PN 465197
READ AND SAVE THESE INSTRUCTIONS
Supplement for QEP Model
Flow Measurement Sensor
QEP Calibration Data Sheet
Flow Sensor Input and Output:
Select output range so the fans operating point is within the sensors input range. Sensor is calibrated for all
three ranges with a density = 0.075 lb/ft3 (square law device)
(Equations provided on back)
Output: 0-25 inches wg.
Unit Size Input (SCFM)
12 0-6,309
15 0-6,311
16 0-7,677
18 0-9,412
20 0-11,261
22 0-13,857
24 0-16,660
27 0-20,176
30 0-24,741
33 0-29,685
36 0-35,956
40 0-43,118
44 0-52,099
49 0-62,287
54 0-75,232
60 0-90,770
66 0-108,807
73 0-132,858
Output: 0-50 inches wg.
Unit Size Input (SCFM)
12 0-8,923
15 0-8,924
16 0-10,857
18 0-13,311
20 0-15,925
22 0-19,567
24 0-23,561
27 0-28,533
30 0-34,989
33 0-41,981
36 0-50,850
40 0-60,978
44 0-73,679
49 0-88,087
54 0-106,394
60 0-128,368
66 0-153,876
73 0-187,890
Output: 0-100 inches wg.
Unit Size Input (SCFM)
12
15
16
18
20
22
24 0-33,320
27 0-40,352
30 0-49,481
33 0-59,370
36 0-71,913
40 0-86,236
44 0-104,197
49 0-124,573
54 0-150,464
60 0-181,540
66 0-217,614
73 0-265,717
Connections:
• High Pressure: 1/8 inch NPT female
• Low Pressure: 1/8 inch NPT female
Installation Notes:
• Mount differential pressure transmitter above sensor elevation to eliminate condensation build-up in the
differential pressure cell.
• Recommended tubing size is 1/4 inch for runs 25 feet or less. For longer runs, (maximum 100 feet) use
3/8 inch tubing or larger.
L1
A1
GND
L2
E3
E1
E2
A2
+
-
SENSOR FE-X
LOWLOW
LOW
HIHI
HI
ELECT ENCLOSURE
1
2
3
1
2
3
4
4-20mA input
0-10v input
COMMON
1 2 3
LINEAR 4-20mA
OUTPUT
TO PANEL
GROUND LUG
115VAC, 60HZ, 20VA
6FT CORD
PROVIDED
STRAIN RELIEF
24VDC out
1/8" NPTF
1/8" NPTF
FUSE = 0.2AMP, 50V
TIME DELAY
EXTERNAL REVIEVER
CONNECTION
MAX LOAD 400ohms
(REMOVE JUMPER)
Sure-Aire™ Flow Equations:
Unit Size Fan Equation
QEP-12 cfm = 345.65*sqrt(∆P/density)
QEP-15 cfm = 345.65*sqrt(∆P/density)
QEP-16 cfm = 420.86*sqrt(∆P/density)
QEP-18 cfm = 515.35*sqrt(∆P/density)
QEP-20 cfm = 616.86*sqrt(∆P/density)
QEP-22 cfm = 759.37*sqrt(∆P/density)
QEP-24 cfm = 912.87*sqrt(∆P/density)
QEP-27 cfm = 1104.91*sqrt(∆P/density)
QEP-30 cfm = 1355.04*sqrt(∆P/density)
QEP-33 cfm = 1625.35*sqrt(∆P/density)
QEP-36 cfm = 1966.53*sqrt(∆P/density)
QEP-40 cfm = 2361.10*sqrt(∆P/density)
QEP-44 cfm = 2853.94*sqrt(∆P/density)
QEP-49 cfm = 3411.00*sqrt(∆P/density)
QEP-54 cfm = 4120.95*sqrt(∆P/density)
QEP-60 cfm = 4972.27*sqrt(∆P/density)
QEP-66 cfm = 5959.86*sqrt(∆P/density)
QEP-73 cfm = 7275.79*sqrt(∆P/density)
∆P = The differential static pressure between the
Sure-Aire™ high and low taps.
Standard Density = 0.075 lb/ft
3
Wiring Schematic for Optional Digital Readout and Transmitter:
Flow Measurement QEP Calibration
Rev. 3 August 2005
Copyright © 2005 Greenheck Fan Corp.