Document number 462103
®
INSTALLATION INSTRUCTION SUPPLEMENT
Sleeve Extensions
Refer to:
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’
(Part #452763)
or
‘Installation Instructions for FSD-XXX, DFD-XXX, CFSD-XXX,
SSFSD-XXX Series Fire & Combination Fire Smoke Dampers’
(Part #461336)
or
‘Installation Instructions for FD & DFD 150X Series Curtain
Fire Dampers’ (Part #453946) for additional details.
11/2 Hour Curtain Fire Dampers and
Combination Fire Smoke Dampers
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 (Listing #R13317)
Standard 555S (Listing #R13447)
FD & DFD Series
FSD Series
Application
Factory installed sleeves may need to be extended in the field. This supplement covers the following
applications:
• When the factory sleeve extends all the way through the rated barrier (Figure 1)
• When the factory sleeve ends in the plane of the rated barrier (Figure 2).
This supplemental installation instruction provides details for attachment of the sleeve extension. Consult
Authority Having Jurisdiction (AHJ) for approval.
Minimum 1 in.
Overlap
Factory Sleeve
Sleeve Extension
Fire or Fire Smoke
Damper
Factory Sleeve
Sleeve
Extension
Figure 1: Factory sleeve extends all the way
through the rated barrier.
Notes
1. Sleeve extension must be same material and gage
as factory sleeve.
2. The inside dimensions of the sleeve extension must
be the same dimensions as the outside dimensions
of the factory sleeve.
3. Sleeve extension must overlap the factory sleeve a
minimum of 1 in. (25mm).
Connecting Joint of Sleeves
See notes 4,5, and 7
Figure 2: Factory sleeve ends in the plane of the rated
barrier.
Fire or Combination Fire
Smoke Damper
4. All four sides of the sleeve extension must be
attached to the factory sleeve. Attachments must
be spaced a maximum of 6 in. (152mm) on center
and a maximum of 2 in. (51mm) from corners. A
minimum of 2 attachments per side (8 per damper )
are required. One of the methods of attachment
shown below must be used.
- tack or spot welds
- #10 sheet metal screws
- 1/4 in. (6mm) bolts and nuts
- 3/16 in. (4.7mm) steel pop rivets
5. Products with a smoke rating (FSD models) require
that the joint between the two sleeves be sealed.
Approved caulks include:
• G.E. 1200 series silicone construction
adhesive
• Component Hardware Group (QMFZ2)
silicone SLT-5000 or SLT-5200
• Silico (QMFZ2) silicone SB or CH (E224060)
• Dow Corning (QMFZ2) silicone SLT-5200
(E40195)
• Dow R/C (QMFZ2) silicone Type RTV732.
Approved duct sealants include:
• Precision PA2084T duct sealant adhesive
• Design Polymetrrics DP1010 water base duct
sealant
• Grey Pookie
• Ductmate PROseal
®
• CL Ward S seal
6. Sleeve extensions can be made to either end of
the factory sleeve. However, the total sleeve length
cannot extend more then 16 in. (406mm) on the
actuator side and not more than 6 in. (152mm) on
the non-actuator side.
7. The joint created by the factory sleeve and sleeve
extension cannot be in the plane of the partition.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in
the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
462103• Sleeve Extension Rev. 5, April 2014 Copyright 2014 © Greenheck Fan Corporation