Greenheck SSIMO-XXX Installation Manual

Part number 464603
IMO-XXX & SSIMO-XXX series
Fire and Combination Fire Smoke Dampers
Vertical or Horizontal Mount
Installation, Operation and Maintenance Instructions
International Maritime Fire Test Procedure Code
USCG Type Approved Approval Number 164.139/0007/0
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (37°C).
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
IF HEIGHT <=11.00 in. (279mm)
IF HEIGHT >11.00 (279mm)
6 in. (152mm)
18 in. (457mm)
6 in. (152mm)
18 in. (457mm)
6 in. (152mm)
6 in. (152mm)
18 in. (457mm)
18 in. (457mm)
Installation Instructions
Greenheck’s IMO dampers were tested per the International Maritime Organization’s Fire Test Procedure (FTP) code in a Class A bulkhead and in a Class A deck for 60 minutes. The FTP code requires that the ductwork (coaming) be insulated and that the damper be bolted or welded to the duct.
1. Insulating the Duct
The ductwork must be insulated a minimum of 6 in. (152mm) on the damper side and 18 in. (457mm) on the non-damper side (see figures 1-4). Any US Coast Guard type approved insulation with an A60 rating can be used. The insulation is to be installed on the duct with 0.106 in. (2.7mm) steel pins and 1.12 in. x 1.24 in. x 0.4 in. (28mm x 31mm x 10mm) steel clips.
2. Attaching Damper to Duct
The damper can be installed to the duct using either bolts or welding. If bolts are used , they are to be a minimum of 0.375 in. (9.5mm) diameter and 1 in. (25mm) long. The fasteners should be spaced 6 in. (152mm) OC and a maximum of 2 in. (51mm) from the corners.
Horizontal Airflow- Vertical Damper mount
Fig. 1
Fig. 2
Vertical Airflow- Horizontal Damper mount
Fig. 3
Fig. 4
Loading...
+ 2 hidden pages