Greenheck RV, RVE Maintenance Manual

Page 1
Document 474612
Model RV / RVE
®
Dedicated Outdoor Air Unit
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Technical Support
Call: 1-866-478-2574
Email: DOAS@greenheck.com
General Safety Information
Only qualified personnel should install and maintain this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly affect motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Verify that the power source is compatible with the equipment.
6. Never open access doors to the unit while it is running.
WARNING
The roof lining contains high voltage wiring. To prevent electrocution, do not puncture the interior or exterior panels of the roof.
DANGER
• Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
• If this unit is equipped with optional gas accessories, turn off gas supply whenever power is disconnected.
CAUTION
This unit is equipped with a compressed refrigerant system. If a leak in the system should occur, immediately evacuate the area. An EPA Certified Technician must be engaged to make repairs or corrections. Refrigerant leaks may also cause bodily harm.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
®
Dedicated Outdoor Air Unit 1
Page 2
®
Table of Contents
General Safety Information ......................1
Receiving, Handling, Storage ....................3
Product Overview .............................4
Subassemblies ...............................5
Installation ...................................6
Recommended Electrical and
Gas Supply Entry Locations ....................12
Piping Installation ............................13
Electrical Information. . . . . . . . . . . . . . . . . . . . . . . . . . 14
Control Center Components ....................15
Component Operation. . . . . . . . . . . . . . . . . . . . . . . . . 16
Optional Component Operation .................16
Factory-Installed Refrigeration System ............20
Start-Up – Unit ..............................24
Start-Up Components .........................29
Optional Polymer Energy Wheel .................32
Optional Aluminum Energy Wheel ...............34
Troubleshooting ..............................35
Routine Maintenance .........................41
Reference
Venting Connection Locations ................44
Rated Airflow ..............................46
Our Commitment ...................... Backcover
Dedicated Outdoor Air Unit2
Page 3
Receiving
This product may have been subject to road salt during transit. If so, immediately wash off all visible white reside from all exterior surfaces. Upon receiving the product, check to ensure all line items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier if any damage is detected, do not refuse shipment. The customer shall make notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which should be countersigned by the delivering carrier. If damaged, immediately contact your manufacturer’s representative. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets provided. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Units designed for outdoor applications may be stored outdoors. All accessories must be stored indoors in a clean, dry atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation. Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid condensation, allow cold parts to reach room temperature. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor. Clearance should be provided to permit air circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated so that it is above water and snow levels. Ensure sufficient support to prevent unit from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive, WD-40® or the equivalent.
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the equipment goes into operation.
Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.
®
Dedicated Outdoor Air Unit 3
Page 4
®
Product Overview
A horizontally configured High Percentage Outdoor Air unit designed for installation either indoors or outdoors. Each unit has multiple options for cooling and/or heating. The unit is designed to replace air that is exhausted from the building and also heat and cool, as needed. The air volume produced by the unit is constant, but can be optionally modulated to provide a variable air volume (VAV) and recirculation is also offered as an option.
Cooling
Units have the following cooling options available:
• Packaged DX
• Split DX (thermal expansion valve is field-provided) Not available on housing sizes 10, 75/150, 110/118.
• Chilled water coil
• Air-source heat pump (ASHP) Not available on housing sizes 10, 75/150, 110/118.
Packaged DX and air-source heat pumps are shipped fully charged with refrigerant and are ready for operation upon arrival.
Heating
There are four different optional heat sources that can be ordered for this unit:
• Indirect gas-fired furnace with one or two sets of heat exchangers
• Electric heat with infinitely variable SCR control
• Hot water coil
• Air-source heat pump (ASHP) Not available on housing sizes 10, 75/150, 110/118.
Models and Capacities
Model Cooling Capacity
RV-10
RV-25
RV-45
RV-75
RV-110
RVE-40
RVE-85
RVE-150
RVE-180
3 to 7 tons
5 to 15 tons
15 to 30 tons
25 to 50 tons
30 to 70 tons
5 to 15 tons
15 to 30 tons
25 to 50 tons
30 to 70 tons
Airflow Arrangement
The unit is capable of Constant Air Volume (CAV), Variable Air Volume (VAV), 100% Outdoor Air and have recirculating air options.
Safety Listing
Models are listed per ANSI/UL 1995, Heating and Cooling Equipment and are ETL Certified.
Dedicated Outdoor Air Unit4
Page 5
Subassemblies
Blower - Either one, two, or three plenum-type fans. All
units are equipped with a plenum fan for Supply Air and a second may be selected for Exhaust (Relief) Air.
Coils - Evaporator coil (optional)
Condenser coil (optional, packaged DX only) Indoor coil (optional, air-source heat pump only) Outdoor coil (optional, air-source heat pump only) Water coil (optional) Reheat coil (optional)
Compressors - Each unit having packaged DX will
have either one, two or four refrigerant compressors. Optionally, one of the compressors may be a digital or inverter scroll type compressor. Air-source heat pump units will have one inverter scroll compressor and may contain a second staged compressor.
Dampers - Motorized intake air damper, optional
motorized recirculating damper. Optional return air damper. Optional gravity-type exhaust damper.
Optional Barometric Relief Damper - Used during
economizer mode of the unit when building pressure increases, relief damper will open due to over pressurization.
Electric Heater - An SCR controlled electric heater (not
shown) is available on the units. It has its own control panel and may require a separate power supply. See unit-specific wiring diagram.
Supply Filters - Housing size 110/180 is available with
a filter bank depth of either 2,4 or 6-inch. All other housings are available with a filter bank depth of either 2 or 4-inch.
Low Sound Condenser Fans
(optional)
Indirect Gas-Fired Furnace - Housing sizes 10, 25/40
and 45/85, use furnace model PVG. Housing sizes 75/150 use furnace models PVG 600-800 or HMA 1000-
1200. Housing sizes 110/180 use furnace model HMA 600-1200.
Packaged DX System - Any unit may be ordered with
a packaged DX system. Housing size 10 will use one compressor; housing size 25/40 will include either one or two compressors; housing size 45/85 will include two compressors; housing size 75/150 will include three compressors; housing size 110/180 will include four compressors; a condenser coil(s) and evaporator coil(s) and all required components. Units that have packaged DX are charged with R410A refrigerant. Do not use tools or parts designed for other refrigerants on these units.
Air-Source Heat Pump - Units having an air-source heat
pump will include either one or two compressors, an indoor and outdoor coil, and all required components. Air-source heat pump units are charged with R410A refrigerant. Do not use tools or parts designed for other refrigerants on these units. Not available on housing sizes 10, 75/150, 110/118.
Split DX - The unit may be ordered with a split DX
system for connection to a building cooling system. Thermal expansion valve (TXV) is field-provided. Not available on housing sizes 10, 75/150, 110/118.
Vestibule - Some units may be ordered with a factory-
assembled vestibule that is to be field-attached to the side of the unit. See lifting instructions.
Energy Wheel (RVE)
(optional)
Outdoor Air Filters
(pre-wheel)
Condenser Coils
(optional)
Packaged DX Compressors
(optional)
Furnace Vest Plate
and
Furnace Control Center
(optional)
®
Main Control
Center
Plenum-Type
Supply Air Blower
Indirect Gas-Fired Furnace
(optional)
Weatherhood Filters
(metal mesh)
Outdoor Air
Damper
Plenum-Type
Exhaust Air Blower
Recirculating
Damper
Coils
(optional)
Dedicated Outdoor Air Unit 5
Page 6
®
Installation
Typical Unit Weights and Dimensions
A
A
1
3
W
5
6
H
3
W
2
1
4
L
7
B
1
2
3
5
4
7
6
H
L
W
Housing size 10
Housing size 25/40 and 45/85
A
A
H
9
8
7
6
2
3
5
4
L
H
1
5
2
3
L
W
4
7
6
Housing size 75/150
Component Access
1 Optional Inverter Compressor
2 Optional Compressor/Electrical
3 Optional Gas Furnace/Optional Electric Heater
4 Electrical
5 Supply Blower
6 Coil
7 Filters
8* Exhaust Blower/Optional Electric Preheat
9 Powered Exhaust Blower Section
* When a powered exhaust fan (or RVE) is selected, door 8 will
be to the immediate right of door 7.
Dedicated Outdoor Air Unit6
Housing size 110/180
Page 7
Installation
Typical Unit Weights and Dimensions
Nominal
Model
tonnage
(tons)
RV-10 3-7 58.1 44.0 82.2
RV-25 5-15 59.3 52.5 98.6
Height
(H)
Width
(W)
Length
Intake
(L)
10
7
/149.5822.1 30.1 2,700
22.3 NA 1,180
RV-45 15-30 72.5 68.2 1097/163.2827.7 30.1 4,500
RV-75 25-50 101.3 98 155.2 39/47.5
RV-110 30-70 99.5 96 185 45.3 NA 7,950
RVE-40 5-15 59.3 52.5 149.5/180.5
5
22.1 30.1 3,400
RVE-85 15-30 72.5 68.2 163.2/197.2527.1 30.1 5,100
RVE-150 25-50 101.3 98 200.4 47.5 NA 8,000 Bottom End
6
RVE-180 30-70 99.5 96 263
/307
5
45.3 NA 10,450
(A)
Condensing
Section
(B)
9
NA 6,500
Nominal
weight (lbs)
Outdoor
Intake
End
End
Supply
Discharge
Bottom
or
Side
Bottom
or
Side
Return
Intake
Bottom or
2
End
Bottom,
2
End
or
1
Side
Bottom or
End
Bottom or
Side
Bottom,
2
End
or
1
Side
Bottom or
Side
Exhaust
Discharge
NA
3
End
or
1
Side
End
Side
3
End
or
1
Side
Side
All dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat, largest indirect-gas fired furnace, and all dampers. Actual weights will vary based on the unit configuration.
1
Only available with powered exhaust
2
Only available without barometric relief
3
Only available with barometric relief
4
Above 12,000 cfm
5
Length with side return
6
Length with bottom return
7
Length with bottom or end return
8
Length with powered exhaust
9
Length with powered exhaust bumpout
10
Optional indirect gas-fired furnace bumpout length is additional 13.3 inches
®
Dedicated Outdoor Air Unit 7
Page 8
®
Installation
Service Clearances
CC
ACCESS DOOR
ACS SIDE
CONTROL
CENTER
CONDENSING SECTION
COMPRESSORS
SUPPLY FAN
HGRH COIL
NA from CS
COOLING COIL
SUPPLY FILTERS
EXHAUST AIR FILTERS
EXHAUST AIR
WEATHERHOOD
WHEEL CASSETTE
EXHAUST FAN
OUTDOOR AIR FILTERS
NA from Unit
OUTDOOR AIR
WEATHERHOOD
OAI
Model
ACS
Access
Side
ACCESS DOOR
CC
Control Cabinet End
Indoor
Other
Mounted
with IG
ACCESS DOOR
OAI
Outdoor Air Intake
Outdoor
Mounted
Indoor
Mounted
CASSETTE REMOVAL
*NA
from Unit
ACCESS DOOR
Condensing
ACCESS DOOR
NA
from
Section
from Piping
Vestibule
(not shown)
Furnace
RV-10 50 42 NA 36 NA 24 NA NA
RV-25 40 42 72 42 18 24 18 30
RV-45 36 58 72 42 18 24 18 30
RV-75 48 48 NA 87 NA 48 NA NA
RV-110 48 48 NA 60 NA 48 NA NA
RVE-40 40 42 72 42 18 24 18 30
RVE-85 36 58 72 42 18 24 18 30
RVE-150 48 48 NA 87 NA 48 NA NA
RVE-180 48 48 NA 60 NA 48 NA NA
All dimensions are shown in inches.
*No condensing section or piping vestibule, or unit has top condensing section.
NA
Dedicated Outdoor Air Unit8
Page 9
Installation
Additional Clearances for Packaged DX Units
Packaged DX units require additional clearance because they must have unrestricted air movement around the condenser coil and condenser fans. Hot air is being discharged from the condenser fans during operation. Enough clearance must be provided to avoid recirculation or coil starvation. When equipped with condenser coils, the unit should never be placed under an overhang or inside a building. A minimum of 48inches above the condenser fans is acceptable, but unobstructed is strongly recommended.
Minimum 48 inches clearance
Condenser Fans
Minimum 18 inches
clearance
Condenser Coil
End view of rooftop unit with Packaged DX
Handling Concerns for Packaged DX or Air-Source Heat Pump
Units with PDX or ASHP have a system that is pressurized with refrigerant. If damage occurs, the refrigerant could leak into the atmosphere or cause bodily harm due to the extreme cold nature of expanding refrigerant. Use protective equipment such as gloves and safety glasses to minimize or prevent injury in case of a system leak during installation.
Before Lifting
Before lifting, be sure that all shipping materials have been removed from the unit.
Vestibule
Determine whether or not the unit has a vestibule that must be field-attached to the side of the unit. Vestibules are shipped assembled but detached from the unit. They have lifting lugs on them so they can also be lifted by crane, but the installed location of the unit may make it preferable to install the vestibule on the unit prior to lifting.
Field Power Access
Determine where high voltage and low voltage wiring is to be brought into the cabinet. If wiring is to be brought into the cabinet through the floor, see Alternate Supply Entry Locations in this manual. If unit is to be installed on a roof, cut access openings in the roof deck as needed.
Additional Clearances for Air Source Heat Pump
IMPORTANT
Air-source heat pumps are equipped with a defrost cycle to remove ice from the outdoor coil. During defrost cycles, melted water may drip from the bottom of the refrigeration section under the outdoor coil. In cold climates, proper drainage/heat tape must be installed under the outdoor coil to prevent the buildup of ice on the roof.
Air-source heat pump units require additional clearance because they must have unrestricted air movement around the outdoor coil and outdoor fans. Enough clearance must be provided to avoid recirculation or coil starvation. Air-source heat pump units should never be placed under an overhang or inside a building. A minimum of 48-inches above the outdoor fans is acceptable, but unobstructed is strongly recommended.
®
Dedicated Outdoor Air Unit 9
Page 10
®
Installation
W
L
L
W
Lifting
1. Ensure that all shipping materials have been
removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Unit Weights & Dimensions section of this manual.
3. Unit must be lifted by all lifting lugs provided at top
of unit.
4. Spreader bars must span the unit to prevent
damage to the cabinet by the lift cables.
5. Never rest the spreader bar on the unit.
WARNING
Spreader bars are required to prevent damage to the cabinet, failure to do so can result in damage that is the installer’s responsibility.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift unit by weatherhood.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the top of the curb prior to lifting the unit and setting on the curb.
11. Do not use forklifts for handling unit on housing
sizes 25/40, 45/85, 75/150, or 110/180.
12. If using forklift on housing 10, use forks with 48-
inch length and ensure forks extend to opposite side of unit using factory-installed forklift pockets at unit base.
Roof Curb Mounting
Roof curb details, including duct locations and dimensions, are to be found in the roof curb assembly instructions.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory-supplied roof curbs. Roof curbs are model GKD which are shipped in a knockdown kit (includes duct adapters) and require field assembly (by others) on all units except RV-110 and RVE-180, which are shipped assembled. Assembly instructions are included with the curb kit.
2. Install curb. Locate curb over roof opening and fasten in place. Check that the diagonal dimensions are within ± 1/8inch of each other and adjust as necessary. For proper coil drainage and unit operation, it is important that the installation be level. Shim the curb as required to level. Install gasketing on top surface of curb (provided by others).
3. Install ductwork. Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapters are provided to support ducts prior to setting the unit.
4. Set the unit. Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and level.
5. Fasten the unit, Fasten the unit to the curb/ equipment support(s) using appropriate methods. The installer is responsible for determining appropriate support and fastening methods to ensure compliance with all applicable codes.
6. Install vestibule. If unit was ordered with a vestibule and it has not yet been attached to the unit, caulk and attach the vestibule at this time.
W
Dedicated Outdoor Air Unit10
Typical Unit with Condensing Section and
Factory-Supplied Curb Kit
L
Page 11
Installation
L
W
Optional Piping Vestibule
If the unit was ordered with the vestibule, the NA (Non­Access side) clearance dimension must be measured from the vestibule.
L
W
Typical Unit with Piping Vestibule and
Factory-Supplied Curb Kit
Rail Mounting and Layout
• The units may be installed on rails provided and installed by others. Ensure that rails are designed to handle the weight of the unit and provide proper load distribution on building supports.
• Make sure that rail positioning does not interfere with the openings on the unit.
• Rails should run the width of the unit and extend beyond the unit a minimum of 12 inches on each side.
• Set unit on rails.
Ductwork Configurations
NOTE
Downblast Discharge Ductwork - whenever
downblast discharge is used, the ductwork directly beneath the unit must be connected with either a “T” or an “L” configuration and the area directly beneath the heat source must not have any openings such as louvers or grates.
Typical Unit Installed on Rails Supplied by Others
No louvers or grates
®
Dedicated Outdoor Air Unit 11
Page 12
®
Recommended Electrical and Gas Supply Entry Locations
Manufacturer recommends that electrical service and gas supply be brought into the cabinet through the end wall, as shown below. There are three penetrations into the cabinet that are required; one for high voltage supply wiring, one for low voltage control wiring and one for either gas supply or high voltage supply wiring for an electric heater.
Optional Unit Disconnect
Indirect Gas Supply Location
Field Wiring
Recommended Gas and Electric Supply Entry Locations
Alternate Supply Entry Locations
Each installation is unique and as a result, alternate entry locations may be field-located. Before using any alternate entry location, verify the suitability of the location and ensure the use of an alternate location does not interfere with unit wiring, components or functionality.
Optional Gas Piping
Units with indirect gas-fired furnaces require field­supplied and installed gas supply piping.
Housing
Size
10
25/40
45/85
75/150
110/180
Total Heating
Capacity
(Input in MBH)
75
100
150
200
100
150
200
250
300
300
500
600
800
100
1200
600 1” NPT
800
1200
Gas
Connection
Size
Max Gas Pressure
¾” NPT 14 in. wg.
¾” NPT 14 in. wg.
¾” NPT 14 in. wg.400
¾” NPT
14 in. wg.
1” NPT
2” NPT1000
13.5 in. wg.
Gas Connections
If this unit is equipped with an indirect gas-fired furnace, connection to an appropriate gas supply line will be required. For complete information on installation procedures for the optional gas furnace, refer the PVF/PVG Indirect Gas-Fired Heat Module Installation, Operation, and Maintenance Manual.
Ground
Gas Cock
From Gas Supply
Bleeder Valve or 1/8 in Plugged Tap
Typical Gas Supply Piping Connection
Joint
Union
8 in. Trap
Gas to
Controls
WARNING
Never drill holes in the roof of the unit! There is high voltage wiring located between the inner and outer roof panels. Damage to the wiring could cause severe bodily harm or death.
NOTE
110/180 gas furnaces are designed for gas pressure of 5-13.5 in. wg for natural gas (6-inch minimum on single 500 and 600 MBH furnaces) and 11-13.5 in. wg for LP. If the gas pressure at the job location is greater than 13.5 in. wg, an additional regulator is required to reduce pressure. For other RV and RVE models, reference the Model PVF and PVG IOM.
Dedicated Outdoor Air Unit12
Page 13
Piping Installation
Optional Coil Piping
Factory-installed cooling and heating components are mounted in the coil section of the unit. The coil section is downstream of the energy wheel on the supply air side of the unit. Note the coil connection locations on the picture. Coil connections are located external to the unit.
Note: DX coil liquid connection is internal to units.
Water Coils
1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. When installing couplings, do not apply undue stress to the connection extending through the unit. Use a backup pipe wrench to avoid breaking the weld between coil connection and header.
2. Connect the water supply to the bottom connection on the air leaving side and the water return to the top connection on the air entering side. Connecting the supply and/or return in any other manner will result in very poor performance. Be sure to replace factory-installed grommets around coil connections if removed for piping. Failure to replace grommets will result in water leakage into the unit and altered performance.
3. Water coils are not normally recommended for use with entering air temperatures below 40°F. No control system can be depended on to be 100% safe against freeze-up with water coils. Glycol solutions or brines are the only safe media for operation of water coils with low entering air conditions. If glycol or brine solutions are not used, coils must be drained when freezing conditions are expected. If required,
vent and drain connections must be field­piped, external to the unit.
4. Pipe sizes for the system must be selected on the basis of the head (pressure) available from the circulation pump. The velocity should not exceed 6 feet per second and the friction loss should be approximately 3 feet of water column per 100 feet of pipe.
5. For chilled water coils, the condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Drain Trap section.
Direct Expansion (DX) Coils (Split DX)
1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. Undue stress should not be applied at the connection to coil headers.
2. The condensate drain pipe should be sized adequately to ensure the condensate drains properly. Refer to Condensate Drain Trap section.
3. When connecting suction and liquid connections make sure the coil is free from all foreign material. Make sure all joints are tight and free of leakage. Be sure to replace factory-installed grommets around coil connections if removed for piping.
4. Manufacturer does not supply compressor, condensing units, or thermal expansion valve (TXV) with standard models. For further instruction on DX coil installation and operation contact your compressor and/or condenser manufacturer.
Condensate Drain Trap
This unit is equipped with a stainless steel condensate pan with a stainless steel connection. It is important that the drain connection be fitted with a P trap to ensure proper drainage of condensate while maintaining internal static pressures and to prevent migration of sewer gas back into the unit.
A P trap assembly (kit) is supplied with each unit and is to be assembled and installed as local conditions require and according to the assembly instructions provided with the P trap. If local and area codes permit, the condensate may be drained back onto the roof, but a drip pad should be provided beneath the outlet. If local and area codes require a permanent drain line, it should be fabricated and installed in accordance with Best Practices and all codes.
In some climates, it will be necessary to provide freeze protection for the P trap and drain line. The P trap should be kept filled with water or glycol solution at all times and it should be protected from freezing to protect the P trap from damage. If severe weather conditions occur, it may be necessary to fabricate a Ptrap and drain line of metal and install a heat tape to prevent freezing.
Condensate Overflow Switch
This unit is equipped with an optional factory-mounted condensate overflow switch. In the event that a high level of condensate is detected, the microprocessor controller will trigger an alarm and shutdown the unit.
®
Dedicated Outdoor Air Unit 13
Page 14
®
Electrical Information
WARNING
The roof lining contains high voltage wiring. To prevent electrocution, do not puncture the interior or exterior panels of the roof.
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect switch open. For units with a gas furnace, if you turn off the power supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached on the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest edition of the National Electric Code ANSI/NFPA70 and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded and bonded. Any wiring running through the unit in the airstream must be protected by metal conduit, metal clad cable or raceways.
CAUTION
If replacement wire is required, it must have a temperature rating of at least 105ºC, except for an energy cut-off or sensor lead wire which must be rated to 150ºC.
DANGER
High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or property damage. Manufacturer is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.
Determine the Size of the Main Power Lines
The unit’s nameplate states the voltage and the unit’s MCA. The main power lines to the unit should be sized accordingly. The nameplate is located on the outside of the unit on the control panel side.
Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate power supply. The power connection should be made to the factory-provided electric heater disconnect and must be compatible with the ratings on the nameplate, supply power voltage, phase and amperage. Consult ANSI/NFPA 70 and CSA C22.1 for proper conductor sizing.
Provide the Opening(s) for the Electrical Connections
Electrical openings vary by unit size and arrangement and are field-supplied.
Connect the Power Supplies
Connect the main power lines and electric heater power lines to the disconnect switches or terminal blocks and main grounding lug(s). Torque field connections to manufacturer’s recommendations.
Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V power supply circuit. The circuit must include short circuit protection which may need to be supplied by others.
Connect Field-Wired Low Voltage Components
Most factory-supplied electrical components are prewired. To determine what electrical accessories require additional field-wiring, refer to the unit-specific wiring diagram located on the inside of the control center access door.
The low voltage control circuit is 24 VAC and control wiring should not exceed 0.75 ohms.
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field-supplied conduit does not interfere with access panel operation. All low voltage wiring should be run in conduit wherever it may be exposed to the weather.
If wire resistance exceeds 0.75 ohms, an industrial­style, plug-in relay should be added to the unit control center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip. The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
Field-Provided Disconnect
If field-installing an additional disconnect switch, it is recommended that there is at least four feet of service room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect, use dual element time delay fuses and size according to the rating plate.
Dedicated Outdoor Air Unit14
Page 15
Control Center Components
Main Control Center Components
Image represents a typical installation for RVE-40 or RVE-85. Components and locations will vary on other models.
Electrical Cabinet
1. Power distribution block; high voltage supply is terminated here
2. Fuse holders
3. Phase monitor
4. Unit Disconnect
5. Condensing fan motor contactors
6. Wheel motor contactor
7. Compressor motor contactors
Controls Cabinet
8. Transformer
9. VFDs
10. Microprocessor controller
11. Monitoring points
12. Low voltage terminal strip
13. Relays
14. Dirty filter switches
15. Wheel pressure switch
16. Outdoor airflow monitor
17. Exhaust airflow monitor
18. Digital scroll controller
11
9
9
14
16
9
17
10
12
13
Controls Cabinet
Accessible via compressor door
18
15
Electrical Cabinet
Accessible via control center door
2 2
1
3
5
5
6
4
2 2
8
7
Optional Indirect Gas-Fired Furnace
Note: In some models, two furnaces are installed to provide greater output. When two furnaces are installed, they are in parallel and both will operate at the same time and the same output. Both furnaces will have identical controls.
7
1. Single-stage valve
2. Modulating valve
4
3
5
4
3
3. PCOE expansion board
4. Ignition controller
5. Transformer
6. Combustion blower
1
2
1
2
7. Burner manifold
8. Collector box
6
8
6
For further information on the optional furnace and its control center, see the Indirect Gas-Fired Heat lOM shipped with the unit.
7
5
8
®
Dedicated Outdoor Air Unit 15
Page 16
®
Component Operation
Optional Component Operation
Phase Monitor
The unit control circuitry includes a phase monitor that constantly checks for phase reversal, phase imbalance, loss of phase or a power brownout. When it detects a fault, it cuts off the 24 VAC that goes to the low voltage terminal strip, thereby shutting off all motors.
Variable Frequency Drive (VFD)
If a VFD was provided and installed at the factory, it has been pre-set to control the speed of the blower motor for optimum performance. The motor speed needs to be verified during test and balance of the unit.
If the system was configured for Constant Air Volume (CAV), the VFD will operate in an ON/OFF fashion and the speed of the motor will not change. If the system was configured for Variable Air Volume (VAV), the microprocessor will constantly monitor operating conditions and provide a signal to the VFD, changing the VFD output as needed.
The VFD may alternatively be connected to an external signal such as provided by a BMS and be operated by a 0-10 VDC input.
Supply Fan VFD Sequence
Optional Room CO2 Sensor: The microprocessor will modulate the supply fan based on a comparison of the CO2 set point to the actual CO2 levels reported from the sensor. Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization.
Optional Duct Static Pressure Sensor: The microprocessor will modulate the supply fan based on a comparison of the duct static pressure set point to the actual duct static pressure level reported from the sensor. Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization. The manufacturer does not assume responsibility for this.
Optional Building Static Pressure Sensor: The supply fan is modulated based upon the signal from a building static pressure sensor. The microprocessor will modulate the supply fan based on a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Optional Single Zone VAV: The microprocessor will use a space mounted temp sensor to vary heating and cooling capacity and the airflow delivered by the fan to maintain room-air temp at a desired set point.
Optional 0-10 VDC by others to VFD: Supply fan is modulated by a 0-10 VDC, field-provided by others.
Exhaust Fan VFD Sequence
Optional Building Static Pressure Sensor: The exhaust fan is modulated based upon the signal from a building static pressure sensor. The microprocessor will modulate the exhaust fan based upon a comparison of the building static pressure level reported from the sensor.
Optional Outdoor Air Damper Tracking: The microprocessor will proportionally modulate the exhaust fan based upon the outdoor air damper position.
Optional Supply Tracking: The microprocessor will proportionally modulate the exhaust fan based upon the supply fan.
Optional 0-10 VDC by Others to VFD: The supply fan is modulated by a 0-10 VDC provided by others in the field.
Outdoor Air and Recirculated (Recirc) Air Damper Sequence
Optional Room CO2 Sensor: The microprocessor will proportionally modulate the OA/RA dampers based upon a comparison of the CO2 set point to the actual CO2 level reported from the sensor. As the CO2 level rises, the controller will proportionally modulate the outdoor air damper open, between the minimum and maximum OA position.
Optional Building Pressure: The OA/RA dampers will modulate based upon the signal from a building static pressure sensor. The controller will modulate the dampers, between the minimum and maximum OA positions, based upon a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Exhaust Fan Only Power
The exhaust fan will have a dedicated power circuit where in the case of a power outage, the exhaust fan will still run. A phase monitor will detect an outage or power loss and open the contact, disconnecting all power to the unit and controller. An external signal will need to be sent to a relay to power the exhaust fan, enabling the fan to run at a maximum speed. This sequence is NOT to be used for high temperature exhaust applications.
Service Lights
Service lights provide light to each of the compartments in the energy recovery unit. The lights are wired to a junction box mounted on the outside of the unit. The switch to turn the lights on is located in the unit control center. The switch requires a separate power source to allow for power to the lights when the unit main disconnect is off for servicing.
Dedicated Outdoor Air Unit16
Page 17
Optional Component Operation
Electronically Commutated (EC) Condenser Fans with Standard Scroll or Digital Scroll Compressors
The EC condenser fan(s) will modulate up and down to maintain the optimal liquid line pressure using built in control sequences within the factory controller. One pressure transducer is provided with each refrigeration circuit for monitoring and the factory controller will ramp condenser fan(s) up or down based on the condenser set point.
Economizer Fault Detection Diagnostics
Provides the status and faults of the air economizer to indicate proper economizer sequence operation. This assures the benefits of free cooling when outdoor conditions are suitable for economizer functions. The fault detection diagnostics system will indicate when free cooling is available and if the outside air damper and recirculation damper are reacting properly. If the dampers are not functioning correctly an alarm will be generated.
Air-Source Heat Pump
Operating Conditions and Limitations
To operate in Cooling mode, the following conditions must be true:
1. Supply air temperature above minimum low supply temperature limit (35°F)
2. Outside air temperature above the cooling ambient lockout (55°F, adj.)
To operate in Heating mode, the following conditions must be true:
1. Supply air temperature below maximum high supply temperature limit (120°F)
2. Supply air temperature above 35°F
3. Outside air temperature above the low ambient lockout (10°F, adj.)
For more information on air-source heat pump operation, reference the supplemental Reference Guide
for Microprocessor Controller.
IMPORTANT
Air-source heat pumps are equipped with a defrost cycle to remove ice from the outdoor coil. During defrost cycles, melted water may drip from the bottom of the refrigeration section under the outdoor coil. In cold climates, proper drainage/heat tape must be installed under the outdoor coil to prevent the buildup of ice on the roof.
IMPORTANT
Melted water from snow accumulation on the unit roof can be sucked into outdoor fans, resulting in ice formation on fan blades under certain conditions. Remove snow accumulation from the unit roof and outdoor coil section after snow storms.
Airflow Monitor
IMPORTANT
For the outdoor airflow monitoring device to perform as intended, field calibration is required. Calibration of the airflow monitoring device requires an independent measurement of airflow and should be performed when the system undergoes test and balance.
A factory-wired, mounted, and powered airflow monitoring system is provided in the outdoor, supply, and/or exhaust air streams. The airflow control system displays outdoor, supply, and/or exhaust air in actual cubic feet per minute (CFM) at factory controller or can be read by a building management system if communication is established.
Operation
Outdoor airflow monitoring is accomplished using two thermal dispersion sensors that accurately measure airflow velocity down to zero feet per minute (fpm). The airflow controller takes the average measurement for two sensor configurations, and determines the outdoor airflow rate based on the effective intake area. Field calibration of the outdoor airflow monitoring device determines the effective intake area of the unit. For additional information on how to navigate through the outdoor airflow controller menus, refer to technical manuals from GreenTrol® Automation Inc. at www. greentrol.com.
Supply and/or exhaust airflow monitoring is accomplished by measuring the pressure drop across the fan inlet venture. The airflow is then calculated by the factory controller based on the measured pressure drop and a K-Factor specific for each fan size.
Hot Gas Reheat Valve
Units equipped with a reheat coil use a three-way valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10VDC signal to control the amount of reheat to meet the supply temperature set point.
Controls by Others
The reheat coil needs to be purged to ensure adequate oil return. It is recommended that every six hours of reheat compressor run time should initiate a six minute purge cycle. During the purge cycle, the reheat valve should be modulated to 100% open to the reheat coil.
®
Dedicated Outdoor Air Unit 17
Page 18
®
Optional Component Operation
VFD Compressor
If the VFD compressor option is included, the compressor VFD is mounted in the end of the condensing section. Condensing section internal components are accessible via the access panel on the side of the condenser coil.
Envelope Control
The unit controller tracks the operating point of the VFD compressor within the operating envelope at all times. If the operating point is out of the envelope, the controller will take action to bring it back in. If unsuccessful, the controller will shut down the compressor. DO NOT operate the compressor VFD in hand mode because the envelope control safeties will not be in place. Refer to the controls IOM for more information on envelope control.
Electronic Expansion Valve
An electronic expansion valve is provided on the VFD compressor circuit to ensure tight superheat control throughout the compressor modulation band. The EXV acts as a liquid line solenoid valve when the compressor is off to prevent refrigerant migration.
Crankcase Heat
The VFD compressor will be heated by the compressor stator. To ensure optimal performance and reliability, do not disable stator heat. All other compressors will be provided with a crankcase heater.
Oil Return Management
The compressor VFD has an oil return purge cycle such that if the compressor has been operating below a set RPM for a set period of time, the VFD will accelerate the compressor to ensure sufficient lubrication.
DO NOT disable the oil return management function.
DO NOT operate the compressor VFD in hand mode because the oil return management will not be operational.
Ultraviolet Germicidal Irradiation (UVGI)
UV-C lights are mounted in the supply blower cabinet and provide air disinfection. The lights are factory­powered and are on when the supply blower is running. A kill switch on the supply blower access door turns the lights off when that door is open.
Housing 110/180 Only
UV-C lights are mounted downstream of the cooling coil, providing coil surface and drain pan disinfection. The lights are factory-powered and are on when there is power to the unit disconnect. A kill switch on the coil access door turns the lights off when that door is open.
Needlepoint Bipolar Ionization (NPBI®)
Needlepoint bipolar ionizers are mounted on the fan inlet cone(s) and provide air disinfection. The ionizers are factory-powered and are on when there is power to the unit disconnect.
Frost Control
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:
Polymer Energy Wheel
Available options are:
1. Timed exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control
These options are provided with a thermodisc mounted in the outdoor air intake compartment and a pressure sensor to monitor pressure drop across the energy wheel. An outdoor air temperature of below 5°F and an increase in pressure drop indicate that frost is occurring. Both the pressure sensor and the outdoor air thermodisc must trigger to initiate frost control. The two sensors together ensure that frost control is only initiated during a real frost condition.
Timed exhaust frost control includes a timer in addition to the thermodisc and wheel pressure sensor. When frost control is initiated, the timer will turn the supply blower off. The default timer setting will shut down the supply fan for 5 minutes every 30 minutes, allowing warm exhaust to defrost the energy wheel. Use the test procedure in the Optional Start-Up Accessories section for troubleshooting.
Electric preheat frost control includes an electric heater (at outdoor air intake) in addition to the thermodisc and wheel pressure sensor. When frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel. Use the test procedure in the Optional Start-Up Accessories section for troubleshooting.
Modulating wheel frost control includes a variable frequency drive (VFD) in addition to the thermodisc and wheel pressure sensor. When frost control is initiated, the VFD will reduce the wheel speed, reducing effectiveness and preventing condensation and frosting. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than 5°F AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The VFD will be fully programmed at the factory.
Dedicated Outdoor Air Unit18
Page 19
Optional Component Operation
Aluminum Energy Wheel
Available options are:
1. Modulating wheel frost control
2. Modulating wheel with electric preheat frost control
These options are provided with a temperature sensor mounted in the exhaust air discharge compartment. Frost control will initiate when the exhaust air temperature is below 36°F.
Modulating wheel frost control includes a variable frequency drive (VFD) in addition to the exhaust air temperature sensor. When frost control is initiated, the VFD will modulate the wheel speed to maintain 36°F exhaust air temperature. The VFD will be fully programmed at the factory.
Modulating wheel with electric preheat frost control includes a variable frequency drive (VFD) and electric heater (at outdoor air intake) in addition to the exhaust air temperature sensor. When frost control is initiated, the VFD will modulate the wheel speed to maintain 36°F exhaust air temperature. The electric heater will turn on when the outdoor air temperature is below 10°F. The VFD will be fully programmed at the factory.
Rotation Sensor
The rotation sensor monitors energy wheel rotation. If the wheel should stop rotating, the sensor will close a set of contacts in the unit control center. Field-wiring of a light (or other alarm) between terminals R and 12 in the unit control center will notify maintenance personnel when a failure has occurred.
Microprocessor Control
The microprocessor controller is specifically designed and programmed to optimize the performance of the unit with supplemental heating and cooling. This option ensures that the outdoor air is conditioned to the desired discharge conditions. The controller and accompanying sensors are factory-mounted, wired and programmed. Default settings are pre-programmed, but are easily field-adjustable.
The microprocessor controller can be interfaced with a Building Management System through LonWorks®, BACnet®, or ModBus.
Please refer to the Installation, Operation and Maintenance manual for detailed information.
Unoccupied Recirculation Damper
The unoccupied recirculation option provides a recirculation damper from the return air intake to the supply airstream. If equipped with a room temperature and/or relative humidity sensor, the unit can cycle on to maintain unoccupied room set points if there is a call for unoccupied heating, cooling, or dehumidification. During the unoccupied mode, the supply and exhaust (if equipped) fans will be off unless there is a call for cooling, heating, or dehumidification in the space.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the outdoor air filters, exhaust air filters, or both. If the pressure drop across the filters exceeds the set point, the sensor will close a set of contacts in the unit control center. Field-wiring of a light (or other alarm) to these contacts will notify maintenance personnel when filters need to be replaced. The switch has not been set at the factory due to external system losses that will affect the switch. This switch will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to the unit control center or in unit control center.
®
Dedicated Outdoor Air Unit 19
Page 20
®
Factory-Installed Refrigeration System Components
Packaged DX Cooling with Three Way Hot Gas Reheat
Dedicated Outdoor Air Unit20
Page 21
Factory-Installed Refrigeration System Components
Packaged DX Cooling with Three Way Hot Gas Reheat
1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure increases above the set point in the discharge line. A manual reset is then required.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a three­way valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the supply temperature set point
4. Hot Gas Reheat Coil (Optional)
5. Hot Gas Reheat Check Valve (Optional)
6. Condenser Fans
7. Condensing Coil
8. Liquid Receiver (Optional)
9. Liquid Line Filter Drier
10. Sight Glass
11. Fan Cycle Switch(es)
The switch(es) open or close based on liquid refrigerant pressure to control the condensing fans to maintain liquid pressure.
12. Thermostatic Expansion Valve (TXV)
Each unit is equipped with a TXV on each refrigerant circuit. The valve controls the flow of liquid refrigerant entering the evaporator coil by maintaining a constant, factory-set superheat of 10°F. The valve is adjustable and is located on the side of the evaporator coil and can be accessed through the coil access panel.
13. Evaporative Coil
14. Low Limit Pressure Switch
The switch is installed on the suction line and disables the DX system when the suction pressure drops below the set point. The switch will auto reset when the pressure rises above the auto-reset set point.
15. Service Access Ports
16. Pressure Gauge & Transducer (Optional EC condenser fans only)
See Optional Electronically Commutated (EC)
Condenser Fans under the component operation.
®
Dedicated Outdoor Air Unit 21
Page 22
®
Factory-Installed Refrigeration System Components
Air-Source Heat Pump with Three Way Hot Gas Reheat
Outdoor Airflow
EXV
HCV
HRV
HPS
SV
PT
PT
LPS
ACC
Compressor
4WV
Outdoor Coil
SG
Supply Airflow
SG
Hot Gas Reheat Coil
FDS
Indoor Coil
Outdoor Airflow
4WV
Outdoor Coil
PT
SG
TXV
Supply Airflow
SG
Indoor Coil
FDS
ACC
LPS
SV
HPS
Compressor
Dedicated Outdoor Air Unit22
Page 23
Factory-Installed Refrigeration System Components
1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure increases above the set point in the discharge line. A manual reset is then required.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a three­way valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the supply temperature set point
4. Hot Gas Reheat Coil (Optional)
5. Hot Gas Reheat Check Valve (Optional)
6. Outdoor Fans
7. Outdoor Coil
8. Refrigeration Accumulator
9. Liquid Line Filter Drier
10. Sight Glass
11. Four Way Reversing Valve
Each compressor circuit is equipped with a reversing valve to reverse the direction of refrigerant flow, switching the unit between heating and cooling mode.
12. Electronic Expansion Valve (EXV) or Thermostatic Expansion Valve (TXV)
An expansion valve is provided on each refrigerant circuit. This valve controls the flow of liquid refrigerant entering the indoor and outdoor coils by maintaining a constant superheat. The TXV is adjustable. Both the EXV and TXV are located on the side of the outdoor coil and can be accessed through the refrigeration system access panel.
13. Indoor Coil
14. Low Limit Pressure Switch
The switch is installed on the suction line and disables the DX system when the suction pressure drops below the set point. The switch will auto reset when the pressure rises above the auto-reset set point.
15. Service Access Ports
Typical port locations are shown. Additional valves may be present in the system.
16. Refrigerant Pressure Transducers
®
Dedicated Outdoor Air Unit 23
Page 24
®
Start-Up Unit
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
CAUTION
Do not operate without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans, and compressors are set-up to run correctly when supplied power. If any one fan is running backwards or the compressor is making loud noises, immediately turn off the power. Switch two leads on the incoming power to the disconnect. This will ensure proper operation of the unit. Failure to comply may damage the compressors and void the warranty.
• Do not jumper any safety devices when operating the unit. This may damage components within or cause serious injury or death.
• Do not operate compressor when the outdoor temperature is below 40ºF.
• Do not short-cycle the compressor. Allow 5 minutes between “on” cycles to prevent compressor damage.
• DX system is charged with refrigerant. Start-up must be performed by EPA Certified Technician.
WARNING
Prior to starting up the unit, power must be energized for 24 hours without a call for cool to allow the compressor crankcase heaters time to boil off any liquid refrigerant present in the compressor.
Every installation requires a comprehensive start-up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed.
Unit Model No. ___________________________________
Unit Serial No. ____________________________________
Energy Wheel Date Code __________________________
Compressor 1 Model No. __________________________
Compressor 2 Model No. __________________________
Compressor 3 Model No. __________________________
Compressor 4 Model No. __________________________
Start-Up Date ____________________________________
Start-Up Personnel Name __________________________
Start-Up Company ________________________________
Phone Number ___________________________________
Dedicated Outdoor Air Unit24
Page 25
Start-Up Unit
Pre-Start-Up Checklist
o Remove any foreign objects that are located in the
unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and accessories for tightness.
o Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
o Verify diameter seal settings on the energy recovery
wheel.
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood.
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify proper drain trap installation. o Check condensing fans for any damage or
misalignment. Spin the blades and make sure they don’t contact any parts and are free turning without any resistance.
o Look over the piping system. o Inspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully straighten fins with a fin comb.
Electrical
oDisconnect and lock-out all power switches. o Verify control wire gauge. o All field-mounted sensors and instruments are
installed and wired.
o Unit controls are off. o Electrical service matches unit voltage. o Electrical field wiring is complete. o All electrical connections are tightened. o Compressor and motor breakers or fuses are open
(disabled).
o Main power is wired to the disconnect. o Discharge air sensor is installed per wiring
instructions.
o Space temperature and humidity sensors are
installed per if selected with unit. Compressors o This unit contains an external crankcase heater for
each standard or digital scroll compressor. The
variable speed compressor uses internal stator
heating. Each compressor needs power supplied to
it 24hours prior to start-up. If start-up is scheduled
in 24 hours, unlock the disconnect power and
energize unit. oCompressor shipping brackets are removed if
provided.
IG Furnace o If there is an indirect gas-fired furnace in this unit,
refer to the manual provided with this unit for Pre­Start-Up information.
o Gas piping is complete and gas lines are purged. o Gas venting is in place.
Hot Water/Chilled Water Coils
o Chilled water piping system is complete. o Hot water piping system is complete. o Control valves are installed, wired, and operating
properly.
o Water coils are balanced to design GPM. o Water system is free of air.
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
• Incline manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must be collected while the unit is running.
o Make sure Pre-Start-Up checklist is complete. o Jumper R to G, R to Y1, and R to Y2 (if applicable)
on the control board.
o Turn the disconnect on. After 3 minutes compressors
will come on. Make sure all fans and compressors are rotating the correct direction.
o Allow the unit to run until the refrigerant system
stabilizes. Approximately 1-2 minutes.
Voltage Imbalance
In a 3-phase system, excessive voltage imbalance between phases will cause motors to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded voltage measurements in this formula.
Key: V1, V2, V3 = line voltages as measured VA (average) = (V1 + V2 + V3) / 3 VD = Line voltage (V1, V2 or V3) that deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA
®
Dedicated Outdoor Air Unit 25
Page 26
®
Start-Up Checklist - General
Line Voltage. Check at unit disconnect.
L1-L2 Volts L2-L3 Volts L1-L3 Volts
Motor Amp Draw
Supply Motor 1 Amps L1 Amps L2 Amps L3 Amps
Supply Motor 2 Amps L1 Amps L2 Amps L3 Amps
Supply Motor 3 Amps L1 Amps L2 Amps L3 Amps
Exhaust Motor 1 Amps L1 Amps L2 Amps L3 Amps
Exhaust Motor 2 Amps L1 Amps L2 Amps L3 Amps
Exhaust Motor 3 Amps L1 Amps L2 Amps L3 Amps
Fan RPM Correct fan rotation direction?
Supply Fan RPM Supply Fan Yes / No
Exhaust Fan RPM Exhaust Fan Yes / No
Energy Wheel Motor (if equipped)
L1 Amps L2 Amps L3 Amps
Condensing Fans (PDX only)
Condensing Fan 1 L1 Amps L2 Amps L3 Amps
Condensing Fan 2 L1 Amps L2 Amps L3 Amps
Condensing Fan 3 L1 Amps L2 Amps L3 Amps
Condensing Fan 4 L1 Amps L2 Amps L3 Amps
Condensing Fan 5 L1 Amps L2 Amps L3 Amps
Condensing Fan 6 L1 Amps L2 Amps L3 Amps
Condensing Fan 7 L1 Amps L2 Amps L3 Amps
Condensing Fan 8 L1 Amps L2 Amps L3 Amps
Outdoor Fans (ASHP only)
Outdoor Fan 1 L1 Amps L2 Amps L3 Amps
Outdoor Fan 2 L1 Amps L2 Amps L3 Amps
Outdoor Fan 3 L1 Amps L2 Amps L3 Amps
Compressors (if equipped)
Outdoor Air Temperature Deg F Outdoor Air Relative Humidity % RH
Return Air Temperature Deg F Return Air Relative Humidity % RH
Dedicated Outdoor Air Unit26
Page 27
Start-Up Checklist - Packaged Direct Expansion (DX)
Compressor 1 Compressor 2 Compressor 3 Compressor 4
L1 Amps Amps Amps Amps
L2 Amps Amps Amps Amps
L3 Amps Amps Amps Amps
Crankcase Heater Not present on inverter compressor
Superheat
(Housings 10, 25/40, 45/85, 75/150)
Should be between 8º and 12ºF
Subcooling
(Housings 10, 25/40, 45/85, 75/150)
Should be between 8º and 12ºF
Superheat
(Housings 110/180)
Should be between 10º and 20ºF (0% reheat)
or should be between 10º and 30ºF (100% reheat)
Subcooling
(Housings 110/180)
Should be between 10º and 15ºF (0% reheat)
or should be between 2º and 10ºF (100% reheat)
Discharge Pressure Should be between 300 and 500 PSIG
Suction Line Pressure Should be between 100 and 135 PSIG
Liquid Line Temp. Deg. F Deg. F Deg. F Deg. F
Suction Line Temp. Deg. F Deg. F Deg. F Deg. F
Moisture Indicating Sight Glass
Liquid Visible Yes / No Yes / No Yes / No Yes / No
Color of Center Dot Purple / Pink Purple / Pink Purple / Pink Purple / Pink
Hot Gas Bypass Operational Yes / No / NA NA NA NA
Amps Amps Amps Amps
Deg. F Deg. F Deg. F Deg. F
Deg. F Deg. F Deg. F Deg. F
Deg. F Deg. F Deg. F Deg. F
Deg. F Deg. F Deg. F Deg. F
PSIG PSIG PSIG PSIG
PSIG PSIG PSIG PSIG
®
Dedicated Outdoor Air Unit 27
Page 28
®
Start-Up Checklist - Air-Source Heat Pump (ASHP)
Compressor 1 Compressor 2
Compressors
L1 Amps Amps
L2 Amps Amps
L3 Amps Amps
Crankcase Heater NA Amps
Cooling
Superheat Should be between 10º and 20ºF (0% reheat) or
should be between 10º and 30ºF (100% reheat)
Subcooling Should be between 10º and 15ºF (0% reheat) or
should be between 2º and 10ºF (100% reheat)
Discharge Pressure Should be between 250 and 500 PSIG
Suction Line Pressure Should be between 96 and 155 PSIG
Liquid Line Temp Deg. F Deg. F
Suction Line Temp Deg. F Deg. F
Moisture Indicating Sight Glass
Liquid Visible Yes / No Yes / No
Color of Center Dot Purple / Pink Purple / Pink
Heating
Superheat Should be between 10º and 20ºF
Subcooling Should be between 10º and 20ºF
Discharge Pressure Should be between 250 and 500 PSIG
Suction Line Pressure Should be between 96 and 155 PSIG
Liquid Line Temp Deg. F Deg. F
Suction Line Temp Deg. F Deg. F
Moisture Indicating Sight Glass
Liquid Visible Yes / No Yes / No
Color of Center Dot Purple / Pink Purple / Pink
Note: Unit may not run at 100% heating mode in ambient temperatures over 70°F (21°C). Modulate compressor as necessary to keep unit running.
Deg. F Deg. F
Deg. F Deg. F
PSIG PSIG
PSIG PSIG
Deg. F Deg. F
Deg. F Deg. F
PSIG PSIG
PSIG PSIG
Dedicated Outdoor Air Unit28
Page 29
Start-Up Components
Fan
The fan should be checked for free rotation. If any binding occurs, check for concealed damage and foreign objects in the fan housing.
CAUTION
When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult manufacturer to determine if the unit can operate safely at the new conditions.
Supply Fan (Plenum Type)
The unit contains one or two plenum supply fans located on the end of the unit opposite the outdoor air intake and may optionally have a relief air blower which is referred to as an exhaust blower in this document. Efficient fan performance can be maintained by having the correct offset.
Offset: Proper offset, or overlap, is adjusted by loosening the wheel hub from the shaft and moving the wheel to the desired position along the shaft. The transition between the inlet cone
and the wheel should
Wheel
Offset
Inlet
Cone
be as shown; there is a smooth feel to the profile when moving one component to the other.
Supply/Exhaust Fan
The optional exhaust fan is a direct-drive plenum type. Fan speed is controlled by a VFD which, in turn, is controlled by the microprocessor controller or by an external signal. Motor speed will be set on the VFD during the unit Test and Balance, but after that, the VFD will not normally be changed. Always check the motor amperage rating shown on the motor nameplate when changing the fan RPM. All access doors must be installed except the control center door.
Vibration
Vibration Causes
Off axis or loose components Drive component unbalance Poor inlet / outlet conditions Foundation stiffness
including structural and/or component failure. The most common sources of vibration are listed.
Many of these conditions can be discovered by careful observation. Refer to the Troubleshooting section of this manual for corrective actions. If observation cannot locate the source of vibration, a qualified technician using vibration analysis equipment should be consulted.
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To eliminate this undesirable effect, the use of flexible connectors is recommended.
Excessive vibration may be experienced during initial start-up. Left unchecked, excessive vibration can cause a multitude of problems,
Fan Size
Offset
(inches)
Tolerance
(inches)
ER35C 5/32 ± 1/32
ER45C 3/16 ± 1/32
ER50C 13/64 ± 1/32
ER56C 1/4 ± 1/32
PDL-355 5/32 ± 1/32
PRM-450 3/16 ± 1/32
PRM-560 15/64 ± 1/32
Refer to the respective Installation, Operation and Maintenance Manual shipped with this unit for additional start-up and maintenance information regarding the plenum fan.
Fan Wheel Rotation Direction
Check for proper wheel rotation by momentarily energizing the fan. Rotation is determined by viewing the wheel from the drive side and should match the rotation decal affixed to the fan housing.
If the wheel is rotating the wrong way, direction can be reversed by interchanging any two of the three electrical leads. Check for unusual noise, vibration or overheating of the bearings. Refer to the Troubleshooting portion of this manual if a problem develops.
Discharge Air Temperature Sensor
Units are supplied with a Discharge Air Temperature Sensor that is to be field-installed prior to unit start­up. The sensor is to be installed at least three duct diameters downstream of the heat exchanger. The sensor must be connected directly to the microprocessor controller. All other sensors and low voltage devices are to be connected to the low voltage terminal strip in the control center. The discharge air sensor is shipped loose and can be found in the unit’s control center. See the unit-specific wiring diagram for connection locations.
Typical Discharge Air
Temperature Sensor
®
Dedicated Outdoor Air Unit 29
Page 30
®
Start-Up Components
Airflow Monitoring
For additional information on how to navigate through the airflow controller menus, refer to technical manuals from GreenTrol® Automation Inc. at www.greentrol. com. Also refer to the Greenheck Reference Guide for Microprocessor Controller.
Display and Navigation
The LCD screen will by default show the current airflow that is being measured. To enter the menu to set up the monitoring station the user must remove the front cover of the GreenTrol to uncover the navigation buttons. Press and hold the UP and DOWN keys at the same time for 3 seconds to enter the menu.
Enter Button Function - The ENTER button allows the user to go into the selected menu or function, as well as save the selected value.
Up/Down Button Function - The UP/DOWN buttons are used to navigate the menu and to change values in the menu.
Esc Button Function - The ESC button allows the user to exit the current menu or function.
Field Calibration
1. Press UP/DOWN = Setup
2. Press DOWN/ENTER = Setup Wizard
3. Scroll Down to Field Adjust and press ENTER
4. Run FAK wizard and press ENTER
5. Set FAW Int and press ENTER
6. FAW INT = 300 and press ENTER
7. Set number of flows and press ENTER
8. Set flow and press ENTER
9. Set flow to actual CFM measured by Test and Balance and press ENTER
10. Wait for calibration before cycling power
11. Proceed to Communication Setup
Communication Setup
1. Press the UP and DOWN keys at the same time for 3 seconds
2. When SETUP appears on the screen press ENTER
3. Scroll DOWN (twice) to the NETWORK menu and press ENTER
4. When NETOUT appears on the screen, press ENTER; when SET NETOUT appears on the screen, press ENTER again
5. Scroll UP or DOWN to set the NETOUT = MODBUS and then press ENTER
6. Scroll DOWN to NETADDR and press ENTER, when SET NETADDR appears on the screen press ENTER again
7. Scroll UP or DOWN to set the NETADDR to the same address that was listed for the airflow monitor in the microprocessor. For instance, the Outdoor Airflow Monitor screen above has an address of 31. Then press ENTER.
8. Scroll DOWN to NETBAUD and press ENTER, when SET NETBAUD appears on the screen, press ENTER again
9. Scroll UP or DOWN until NETBAUD = 19200, then press ENTER
10. Scroll down to PARITY and press ENTER, when SET PARITY appears on the screen press ENTER again
11. Scroll UP or DOWN until PARITY = NONE2, then press ENTER
12. Once the address is set and the communication wires are connected, “Status” LED should be a steady green and the “RS485” LED should be a quick blinking green LED.
Dedicated Outdoor Air Unit30
Page 31
Start-Up Components
Optional Dirty Filter Switch
To adjust the switch, the unit must be running with all of the access doors in place, except for the compartment where the switch is located (exhaust intake compartment). The adjusting screw is located on the top of the switch.
1. Open the filter compartment and place a sheet of plastic or cardboard over 50% of the filter media.
Setscrew (on front of switch) must be manually adjusted after the system is in operation.
Negative pressure connection is toward the ‘front or top’ of the switch. (Senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’ of the switch. (Senses pressure at air inlet side of filters)
2. Replace the filter compartment door.
3. Check to see if there is power at the alert signal leads (refer to electrical diagram).
4. Whether there is power or not, turn the adjustment screw on the dirty filter gauge (clockwise if you did not have power, counterclockwise if you did have power) until the power comes on or just before the power goes off.
5. Open the filter compartment and remove the obstructing material.
6. Replace the door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for operation.
Troubleshooting
Symptom Possible Cause Corrective Action
Refer to Adjust the Air Seals in the Optional Energy Wheel Start-Up section.
Recheck air seals, make sure they are not too tight. See Adjust the Air Seals in the Optional Energy Wheel Start-Up section.
Energy wheel does NOT turn
Energy wheel runs intermittently
®
Air seals are too tight.
Broken belt. Replace.
No power to wheel motor. Make sure wheel drive is plugged in. Verify power is available.
Wheel motor overloads are tripping due to rubbing between wheel and air seals.
Dedicated Outdoor Air Unit 31
Page 32
®
Optional Polymer Energy Wheel
Start-Up
If selected, the energy wheel is installed in the unit with one half of the wheel in the outdoor airstream and one half in the exhaust airstream. The energy wheel includes air eals to minimize leakage between airstreams.
Retaining
Adjustable
Air Seals
Drive Belt
Screws
Bearing
Support
Label
showing
cassette
serial # and
date code
Drive Pulley
Drive Belt
Inspect the drive belt. Make sure the belt rides smoothly in the pulley and around the outside of the wheel. Note the directional arrow and data information shown in the image.
Adjust the Air Seals (Polymer wheels only)
The information below only applies to polymer wheels, which require air seal adjustment at the time of start-up for proper performance. Aluminum wheel air seals are factory-set and do not require field adjustment.
Make sure the unit power supply is locked out. Disconnect the wiring to the wheel module and pull the wheel cassette out of the cabinet on its tracks. Large cassettes are not removable. Then slowly rotate the wheel by hand to make sure there is no binding or misalignment.
There is a perimeter seal located around the outside of the wheel and a diameter seal across the face of the wheel on both sides. Check to make sure that all air seals are secure and in good condition.
Adjust the air seals by loosening all the air seal retaining screws on the bearing support. Using a piece of paper as a feeler gauge, adjust the seals so they almost touch the face of the wheel while tugging slightly on the paper. When the wheel is rotated, there should be a slight tug on the paper. Tighten the screws, repeat the steps on the other set of seals.
Push the wheel cassette back into the unit and plug in the power connector. Turn the main power supply back on and then observe the operation of the wheel by opening the wheel access door slightly. Remove filters if necessary to observe the wheel.
Sequence of Operation
Optional Economizer - The economizer will be locked out when: the outside air is below economizer lockout; the unit is operating in dehumidification mode; or there is a call for heating.
Stop Wheel: When economizer mode is enabled and there is a signal for cooling, the wheel will stop rotating to allow free cooling.
Modulate Wheel: When economizer mode is enabled and there is a signal for cooling, the wheel VFD modulates wheel speed to maintain the discharge temperature set point.
Optional Frost Control - Polymer Wheel The microprocessor controller will output a signal when wheel frosting is occurring which is determined by a temperature set point (OA <5°F – 2°F hysteresis, adjustable) and wheel pressure drop increase.
Preheat: When frosting is occurring, the preheater is energized to defrost the wheel. Once the pressure drop decreases below the set point, the preheater is de-energized.
Timed Exhaust: When frosting is occurring, the supply blower is cycled off. The exhaust blower shall continue to run, allowing the warm exhaust air to defrost the wheel. After the 5 minute cycle, the supply fan is re-energized to continue normal operation.
Modulating Wheel: When frosting is occuring, the wheel VFD will reduce wheel speed to prevent condensation and frosting. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The temperature and pressure differential set points are set at the factory, but are field-adjustable. The VFD will be fully programmed at the factory.
Dedicated Outdoor Air Unit32
Page 33
Optional Polymer Energy Wheel
Maintenance
WARNING
Whenever performing maintenance or inspections, always disconnect the power source.
Inspection
The wheel should be inspected semiannually in accordance with the maintenance schedule. Maintenance of the wheel consists mainly of inspecting the wheel for cleanliness and then checking the drive motor, belt, and pulley for wear. If the wheel appears dirty, the wheel should be disassembled and cleaned.
The wheel rotates through two airstreams moving in opposite directions, which means the wheel is self-cleaning, up to a point. If the
Energy Wheel
Cassette
wheel media becomes blocked by dirt or dust, or if the media collects a layer of smoke residue or an oily film, the energy transfer efficiency drops.
The main factor in the frequency of cleaning is the cleanliness of the air. If air filters are not changed frequently, the wheel will collect contaminants and will then have to be cleaned.
Wheel Disassembly
Wheels are part of a cassette that may be pulled from the unit for easy access. There may be a small damper assembly or other component that blocks removal of the cassette. Before sliding out the cassette or any other component, disconnect any power supply cord and secure it so it cannot jam or otherwise get damaged.
Each wheel has removable segments that hold the coated layers of media and each segment is held in place with two retaining clips located on the outer rim of the wheel. When removing more than one segment, remove them in sequence from opposite sides of the wheel (180 degrees apart) to reduce the imbalance. Secure the wheel against rotation. Carefully release the two retaining clips and swing them fully open. The segment can now be removed by pushing the face of the segment close to the outer rim of the wheel. Wheel segments are built to close tolerances and the segment may have to be jiggled to remove it. Do not use a hammer or otherwise force the segment because these are high value items and are not built to withstand abuse.
Segment Retaining Clip
Whenever retaining clips are opened, they should be closed as soon as possible. If the wheel should rotate when a clip is open, the clip will jam against the bearing support bar and could cause damage.
Cleaning
Maintenance or cleaning of the wheel segments should be done with the segments removed from the wheel cassette to avoid splashing liquids or cleaning agents inside the cabinet. If the energy wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only excessive buildup of foreign materials needs to be removed.
DISCOLORATION AND STAINING OF ENERGY RECOVERY WHEEL DOES NOT AFFECT ITS PERFORMANCE.
Thoroughly spray the wheel matrix with a household cleaner such as Fantastik™ or the equivalent. Gently rinse with warm water and use a soft brush to remove any heavy accumulations. A detergent/water solution can also be used. Avoid aggressive organic solvents, such as acetone. Wheel segments can be soaked in the above solution overnight for removal of stubborn dirt or accumulations.
After cleaning is complete, shake excess water from the wheel or segments. Dry the wheel or segments before putting them back into the cassette.
Reassembly
When reinstalling the segments, be sure to install them with the correct face toward the motor side of the cassette. Note that one face of each segment is smooth and the other face has a reinforcing channel or support cut into the surface.
Wheel Segment
(Pulley Side)
Wheel Segment
(Motor Side)
Wheel Belt
Inspect belts each time filters are replaced. Belts that look chewed up or are leaving belt dust near the motor pulley may indicate a problem with the wheel. Be sure to inspect wheel for smooth and unrestricted rotation. If a belt requires replacement, contact the local manufacturer representative. Instructions for replacement will ship with the new belt.
Wheel Bearing
In the unlikely event that a wheel bearing fails, the bearing is behind a removable plate on the wheel support beam (slide cassette halfway out of cabinet to access). Contact the local manufacturer's representative for detailed instructions on how to replace the bearing.
®
Dedicated Outdoor Air Unit 33
Page 34
®
Optional Aluminum Energy Wheel
Start-Up
Optional Frost Control
The microprocessor controller will output a signal when wheel frosting is occurring which is determined by a temperature set point (EA < 36°F, adjustable).
Modulating wheel frost control: When frosting is occurring, the wheel VFD will modulate the wheel speed to maintain 36°F exhaust air temperature. The VFD will be fully programmed at the factory.
Modulating wheel with electric preheat frost control: When frosting is occurring, the wheel VFD will modulate the wheel speed to maintain 36°F exhaust air temperature. The electric preheater will energize when the outdoor air temperature is below 10°F. The VFD will be fully programmed at the factory.
Maintenance
WARNING
Whenever performing maintenance or inspections, always disconnect the power source.
Inspection
The wheel should be inspected in accordance with the maintenance schedule. Maintenance of the wheel consists mainly of inspecting the wheel for cleanliness and then checking the drive motor, belt, and pulley for wear. If the wheel appears dirty, the wheel should be cleaned.
The wheel rotates through two airstreams moving in opposite directions, which means the wheel is self­cleaning up to a point. If the wheel media collects a layer of smoke residue or an oil film, the energy transfer efficiency drops.
The main factor in the frequency of cleaning is the cleanliness of the air. If air filters are not changed frequently, the wheel will collect contaminants and will then have to be cleaned.
Wheel Belt
Inspect belts each time filters are replaced. Belts that look chewed up or are leaving belt dust near the motor pulley may indicate a problem with the wheel. Be sure to inspect wheel for smooth and unrestricted rotation. If a belt requires replacement, contact the local manufacturer representative. Instructions for replacement will ship with the new belt.
Wheel Bearing
In the unlikely event that a wheel bearing fails, contact the local manufacturer's representative for detailed instructions.
Cleaning
Accumulation of dust or particles on the surface of the wheel can typically be vacuumed, purged with compressed air, or wiped from the surface. In cases when a more thorough cleaning is required, use the following procedure.
Liberally spray 409 cleaner onto a small section of the dirty side of the energy wheel, letting it foam to soften debris and residue. Blow approximately 90 psi of compressed air and from the opposite side of the wheel, catching the blown-off material on pre-placed drop cloths. Lightly sweep a soft sash paint brush across the face of the wheel to remove any leftover residue. A SLIGHT CLEANER SMELL MAY BE PRESENT FOR A SHORT TIME AFTER THE UNIT IS TURNED BACK ON. THIS SMELL WILL DISSIPATE QUICKLY.
Dedicated Outdoor Air Unit34
Page 35
Troubleshooting – Alarms
Several of the electronic controls in the unit monitor the system for faults and will go into alarm, shutting down the unit or a single function within the unit.
Microprocessor Controller
The microprocessor is located in the main control center. If the microprocessor is in alarm condition, the Alarm button will blink red. Press the Alarm button to see the specific condition or to reset the microprocessor. Refer to the microprocessor IOM for detailed information on fault codes and see the unit­specific wiring diagram.
Phase Monitor
The phase monitor has two LED indicator lights, one red and one green. Green indicates proper operational status, red indicates the unit has detected a fault and is in alarm condition. The alarm LED will blink to show the specific fault and there is a chart printed on the monitor that shows the code for the blinking light. The phase monitor is self-resetting once the alarm condition is corrected. It is located in the main control center.
Variable Frequency Drive (VFD)
Variable frequency drives have a display screen that will show an alarm condition. If a fault such as a voltage spike occurs, the VFD will go into alarm and will not reset until a hard restart is performed. See the unit­specific manufacturer’s manual supplied with the unit. VFDs are located in the main control center.
Optional Digital Scroll Compressor Controller
Present only if packaged DX with digital scroll option is selected. The controller has three LED indicator lights. One is green, indicating that it has power, one is an alarm indicator that will flash a code for various alarm conditions and the third indicates whether the compressor is operating in a loaded or unloaded condition. See the manufacturer’s unit-specific manual for further information.
See the Fault Code chart below. The Fault Code chart is also printed on the back of the controller. Note that if the controller generates either a Code 2 or a Code 4 Lockout, a manual reset must be performed. Manual Reset is accomplished by shutting off main power to the unit and then turning it back on.
Digital Scroll Compressor
Controller Fault Codes
Alert Code
Code 2*
Code 3
Code 4* Locked Rotor Blinks 4 Times Lockout
Code 5
Code 6
Code 7 Future N/A N/A
Code 8
Code 9 Low Voltage Blinks 9 Times Trip Compressor
System Condition
High Discharge Temperature Trip
Compressor Protector Trip
Demand Signal Loss
Discharge Thermistor Fault
Welded Contactor
*Protective faults that require manual reset.
Diagnostic Alert Light
Blinks 2 Times Lockout
Blinks 3 Times Lockout
Blinks 5 Times Lockout
Blinks 6 Times
Blinks 8 Times
Action
Reduce Capacity
Unload Compressor
®
Dedicated Outdoor Air Unit 35
Page 36
®
Troubleshooting – Unit
Symptom Possible Cause Corrective Action
Blown fuse or open circuit breaker. Replace fuse or reset circuit breaker and check amps.
Blower fails to operate
Motor starters “chatter” or do not pull in
Motor over amps
Low airflow (cfm)
High airflow (cfm)
Excessive noise or vibration
Defective motor or capacitor. Replace.
Motor overloaded. Reset VFD and check amps.
Electrical.
Control power (24 VAC) wiring run is too long. (Resistance should not exceed 0.75 ohms).
Check for On/Off switches. Check for correct supply voltage. Check Control wiring.
Shorten wiring run to mechanical room or install a relay to turn unit on/off. Consult factory for relay information. Increase wire gauge size so that resistance is 0.75 ohms or less.
Incoming supply power is less than anticipated. Voltage supplied to starter coil must be within +10% / -15% of
Need to increase supply power or use a special control transformer which is sized for the actual supply power.
nominal voltage stated on the coil.
Static pressures are higher than design. Check for dirty filters. Improve ductwork.
Motor voltage incorrect.
Motor horsepower too low.
Check motor wiring. Check motor nameplate versus supplied voltage.
See specifications and catalog for fan curves to determine if horsepower is sufficient.
Shorted windings in motor. Replace motor.
Unit damper not fully open. Adjust damper linkage or replace damper motor.
System static pressure too high.
Improve ductwork to eliminate losses using good duct practices.
Check maximum motor RPM and compare with catalog
Blower speed too low.
data. Verify that external control wiring is in place if required.
Fan wheels are operating backwards.
Dirty filter.
For 3-phase, see Direction of Fan Wheel Rotation Direction in Start-Up, Components section.
Replace filters or follow cleaning procedures in Routine Maintenance section of this manual.
Leaks in ductwork. Repair.
Elbows or other obstructions may be obstructing fan outlet.
Blower fan speed too high.
Correct or improve ductwork.
Check for correct maximum fan RPM. Decrease maximum fan speed if necessary in the VFD.
Filter(s) not in place. Install filters.
Insufficient static pressure (Ps). (airflow resistance)
Fan wheel rubbing on inlet.
Bearings.
Induce Ps into system ductwork. Make sure grilles and access doors are installed. Decrease fan speed if necessary.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Loose wheel on shaft. Tighten wheel hub.
Motor base or blower loose. Tighten mounting bolts.
Make sure ductwork is supported properly. Make sure
Noise being transmitted by duct.
ductwork metal thickness is sized for proper stiffness. Check duct size at discharge to ensure that air velocities are not too high.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
Dedicated Outdoor Air Unit36
Page 37
Troubleshooting – Refrigeration Circuit
TROUBLESHOOTING NOTE
IMPORTANT
Do not release refrigerant to the atmosphere! If
Before any components are changed on the refrigeration system, the cause of the failure must be identified. Further problems will exist unless the true cause or problem is identified and corrected.
required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be performed by a qualified EPA Certified Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply.
The first step in troubleshooting a refrigeration circuit is to examine the microprocessor controller and digital scroll compressor controller (if present) and see if there is a fault code. The next step is to check airflow conditions (e.g. improper ductwork, atypical wet bulb / dry bulb, etc.). After these steps have been eliminated, proceed with troubleshooting by following this guide.
Symptom Possible Cause Corrective Action
Open disconnect switch or circuit breaker.
Compressor contactor not closing.
Blown fuse or tripped breaker.
Close switch and/or breaker.
Check voltage to contactor coil, transformer, slave relay, system. Replace parts as necessary.
Check for reason and repair. Replace fuse after correcting problem.
Compressor will not run or does not start
Compressor starts but cuts out on low pressure
Low pressure switch cuts out at 50 PSIG (PDX) or 25 PSIG (ASHP)
Low line voltage.
Check line voltage. If more than 10% from compressor marking, correcting is necessary.
Motor thermal protector automatically resets. Allow time
Compressor motor protector open.
(2 hours) for compressor to cool down so protector will reset. Restart and check for reason overheat occurred.
Check motor for open circuit, short circuit, grounded
Compressor defective.
windings, or burn out. Compressor may be seized; check refrigerant. If necessary, replace compressor.
High pressure switch open or defective.
Low pressure switch open or defective.
Open room thermostat or control. (No cooling required).
If manual reset (high pressure), reset switch. (Switch opens at 610 psi and will not reset above 420 psi for R-410A). Replace if defective.
See switch label for setpoint.
Check room temperature. If temperature is proper, wait for thermostat to close.
Loose wiring. Check all wire terminals and tighten as necessary.
Low or loss of refrigerant charge.
Check refrigerant pressures and temperatures (subcooling.)
Check for dirty evaporator coil, dirty filters, dampers
Airflow restricted.
closed, iced evaporator coil, improper belt, check motor amps, check duct design.
Check refrigerant pressures, look for frosted tubing and
Restriction in refrigerant line.
components indicating a restriction. Check pressure drop across the filter drier.
Defective low pressure switch. Replace.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
®
Dedicated Outdoor Air Unit 37
Page 38
®
Troubleshooting – Refrigeration Circuit
Symptom Possible Cause Corrective Action
Compressor starts but cuts out on high pressure switch
High pressure switch cuts out at 610 PSIG
Compressor cuts out on thermal overload
Refrigerant overcharge. Check pressures, charge by subcooling.
Condenser fan motor defective. Check fan motor.
Condenser coil inlet obstructed or dirty. Check coil and clearances. Clean coil if necessary.
Air or non-condensables in system.
Check high side equalized pressures, check expansion valves.
Defective high pressure switch. Replace.
Restriction in discharge or liquid line.
Check refrigerant line pressures, check expansion valves, replace any defective component.
Condensing fan relay not pulling in. Replace.
Low voltage. Check voltage.
Sustained high discharge pressure.
High suction and discharge pressures.
Defective compressor overload.
Check running amperage and conditions described under “low suction pressure” symptoms.
Check thermal expansion valve setting, check for air in system. Check air conditions and cfm.
If compressor is hot, allow compressor to cool for two hours. Recheck for open circuit.
Improper refrigerant charge. Check subcooling.
Improperly wired. Review wiring schematics.
Compressor hums, but will not start
Compressor noisy or vibrating
Loose wiring. Check all connections.
Defective start relay. Replace relay.
Motor windings damaged. Verify amp draw.
Improperly wired. Review wiring schematics.
Low line voltage. Check voltage.
Loose wiring. Check all connections.
Defective start relay. Replace relay.
Motor winding damaged. Verify amp draws. Replace compressor if necessary.
Internal compressor mechanical damage.
Replace.
Refrigerant overcharge. Check pressures and subcooling.
Liquid floodback.
Tubing rattle.
Scroll compressor rotating in reverse. (3-phase)
Check thermal expansion valve setting. Check for refrigerant overcharge.
Dampen tubing vibration by taping or clamping. Carefully bend tubing away from contact where possible.
Check high and low side pressures during operation to confirm. Rewire for opposite rotation.
Damaged compressor. Replace the compressor.
Improper mounting on unit base.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
Dedicated Outdoor Air Unit38
Check that compressor is properly isolated and mounting bolts are tight.
Page 39
Troubleshooting – Refrigeration Circuit
Symptom Possible Cause Corrective Action
High suction pressure
High discharge pressure
Excessive load on evaporator coil.
Compressor is unloaded. (digital scroll)
Check for high entering wet bulb temperature, check for excessive air flow.
Check digital scroll controller signal and solenoid valve.
Check the thermal expansion valve, ensure bulb is
insulated. Check superheat. If superheat is high, then Expansion valve sensing bulb not secured to suction line.
valve is choking refrigerant flow.
• Check bulb for contact.
• Adjust valve for superheat ~10°F.
• Replace valve powerhead or valve.
Thermostatic expansion valve. Overfeeding.
Check bulb location and clamping. Adjust superheat.
Replace expansion valve power head.
Room load too large. Reduce the load or add more equipment.
Overcharged. Check pressures and subcooling.
Thermal expansion valve setting.
Air inlet to condenser coil dirty or obstructed.
Check thermal expansion setting and calibrate
superheat/subcooling.
Check for proper clearances and possible air
recirculating. Clean coil.
Condenser fan motor defective. Check condenser fan motor.
Too much refrigerant. Check subcooling. Remove excess refrigerant.
Non-condensable in system. Remove non-condensable from system.
Low suction pressure
Dirty condenser coil. Clean condenser coil.
Condenser fan not running or running backwards.
Check electrical circuit and fuse. Check fan cycling
controls.
High load conditions. Add more equipment or reduce load.
Refrigerant undercharge/loss of refrigerant charge.
Blower running backward.
Low entering air temperature. (Low load conditions).
Check pressures and subcooling.
Confirm blower rotation. If reversed, interchange any two
wires from 3-phase disconnect.
Check entering air wet bulb conditions.
Refrigerant leak. Check system for leaks. Repair leaks and add refrigerant.
Evaporator dirty or iced-up, or airflow restricted.
Clean the coil. Check fan operation. Check airflow.
Plugged liquid line filter-drier. Replace filter-drier, check psi across filter.
Improper hot gas bypass setting (if equipped).
Expansion valve defective, superheat too high or valve too small.
Check setting and correct as required.
Adjust valve for proper superheat or replace the
expansion valve if too small or defective.
Moisture in system, check sight glass. Reclaim refrigerant, check for leaks, recharge.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
®
Dedicated Outdoor Air Unit 39
Page 40
®
Troubleshooting – Refrigeration Circuit
Symptom Possible Cause Corrective Action
Low discharge pressure
Compressor short cycles
Compressor loses oil
Not enough capacity or lack of performance
Liquid line is frosted or wet
Suction line is frosting
Frost on evaporating coil (Note: Normal on ASHP units in heating mode).
Insufficient refrigerant charge.
Defective or improperly adjusted expansion valve.
Check subcooling, check for leak. Repair leak and add refrigerant.
Check superheating and adjust thermal expansion valve.
Low suction pressure. See “low suction pressure”.
Faulty condenser temperature controls. (Condensing fan cycle switch).
Thermostat location or controls malfunction.
Check condenser controls and reset to obtain desired condensing temperature.
Check thermostat, check heat anticipator setting.
Improper refrigerant charge. Check subcooling, verify superheat.
Defective high or low pressure control. Check high or low pressure switch.
Poor air distribution. Check ductwork for recirculating.
Low airflow at evaporator coil. Check blower operation and airstream restrictions.
Incorrect unit selection (oversized). Contact factory.
Refrigerant leak. Check system for leaks. Repair leaks and add refrigerant.
Short cycling. Check low pressure control settings.
Check thermal expansion valve setting. Check for
Refrigerant flood back.
refrigerant overcharge. Check crankcase heater operation.
Reheat flush cycle inadequate. Contact factory.
Refrigeration undercharged. Check subcooling. Adjust charge, if necessary.
Dirty filter or evaporating coil. Check filter, coil and airflow.
Dirty or clogged condensing coil. Check coil and airflow.
Air or other non-condensables in system.
Check equalized high side pressure with equivalent outdoor temperature.
Restriction in suction and liquid line. Check for restrictions in refrigerant circuit.
Control contacts stuck. Check wiring.
Excessive load. Add more equipment or reduce room load.
Restriction in liquid line.
Insufficient evaporating coil airflow.
Malfunctioning or defective expansion valve.
Hot gas bypass valve not functioning properly (if equipped).
Manual hot gas bypass valve closed (if equipped).
Clear restriction upstream of point of frosting. (Note: liquid line frosting in normal on ASHP units).
Check airflow, check filters, check VFD control signal for proper operation.
Check bulb of thermal expansion valve.
Check valve. If defective, replace.
Open valve.
Low load or airflow. Increase airflow, check filters.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information.
Dedicated Outdoor Air Unit40
Page 41
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to the unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
This unit requires minimal maintenance to operate properly. Maintenance requirements for this model vary for each installation and depend greatly on how much the system is used and the cleanliness of the air. Proper maintenance will both increase the life of the system and maintain its efficiency. Maintenance must be performed by experienced technicians and in the case of refrigeration systems, must be done by an EPA certified technician.
Maintenance frequency is based on a presumed nominal use of the system. If the system is being run constantly, the frequency should be adjusted accordingly. If there is seasonal debris in the air which can be drawn into the filters and the coils, they should be checked more frequently. If the system is being used for only a few hours per day, the frequency may be reduced. Use the maintenance log at the end of this manual to record each maintenance session and observations and then establish a maintenance schedule that is appropriate for the installation. The following is provided as a guideline.
Annually
It is recommended that the annual inspection and maintenance occur at the start of the cooling season. After completing the checklist, follow the unit start-up checklist provided in the manual to ensure the refrigeration system operates in the intended matter.
1. Lubrication Apply lubricant where required
2. Dampers Check for unobstructed operation
3. Blower Wheel and Fasteners Check for cleanliness
Check all fasteners for tightness Check for fatigue, corrosion, wear
4. Door Seal Check if intact and pliable
5. Wiring Connections Check all connections for tightness
6. Cabinet Check entire cabinet, inside and out, for dirt
buildup or corrosion. Remove accumulated dirt, remove any surface corrosion and coat the area with appropriate finish.
Maintenance Frequency:
Monthly
1. External Filter Clean metal mesh filters
2. Internal Filters Replace MERV 8 filters monthly.
Adjust replacement schedule for MERV 13 and MERV 14 or other filters as inspection requires.
Semiannually
1. Check motor and motor bearings Check for excessive heat, vibration or noise.
Lubricate bearings in accordance with the motor manufacturer’s recommendations.
2. Condensate Drain (if applicable) Inspect and clean – refill with water
3. Heat Transfer Coils (if applicable) Inspect for cleanliness – clean as required
4. Outdoor Fan Blades and Motor (if applicable) Check for cleanliness
Check all fasteners for tightness Check for fatigue, corrosion, wear
®
Dedicated Outdoor Air Unit 41
Page 42
®
Filter
Routine Maintenance
Maintenance Procedures:
Lubrication - Check all moving components for
proper lubrication. Apply lubricant where required. Any components showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation.
Dampers - Check all dampers to ensure they open and
close properly and without binding. Backdraft dampers can be checked by hand to determine if blades open and close freely. Apply power to motorized dampers to ensure the actuator opens and closes the damper as designed.
Gas Furnace - Maintain furnace in accordance with
instructions in the Indirect Gas-Fired Heat IOM shipped with this unit.
Fan Motors - Motor maintenance is generally limited
to cleaning and lubrication. Cleaning should be limited to exterior surfaces only. Removing dust and grease buildup on the motor housing assists proper cooling. Never wash-down the motor with high pressure spray. Greasing of motors is only intended when fittings are provided. Fan motors typically have two grease fittings. Each motor manufacturer has different lubrication schedules for different models. Go to the motor manufacturer’s website and download their maintenance requirements. Do not over-lubricate motors or use an incompatible grease. Many fractional motors are permanently lubricated for life and require no further lubrication.
Fan Wheel and Fasteners - Wheels require very little
attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs, the wheel and housing should be cleaned to assure smooth and safe operation. Inspect fan impeller and housing for fatigue, corrosion, or wear.
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness. A proper maintenance program will help preserve the performance and reliability designed into the fan.
Coil Maintenance - Coils must be cleaned to maintain
maximum performance. Check coils once per year under normal operating conditions and if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more energy from the fan and create an environment for odor and bacteria to grow and spread through the conditioned zone. High pressure water (700 psi or less) may be used to clean coils with a fin thickness over 0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil cleaners use harsh chemicals, so they must be used with caution by qualified personnel only. Care must be taken not to damage the coils, including the fins, while cleaning. Caution: Fin edges are sharp!
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate this unit without the filters and birdscreen installed. They prevent the entry of foreign objects such as leaves, birds, etc.
Do not remove access panels or other unit components while standing on a ladder or other unsteady base. Access panels and unit components are heavy and serious injury may occur.
Internal Filter Maintenance - The unit will typically be
provided with 2-inch thick pleated paper filters in the airstream. These filters should be checked according to a routine maintenance schedule and replaced as necessary to ensure proper airflow through the unit. Replacement filters shall be of same performance and quality as factory installed filters. Filter must be pleated design with integral metal grid. Two acceptable filter replacements are Aerostat Series400 or Farr 30/30®.
Filters upstream of the coil should be checked regularly. If the filters are dirty, they should be cleaned or replaced. It is important the filters stay clean to maintain desired airflow.
External Filter Maintenance - Aluminum mesh, 2-inch
thick filters are located in the supply weatherhood (if the weatherhood option was purchased). These filters should be checked and cleaned on a regular basis for best efficiency. The frequency of cleaning depends upon the cleanliness of the incoming air. These filters should be cleaned by rinsing with a mild detergent in warm water prior to start-up.
Outdoor Air Intake Hood
Mesh Filter Access
WARNING
Biological hazard. May cause disease. Cleaning should be performed by qualified personnel.
Drain pans in any air conditioning unit will have some moisture in them, therefore, algae and other organisms will grow due to airborne spores and bacteria. Periodic cleaning is necessary to prevent this buildup from plugging the drain and causing the drain pan to overflow. Inspect twice a year to avoid the possibility of overflow. Also, drain pans should be kept clean to prevent the spread of disease. Cleaning should be performed by qualified personnel.
Dedicated Outdoor Air Unit42
Page 43
Routine Maintenance
Outdoor Air
Model
Weatherhood
Pre-Wheel Outdoor Exhaust Filters
(Aluminum Mesh)
RV-10 (1) 16x20x1 NA NA
Supply Final
(Pre-coil)
(1) 12x24 +
(1) 24x24
RV-25 (4) 20x20x2 NA NA (4) 20x20
RV-45 (4) 25x25x2 NA NA (6) 16x25
RV-75
(12) 16x20x2 NA NA (6) 20x20 + (6) 16x20
6-row DX coil:
RV-110
(30, 40 tons)
(8) 20x25x1 NA NA
(4) 20x24 + (4) 20x20
4-row DX coil:
(6) 20x24 + (6) 20x20
RV-110
(50, 60, 70 tons)
(8) 20x25x1 NA NA (6) 20x24 + (6) 20x20
RVE-40 (4) 20x20x2 (2*) 20x25x2 (2*) 20x25x2 (4) 20x20
RVE-85 (4) 25x25x2 (4**) 16x25x2 (4**) 16x25x2 (8) 16x25
RVE-150
(12) 16x20x2 (8) 20x24 (8) 20x24 (6) 20x20 + (6) 16x20
Filters
RVE-180
(30, 40 tons)
RVE-180
(50, 60, 70 tons)
(8) 20x25x1
(8) 20x25x1
(9) 20x24x2 +
(3) 20x20x2
(9) 20x24x2 +
(3) 20x20x2
(6) 20x24x2 +
(2) 20x20x2
(6) 20x24x2 +
(2) 20x20x2
* Based upon a 30 / 36 in. energy wheel (16x25x2, quantity of 3 for 41 in. energy wheel) ** Based upon a 52 in. energy wheel (16x16x2, quantity of 8 for 58 in. energy wheel)
6-row DX coil:
(4) 20x24 + (4) 20x20x
4-row DX coil:
(6) 20x24 + (6) 20x20
(6) 20x24 + (6) 20x20
®
Dedicated Outdoor Air Unit 43
Page 44
®
Reference - Venting Connection Locations (Models RV-25, -45, RVE-40, -85)
B
COMBUSTION AIR INLET
EXHAUST OUTLET
B
200-300MBH
COMPRESSOR / CONTROL CENTER
ACCESS
COMBUSTION AIR INLET
COMBUSTION AIR INLET
IG FURNACE
ACCESS
A
C
D
EXHAUST OUTLET
EXHAUST OUTLET
B
A
500MBH
COMPRESSOR
ACCESS
A
CONTROL CENTER
ACCESS
IG FURNACE
ACCESS
COMPRESSOR
ACCESS
IG FURNACE
ACCESS
B
A
100-150MBH
COMPRESSOR / CONTROL CENTER
ACCESS
C
D
300-400MBH
CONTROL CENTER
ACCESS
IG FURNACE
ACCESS
COMBUSTION AIR INLET
EXHAUST OUTLET
Housing
Size
25/40
45/85
C
D
C
D
IG Venting Location
Furnace
Size
(MBH)
100 150 4 4 4
A B C D
14 23.5 20.5 20.5
Standard 2-Pipe/Concentric
200 250 6 6 6
15.2 23.7 31.5 35.9
Flue Connection Size
(diameter in inches)
Exhaust Exhaust Intake
4 4 4
6 6 6
300 6 6 6 300 400 6 6 6
14.8 23.3 38.1 44.1
6 6 6
500 14.9 23.6 25.2 57.1 6 6 6
Dedicated Outdoor Air Unit44
Page 45
COMBUSTION AIR INLET
Reference - Venting Connection Locations Cont. (Models RV-110, RVE-180)
EXHAUST OUTLET
COMBUSTION AIR INLET
Housing
Size
110/180
C
A
B
D
E
EXHAUST OUTLET
G
F
I
J
H
IG Venting Location
Furnace
Size
(MBH)
A B C D E F G H I J
Inlet Dimensions Outlet Dimensions
Length Height
Edge
Thickness
Length Height
600 6 13.8 17.2 20.5 50 NA NA NA NA NA 21.5 6 1 6.5 5.5
800 6 13.8 24.7 20.5 49.8 6 13.7 18.5 20.5 49.7 20.5 6 1 6.5 5.5 1000 6 13.8 17.2 20.5 50 6 13.7 24.2 20.5 49.9 21.5 6 1 6.5 5.5 1200 6 13.8 17.2 20.5 50 6 13.7 24.2 20.5 49.9 21.5 6 1 6.5 5.5
®
Dedicated Outdoor Air Unit 45
Page 46
®
Reference - Rated Airflow
Model Airflow (SCFM)
RV-10-3I 1100
RV-10-4I 1450
RV-10-5I 1700
RV-10-6I 1900
RV-10-7I 1900
RV-25-5I 2325
RV-25-5D 2325
RV-25-5S 2325
RV-25-5A 3400
RV-25-7.5I 2300
RV-25-7.5D 2300
RV-25-7.5S 2300
RV-25-7.5A 3000
RV-25-10I 2700
RV-25-10D 2800
RV-25-10S 2800
RV-25-10A 4400
RV-25-12.5I 3400
RV-25-12.5D 3550
RV-25-12.5S 3550
RV-25-12.5A 4400
RV-25-15I 3775
RV-25-15D 3775
RV-25-15S 3775
RV-25-15A 4300
RV-45-15I 4100
RV-45-15D 4100
RV-45-15S 4100
RV-45-15A 4800
RV-45-17.5I 4650
RV-45-17.5D 4650
RV-45-17.5S 4650
Model Airflow (SCFM)
RV-45-17.5A 5500
RV-45-20I 4900
RV-45-20D 5100
RV-45-20S 5100
RV-45-20A 6400
RV-45-25I 5750
RV-45-25D 5600
RV-45-25S 5600
RV-45-25A 7200
RV-45-30I 6000
RV-45-30D 6000
RV-45-30S 5750
RV-45-30A 7000
RV-75-25I 8300
RV-75-25D 8300
RV-75-30I 9400
RV-75-30D 9500
RV-75-40I 10000
RV-75-40D 10000
RV-75-50I 10800
RV-75-50D 10800
RV-110-30I 9000
RV-110-30D 9000
RV-110-40I 10500
RV-110-40D 10500
RV-110-50I 10500
RV-110-50D 10500
RV-110-60I 14000
RV-110-60D 14000
RV-110-70I 16000
RV-110-70D 16000
Full load rating airflow per AHRI 340/360
Dedicated Outdoor Air Unit46
Page 47
®
Dedicated Outdoor Air Unit 47
Page 48
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.
Greenheck’s Model RV and RVE catalog provides additional information describing the equipment, fan performance, available accessories, and specification data.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
474612 • RV/RVE, Rev. 15, April 2021 Copyright 2021 © Greenheck Fan Corporation48
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
Loading...