Greenheck SED-501 Installation Manual

Page 1
Sightproof Louver
Drainable Blade
Application and Design
SED-501 is a sightproof weather louver designed to protect air intake and exhaust openings in building exterior walls when visual see through prevention is needed. Design incorporates a drainable head member and drainable horizontal Chevron style blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The SED-501 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
5 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Chevron style drainable design, heavy gauge
extruded 6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned on approximately 2 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
SED-501
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Page 2
Free Area Chart (Sq. ft.)
Louver Height Inches
12 24 30 42 48 60 66 78 84 96 102 114 120
12 0.32 0.74 0.95 1.37 1.58 1.95 2.16 2.57 2.78 3.20 3.41 3.83 3.99
18 0.58 1.33 1.71 2.46 2.84 3.49 3.87 4.62 5.00 5.75 6.12 6.88 7.16
24 0.84 1.92 2.46 3.55 4.09 5.04 5.58 6.67 7.21 8.30 8.84 9.92 10.33
30 1.09 2.51 3.22 4.64 5.35 6.59 7.30 8.71 9.42 10.84 11.55 12.97 13.50
36 1.35 3.10 3.98 5.73 6.60 8.13 9.01 10.76 11.64 13.39 14.26 16.01 16.67
42 1.61 3.69 4.73 6.82 7.86 9.68 10.72 12.81 13.85 15.93 16.98 19.06 19.84
48 1.86 4.28 5.49 7.91 9.11 11.23 12.44 14.85 16.06 18.48 19.69 22.10 23.01
54 2.12 4.87 6.24 8.99 10.37 12.78 14.15 16.90 18.28 21.03 22.40 25.15 26.18
60 2.38 5.46 7.00 10.08 11.63 14.32 15.86 18.95 20.49 23.57 25.11 28.20 29.35
66 2.63 6.05 7.76 11.17 12.88 15.87 17.58 20.99 22.70 26.12 27.83 31.24 32.52
72 2.89 6.64 8.51 12.26 14.14 17.42 19.29 23.04 24.91 28.66 30.51 34.29 35.69
78 3.15 7.23 9.27 13.35 15.39 18.96 21.00 25.09 27.13 31.21 33.25 37.33 38.86
84 3.40 7.82 10.03 14.44 16.65 20.51 22.72 27.13 29.34 33.76 35.96 40.38 42.03
90 3.66 8.41 10.78 15.53 17.90 22.06 24.43 29.18 31.55 36.30 38.68 43.42 45.20
96 3.92 9.00 11.54 16.62 19.16 23.61 26.15 31.23 33.78 38.85 41.39 46.47 48.37
102 4.17 9.59 12.29 17.71 20.41 25.15 27.86 33.27 35.98 41.39 44.10 49.51 51.54
108 4.43 10.18 13.05 18.80 21.67 26.70 29.57 35.32 38.19 43.94 46.81 52.56 54.72
114 4.69 10.77 13.81 19.89 22.93 28.25 31.29 37.37 40.41 43.49 49.53 55.61 57.89
120 4.94 11.36 14.56 20.98 24.18 29.79 33.00 39.41 42.62 49.03 52.24 58.65 61.06
Louver Width in Inches
SED-501PERFORMANCE DATA
Sightproof Louver Drainable Blade
Extruded Aluminum
Greenheck Fan Corporation certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
the SED­501 louvers shown
®
herein are licensed to
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Intake
Exhaust
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model SED-501 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
1000 1050 1100 1150 1200 1250 1300
ft/min:
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.5 6.6
m/s:
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model SED-501 is 1134 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Page 3
SED-501INSTALLATION DETAILS
Maximum Size and Installation Information
Maximum single section size for model SED-501 is 120 in. W x 84 in. H or 84 in. W x 120 in. H (70 sq. ft). Larger openings require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand a 25 PSF wind-load (please consult Greenheck if the louvers must withstand higher wind-loads). Structural reinforcing members may be required to adequately support and install multiple louver panels within a large opening. Structural reinforcing members along with any associated installation hardware is not provided by Greenheck unless indicated otherwise by Greenheck. Additional information on louver installation may be found in AMCA Publication #501, Louver Application Manual.
Sightproof Louver Drainable Blade
Extruded Aluminum
Minimum Single Section Size
12 in. W x 12 in. H
Maximum Single Section Size
70 ft. sq.
Page 4
PRODUCT DETAILS
SED-501
Sightproof Louver Drainable Blade
Extruded Aluminum
Page 5
SED-501OPTION DRAWINGS
Sightproof Louver Drainable Blade
Extruded Aluminum
FINISHES
Finish Type Description/Application Color Selection
2-coat 70% KYNAR 500®/HYLAR 5000® AAMA 2605 –
Dry fi lm thickness 1.2 mil. (AKA: Duranar®, Fluoropon®, Trinar®, Flouropolymer, Polyvinylidene Fluoride, PVDF2)
2-coat 50% KYNAR 500®/HYLAR 5000® AAMA 2604 – Dry fi lm thickness 1.2 mil. (AKA: Acrofl ur®, Acrynar®)
Baked Enamel AAMA 2603 – Dry fi lm thickness 0.8 mil. (AKA: Acrabond Plus®, Duracron®)
Integral Color Anodize AA-M10C22A42 (>0.7 mil)
Clear Anodize 215 R-1 AA-M10C22A41 (>0.7 mil)
Clear Anodize 204 R-1 AA-M10C22A31 (0.4-0.7 mil)
Industrial coatings
Mill
“Best.” The premier fi nish for extruded aluminum. Tough, long-lasting coating has superior color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.
“Better.” Tough, long-lasting coating has excellent color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.
“Good.” Provides good adhesion and resistance to weathering, corrosion and chemical stain.
“Two-step” anodizing is produced by following the normal anodizing step with a second, colorfast process.
Clear, colorless and hard oxide aluminum coating that resists weathering and chemical attack.
Clear, colorless and hard oxide aluminum coating that resists weathering and chemical attack.
Greenheck offers a number of industrial coatings such as Hi-Pro Polyester, Epoxy, and Permatector®. Consult a Greenheck Product Specialist for complete color and application information.
Materials may be supplied in natural aluminum or galvanized steel fi nish when normal weathering is acceptable and there is no concern for color or color change.
Finishes meet or exceed AAMA 2605, AAMA 2604, and AAMA 2603 requirements. Please consult www.greenheck.com for complete information on standard and extended paint warranties. Paint fi nish warranties are not applicable to steel products.
Standard Colors: Any of the 24 standard colors shown can be furnished in 70% or 50% KYNAR 500®/HYLAR 5000® or Baked Enamel.
2-Coat Mica:
Greenheck offers 9 standard 2­coat Mica colors. Other colors are available. Consult Greenheck for possible extra cost when selecting non-standard colors or special fi nishes.
Light, Medium or Dark Bronze; Champagne; Black
Clear 5 years
Clear 1 Year
Copyright © 2007 Greenheck Fan Corporation
Standard Warranty
(Aluminum)
10 Years (Consult Greenheck for availability of extended
warranty)
5 Years
1 Year
5 years
Consult Greenheck
n/a
SED-501
August 2007 Rev. 2
Greenheck Fan Corporation reserves the right
to make product changes without notice.
Loading...