Greenheck Vari-Flow Air Management System User Manual

Document 476251
Vari-Flow Air Management System
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
Vari-Flow Air Management System
General Safety Information
Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces, or chemicals. Replace cord immediately if damaged.
3. Verify that the power source is compatible with the equipment.
®
WARNING
DANGER
Always disconnect power before working on or near a unit. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, variable frequency drives may be hot enough to cause pain or injury. Allow motor to cool before servicing.
CAUTION
It is the responsibility of the installer to make sure both electrical and gas appliances shut down in the event of a fire or in the event of a power loss to the building when this sequence is required by the authority having jurisdiction.
Vari-Flow Air Management System
1
Table of Contents
Receiving and Handling
Receiving and Handling ........................2
Installation
Control Box Mounting ........................3
Resistive Temperature Detector ................3
Pneumatic Static Pressure Kit ...................4
Keypad Mounting .............................4
Touchscreen Mounting .........................5
Electrical Connections
Power for Vari-Flow Control ...................5
Power for Lights ............................5
Variable Frequency Drives (VFD) ................6
Vari-Green® Motor ..........................6
VFD Provided by Others ......................6
Make-Up Air VFD in Vari-Flow Wiring ............7
Make-Up Air VFD in Make-Up Air Wiring .........7
Auto Tempering .............................7
Fire System Microswitch ......................7
Resistive Temperature Detector(s) ..............8
Temperature Sensors ........................8
Keypad ...................................8
Touchscreen ...............................8
Remote Enable .............................8
Shunt Trip .................................9
Electric Gas Valve with Gas Reheat .............9
Spare Fire Relay Contacts ....................9
High Temperature Alarm Contacts ..............9
Airflow Proving .............................9
Wash Interface ..............................9
Vari-Flow Connection Checklist .................10
Sequence of Operation .......................11
System Optimization ..........................12
Controller Setup and Tutorial ................ 13-14
Menus A. B. C. D.
G. H.
Keypad Navigation and Information ..............24
Touchscreen Navigation .................... 25-26
General Information .........................26
Settings ............................... 26-27
Configuration ..............................28
Information ...............................29
Troubleshooting .............................30
Maintenance Log .............................31
Our Commitment .............................32
On/Off Unit ........................15
Setpoint ..........................16
Clock/Scheduler ....................17
Input/Output .......................17
Service ........................18-21
Manufacturer ................... 21-23
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all of the copies of the bill of lading which is countersigned by the delivering carrier. If damaged upon arrival, file a claim with the carrier. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts.
Storage
If a kitchen fan control center must be stored prior to installation, it must be protected from dirt and moisture. Indoor storage is highly recommended. For outdoor storage, cover the control package with a tarp to keep it clean, dry, and protected from UV (ultraviolet) radiation damage.
NOTE
Improper storage which results in damage to the unit will void the warranty.
Handling
Make sure the equipment does not suffer any heavy vibration or knocks.
Vari-Flow Air Management System
2
®
Installation
Control Box Mounting
1. Locate an area with enough space to mount the control box and fasten to the wall.
NOTE
Control Box may be factory mounted. If so, continue to the next section.
NOTE
If the Vari-Flow system is equipped with static pressure controls it will be located in the Vari-Flow cabinet, therefore this control box should be mounted in the space to be controlled. If the control box is mounted outside of this space, please refer to the Pneumatic Static Pressure Kit Installation Instructions.
4. Insert the compression seal into the hole from the inside of the hood making sure the gasket is placed on the fitting before inserting it into the hole. Place the octagon box and J-box plate provided over the fitting on the top of the hood, keeping the fitting centered in the box. Install the lock washer and 1-1/2inch nut on the threaded portion of the compression seal and tighten securely.
1/4 inch Compression Seal
Gasket
J-Box Plate
Resistive Temperature Detector(s) (RTD) Mounting
NOTE
Resistive temperature detector(s) may be factory installed. If so, continue to the next section.
1. Locate flat area(s) at the top interior of the hood in front of the filters, towards the front of the hood.
Exhaust Area
Sensor Install
Cut Out Area
Supply Area (optional)
Top View of Exhaust Hood
2. Cut a 3/4-inch diameter hole into the top of the capture tank. Make sure the resistive temperature detector(s) will not interfere with fire system nozzles and is not within 12 inches of light fixtures.
Temperature Sensor
Lock Washer
Nut
Octagon Cover
5. Insert the resistive temperature detector (RTD) into compression seal and tighten to 35 ft-lbs.
6. Place octagon cover onto J-box plate and fasten it.
NOTE
All field installation and wiring of electrical equipment must be done to meet NEC and local codes.
.75 to .875 inch diameter hole
Hood Surface
3. Center the octagon extension over the hole on the hood surface.
Octagon Extension
®
Vari-Flow Air Management System
3
Pneumatic Static Pressure Kit
- if equipped
NOTE
The Vari-Flow system may not be provided with the static pressure controls, if not move onto the next section.
1. Locate the Dwyer static pressure sensor outside of the building in a secure location free from as many obstructions as possible.
2. Refer to the instruction manual with the static pressure sensor for installation and operation details.
3. Once the static pressure probe is mounted, run vinyl tubing from the probe back to the control panel and coil the excess tubing. Do not kink or trim the tubing.
4. If the control panel is located in the space to be controlled, go to the next section. If the control panel is mounted remotely from the space to be controlled, continue to step 5.
5. Run 1/4 inch virgin poly tubing (by others) from the sensor in the control panel to a secure location in the space to be controlled.
Keypad Mounting
NOTE
The keypad may be factory mounted. If so, continue to the Electrical Connections section.
1. For systems with remote controls or keypad, a 35, 75, or 150 foot RJ25 cable is supplied to connect the keypad to the controls. The cable is plenum rated and does not need to be run through conduit unless required by local codes. If the keypad is to be mounted further away than the cable that is received, additional cable will be needed. Additional cable is available at the lengths mentioned above.
Keypad Mounting Diagram
Vari-Flow Air Management System
4
®
Touch Screen Mounting - if equipped
Electrical Connections
NOTE
The touch screen may be factory mounted. If so, continue to the Electrical Connections section.
1. For systems with remote controls or touch screen, two 35, 75, or 150 foot sets of cables are supplied to connect the touch screen to the controls. The cables are plenum rated and do not need to be run through conduit unless required by local codes. If the keypad is to be mounted further away than the cable that is received, additional cable will be needed. Additional cables are available at the lengths mentioned above.
Touch Screen Mounting Diagram
NOTE
All wiring of electrical equipment must be done to meet NEC and local codes.
Power for Vari-Flow Cabinet
• 115 VAC, power for controls (Terminals H and N)
CONTROL INPUT:
115 VAC, 15 AMPS FROM BREAKER
H
N
Power for Lights
• 115 VAC, power for hood lights, one per light circuit (Terminals H1, N1 | H2, N2 | H3, N3 | H4, N4)
• 115 VAC, power to lights, one per light circuit (Terminals B1, W1 | B2, W2 | B3, W3 | B4, W4)
EACH CANOPY LIGHTING CIRCUIT MUST NOT EXCEED 15A TOTAL CURRENT
LIGHT CIRCUIT 1: 115 VAC, 15 AMPS FROM BREAKER
R1
11
H1 W1B1
BK 14GA
H2 B2 N2W2
14
HOOD LIGHT
RELAY 1
LIGHT CIRCUIT 2: 115 VAC, 15 AMPS FROM BREAKER
R2
11
14
HOOD LIGHT
RELAY 2
HOOD LIGHT(S)
HOOD LIGHT(S)
WH 14GABK 14GA BK 14GA
WH 14GABK 14GA
G
N1
G
LIGHT CIRCUIT 3: 115 VAC, 15 AMPS FROM BREAKER
R3
11
BK 14GA BK 14GA
H3 B3 N3W3
BK 14GA BK 14GA
H4 B4 N4W4
14
HOOD LIGHT
RELAY 3
LIGHT CIRCUIT 4: 115 VAC, 15 AMPS FROM BREAKER
R4
11
14
HOOD LIGHT
RELAY 4
HOOD LIGHT(S)
HOOD LIGHT(S)
WH 14GA
WH 14GA
®
Vari-Flow Air Management System
5
Variable Frequency Drives (VFD) - if equipped
NOTE
If electrically commutated motors are being used, VFDs will not be needed.
1. Bring power to the input of each VFD from a dedicated power source using conduit to the NEMA-1 enclosure on the bottom of the drive. Each power source shall be of the same voltage as the respective fan and of a high enough amp rating to handle the full load amp draw of the respective fan.
NOTE
The VFD motor overload parameter (E2-01) need to be set to the motor nameplate FLA. Refer to the Quick Start Guide from Yaskawa (pages 83-89) for setting these parameters on the Yaskawa drive.
NOTE
Be sure to use appropriately sized wire for the full load amp draw.
2. To avoid interference between the conductors, separate conduit from the VFD output to the input power of the fan must be used for each fan.
Vari-Green® Fan Wiring - if equipped
• 24 VAC from Vari-Flow to Vari-Green motor control wire, black (Terminal E__-24)
• 0-10 VDC Speed Reference from Vari-Flow to Vari-Green motor control wire, red (Terminal E__S+)
• Common from Vari-Flow to Vari-Green motor control wire, white (Terminal E__S-)
E1-24 E1-S+ E1-S-
24 VAC RUN (BLACK) SPEED REF. + (RED) SPEED REF. - (WHITE)
G
NH
NOTE: POWER FOR THE
VARI-GREEN FAN GOES DIRECTLY T O FAN
VFD-F1-E
MARK: VG
115/1
0.75 HP
VARI-GREEN
VARI-GREEN MOTOR
LINE
This is an example of Exhaust Fan 1 provided with a Vari-Green motor.
R+ R­S+
S2
S­IG
OFF
L3
L2L1
LINE
Each variable frequency drive must have the
LINE and LOAD wiring in separate conduit
VFD-F1-E
MARK: FAN MARK
VOLT/HP
MODBUS VFD
ADDRESS: X
T2T1
LOAD
T3
VFD Provided by Others, Control Wiring - if equipped
• Fault command from Vari-Flow to VFD provided by
• Run command from Vari-Flow to VFD provided by
• Speed reference from Vari-Flow to VFD provided by
MODBUS VFD
• Line power to VFD
• Load power from VFD to fan
This is an example of Exhaust Fan 1 provided with a VFD by others.
others (Terminal E__-FA, E__-FB)
others (Terminal E__-RA, E__-RB)
others (Terminal E__S+, E__S-)
E1-FA E1-FB E1-RA E1-RB E1-S+ E1-S-
NORMALLY OPEN
FAULT CONTACT
COMMON RUN COMMAND RUN COMMAND SPEED REFERENCE + SPEED REFERENCE -
L3
L2L1 T3T2T1
VFD BY OTHERS
LINE LOAD
VFD-F1-E
MARK: VFD BY
OTHERS VOLT/PH
HP
VFD BY OTHERS
Vari-Flow Air Management System
6
®
Make-Up Air VFD in Vari-Flow Wiring - if equipped
• 24 VAC run command from Vari-Flow to make-up air unit (Terminals S__-42, S__-43)
• Tempering status from Vari-Flow to make-up air unit (Terminals S__-44, S__-45)
• Line power to VFD input, bottom left of VFD (Terminals L1, L2, L3)
• Load power from VFD output, bottom right of VFD to make-up air disconnect (Terminals T1, T2, T3)
Make-up air unit requires separate 115 VAC control power circuit.
THIS LAST VFD IN
R+
MODBUS LINE MUST
HAVE THE END OF
R-
LINE RESISTOR
SWITCHED ON
S+
S2
S-
ON
IG
L2L1
L3
VFD-F2-S
MARK: MUA - VFD
VAV
VOLT/PH
HP
MODBUS VFD
ADDRESS: X
T3
T2T1
MODBUS VFDMUA UNIT
Make-Up Air VFD in Make-Up Air Wiring - if equipped
• 24 VAC run command from Vari-Flow to make-up air unit (Terminals S__-42, S__-43)
• Tempering status from Vari-Flow to make-up air unit (Terminals S__-44, S__-45)
• 0-10 VDC speed reference from Vari-Flow to make-up air unit (Terminals S__-46, S__-47)
Power for make-up air goes directly to make-up air unit.
S1-42 S1-43 S1-44 S1-45 S1-46 S1-47
24 VAC RUN 24 VAC COM TEMPERING STATUS TEMPERING STATUS SPEED REFERENCE + SPEED REFERENCE -
NOTE: CONTROL POWER FOR MUA GOES DIRECTLY FROM BREAKER PANEL TO MUA.
MARK: MUA - VFD
VFD IN MUA UNIT
(0-10 VDC)
VFD-F2-S
MUA
VOLT/PH
HP
MUA - VFD IN UNIT
S2-42 S2-43 S2-44 S2-45
LINE
RUN
24 VAC
COM TEMPERING STATUS TEMPERING STATUS
SEPARATE CONTROL POWER TO UNIT REQUIRED
LOAD
DISCONNECT IN UNIT
MAKE UP AIR UNIT CONTROL WIRING MARK: MUA - VFD
VAV F2-S
This is an example of Supply Fan 1 being a
make-up air with VFD in the Vari-Flow.
being a make-up air with VFD in the make-up air unit.
This is an example of Supply Fan 1
Auto Tempering - if equipped
• Auto Heat/Cool enable
(Terminals S1-R, S1-W1, S1-Y1)
S1-42 S1-43 S1-44 S1-45 S1-46 S1-47
S1-R
S1-W1
S1-Y1
24 VAC RUN 24 VAC COM TEMPERING STATUS
TEMPERING STATUS SPEED REFERENCE + SPEED REFERENCE ­CONTROL COMMON HEAT COOL
NOTE: CONTROL POWER FOR MUA GOES DIRECTLY FROM BREAKER PANEL TO MUA.
This is an example of Supply Fan 1 with auto tempering.
MARK: MUA - VFD
VFD IN MUA UNIT
(0-10 VDC)
VFD-F2-S
VOLT/PH
MUA
HP
MUA - VFD IN UNIT
Fire System Microswitch
• Fire system microswitch common to Vari-Flow (Terminal C1)
• Fire system microswitch normally closed contact to Vari-Flow (Terminal NC1)
C1 NC1
®
Vari-Flow Air Management System
7
Resistive Temperature Detectors (RTD)
Wire the two leads of the sensors to be designated terminals in the control panel as shown below. This is determined by the number of temperature sensors on the job (1-10 sensors). The two wires of the sensor are not polarity sensitive. If more than one hood is being controlled, be sure that the appropriate sensor is wired to the appropriate terminals as depicted on the job specific wiring diagram.
NOTE
The RTD’s should not be exposed to direct flame. The RTD’s are rated up to 250°F
CAUTION
Exposing the sensor to direct flame may render the sensor inoperable and will void the warranty.
Temperature Sensors* - installed in hood
• Temperature Sensor T1 to Vari-Flow (Terminals T1-A, T1-B)
Refer to table (example below) to cross reference the temperature sensor and the hood mark.
*Repeat based on the number of temperature sensors. (Terminals T2-A, T2-B | T3-A, T3-B | T4-A, T4-B | T5­A, T5-B | T6-A, T6-B | T7-A, T7-B | T8-A, T8-B | T9-A, T9-B| T10-A, T10-B)
T1
T1-A T1-B
T2-A
T3-A
T4-A T4-B
T5-A T5-B
T6-A
T7-A
T8-A
T9-A
T10-A
T3
T5
T7
T9
T2
T4
T6
T8
T10
T2-B
T3-B
T6-B
T7-B
T8-B
T9-B
T10-B
Keypad - if equipped
• Connect provided cable from back of keypad to CAREL® PCO5+ controller (Terminal J10)
CONNECT FACTORY PROVIDED RJ25 CABLE
TO J10 ON PCO5+ AND BACK OF KEYPAD
PCO5+ J10 KEYPAD
35 Foot Cable Provided
75 or 150 Foot Cable is Optional
Touchscreen - if equipped
Power Wiring
• Connect provided 2-wire cable from Vari-Flow (Terminals 24H, 24C) to touch screen (Terminals G, GO)
Control Wiring
• Connect provided 3-wire cable from Vari-Flow (Terminals -, +, GND) to touch screen (Terminals -, +, GND)
Power Wiring
24C 24H
TOUCH
SCREEN
GO
G
Control Wiring
-
+
GND
TOUCH
SCREEN
-
+
GND
Remote Enable - if used
• Connect remote enable common and normally open
from BMS to Vari-Flow (Terminals RE-1A, RE-1B)
A closed contact will turn on all fans. An open contact will turn off all fans.
NOTE: Temperature interlock will override the remote
enable input.
RE-1A RE-1B
NOTE: The Vari-Flow job specific temperature sensor table is found in the wiring diagram located on the Vari­Flow panel door. This table is an example, do not use for your specific job.
Sensors (Field Wiring) Related Fans
Sensor Hood Mark Exhaust Fans Supply Fans
T1 Hood Mark Name 1 F1-E F11-S T2 Hood Mark Name 2 F2-E F11-S T3 Hood Mark Name 3 F3-E F12-S T4 Hood Mark Name 4 F4-E F12-S T5 Hood Mark Name 5 F5-E F12-S T6 Hood Mark Name 6 F6-E F13-S T7 Hood Mark Name 7 F7-E F13-S T8 Hood Mark Name 8 F8-E F14-S T9 Hood Mark Name 9 F9-E F14-S
T10 Hood Mark Name 10 F10-E F14-S
Vari-Flow Air Management System
8
®
Shunt Trip - if used
• 115 VAC from Vari-Flow to shunt trip breaker coil
(provided by others) (Terminals STH, STN)
Voltage across STH, STN when in fire will be 115 VAC Voltage across STH, STN when not in fire will be 0 VAC
STH STN
STB
Electric Gas Valve with Gas Reset - if equipped
• 115 VAC from Vari-Flow to gas solenoid (Terminals SVH, SVN)
Voltage across SVH, SVN when in fire will be 0 VAC Voltage across SVH, SVN when not in fire and turn on will be 115 VAC
SVH SVN
SV1
SV2
Spare Fire Relay Contacts - if equipped
• Power to common (Terminal C3)• Power out, normally open, closed in fire
(Terminal NO3)
• Power out, normally closed, open in fire
(Terminal NC3)
• Power to common (Terminal C4)• Power out, normally open, closed in fire
(Terminal NO4)
• Power out, normally closed, open in fire
(Terminals NC4)
(Can be used for shunt trip, alarms, etc.)
C3 A B
NO3
NC3
121411
R6
A B
C4 NO4 NC4
222421
R6
High Temperature Alarm Contacts - if equipped
• Power to common (Terminal HT-C)• Power out, normally closed, open in high
temperature alarm (Terminal HT-NC)
• Power out, normally open, closed in high
temperature alarm (Terminal HT-NO)
(Can be used for shunt trip, alarms, etc.)
HT-C A B
A: Closed with power at H & N and high temperature alarm inactive, closed with no power
B: Open with power at H & N and high temperature alarm active, open with no power
HT-NC HT-NO
222421
R13
Airflow Proving Switch(es) (provided by others) - if equipped
• Common and normally open from supply fan 1 air proving switch to Vari-Flow (Terminals AP-1A, AP-1B)
• Common and normally open from supply fan 2 air proving switch to Vari-Flow (Terminals AP-2A, AP-2B)
• Common and normally open from supply fan 3 air proving switch to Vari-Flow (Terminals AP-3A, AP-3B)
• Common and normally open from supply fan 4 air proving switch to Vari-Flow (Terminals AP-4A, AP-4B)
NOTE: Airflow proving switch(es) are not provided with
the Vari-Flow system.
AP-1A AP-1B
AP-2A AP-2B
AP-3A AP-3B
AP-4A AP-4B
AIR PROVING SUPPLY FAN 1
AIR PROVING SUPPLY FAN 2
AIR PROVING SUPPLY FAN 3
AIR PROVING SUPPLY FAN 4
A: Open with power at H & N and fire system armed closed on fire or no power
B: Closed with power at H & N and fire system armed open on fire or no power
®
Wash Interface - if equipped
• Wash input from waterwash control panel (WWCP) to
Vari-Flow (Terminals WI-1A, WI-1B)
• Wash output from Vari-Flow to Grease Grabber H
O
2
or WWCP (Terminals WO-1A, WO-1B)
• Low detergent input from Grease Grabber H
O or
2
WWCP to Vari-Flow (Terminals WD-1A, WD-1B)
WASH FAN ENABLE/DISABLE
WI-1A WI-1B
WD-1A WD-1B
WO-1A
WO-1B
WASH DETERGENT
WASH OUTPUT
Vari-Flow Air Management System
9
Vari-Flow Connection Checklist
Power for Vari-Flow Cabinet
Connect 115 VAC power for controls (Terminals H, N) Connect 115 VAC power for hood lights, one per light
circuit (Terminals H1, N1 | H2, N2 | H3, N3 | H4, N4)
Connect 115 VAC power to lights, one per light circuit
(Terminals B1, W1 | B2, W2 | B3, W3 | B4, W4)
Power to Variable Frequency Drives (VFD)*
Line power to VFD input, bottom left of VFD
(Terminals L1, L2, L3)
Load power from VFD output, bottom right of VFD
(Terminals T1, T2, T3)
Vari-Green® Fan Wiring* - if equipped
24 VAC from Vari-Flow to Vari-Green motor control wire,
black (Terminal E__-24)
0-10 VDC Speed Reference from Vari-Flow to Vari-Green
motor control wire, red (Terminal E__S+)
Common from Vari-Flow to Vari-Green motor control wire,
white (Terminal E__S-)
VFD Provided by Others, Control Wiring* - if equipped
Fault command from Vari-Flow to VFD provided by others
(Terminal E__-FA, E__-FB)
Run command from Vari-Flow to VFD provided by others
(Terminal E__-RA, E__RB)
Speed reference from Vari-Flow to VFD provided by others
(Terminal E__S+, E__S-)
Line power to VFD Load power from VFD to fan
Make-Up Air VFD in Vari-Flow Wiring* - if equipped
24 VAC run command from Vari-Flow to make-up air unit
(Terminals S__-42, S__-43)
Tempering status from Vari-Flow to make-up air unit
(Terminals S__-44, S__-45)
Line power to VFD input, bottom left of VFD
(Terminals L1, L2, L3)
Load power from VFD output, bottom right of VFD to make-
up air disconnect (Terminals T1, T2, T3)
Make-Up Air VFD in Make-Up Air Wiring* - if equipped
24 VAC run command from Vari-Flow to make-up air unit
(Terminals S__-42, S__-43)
Tempering status from Vari-Flow to make-up air unit
(Terminals S__-44, S__-45)
0-10 VDC speed reference from Vari-Flow to make-up air
unit (Terminals S__-46, S__-47)
Auto Tempering - if equipped
Auto Heat/Cool enable
(Terminals S1-R, S1-W1, S1-Y1)
Fire System Microswitch
Fire system microswitch common to Vari-Flow (Terminal C1) Fire system microswitch normally closed contact to
Vari-Flow (Terminal NC1)
* Wiring repeated based on the number of
fans of that type. This is based on the job specific Vari-Flow wiring diagram.
Resistive Temperature Sensors* - installed in hood
Temperature Sensor T1 (Terminals T1-A, T1-B)
If more than one temperature sensor is used, wire the
following if applicable:
Temperature Sensor T2 (Terminals T2-A, T2-B) Temperature Sensor T3 (Terminals T3-A, T3-B) Temperature Sensor T4 (Terminals T4-A, T4-B) Temperature Sensor T5 (Terminals T5-A, T5-B) Temperature Sensor T6 (Terminals T6-A, T6-B) Temperature Sensor T7 (Terminals T7-A, T7-B) Temperature Sensor T8 (Terminals T8-A, T8-B) Temperature Sensor T9 (Terminals T9-A, T9-B) Temperature Sensor T10 (Terminals T10-A, T10-B)
Keypad - if equipped
Connect provided RJ25 cable from back of keypad to
CAREL® PCO5+ (Terminal J10).
Touch Screen - if equipped
Connect provided 2-wire cable from Vari-Flow
(Terminals 24H, 24C) to touch screen (Terminals G, GO)
Connect provided 3-wire cable from Vari-Flow
(Terminals -, +, GND) to touch screen (Terminals -, +, GND)
Remote Enable- if used
Connect remote enable common and normally open from
BMS to Vari-Flow (Terminals RE-1A, RE-1B)
Shunt Trip - if used
115 VAC from Vari-Flow to shunt trip breaker coil (provided
by others) (Terminals STH, STN)
Electric Gas Valve with Gas Reset - if equipped
115 VAC from Vari-Flow to gas solenoid
(Terminals SVH, SVN)
Spare Fire Relay Contacts - if equipped
Power to common (Terminal C3) Power out, normally open, closed in fire (Terminal NO3) Power out, normally closed, open in fire (Terminal NC3)
Power to common (Terminal C4) Power out, normally open, closed in fire (Terminal NO4) Power out, normally closed, open in fire (Terminal NC4)
High Temperature Alarm Contacts - if equipped
Power to common (Terminals HT-C) Power out, normally closed, open in high temperature alarm
(Terminal HT-NC)
Power out, normally open, closed in high temperature alarm
(Terminal HT-NO)
Air Proving Switch(es) (provided by others) - if equipped Common and normally open from supply fan 1 air proving
switch to Vari-Flow (Terminals AP-1A, AP-1B)
Common and normally open from supply fan 2 air proving
switch to Vari-Flow (Terminals AP-2A, AP-2B)
Common and normally open from supply fan 3 air proving
switch to Vari-Flow (Terminals AP-3A, AP-3B)
Common and normally open from supply fan 4 air proving
switch to Vari-Flow (Terminals AP-4A, AP-4B)
Wash Interface - if equipped
Wash input from waterwash control panel (WWCP) to
Vari-Flow (Terminals WI-1A, WI-1B)
Wash output from Vari-Flow to Grease Grabber H
O or
2
WWCP (Terminals WO-1A, WO-1B)
Low detergent input from Grease Grabber H
O or WWCP to
2
Vari-Flow (Terminals WD-1A, WD-1B)
Vari-Flow Air Management System
10
®
Loading...
+ 22 hidden pages