Greenheck RRL User Manual

APPLICATION
1
5
3
(1) Cover Plate
(1) RRL
(2) #10-16 3/4 SIHWH Screws
(1) Handy Box
(1) Gasket
6
4
2
The RRL Option replaces the fusible link on a combination fire smoke damper wih an electric sensor (thermostat). The sensor has a fixed temperature setting (usually 212° F [100°C]) and performs the same function as the fusible link that it replaces. The sensor interrupts power to the actuator and the actuator’s spring return mechanism causes the damper to close.
This option requires factory installation of the damper actuator and factory wiring of the electric sensor to meet UL requirements for fire dampers. If the damper is equipped with a pneumatic actuator, an EP switch is required with an appropriate electric power circuit, to allow the electric thermostat to control the pneumatic actuator.
RRL Option
Resettable Link Option for
Combination Fire Smoke Dampers
Item
Number
1 821278 (212°)
Part
Number
Qty. Description
RRL Switch Box
820734 (165°)11
2 380864 1 4 in. x 4 in. Cover Plate
3 415555 4 #10 Self Drilling Tek Screws
4 658593 1 4 in. x 4 in. Handy Box
5 460632 1 Label
6 370119 1 Gasket
WIRING DIAGRAM
Copyright © 2008 Greenheck Fan Corporation
RRL Option Rev 8 Nov 2008