode reference will be determined by the following scenario listed:
A. All fans in system running at minimum. Minimum
flow condition.
a. BMS will control fan speed and monitor nozzle
feedback as required to maintain system set point.
b. Decreased flow condition from minimum speed.
When the speed is equal to the minimum specific fan speed and nozzle feedback is at minimum for a set time period (user-defined), the BMS will begin to modulate the bypass damper(s) open to assist with pressure control.
Increased flow condition from minimum speed. If
the bypass damper(s) are at full closed for a set time period (user-defined), the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control.
c. The PID sequence to be programmed at the BMS
for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference.
B. Normal operation. Fan operation normal system
flow.
a. Flow requirement for system within reach of fan
operation. Fans operating will float together from minimum speed to maximum speed to keep set point.
b. If any of the fans run in the surge area for a set
time period, the BMS will need to add the bypass damper(s).
c. The PID sequence to be programmed at the BMS
for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference.
Definition of typical operation modes:
Mode #1: Unoccupied. Defined as no one inside the
lab(s), all lab hoods are closed.
1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required.
Note: Follow bypass damper(s) operation
depending on number of fans running.
4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system.
Mode #2: Occupied; no lab hoods being used. Defined as people entering the lab(s), no work being done at the hoods.
1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity out the fan(s). BMS to monitor nozzle actuator feedback for each fan and keep fan speed above the minimum required to maintain velocity.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required.
Note: Follow bypass damper(s) operation
depending on number of fans.
4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system.
Mode #3: Occupied; some or all lab hoods being used. Defined as people in the lab(s), lab hood sashes
being used.
A. Sashes opening in the lab
1. Fan(s) will operate at BMS required speed and
nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to increase fan(s) speed and increase nozzle open area.
2. Sure-Aire will measure airflow of the fan. VFD or the
nozzle controller for each fan will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate
bypass damper(s) as required.
Note: Follow bypass damper(s) operation
depending on number of fans running.
4. VFD speed, duct pressure control and the bypass
damper(s) operation is provided by the BMS system.
VGN Technology
6
®
General Electrical Controls Information
B. Sashes closing in the lab
1. Fan(s) will operate at BMS required speed and nozzle will modulate as necessary to achieve the required velocity. Typical system response should be to decrease fan(s) speed and decrease nozzle open area.
2. Sure-Aire will measure airflow of the fan. VFD or the nozzle controller for each fan will report this value to BMS.
3. Duct pressure control, by the BMS, will modulate bypass damper(s) as required.
Note: Follow bypass damper(s) operation
depending on number of fans running.
4. VFD speed, duct pressure control and the bypass damper(s) operation is provided by the BMS system.
Mode #4: Fault Mode. Defined as safety mode; the system has an issue and needs to default to VFD bypass.
1. VFD failure detected, automatically or manually put
into VFD bypass if available by operator or BMS.
2. Nozzle area to increase proportional to fan airflow
which will increase as fan speed is at maximum.
3. Sure-Aire will measure airflow of the fan. VFD or the
nozzle controller for each fan will report this value to BMS.
4. Duct pressure control will modulate bypass
damper(s) as required if system is in alarm mode. Duct pressure control is provided and programmed by the BMS system.
5. System manually to be reset and placed back in VFD
auto mode.
®
VGN Technology
7
General Electrical Controls Information
VGN Technology Control Flow Chart - Multiple Fans, No Staging
Positive Pressure Fault
Negative Pressure Fault
No
Increase
Fan(s) Speed
Send to
BMS Controller
Max. VFD
Monitor
Time
Above Setpoint
(more positive)
VFD(S) at
Full Speed
Yes
Time Period
Met?
Positive
Pressure
Alarm
Yes
Yes
BMS
Control
Drive Fault
Bypass
Mode
Fan(s) in
Stall Mode
Static Pressure
Value
Static
Pressure
= Setpoint
Static Pressure
Value
No
No
No
No
Reset at Fault Clr
Yes
Yes
Below Setpoint
(more negative)
No
Decrease
Fan(s) Speed
Fan Stall
Monitor Time
All Nozzle
Feedback at
Minimum
No
VFD(S)
Minimum
Speed
Yes
Yes
Time
Period
Yes
Reset by
BMS
Time Period
Time Met?
Period
Yes
BMS Control
Bypass Damper
PID
Min. VFD
Monitor
Time
No
Reset by
BMS
Yes
Drive Fault
Alarm
Fan
Full Speed
Yes
Required
Nozzle Area
VGN Technology
8
No
Above Setpoint
(more positive)
Close Bypass Damper
Bypass
Feedback
= Min. VDC
Yes
Yes
Yes
Time Period
Met?
Reset by
BMS
Static Pressure
Value
Static
Pressure
= Setpoint
No
Static
Pressure
Value
Below Setpoint
(more negative)
Yes
Time Period
Met?
Yes
Negative Pressure
Alarm
Feedback
= Max. VDC
NoNo
Open
Bypass
Damper
Bypass
BMS Controller
Reset at Fault Clr
Send to
No
Damper Position Monitor
Time
®
General Electrical Controls Information
Fan Operation - Multiple Fans, With Staging
Set point and minimum variables
1. System will maintain a minimum of 3000 fpm velocity (factory default) at the outlet of each fan, based on the airflow monitoring station. Building Management System (BMS) to monitor each fan nozzle actuator feedback and keep fan speed above the minimum required set point to maintain velocity.
2. Each fan to run at BMS defined operation for fan staging, on or off, and event timing, as required per system airflow requirements. BMS is also required to control fan speed for all fans. Bypass damper mode reference will be determined by the following scenario listed:
A. One fan in system running, all other fans off.
Minimum flow condition.
a. One fan in operation, BMS will control fan speed
and monitor nozzle feedback as required to maintain system set point.
b. Decreased flow condition from minimum speed.
When the speed is equal to the minimum specific fan speed and nozzle feedback is at minimum for a set time period (user-defined), the BMS will begin to modulate the bypass damper(s) open to assist with pressure control.
Increased flow condition from minimum speed. If
the bypass damper(s) are at full closed for a set time period (user-defined), the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control.
c. If one fan is at maximum speed for a set time
period, another fan may be required to keep system set point. Note section B for multiple fan operation.
d. The PID sequence to be programmed at the BMS
for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference.
B. Two or more fans running, normal operation. Fan
operation normal system flow.
a. Flow requirement for system within reach of fan
operation. Fans operating will float together from minimum speed to maximum speed to keep set point.
b. If all fans in operation are at maximum speed for
a set time period (user-defined) and other fans are available, another fan can be added by the BMS as required.
c. With additional fan added to the system, all fans in
operation will decrease and match speed of new fan until set point is reached, then fans can float together between minimum to maximum speed. Note section “C” if a dead band zone is created.
d. When more than one fan is operating and all are at
the minimum speed for a set time period and the pressure is still too negative, the BMS will need to subtract a fan.
e. When more than one fan is in operation and any of
the fans run in the surge area for a set time period, the BMS will need to subtract a fan or bypass damper(s) may need to be used.
f. With the subtraction of a fan from the system, the
BMS will need to increase speed of all remaining fans and they will float together until set point is reached. Note section “C” if a dead band zone is created.
g. The PID sequence to be programmed at the BMS
for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference.
C. Dead band in system. Flow between fans cycle
on/off.
Flow requirement for system out of reach causing
undesirable fan cycling on and off. If the fans in the system running at full speed is not enough air and adding an additional fan and running all fans at minimum is too much air, then the bypass damper mode may be necessary to settle these dead band zones.
a. The BMS notices and counts cycling of fans to
determine dead band zone. If a dead band is determined, the BMS will begin to modulate the bypass damper(s) open to assist with pressure control.
b. If the bypass damper(s) are at full closed for a set
time period, the BMS will increase fan speed and the fan control will increase the nozzle area as required to assist with pressure control.
c. The PID sequence to be programmed at the BMS
for the bypass damper(s) operation. The BMS to provide fan enable and VFD speed reference.
®
VGN Technology
9
Loading...
+ 19 hidden pages