Installation Instruction
for RRL (resettable/reusable link) on
FSD, SSFSD, SEFSD, IMO series
Combination Fire Smoke Dampers
Steps to install an RRL in a Fire Smoke Damper:
1) Drill/Saw a 3 5/8 in. (92mm) diameter hole in sleeve
(Detail 2).
2) Insert OCI unit through hole in sleeve (round end inside).
3) Place 4 x 4 in. J-Box over the flange of the OCI unit and
align holes.
4) Mount control box to sleeve/sideplate with #10-16 x 3/4 in.
(19mm) TEK screw (or equivelant) (Detail 1).
5) Complete wiring and install J-Box cover.
Detail 1
#10 1/2 in. Te k
3
Scr ew
2 Req’ d
2
J-Box Cover
1 Req’ d
J-Box
1 Req’ d
4
Gasket
1 Req’ d
6
RRL
Req’ d
Nominal
Section
Height
6-7 2.625 2.625
8 3.125 3.125
9 3.625 3.625
10-11* 2.625 3.625
12-13* 2.625 4.125
14-15* 3.125 4.625
16* 3.625 5.125
17* 4.125 5.625
18 13.125 13.125
19 14.125 14.125
20 14.625 14.625
21 15.625 15.625
22 16.625 16.625
23 17.125 17.125
24 18.125 18.125
25 19.625 19.625
26 20.625 20.625
27, 39,
40, 41
28, 42 22.125 22.125
29, 43, 57 23.125 23.125
30, 44, 58 24.125 24.125
31, 45,
55, 56, 59
32 26.625 26.625
33, 47 27.625 27.625
34, 46 28.625 28.625
35, 49 29.125 29.125
36, 48 30.625 30.625
37, 51 31.125 31.125
38, 50, 52 32.125 32.125
53 23.625 23.625
54 24.625 24.625
60 4.125 4.125
3V
Style
(D)
21.625 21.625
25.125 25.125
Steel
Airfoil
Style (D)
Detail 2
INSIDE
D
SURF ACE
Wiring Diagram
8.375
3.563
Ø3.625
All dimensions shown in inches.
< 11" NOM HEIGHT
>11" NOM HEIGHT
* Note: Operator mounted
upside down on steel airfoil
units from 10 in. to 17 in.
(254mm to 432mm)
Copyright © 2015 Greenheck Fan Corporation
459840 RRL IOM Rev. 7 March 2015