Greenheck S73 User Manual

The High Performance Company
SERIES 73
ELECTRIC ACTUATOR
OPERATION AND MAINTENANCE MANUAL
Table Of COnTenTs:
page
Safety inStructionS: DefinitionS of termS................................................................. 2
introDuction
principle of operation.............................................................................................. 3
electrical operation................................................................................................ 3
mechanical operation.............................................................................................. 3
inStallation
pre-inStallation Storage......................................................................................... 3
mounting to valve.................................................................................................... 4
manual overriDe operation..................................................................................... 4
electrical inStallation............................................................. .............................. 5
multiple actuator wiring......................................................................................... 6/7
travel limit Switch aDjuStment............................................................................... 8
fielD or factory inStallable optionS
heater........................................................................................................................ 8
auxiliary SwitcheS.................................................................................................... 9
typical Single phaSe & Dc wiring DiagramS.......................................................... 10
appenDix a
baSic toolS................................................................................................................ 11
appenDix b
actuator troubleShooting chart........................................................................... 12
for information on thiS proDuct anD other bray proDuctS
pleaSe viSit uS at our webpage - www.bray.com
BRAY Series 73 Electric Actuator
!
!
!
Operation and Maintenance Manual
1.0 safeTy InfOrmaTIOn - DefInITIOn Of Terms
WARNING indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
NOTICE used without the safety alert symbol indicates a potential situation which, if not avoided, may result in an undesirable result or state, including property damage.
1.1 HazarD-free use
This device left the factory in proper condition to be safely installed and operated in a hazard-free manner. The notes and warnings in this document must be observed by the user if this safe condition is to be maintained and hazard­free operation of the device assured.
Take all necessary precautions to prevent damage to the actuator due to rough handling, impact, or improper storage. Do not use abrasive compounds to clean the actuator, or scrape metal surfaces with any objects.
ground, tag and lock electrical circuits and equipment in
accordance with established safety practices
Is trained in the proper use and care of personal pro-
tective equipment (PPE) in accordance with established safety practices
• Is trained in rst aid
In cases where the device is installed in a potentially
explosive (hazardous) location – is trained in the opera­tion, commissioning, operation and maintenance of equipment in hazardous locations
The control systems in which the actuator is installed must have proper safeguards to prevent injury to person­nel, or damage to equipment, should failure of system components occur.
1.2 QualIfIeD PersOnel
A qualied person in terms of this document is one who is
familiar with the installation, commissioning and operation of
the device and who has appropriate qualications, such as:
Is trained in the operation and maintenance of electric
equipment and systems in accordance with established safety practices
Is trained or authorized to energize, de-energize,
2
WARNING
The actuator must only be installed, commissioned, oper-
ated and repaired by qualied personnel.
The device generates large mechanical force during normal operation. All installation, commissioning, operation and maintenance must be performed under strict observation of all applicable codes, standards and safety regulations. Reference is specically made here to observe all appli­cable safety regulations for actuators installed in potentially explosive (hazardous) locations.
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
Part nuMbering systeM reference chart
Part nuMber tOrque sPeed, 1/4 turn suPPly suPPly
(In.Lbs) (Seconds) (Volts AC) (Volts DC)
73-010Y-113ZV-536 100 2/5/10 120/240 NA
73-030Y-113ZV-536 300 5/10/15 120/240 12/24
73-060Y-113ZV-536 600 5/10/15/30/60 120/240 12/24
Y - DESIGNATES THE SPEED S Y = 0 1 2 3 4 5 SEC = 2 5 10 15 30 60
Z - DESIGNATES DRIVE TYPE Z=
TYPE=
Use this chart as a guide to interpret the S73 electric actuator part number.
D S
DOUBLE D STAR
InTrODuCTIOn
The Bray Series 73 is a quarter turn electric actuator with manual override for use on any quarter turn valve requiring up to 600 Lb-In of torque. Operating speeds vary between 2 to 60 seconds. Adjusting two cams sets the open and close travel limit switches. These cams can be adjusted to allow rotational travel anywhere from 45° to 300°. Standard Factory setting allows for 90° reversible rotation.
PrinciPle Of OPeratiOn
The Series 73 actuator is basically divided into two internal sections; the power center below the switchplate, and the control center above the switchplate. Below the switch­plate the spur geartrain drives an output coupling. The override mechanism for manual operation is also located here. Above the switchplate are components requiring customer adjustment. The indicator shaft assembly, limit switches, terminal strips, heater, capacitor and motor are all placed here for easy access. External to the unit are a highly visible valve position indicator, the unique manual override shaft and two 1/2” NPT conduit entry ports. The
external nish is a high quality polyester powder coating,
which has exceptional UV as well as chemical resistance.
electrical OPeratiOn
The motor used in the Bray Series 73 is a permanent induction split capacitor design (single phase AC power). Travel limit switches are mechanical form C (SPDT) are rated at 10 amp (0.8 PF), 1/2 HP 125 VAC and 3/4 HP 250 VAC. In situations where the torque capacity of the unit is exceeded to the point where the motor stalls and overheats, a thermal protector switch built into the motor windings will automatically disconnect the motor power.
Once the motor cools sufciently the thermal switch will
V - DESIGNATES VOLTAGE
V= VOLTAGE
3 4 5 6
12VDC 24VDC 120VAC 220VAC
reset. The motor has a spring loaded brake that activates when power is removed from the unit. The brake prevents the spur gears from being back driven.
General Electrical Schematic
(Note: the schematic below is for reference only. The actual wiring
diagram for each specic unit is placed inside the actuator cover).
Mechanical OPeratiOn
Mechanically, the ratio of the gearmotor determines the
speed of the unit. The gearmotor utilizes high efciency
spur gears with various ratios for the actuation speeds. Positioning is determined by an indicator-camshaft linked to the output coupling.
Pre-installatiOn stOrage
Units are shipped with two metal conduit entry plugs to prevent foreign matter from entering the unit.
nOTICe
To prevent condensation from forming inside these units, maintain a near constant external temperature and sup­ply power to the optional heater internal to the unit.
3
Open Travel Switch
Close Travel Switch
Gear With Square Drive Hole (Cutaway)
Switch Plate (Cutaway)
Spring
Valve Stem
Gear With Square Drive Hole (Cutaway)
Switch Plate (Cutaway)
Double D Drive End of Indicator Shaft
Actuator Drive Coupling
Valve Stem
Double D Drive End of Indicator Shaft
Actuator Drive Coupling
Indicator Shaft
Spring
Snap Ring
Open Travel Switch
Close Travel Switch
Open Cam
Close Cam
Square Drive of Indicator Shaft
Square Drive of Indicator Shaft
Snap Ring
Indicator Shaft
Using an Adjustable Wrench, Push Down and Rotate the Indicator Shaft to Manually Drive the Actuator & Valve
Series 73 Under Normal Electrical Operating Conditions
Open Cam
Close Cam
BRAY Series 73 Electric Actuator
!
Operation and Maintenance Manual
WARNING Turn off all power and lock out service panel before installing or modifying any
electrical wiring.
InsTallaTIOn
MOunting tO a ValVe
All Bray Series 73 electric actuators mount directly to Bray
buttery valves. With proper mounting hardware, the S73
actuator can be installed onto other quarter-turn valves or devices. For horizontal installation, the standard mount­ing position aligns the actuator parallel and upright to the pipeline. If the actuator is to be mounted on a vertical pipe, it is recommended that the unit be positioned with the conduit entries on the bottom to prevent condensa­tion from entering the actuator through the conduit. In all cases, the conduit should be positioned to prevent drainage into the actuator.
manual OverrIDe OPeraTIOn
1. Ensure that electrical power to the unit is off.
2. Press valve position indicator down, then release a few times to ensure ease of movement.
3. Remove the valve position indicator pointer.
4. Using an adjustable wrench, 6” or 12” depending on actuator size, push down on indicator shaft to disengage it from output gear, then turn shaft to required position. Open and Close lettering and a
The actuator should be mounted to the valve as follows:
1. Manually operate the actuator until the output shaft of the actuator is in line with the valve stem. If possible, use an intermediate position (i.e. valve disc/stem and actuator half open).
2. Place the proper adapter, if required, onto the valve stem. It is recommended that a small amount of grease be applied to the adapter to ease assembly.
3. Mount the actuator onto the valve stem. It may be necessary to manually override the actuator to align the bolt patterns.
4. Install the furnished mounting studs by threading them all the way into the actuator base.
5. Fasten in place with the furnished hex nuts and lock washers.
direction of travel arrow are molded into the hous­ing for easy reference and permanent position
indication. The double D ats on the indicator shaft
are in alignment with the valve disc position.
5. Return to electrical operation by turning power on to the unit. The shaft will re-engage the output gear when electrical power is applied to the actuator.
6. Replace the valve position indicator pointer.
4
electrical installatiOn
SERIES
73
TORQUE
VOLTAGE
SPEED
[N m] In. lbs.
TAG
sec.
DUTYF.L.C.
XXX
INT.O.4
120VAC
100 10
Amps
1 /4 turn
C US
!
!
1. Check the actuator’s nametag for conrmation of:
Torque Rating, Quarter Turn Time, Duty Rating and Power Supply. Example ‘A’ below is shown for S73 PN: 73-0102-113D5-536
2. Suitably rated wire should be used for actuator voltage
and current rating. 18AWG, 300V minimum, insulated
wire is recommended for all sizes.
3. Field control scheme (supplied by others) should be compatible with the operation of actuator motor (AC or DC).
NOTE: Do not parallel wire multiple actuators - refer
to explanation on parallel wiring.
CAUTION
Do not reverse motor instantaneously when it is still running - Reversing direction to actuator motor when it is running can cause damage to motor, switches and gearing. Directional control switching can be done by PLC in 20ms or by a small relay in 45ms. Therefore time delay of 1s has to be incorporated into the control scheme to avoid damage.
NOTICE
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
CAUTION
Do not reverse motor instantaneously when it is still running - Reversing direction to actuator motor when it is running can cause damage to motor, switches and gearing. Directional control switching can be done by PLC in 20ms or by a small relay in 45ms. Therefore time delay of 1s has to be incorporated into the control scheme to avoid damage.
Figure A
Correct
18 AWG minimum wire is recommended for all eld wiring
4. Actuator must have its eld wiring terminated as shown
in the supplied wiring diagram (diagram attached to
inside of cover). Wiring diagrams (AC or DC) show
remote (customer supplied) typical control switching
devices. Refer to customers/eld wiring for details of the specic control devices.
The conduit connections must be properly sealed to main­tain the weatherproof integrity of the actuator enclosure.
Example A:
NOTICE
Incorrect
5
BRAY Series 73 Electric Actuator Operation and Maintenance Manual
Multiple Actuator (Parallel) Wiring
A voltage is present on both motor windings, these voltages are out of phase and different in magnitude. If these windings are connected to one another as shown in the INCORRECT diagrams, this will interfere with the motor performance. Use a multiple pole switch as shown in the CORRECT diagram.
incOrrect cOnnectiOns
A. No supply on terminal L. B. Control switch in “Open Run Position” C. Both actuators in a mid-travel position. i.e. Their open
& close travel switches are closed, allowing them to operate in an open or close travel direction.
*The following three diagrams show progressive result of parallel wiring.
D. 120VAC source applied, both motors start to run “open”.
(Shows current ow)
E. #1 actuator runs fully open and its travel limit switch
opens circuit. This actuator stops (perhaps only for a short time!). #2 actuator continues to run open.
(Shows current ow)
F. The other “Back Feeding” current path existing between
the actuators is shown.
G. Though actuator #1 had come to rest (full open), it can
and does get current owing through its close travel leg
via this “Back Feeding” current from #2 actuator.
This causes actuator #1 to run a couple of degrees in the closed direction, #2 actuator will then reach its fully open position. If left running for a “good” period, both actuators end up driving each other OPEN-CLOSED at strange positions.
(Shows current ow) (Shows other “Back Feeding” current ow)
6
cOrrect cOnnectiOns
To eliminate this “BACK FEEDING PARALLEL” driv­ing, we suggest separate contacts for each actuator.
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
If we redraw the diagram for the #1 actuator having reached its fully open travel position and having tripped its open travel limit switch. You can see that the #2 actuator would still run on, until it reached its fully open position. The #2 actuator when running open can not
“BACK FEED”, the rst actuator’s closed travel motor
winding (as it did in G). on the previous page).
(Shows current ow)
7
BRAY Series 73 Electric Actuator
!
!
Operation and Maintenance Manual
traVel liMit switch caM adjustMent
Each cam has two tapped holes with one setscrew that may be placed at either location for easy access.
Cams are innitely adjustable by using a 5/64” hex key.
Standard factory setting allows for 90 degrees reversible rotation between open and close positions. The bottom of the cam must be aligned with the bottom of the travel limit switch button to allow the switch to function properly during manual override.
Correct positioning of cam & switch are shown in the il­lustration below, when in motor/automatic drive condition.
heater
To prevent condensation from forming inside the actuator, Bray offers an optional heater. The heater is a PTC (Posi-
tive Temperature Coefcient) type, which has a unique
temperature - resistance characteristic. The heater self­regulates by increasing its electrical resistance relative to its temperature. The heater does not require external thermostats or switches to control its heat output. It is constructed of a polycrystalline ceramic, sandwiched between two conductors, and wrapped inside a thermally conductive electrical insulator. Connect the heater wires to the terminal strip as indicated on the wiring diagram.
heater Kit cOnsists Of:
1. Heater with ying leads
2. Heater Mounting Bracket
3. #10 pan head screw, phillips drive
tOOls required:
For terminal wiring Screwdriver, 3/16” tip at blade
For heater mounting screw Screwdriver, No.1 phillips
installatiOn PrOcedure:
WARNING
Turn off all power and lock out service panel before installing or modifying any electrical wiring.
The heater is mounted through a hole provided in the switchplate.
1. Place the heater snugly into its mounting bracket until approx. 1/2” is below the bracket as shown in the illustration below.
2. Slip the heater into its mounting hole
3. Align the fastening hole in the bracket with the threaded screw hole in the plate. Fasten the heater to the switchplate.
4. Connect the heater wires to the terminal strip as indicated on the wiring diagram.
WARNING
The heater surface can reach temperatures in excess of 200 degrees Celsius.
8
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
field install. Of auxiliary switch (es)
The maximum allowable auxiliary switch conguration is
shown in the illustrations below for each size of actuator.
auxiliary switch Kit cOnsists Of:
1. Switch with ying leads
2. Switch spacers
3. Cam with set screw
4. Cam spacers
5. Pan head screw, phillips drive
tOOls required
For terminal wiring Screwdriver, 3/16” at tip blade
installatiOn PrOcedure:
For switch mounting Screwdriver, No. 1 phillips
1. Remove switch mounting screws & discard
2. Remove switch bracket & retain for use later
3. Install auxiliary cam(s) and spacers as shown
4. Install auxiliary switch(es) and spacers as shown
5. Reinstall switch bracket
6. Install longer switch mounting screws from kit
7. Connect switch wiring to terminal strip per wiring diagram
8. Adjust cams as required
9
BRAY Series 73 Electric Actuator Operation and Maintenance Manual
Typical actuator wiring diagrams shown for single phase A.C. and D.C. motorized units. Diagrams show actuators in their fully closed positions.
10
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
aPPenDIx a
basic tOOls required fOr installatiOn
cOMMOn tO all units
Position Indicator Knob Screwdriver, 3/4” tip at
All switches, heater kit Screwdriver, No.1 phillips
Terminal strip wiring Screwdriver, 3/16” at tip
Cam adjustment Hex key, 5/64”
Cover socket head cap screws Hex key, 9/64”
100-300 lb-in units
Switchplate socket head cap screws Hex key, 9/64”
Valve mounting nuts (small bolt circle) Wrench, 3/8”
Valve mounting nuts (large bolt circle) Wrench, 7/16”
600 lb-in units
Switchplate socket head cap screws Hex key, 7/64”
Valve mounting nuts (small bolt circle) Wrench, 7/16”
Valve mounting nuts (large bolt circle) Wrench, 1/2”
11
BRAY Series 73 Electric Actuator Operation and Maintenance Manual
aPPenDIx b
actuatOr trOubleshOOting chart
Problem Possible cause Solutions
Actuator does not operate Cams are depressing travel switch Adjust cams to their correct positions Override is engaged/shaft depressed Apply electricity to cancel manual mode
Wiring is incorrect Check wiring and power supply
Actuator has reached its thermal Allow time to cool shutdown temperature
Actuator operates in reverse Field wiring is reversed Rewire eld wiring
directions
Actuator does not fully close valve Limit switches are tripping Readjust travel limit switches (or open valve) Valve torque requirement is higher Manually override out of seat, try
than actuator output angle seating or t larger actuator
Voltage power supply is low Check power source
Motor hums but does not run Motor brake engaged Check that brake is not obstructed
Corrosion inside unit Condensation forming Test heater wiring, should have constant power supply
Water leaking into the unit Check all seals and possible water
entry through conduit
12
nOTes
BRAY Series 73 Electric Actuator
Operation and Maintenance Manual
13
A Division of BRAY INTERNATIONAL, Inc. 13333 Westland East Blvd. Houston, Texas 77041
281.894.5454 FAX 281.894.9499 www.bray.com
Bray® is a registered trademark of BRAY INTERNATIONAL, Inc. © 2009 Bray International. All rights reserved. OM-73-001 12-2009
Loading...