Greenheck QEID-15 User Manual

Direct Drive Mixed Flow Fans
Model QEID
Sound & Air Performance Supplement
• Motor Information
• Engineering Information
• Air/Sound Performance
• Dimensional Data
Greenheck Fan Corpor ation certifies that the Model QEID Mixed Flow Inline fans shown herein are licensed to bear the AMCA seal. The ratings shown
SOUND
and
R
AIR MOVEMENT AND CONTROL ASSOCIATION
®
INTERNATIONAL, INC.
are based on tests and procedures performed
AIR
PERFORMANCE
in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
®
January
Direct Drive Model Selection
The following performance charts are for the selection of QEID mixed flow inline fans. All charts are organized by fan size and nominal motor RPM. Within each chart, there are a series of solid black lines with corresponding dashed lines. The solid black lines represent the fan curves for each fan and are broken down by partial wheel widths. Minimum, maximum, and 10 percent intervals are shown. The dashed lines are brake horsepower (Bhp) curves and are also labeled by percentage wheel width.
Example Selection: 1,700 cfm @ 2.0 inches Ps wg.
To make a selection, start by finding a size and RPM that will attain the design static pressure (Ps). Next, scan for fan sizes and RPMs that meet the CFM requirement at the design pressure. The intersection point of the static pressure and CFM needs to be between the minimum and maximum percent wheel width for each fan.
To determine the partial wheel width and brake horsepower, start at 2.0 inches Ps and move across the graph until intersecting the next percent wheel width beyond the required 1,700 cfm, point A. For this example, the next largest percent wheel width is 70. Draw a vertical line from point A that crosses the 70 percent Bhp curve. In this case, slide vertically downward from A to point B. From point B, read the Bhp on the right vertical axis of the chart. The Bhp for this point of operation is 0.9 Bhp. Note: If the operating point falls between two partial wheel
width curves, select the next larger wheel width at the same pressure. This will result in more CFM as compared to the original design requirements. Wheels are available in 5% partial width increments.
A
Minimum Percent Wheel Width
B
Maximum Percent Wheel Width
Sound data values are provided for both the inlet and outlet of the fan and are based on 100 percent wheel widths. Values shown in the tables are based on the design static pressure. If the design static pressure is not listed in the table, the sound power levels need to be interpolated from the values found on either side of the design static pressure. If the design static pressure exceeds the maximum pressure listed in the table, then the maximum values in the table should be used.
Example: 1,700 cfm @ 2.0 inches Ps wg. with 1770 fan RPM
Since 2.0 inches Ps exceeds the maximum static pressure in the table, the sound power levels for the maximum static pressure should be used. Sound power levels should be interpolated for pressures between those listed.
Inlet Sound Power, L
RPM Ps 1 2 3 4 5 6 7 8 L
1170
1770
0.00 71 79 75 72 75 70 59 50 78
0.40 70 75 72 70 73 65 55 46 75 0.40 80 78 71 73 76 66 56 45 78
0.60 69 74 70 69 72 62 53 45 74 0.60 79 77 69 71 76 64 54 44 77
0.80 69 73 68 66 71 59 50 44 72 0.80 82 76 68 70 75 60 51 43 76
0.00 76 77 85 83 82 81 77 63 87
0.90 75 75 84 80 79 78 71 61 84 0.90 83 80 80 82 82 78 71 59 86
1.40 75 75 82 78 78 76 69 60 83 1.40 84 79 78 80 81 76 68 58 84
1.83 76 74 78 75 76 73 65 59 80 1.83 87 79 78 78 78 73 64 57 81
[dB ref 10
Wi
-12 watts] Outlet Sound Power, L
[dB ref 10
A RPM Ps 1 2 3 4 5 6 7 8 LWoA
Wi
1170
1770
0.00 82 81 75 76 78 71 60 48 81
0.00 85 82 83 86 85 81 77 62 89
Wo
-12 watts]
2
®
Effect of Air Density - Temperature and Elevation
Ratings in the fan performance tables and curves of this catalog are based on standard air (clean, dry air with a density of .075 pounds per cubic foot, barometric pressure at sea level of 29.92 inches of mercury, temperature of 70°F). Selecting a fan to operate at conditions other than standard air requires an adjustment to both static pressure and brake horsepower.
A cubic foot of air has a constant volume regardless of temperature or elevation. However, air density changes with non-standard temperature or elevation. Therefore, when selecting a fan to operate at a non-standard air density using standard air density tables and curves, corrections must be made to parameters affected by air density. These parameters are static pressure and brake horsepower.
For example, a size 30-QEID mixed flow fan is to deliver 20,000 CFM at
5.0in. static pressure. Elevation is 3000 feet, temperature is 100°F.
The 5.0 in. static pressure refers to
Altitude, (Z) ft. -1000
Barometric
Pressure
( p
the static pressure at the operating air density, in this case at 3000 feet, 100°F. Intuitively, we realize that at higher than standard elevations and temperatures, air density will be lower than standard. Therefore, we must determine what static pressure at standard air density will equate to 5.0 in. static pressure at our
Temperature °F
operating density. Since standard air density is greater than operating air density in this case, we would expect the static pressure after applying the correction to be greater than the original operating static pressure.
The table gives air density correction factors for non-standard temperatures and elevations.
Adapted from AMCA Standard 99-09, section 0200, Charts and Tables, with written permission from Air Movement and Control Association International, Inc.
The example below shows the relationship of fan performance at sea level and at 3000 ft. elevation and 100°F.
EXAMPLE
The following example shows how to properly select the fan described above:
1. Since the air volume delivered by the fan is not affected by density, airflow remains 20,000 CFM.
2. Determine correction factor from chart for an elevation of 3000 feet and air temperature of 100°F. The correction factor is 0.848
3. Divide the specified operating static pressure by the correction factor to determine the standard air density equivalent static pressure (Corrected static pressure = 5.0 in. ÷ 0.848 = 5.9 in. Ps).
4. Refer to the fan performance table for a 30-QEID. At 20,000 CFM and 5.9 in. Ps: Fan RPM = 1770, Percent Wheel Width = 70, Actual Volume 20,800 CFM, Bhp = 31.
5. Since the horsepower selected refers to standard air density, this must be corrected to reflect actual Bhp at the lighter operating air. Operating Bhp = standard Bhp x 0.848, or 31 x
0.848 = 26.3 Bhp. 30 HP motor would meet requirements.
If a fan is selected to operate at high temperatures, the motor must be of sufficient horsepower to handle the increased load at any lower operating temperature where the air is more dense. Assume the air entering the 30 QEID fan at start-up is 0°F. For 0°F and 3000 feet elevation the air density correction factor is 1.033. Bhp at 0°F = 31 x 1.033 = 32, therefore, a 40 HP motor is required.
Dry Air Density Correction Factor (I-P)
Multiply Standard Air Density, 0.075 lbm / ft3 by the Factor to obtain Density at Condition p
Sea
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Level
in. Hg 31.02 29.92 28.85 27.82 26.82 25.84 24.89 23.98 23.09 22.22 21.39 20.58
in. wg 421.71 406.75 392.21 378.20 364.61 351.29 338.37 326.00 313.90 302.07 290.79 279.78
)
b
-40 1.309 1.262 1.217 1.174 1.131 1.090 1.050 1.012 0.974 0.937 0.902 0.868
0 1.195 1.152 1.111 1.071 1.033 0.995 0.959 0.924 0.889 0.856 0.824 0.793
40 1.099 1.060 1.022 0.986 0.950 0.915 0.882 0.850 0.818 0.787 0.758 0.729
70 1.037 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
100 0.981 0.946 0.913 0.880 0.848 0.817 0.787 0.759 0.730 0.703 0.677 0.651
150 0.901 0.869 0.838 0.808 0.779 0.750 0.723 0.696 0.670 0.645 0.621 0.598
200 0.832 0.803 0.774 0.747 0.720 0.693 0.668 0.644 0.620 0.596 0.574 0.552
250 0.774 0.746 0.720 0.694 0.669 0.645 0.621 0.598 0.576 0.554 0.534 0.513
300 0.723 0.697 0.672 0.648 0.625 0.602 0.580 0.559 0.538 0.518 0.498 0.480
350 0.678 0.654 0.631 0.608 0.586 0.565 0.544 0.524 0.505 0.486 0.468 0.450
(t)
400 0.639 0.616 0.594 0.573 0.552 0.532 0.513 0.494 0.475 0.458 0.440 0.424
450 0.604 0.582 0.561 0.541 0.522 0.503 0.484 0.467 0.449 0.432 0.416 0.401
500 0.572 0.552 0.532 0.513 0.495 0.477 0.459 0.442 0.426 0.410 0.395 0.380
550 0.544 0.525 0.506 0.488 0.470 0.453 0.436 0.420 0.405 0.390 0.375 0.361
600 0.518 0.500 0.482 0.465 0.448 0.432 0.416 0.401 0.386 0.371 0.357 0.344
700 0.474 0.457 0.440 0.425 0.409 0.394 0.380 0.366 0.352 0.339 0.327 0.314
800 0.436 0.420 0.405 0.391 0.377 0.363 0.350 0.337 0.324 0.312 0.301 0.289
900 0.404 0.390 0.376 0.362 0.349 0.336 0.324 0.312 0.301 0.289 0.278 0.268
1000 0.376 0.363 0.350 0.337 0.325 0.313 0.302 0.291 0.280 0.269 0.259 0.250
Standard Air 70°F, Sea Level
Corrected Air 100°F, Altitude of 3000 ft.
12
S
t
a
n
d
a
r
d
A
i
r
,
1
7
7
25
20
15
10
Static Pressure (Pa x 100)
5
0
0
10
Static Pressure (in. wg)
R
P
M
C
o
r
r
e
c
t
e
d
A
i
r
,
1
7
7
0
R
P
M
8
6
4
2
0
0 5 10 15 20 25 30
0 10 20 30 40 50
p
h
B
,
r
i
A
d
r
a
d
n
a
t
S
p
h
B
,
r
i
A
d
e
t
c
e
r
r
o
C
Volume (cfm x 1000)
Volume (m
5.0 in. wg
3
/hr x 1000)
26 Bhp
b
QEID-30
31 Bhp
5.9 in. wg
70º pitch
Density 0.075
RPM
36
30
24
18
12
6
0
Brake Horsepower
®
3
Motor Data
Greenheck QEID mixed flow fans can be supplied with any cast iron motor that is commercially available and is appropriate for the fan size and performance required. The tables show motor frame sizes corresponding to readily available 230/460 volt 3-phase 60 Hz motors. Consult factory (CF) for motor frame sizes on motors with larger horsepower, 50 Hz, or different voltages. See the listed maximum and minimum motor frame size for each fan size found on individual performance pages.
Notes:
1. Open Drip-Proof and Totally Enclosed motors have a 1.15 service factor.
2. Energy Efficient motors are in compliance with Energy Policy Act of 1992 (EPAct)
3. Premium Efficient motors meet NEMA Premium and CEE efficiency levels
690 RPM MOTORS
All 690 RPM motors are build-ups. Consult factory for motor frame sizes.
1170 RPM MOTORS
Single Speed
HP
3/4 143T 143T CF 143T 143T
1 145T 145T 145T 145T 145T
1 1/2 182T 182T 182T 182T 182T
2 184T 184T 184T 184T 184T
3 213T 213T 213T 213T 213T
5 215T 215T 215T 215T 215T
7 1/2 254T 254T 254T 254T 254T
10 256T 256T 256T 256T 256T
15 284T 284T 284T 284T 284T
20 286T 286T 286T 286T 286T
25 324T 324T 324T 324T 324T
30 326T 326T 326T 326T 326T
40 364T 364T 364T 364T 364T
50 365T 365T 365T 365T 365T
60 404T 404T 404T 404T 404T
75 405T 405T 405T 405T 405T
100 444T 444T 444T 444T 444T
125 445T 445T 445T 445T 445T
Standard
Efficient
Open TE Open TE
Explosion
Resistant
Premium
Efficient
870 RPM MOTORS
Single Speed
HP
5 254T 254T CF 254T 254T
7 1/2 256T 256T CF 256T 256T
10 284T 284T CF 284T 284T
15 286T 286T CF 286T 286T
20 324T 324T CF 324T 324T
25 326T 326T CF 326T 326T
30 364T 364T CF 364T 364T
40 365T 365T CF 365T 365T
50 404T 404T CF 404T 404T
60 405T 405T CF 405T 405T
75 444T 444T CF 444T 444T
100 445T 445T CF 445T 445T
Standard
Efficient
Open TE Open TE
Explosion
Resistant
Energy
Efficient
1770 RPM MOTORS
Single Speed
HP
1 143T 143T CF 143T 143T
1 1/2 145T 145T 145T 145T 145T
2 145T 145T 145T 145T 145T
3 182T 182T 182T 182T 182T
5 184T 184T 184T 184T 184T
7 1/2 213T 213T 213T 213T 213T
10 215T 215T 215T 215T 215T
15 254T 254T 254T 254T 254T
20 256T 256T 256T 256T 256T
25 284T 284T 284T 284T 284T
30 286T 286T 286T 286T 286T
40 324T 324T 324T 324T 324T
50 326T 326T 326T 326T 326T
60 364T 364T 364T 364T 364T
75 365T 365T 365T 365T 365
Standard
Efficient
Open TE Open TE
Explosion
Resistant
Premium
Efficient
4
®
QEID-12
Wheel Diameter 15.00 in. Outlet Area 1.56 ft
2
Minimum Frame Size 143T Maximum Frame Size 184T
Inlet Sound Power, L
RPM Ps 1 2 3 4 5 6 7 8 L
0.00 70 71 74 75 73 73 71 57 79
0.60 71 69 72 71 71 71 65 55 76 0.60 79 73 75 73 76 73 66 55 79
1770
1.00 71 69 72 69 69 69 64 55 75 1.00 82 71 74 70 73 70 65 55 77
1.30 83 74 74 70 69 68 63 55 74 1.30 98 85 78 75 75 70 65 56 80
0.00 89 78 83 87 88 87 84 85 93
2.50 80 78 82 87 86 86 82 79 91 2.50 92 88 86 89 88 89 86 80 94
3500
4.00 82 80 80 84 85 85 81 79 90 4.00 97 90 87 91 88 90 87 80 95
5.00 86 84 84 89 87 86 82 77 92 5.00 98 94 90 91 87 89 84 78 94
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10 outlet L effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301.
, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
Wo
®
[dB ref 10
Wi
-12
watts] Outlet Sound Power, L
A RPM Ps 1 2 3 4 5 6 7 8 LWoA
Wi
-12
watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
0.00 81 76 79 77 78 75 71 57 82
1770
0.00 97 87 89 91 89 89 86 85 95
3500
[dB ref 10
Wo
-12
watts]
5
5
QEID-15
Wheel Diameter 18.25 in. Outlet Area 2.32 ft
2
Minimum Frame Size 143T Maximum Frame Size 145T
Inlet Sound Power, L
RPM Ps 1 2 3 4 5 6 7 8 L
1170
1770
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10 outlet L effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301.
0.00 71 79 75 72 75 70 59 50 78
0.40 70 75 72 70 73 65 55 46 75 0.40 80 78 71 73 76 66 56 45 78
0.60 69 74 70 69 72 62 53 45 74 0.60 79 77 69 71 76 64 54 44 77
0.80 69 73 68 66 71 59 50 44 72 0.80 82 76 68 70 75 60 51 43 76
0.00 76 77 85 83 82 81 77 63 87
0.90 75 75 84 80 79 78 71 61 84 0.90 83 80 80 82 82 78 71 59 86
1.40 75 75 82 78 78 76 69 60 83 1.40 84 79 78 80 81 76 68 58 84
1.83 76 74 78 75 76 73 65 59 80 1.83 87 79 78 78 78 73 64 57 81
, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
Wo
[dB ref 10
Wi
6
-12
watts] Outlet Sound Power, L
A RPM Ps 1 2 3 4 5 6 7 8 LWoA
Wi
1170
1770
-12
watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
0.00 82 81 75 76 78 71 60 48 81
0.00 85 82 83 86 85 81 77 62 89
[dB ref 10
Wo
®
-12
watts]
Loading...
+ 14 hidden pages