Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
DOAS v3.001
Introduction
Program Features
The microprocessor controller offers control through
easy monitoring and adjustment of unit parameters by
way of a lighted graphical display and an integral pushbutton keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer
multiple control sequences to provide tempered air.
Factory default settings allow for easy setup and
commissioning. The sequence parameters are fully
adjustable. Refer to the Sequence of Operation for
details.
BMS Communication
The user can remotely adjust setpoints, view unit status
points and alarms. The microprocessor controller is
capable of communicating over several protocols:
• BACnet® MSTP • Modbus RTU
• BACnet® IP • Modbus TCP
• LonWorks®
Reference Points List for a complete list of BMS points.
Internal Time Clock (Schedule)
The controller has an internal programmable time clock,
allowing the user to set occupancy schedules for each
day of the week. The controller option also has morning
warm-up and cool down capability for improved
comfort at the time of occupancy.
Alarm Management
The microprocessor controller will monitor the unit’s
status for alarm conditions. Upon detecting an alarm,
the controller will record the alarm description, time,
DOAS Technical Support
Call 1-866-478-2574
date, and input/output status points for user review. A
digital output is reserved for remote alarm indication.
Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of
determining occupancy: a digital input, the internal time
clock or the BMS. If in the unoccupied mode, the unit
will either be shut down, continue normal operation
utilizing adjustable unoccupied setpoints, recirculate
with unoccupied setpoints or will cycle on to maintain
adjustable unoccupied room temperature and humidity
setpoints (room temperature and humidity sensor is
optional).
Remote Display Panel (if equipped)
A touch pad display panel allows for remote monitoring
and adjustment of parameters, allowing ease of control
access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury or
equipment damage. Service must be performed only
by personnel that are knowledgeable in the operation
of the equipment being controlled.
WARNING
Mechanical high static protection cutoffs must
be installed by others to protect the system and
equipment from over-pressurization when using
factory provided control sensors. The manufacturer
does not assume responsibility for this.
The microprocessor controller can be configured for
air handler, energy recovery, and dedicated outdoor air
systems. Each application utilizes similar technologies
for heating and cooling: chilled water, hot water, indirect
gas, electric heat, packaged DX cooling, and packaged
DX cooling with digital and inverter scrolls. All setpoints,
lockouts and delays are user adjustable via the integral
keypad display, remote display, or web user interface.
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation.
The unit can then be commanded on or off by this
digital input, keypad, the BMS or internal time clock.
When a start command becomes active the following
steps occur:
• Energy recovery wheel starts, if equipped
• Factory mounted and wired dampers are powered
(Outdoor air, exhaust air, and recirculation air
dampers, if equipped)
• Exhaust fan, if equipped, starts after adjustable delay
• Supply fan starts after adjustable delay
• Tempering operation starts after adjustable delay
UNIT STOP COMMAND: A shutdown occurs when
there is not an occupied or unoccupied start command.
The following shutdown methods can occur.
Hard shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the
supply temperature is less than the soft shutdown
enable setpoint.
• Occupancy is commanded to unoccupied while there
is no unoccupied start command, and the supply
temperature is less than the soft shutdown enable
setpoint.
When a hard shutdown occurs:
• The unit shuts down immediately.
• Dampers spring-return to their off position.
Soft shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the
supply temperature is greater than or equal to the
soft shutdown enable setpoint.
• There is no unoccupied or occupied start command
and the supply temperature is greater than or equal
to the soft shutdown enable setpoint.
The following occurs during a soft shutdown:
• Tempering outputs immediately revert back to their
off value; while
• Dampers remain open and fans continue to run; until
– The supply air temperature falls below the soft
shutdown enable setpoint minus 5.0°F; or
– The soft shutdown delay timer has expired.
UNIT/SYSTEM DISABLED COMMAND:
The unit becomes disabled due to the following:
• The unit was disabled from the controller’s Unit
Enable screen.
• The unit was disabled from the BMS.
• The shutdown input is in the shutdown position.
• A shutdown alarm was activated.
When disabled the following actions occur:
• The unit shuts down immediately; and
• Dampers spring-return to their off position.
OCCUPIED/UNOCCUPIED MODES: The
microprocessor controller offers three modes of
determining occupancy: digital input, the internal time
clock or the BMS. When in the unoccupied mode, the
unit can be configured to shut down, or cycle on to
maintain the unoccupied room setpoints. The unit can
be temporarily overridden to the occupied mode via
a digital input, keypad display, or room thermostat, if
equipped.
The controller can be configured with morning warmup and cool down to bring the space to the occupied
setpoint prior to occupancy.
• Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to
Energy Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
• Unoccupied Mode (Unit Off): Unit remains off when
in unoccupied mode.
• Normal Operation with Unoccupied Setpoints:
Optional unoccupied mode will operate as if in
occupied mode but will utilize adjustable unoccupied
setpoints.
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to Energy
Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
• Recirculation with Unoccupied Setpoints: Optional
unoccupied mode when there is an unoccupied
recirculation damper. The unit will continue to run,
but in full recirculation.
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
®
Microprocessor Controller for DOAS3
Sequence of Operation
• Unoccupied Mode (Cycle on Room): Optional
unoccupied mode when there is an unoccupied
recirculation damper and room temperature and/
or humidity sensor(s) connected to the controller.
The unit will cycle on to maintain unoccupied room
setpoints if there is a call for unoccupied heating,
cooling or dehumidification.
- Exhaust fan off, if equipped
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
Setpoint Control (Occupied)
Supply air temperature setpoint can be configured
as constant, or can be reset by either outside air
temperature, or room temperature setpoint. If equipped
with BMS communications, the user can also directly
command the supply temperature setpoint, or room
temperature setpoint, if equipped.
• Outdoor Air Temperature Reset Function: The
controller will default to supply temperature reset
based on outdoor air temperature. The controller will
monitor the OA temperature and reset the supply
temperature setpoint based upon the outdoor air
reset function.
• Room Temperature Reset (optional): With a
room temperature sensor, the controller will adjust
the supply air temperature setpoint between
the minimum (55°F) and maximum (90°F), to
satisfy the desired room temperature. Room
temperature setpoint can be adjusted locally at
the microprocessor by BMS or room thermostat, if
equipped.
Setpoint Control (Unoccupied)
When equipped with an unoccupied recirculation
damper and optional room temperature and/or
humidity sensors, the unit will cycle on to maintain the
unoccupied room setpoints.
• Unoccupied Heating: If equipped with heating,
the unit is enabled when the room temperature is
less than the unoccupied heating setpoint minus
differential (60°F). The supply air temperature setpoint
will be set to the supply maximum reset limit (90°F).
The unit cycles off when the room temperature
reaches the unoccupied heating setpoint.
• Unoccupied Cooling: If equipped with cooling, the
unit is enabled when the room temperature is greater
than the unoccupied cooling setpoint plus differential
(80°F+5°F). The supply air temperature setpoint will
be set to the supply minimum reset limit (55°F). The
unit cycles off when the room temperature reaches
the unoccupied cooling setpoint.
• Unoccupied Dehumidification: If equipped with
cooling, the unit is enabled when the room relative
humidity exceeds the unoccupied room relative
humidity setpoint plus differential (50%+5%). The
supply air temperature setpoint will be set to the
equivalent occupied supply setpoint.
• Morning Warm-Up/Cool Down: The unit uses
adjustable preset time to temper the space to
occupied setpoint prior to occupancy (room
temperature sensor is optional).
Heating
The heating is controlled to maintain the supply
temperature setpoint. The heating will be locked out
when the outside air temperature is above the heating
lockout (80°F adj).
• Indirect Gas Furnace: Microprocessor controller
will modulate the indirect gas furnace to maintain the
supply temperature setpoint.
• Hot Water Coil: Microprocessor controller will
modulate a hot water valve (provided by others) to
maintain the supply temperature setpoint. Coil freeze
protection must be provided by others in the field!
• Electric Heater: Microprocessor controller will
modulate an electric heater to maintain the supply
temperature setpoint.
Cooling
The cooling is controlled to maintain the supply
temperature setpoint. The mechanical cooling will be
locked out when the outside air temperature is below
the cooling lockout (55°F).
• Chilled Water: Microprocessor controller will
modulate a chilled water valve (provided by others) to
maintain supply air setpoint. Coil freeze protection
must be provided by others in the field!
• Packaged/Split DX Cooling (Standard Scroll):
Microprocessor controller will enable stages of
cooling to maintain the supply air setpoint.
• Packaged DX Cooling (Digital Scroll):
Microprocessor controller will modulate the digital
scroll to maintain the supply air temperature setpoint.
• Packaged DX Cooling (Inverter Scroll):
Microprocessor controller will modulate the inverter
scroll to maintain the supply air temperature setpoint.
Microprocessor Controller for DOAS4
®
Sequence of Operation
Economizer
If the application requires cooling, and the outdoor
air conditions are suitable for free cooling, the
controller may enter the economizer state. If the unit is
economizing and the discharge temperature setpoint is
not being met, the controller may bring on mechanical
cooling. If equipped with a modulating outdoor air and
recirculated air damper, the dampers will modulate
between the minimum OA and maximum positions to
maintain the supply temperature setpoint. If equipped
with an energy wheel, Reference Energy Recovery
Wheel Sequence.
• Temperature: The economizer will be locked out
when:
- The outside air is greater than the economizer
high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
• Temperature/Enthalpy: The economizer will be
locked out when:
- The outside air is greater than the economizer
high lockout (65°F dry-bulb).
- The outside air is greater than the economizer
high enthalpy lockout (23 btu/lb).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil
setpoint. The dehumidification sequence will be locked
out when the OA is less than the dehumidification
lockout (10°F) above the cold coil setpoint. If equipped
with BMS communications, the user can also directly
set the cold coil leaving air setpoint.
• Optional Room Relative Humidity Sensor or Thermostat: The controller will adjust the cold
coil leaving air temperature setpoint between the
minimum (50°F) and maximum (55°F) setpoint to
satisfy the desired room relative humidity setpoint.
Reheat
While the unit is in dehumidification mode, the supply
air can be reheated via Primary Heating Source, On/Off
Hot Gas Reheat or Modulating Hot Gas Reheat.
• Modulating Hot Gas Reheat (valve): The
microprocessor controller will modulate the hot gas
reheat valve to maintain the supply temperature
setpoint.
• Reheat Plus: The primary heat source configured to
act as secondary reheat.
Supply Fan VFD Sequence
The factory installed VFD is wired to the controller.
Supply fan speed needs to be set during test
and balance of the unit. If equipped with BMS
communications, the user can also directly command
the supply fan speed.
• Optional Space/Duct CO
Sensor: The controller
2
will modulate the supply fan based upon a
comparison of the CO2 setpoint to the actual CO2
levels reported from the sensor.
• Optional Duct Static Pressure Sensor: The
controller will modulate the supply fan based upon
a comparison of the duct static pressure setpoint to
the actual duct static pressure level reported from the
sensor.
• Optional Building Static Pressure Sensor: The
controller will modulate the supply fan based upon a
comparison of the building static pressure setpoint to
the actual building static pressure level reported from
the sensor.
• Optional Single Zone VAV (SZ): The controller will
control the supply air temperature and supply fan
speed to maintain the room temperature setpoint.
This sequence requires a room temperature sensor.
Heating - When the room requires heating,
the controller will reset the supply air temperature
setpoint up to the maximum (90°F) while increasing
the supply fan speed up to its maximum heating
speed.
Cooling - When the room requires cooling, the
controller will first reset the supply air temperature
setpoint down to the minimum (55°F) while the
supply fan remains at the minimum cooling speed.
After a time delay, the supply fan speed will increase
up to its maximum cooling speed to maintain the
room temperature setpoint.
Exhaust Fan VFD Sequence
The factory installed VFD is wired to the controller.
Exhaust fan speed needs to be set during test
and balance of the unit. If equipped with BMS
communications, the user can also directly command
the exhaust fan speed.
• Optional Building Static Pressure Sensor: The
controller will modulate the exhaust fan based upon a
comparison of the building static pressure setpoint to
the actual building static pressure level reported from
the sensor.
• Optional Supply Fan Tracking: The controller will
proportionally modulate the exhaust fan based upon
the supply fan speed.
• Optional Outdoor Air Damper Tracking: The
controller will proportionally modulate the exhaust fan
based upon the outdoor air damper position.
®
Microprocessor Controller for DOAS5
Sequence of Operation
Outdoor Air and Recirculated (Recirc) Air
Damper Control
If equipped with a modulating outdoor air and
recirculated air damper, the recirculated air damper will
operate inverse of the outdoor air damper. The outdoor
air damper will open to a Minimum Outdoor Air Position
(Min OA) when in occupied mode. If the controller
is configured to modulate the supply fan speed, the
minimum and maximum OA positions can be reset
based on supply fan speed. If equipped with BMS
communications, the user can also directly reset the
damper position up to the maximum OA position.
• Optional Space CO
proportionally modulate the OA/RA dampers based
upon a comparison of the CO
CO2 level reported from the sensor. As the CO2 level
rises, the controller will proportionally modulate the
outdoor air damper open, between the minimum OA
damper position and maximum CO
• Optional Building Pressure: The OA/RA dampers
will modulate based upon the signal from a building
static pressure sensor. The controller will modulate
the dampers, between the minimum and maximum
OA positions, based upon a comparison of the
building static pressure setpoint to the actual building
static pressure level reported from the sensor.
Sensor: The controller will
2
setpoint to the actual
2
position.
2
Energy Recovery Wheel Sequences
Economizer (optional): If the unit is equipped with an
energy recovery wheel, the economizer will modulate/
stop the energy wheel to achieve free cooling. Jog
wheel control is available during stop wheel economizer
operation. This sequence allows the wheel to rotate for
a short period of time exposing a new section to the air
stream.
• Stop Wheel: When economizer mode is enabled
and there is a signal for cooling, the wheel will stop
rotating to allow free cooling.
• Modulate Wheel: When economizer mode is
enabled and there is a signal for cooling, the
controller modulates wheel speed to maintain the
supply temperature setpoint.
• Energy Wheel Bypass Dampers, if equipped:
During normal operation, the dampers shall remain
closed to allow full operation of the energy wheel.
During economizer sequences, the dampers will be
open to bypass the energy wheel.
Frost Control (optional): The microprocessor
controller will activate the frost control method when
the outdoor air temperature is less than the defrost
setpoint (5°F) and the wheel pressure switch is closed
due to a high wheel pressure drop. Once the pressure
drop decreases below the pressure switch point or the
outdoor air temperature increases, the unit will resume
normal operation.
• Electric Preheater: When frosting is occurring, the
preheater is energized to defrost the wheel.
• Modulate Wheel: When frosting is occurring, the
wheel slows to allow defrosting to occur.
• Cycle Wheel: When frosting is occurring, the
energy wheel is cycled off for a defrost cycle time
(5 minutes). After the defrost cycle time, the wheel
is re-energized to continue normal operation. The
controller will not allow another defrost cycle for a
minimum normal operating cycle time (30 minutes).
• Timed Exhaust: When frosting is occurring, the
supply fan is cycled off along with the tempering for
a defrost cycle time (5 minutes). The exhaust fan
will continue to run allowing the warm exhaust air
to defrost the wheel. After the defrost cycle time,
the supply fan and tempering are re-energized to
continue normal operation. The controller will not
allow another defrost cycle for a minimum normal
operating cycle time (30 minutes).
Microprocessor Controller for DOAS6
®
Sequence of Operation
Alarms
The microprocessor controller includes a digital output
for remote indication of an alarm condition, which
connects via the J15 port. Possible alarms include:
• Dirty Filter Alarm: If the outside air or return air
filter differential pressure rises above the differential
pressure switch setpoint, the microprocessor
controller will activate an alarm.
• Supply and Exhaust Air Proving Alarm:
Microprocessor controller monitors proving switch on
each blower and displays an alarm in case of blower
failure.
• Sensor Alarm: Microprocessor controller will send
an alarm if a failed sensor is detected (temperature,
pressure, relative humidity).
• Supply Air Low Limit: If the supply air temperature
drops below the supply air low limit (35°F), the
microprocessor controller will de-energize the unit
and activate the alarm output after a preset time
delay (300s).
• Other Alarms: Wheel Rotation, High Wheel
Pressure, High/Low Refrigerant Pressure.
®
Microprocessor Controller for DOAS7
Large Controller Overview
24VAC to Controller
Room RH
CO2 Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Outdoor Air Damper Analog Output
Heating Analog Output
Cooling/VSC Cond Fan Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure Limit
Wheel Rotation Alarm
Unit On/Off Input
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter Input
Outdoor Relative Humidity Sensor
Building Pressure Sensor
Duct Pressure Sensor
Compressor Limit Circuit A
Compressor Limit Circuit B
Compressor Limit Circuit C
Compressor Limit Circuit D
Supply Fan VFD Output
Exhaust Fan VFD Output
Room Temperature Sensor
Discharge Pressure Circuit B (VSC)
2 Speed Fan Input
2 Position Damper Input
G
G0
+Vter m
GND
+5 V
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
J1
J10
J11 pLAN
J24J2J3
REF
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
J12
C1
NO1
J25
J4J5J7
BMS2
J26
drac SMBdrac suBdleiF
ID15H
ID15
J19
IDC15
ID16
J6
ID16H
Y5
Y6
U9
J20
GND
U10
GND
ID17
ID18
IDC17
FBus2
4321
NO14
J21
NC14
NO15
NC15
NO16
J22
NO17
NO18
J23 FBus2
NO2
NO3
C1
C4
J13
NO4
NO5
NO6
C4
C7
J14
NO7
C7
C14
NO8
J15
C8
NC8
C15
J16
C9
NO9
C16
NO10
NO11
C9
C16
NO12
J17
C12
NC12
NO13
J18
C13
NC13
24 VAC When Unit On
Wheel Frost Mode
Supply Fan Enable
Exhaust Fan Enable
24 VAC from Supply Fan Proving
Heating Enable
Staged Compressor 1
Staged Compressor 2
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Staged Compressor 3
Staged Compressor 4
Energy Recovery Wheel Enable
Inverter Compressor E-Stop (VSC)
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Compressor Fan 1 Enable (VSC)
Compressor Fan 2 Enable (VSC)
Optional LonWorks cards are
located in BMS Card port.
Microprocessor Controller for DOAS8
Optional Modbus RTU/BACnet MSTP connections
are made to the J26 FBus2 terminal.
®
Medium Controller Overview
24VAC to Controller
Refrigerant Pressure Circuit A
Refrigerant Pressure Circuit B
Supply Discharge Air Temperature
Sensor B1, B2, B3 Commons
After Cold Coil Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Cooling Analog Output
Condenser Fan Circuit A or Heating Analog Output
Hot Gas Reheat Analog Output
Condenser Fan Circuit B or Heating Analog Output
Supply Fan Proving
High Pressure Switch Circuit A
Low Pressure Switch Circuit A
Occupied/Unoccupied Input
OA/RA Damper End Switch
Unit On/Off Input
High Pressure Switch Circuit B
Low Pressure Switch Circuit B
Outdoor Relative Humidity Sensor
Outdoor Air Damper Output
Supply Fan VFD Output
Exhaust Fan Proving
Dirty Filter Input
Wheel Rotation Alarm
Freeze Stat Input
Condensate Drain Pan Switch
Remote Start Input
G
G0
+Vterm
GND
+5 V
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
J1
J10
J11 pLAN
J24J2J3
REF
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
J12
C1
NO1
J25
J4J5J7
drac SMBdrac suBdleiF
ID15H
ID15
J19
IDC15
ID16
J6
ID16H
Y5
Y6
U9
J20
GND
U10
GND
ID17
ID18
IDC17
BMS2
J26
FBus2
NO14
J21
NC14
NO15
NC15
NO16
J22
NO17
NO18
J23 FBus2
NO2
NO3
C1
C4
J13
NO4
NO5
NO6
J14
J16
J17
J15
J18
C4
C7
NO7
C7
NO8
C8
NC8
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
4321
C14
C15
C16
C16
24 VAC When Unit On
Stagged Compressor 1
Stagged Compressor 2
Stagged Compressor 3
24 VAC from Supply Fan Proving
Stagged Compressor 4
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Condenser Fan VFD Start
Condenser Fan Stage 2 Start
Condenser Fan Stage 3 Start
Inverter Compressor E-Stop (VSC)
Optional LonWorks cards are
located in BMS Card port.
®
Optional Modbus RTU/BACnet MSTP connections
are made to the J26 FBus2 terminal.
Microprocessor Controller for DOAS9
c.pCOe - Expansion Board Overview, Medium Controller Arrangement
24 VAC Power
Heating Output
Exhaust Fan VFD Output
Energy Recovery Output
Space Temperature
Mixed Air Temperature
Exhaust Air Temperature
Space Static Pressure
Supply Air Duct Static Pressure
Space Setpoint Adjustment
AddressExt.ProtBaud
OFF
ON
8
38.4 K
57.6 K
CAREL
Modbus
9.6 K
Address Ext Baud Prot
1234567
9101112131415
19.2 K
Wheel Enable
Furnace Heating Stage 1
Furnace Heating Stage 2
Preheater Enable
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from
medium board controller.
Microprocessor Controller for DOAS10
®
pCOe - 4:1 Furnace Overview
High Speed Pressure Switch
24 VAC to Controller
Main Gas Valve
Ignition Controller Alarm
Low Speed Pressure Switch
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
Ignition Controller
24 VAC
High Speed Fan
24 VAC
Modbus Address Switches
pCOe - High Turndown Furnace
24 VAC to Controller
Main Gas Valve - Small Manifold
Main Gas Valve - Large Manifold
Ignition Controller Alarm
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
Low Speed Pressure Switch
Modbus Address Switches
High Speed Pressure Switch
Ignition Controller - Small Manifold
24 VAC
High Speed Fan
24 VAC
Ignition Controller - Large Manifold
24 VAC
®
Microprocessor Controller for DOAS11
Display Use
The microprocessor controller is located in the unit control center. The face of the controller has six buttons,
allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre-programmed
with easy to use menus. A remote display is also available, which connects via the J10 port. A six wire patch cable
is needed.
Keypad Description
ButtonDescriptionFunctions
Main MenuPress to go directly to the Main Menu from any screen.
From the Main Menu, navigate to the following screens:
• Unit Enable
• Unit Status
• Ctrl Variables
• Alarm Menu
AlarmThe Alarm button flashes when there is an active alarm.
Press to view active alarms.
Press twice to go to the alarms reset screen.
EscapePress from the Main Menu to view the Unit Status screen.
Press to go back one menu level.
Press when editing a variable to cancel editing.
UpPress to navigate through the menus/screens.
Press after entering a variable to increase a current value.
EnterPress to enter a highlighted menu or screen item.
Press to enter a writable variable and press again to confirm the new variable value.
DownPress to navigate menus/screens.
Press after entering a variable to decrease the current value.
Virtual keypad/display on web interface only.
These two buttons on the virtual keypad/display are used to simulate two-button actions on the handheld
keypad/display.
To simulate pressing two buttons simultaneously:
1. Click on 2-Button Click.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
To simulate pressing and holding two buttons simultaneously:
1. Click on 2-Button Hold.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
Supply air low limit
Alarm when supply is
below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be
blinking. Press the button to move the cursor down for parameter adjustment.
Once the cursor has reached the desired parameter, press the
adjust the value.
buttons to
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Microprocessor Controller for DOAS12
When satisfied with the adjustment, press the button to save the parameter.
When finished, make certain the cursor is in the upper left corner. If the cursor is
not in the upper left corner, the changes will not be saved. The cursor must be in
the upper left corner to enable screen advancement.
®
Web User Interface
The Web User Interface allows access to the unit controller through the building network. Reference Cntrl Variables/
Advanced/Network Settings to set the IP network protocol. Once proper communication is established, the user
can click on the follow tabs:
Overview – Includes a functioning unit graphic, monitoring points, and active setpoint adjustment.
Alarm – Shows current and cleared alarms.
Unit Display – Mimics the unit controller display. Allows the user full access to the controller without physically
being at the unit.
Trending – User can view past and present controller points.
Information – Provides manufacturer support information as well as IOM resources.
Service – User must be logged with service access criteria (9998). Once proper login is established, the user can
view configured input/output points associated with the unit controller
®
Microprocessor Controller for DOAS13
Main Menu Navigation
UnitEnable
Main StatusCtrl VariablesAlarm Menu
Unit Status
Input Output Status
Note:
Additional status screens
are displayed depending
on unit configuration.
Screens may include, but
are not limited to:
Occupancy
Damper positions
Fan status
Airflow
Setpoints
Economizer
Energy recover y
Cooling
Circuit pressure
Heating
Dehumidification
Static pressure
Temp Control
Dehumidification
Refrigeration Compressor Control
Pressure Control
Damper Control
Energy Recovery
Fan Control Supply Fan Control
Exhaust Fan Control
Occupancy
Advanced
Note:
The Advanced
menu is readonly. The service
password is
required to change
these settings.
Reference the
Advanced menu
section for more
information.
*Consult
factory for more
information.
Login
Manual Overrides
Adv. Setpoints*
Network Settings
Backup/Restore
IO Status/Offset*
IO Config
Unit Config
Unit Settings*
Active Alarms
Reset Alarms
Alarm History
Clear History
Export History
Service Info*
Alarm
Management
Shutdown
Alarms
General
Alarms
Microprocessor Controller for DOAS14
®
Unit Status Overview
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the
Supply air fan status.
Rotation indicates airflow; static blades indicate no airflow.
Cooling
Heating
• Shutdown Alarm
• Fans Only
• Economizing
• Cooling
• Dehumidifying
• Heating
• HGRH Purging
• Defrost Active
• Overrides Active
• Expansion Offline
buttons.
Dehumidifying
Economizing
Defrost
INPUT OUTPUT STATUS
Displays real time conditions from sensors located in the unit and building space
if equipped with space mounted sensors. Controller output conditions can also
be viewed from this screen. To view the desired input/output point, the user must
select the desired channel. Reference the Controller Overview section in this IOM
for individual point locations.
OCCUPANCY STATU S
Displays current status of occupancy and the configured occupancy control
method and time zone.
DAMPER COMMANDED POS
This screen appears if equipped with modulating outdoor air and recirculated air
dampers. Displays current position of the outdoor air damper. Recirculating air
damper position is the inverse of outside damper position.
®
SUPPLY FAN STATUS
This screen displays the fan enable command, fan proving status, and the supply
fan ramp being sent from the controller to the VFD. The minimum and maximum
speeds are set in the VFD (Reference unit Installation and Operation Manual for
VFD programming). The controller can modulate the fan between the min and
max speeds via an analog output.
Microprocessor Controller for DOAS15
Unit Status Overview
EXHAUST FAN STATU S
This screen displays the fan enable command, fan proving status, and the
exhaust fan ramp being sent from the controller to the VFD. The minimum and
maximum speeds are set in the VFD (Reference unit Installation and Operation
Manual for VFD programming). The controller can modulate the fan between the
min and max speeds via an analog output.
AIRFLOW STATUS
This screen displays the current status of airflow volumes if the unit is provided
with airflow monitoring.
AMBIENT LOCKOUT STATUS
Displays heating and cooling lockout status based on the outside air ambient
temperature. Ambient lockouts for heating and cooling can be altered by entering
Main Menu/Ctrl Variables/Temp Control/Cooling or Heating.
OUTSIDE RESET
This screen will be active if the controller is configured for outside air reset. The
heating and cooling devices modulate to maintain the supply air temperature
setpoint as determined by the outside reset calculation.
ACTIVE RESET
This screen will be active if temperature control mode is set for space or return air
reset. The supply temperature setpoint is calculated based on the active setpoint
and the current space or return temperature. The calculated setpoint is scaled
between the supply temperature minimum and maximum setpoints determined by
the current mode of operation.
SUPPLY SETPOINT
Displays current supply temperature and supply temperature setpoint to be
achieved.
ECONOMIZER RAMP
The economizer ramp screen will be active if the unit is configured for an
economizer control method. This screen displays the economizer setpoint, supply
air discharge temperature, economizer ramp status, and economizer control
mode of control. Economizer control mode options include, outside dry bulb,
outside enthalpy, comparative dry bulb, and comparative enthalpy.
CO2 RAMP OUTPUT
The CO2 Ramp Output screen will be active if the unit is configured for CO
2
control. This screen displays the CO2 setpoint, CO2 level from the space, and the
status of the control ramp.
ENERGY RECOVERY WHEEL STATUS
This screen provides overall status of the energy recovery wheel.
Microprocessor Controller for DOAS16
®
Unit Status Overview
DEFROST RAMP OUTPUT
This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided on the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will
go into defrost if the outside air temperature is below the defrost temperature
setpoint.
COOLING RAMP
This screen displays the active setpoint, supply discharge temperature, cooling
enable/disable, cooling ramp being sent from the controller, and the overall
capacity being demanded.
COMPRESSOR REQUEST
The compressor request screen will be active if the unit is equipped with DX
cooling. Screen displays overall status of individual compressor operation being
sent from the unit controller. Example: Circuit A compressor enable (On) with
modulating value of 26%.
HEATING RAMP
This screen displays the active setpoint, supply air temperature, heating enable/
disable, and heating ramp being sent from the controller.
DEHUMIDIFICATION
This screen will display the overall dehumidification status and selected mode of
dehumidification control.
The following dehumidification modes are available when the space is in occupied
mode:
• Cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
HGRH RAMP OUTPUT
This screen will display overall hot gas reheat status which includes active
setpoint, supply air discharge temperature, hot gas reheat enable/disable, and hot
gas reheat control loop being sent from the controller.
SUPPLY SPACE STATIC
This screen displays status points if the unit is configured for space static
pressure control. Status points include controller output ramp, static pressure
in the space, and the space static pressure setpoint. Similar status screen will
appear for the exhaust fan if the unit is configured for exhaust fan space static
control.
®
SUPPLY/RETURN DUCT STATIC
This screen displays status points if the unit is configured for duct static pressure
control. Status points include controller output ramp, static pressure in the duct,
and the duct static pressure setpoint. Similar status screen will appear for the
exhaust fan if the unit is configured for exhaust fan duct static control.
Microprocessor Controller for DOAS17
Menu
The controller is equipped with several menus to help guide users with altering program parameters. The following
menus can be accessed by pressing the
button. To enter the desired menu, press the button.
Unit Enable
Control Variables
Control Variables
Temp Control
The Unit Enable menu allows the user to enable and disable the unit through the
controller. Reference sequence of operation for additional unit starts/stop details.
The unit ships from the factory in a disabled state. To allow the unit to operate,
the controller must receive a run command from digital input ID4. Jumper unit
terminals R - G to allow the unit to operate.
Change to (Enabled/Disabled): Enables user to manually turn unit on/off via
display. Unit terminal G must have 24 VAC power to enable the unit.
The Controls Variables menu allows the user to view and adjust unit control
parameters.
The Temperature Control menu allows the user to view and adjust temperature
control conditions of the unit.
METHODFOR TEMPERATURE CONTROL
Possible Setpoint Sources:
Supply Temp Control – The supply discharge setpoint to be a constant value (e.g.
72°F). Reference Temperature Setpoint screen for setpoint adjustment.
Space Reset – The controller will reset the supply air temperature set point to
maintain the room temperature set point (requires room temp sensor). Reference
the Temperature Setpoint screen for room setpoint adjustment.
Return Reset – The controller will reset the supply air temperature set point to
maintain the return air temperature set point (requires duct mounted return air
temp sensor). Reference the Temperature Setpoint screen for return air setpoint
adjustment.
OA Reset – The controller monitors the outdoor air temperature and adjusts the
desired supply temperature set point accordingly. For example, when the outdoor
air is below 55°F, the controller will change the supply set point to 70°F. If the
outdoor air is above 65°F, the controller will change the supply set point to 55°F.
If the outdoor air temperature is between 55°F and 65°F, the supply set point
changes according to the outdoor air reset function. A visual representation of
the outdoor air reset function is shown below. Reference Outside Setpoints for
minimum and maximum outside air limits.
Microprocessor Controller for DOAS18
Outdoor Air Reset Function
75°
70°
65°
60°
55°
50°
Supply Air Set Point (°F)
45°
50°55°60°65°70°
Outside Air Temperature (°F)
®
Menu
OUTSIDE SETPOINTS
This screen only appears if outside reset is selected as the reset control mode.
TEMPERATURE SETPOINT
This screen only appears if supply temp control, space reset, or return reset is
selected as the reset control mode.
Possible Setpoint Sources:
Local – The room set point will be constant; set from screen (e.g. 72°F).
BMS – The BMS can directly control the room temperature set point (requires
BMS communication option).
T-Stat – The room set point will be adjustable from the room thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
HEAT COOL DEADBAND
This screen only appears if space reset or return air reset is selected as the reset
control mode. The heat cool deadband allows for separate cooling and heating
setpoints when the reset control mode is set for space reset or return air reset.
SUPPLY SETPOINTS
Cooling and heating supply setpoints screens only appear if outdoor reset,
space reset, or return air reset is selected. These screens allow the user to set
the minimum and maximum setpoint limits for cooling or heating operation.
The controller will adjust the supply temperature setpoint between the set limits
depending on mode of operation.
MODE SWITCH DISPLAY
This screen displays the delay time required before switching between heating
and cooling mode.
STAR TUP DISPLAY
This screen displays the delay time after the fans have started and tempering
begins
®
COOLING LOCKOUT
This screen displays the cooling lockout temperature. Cooling will be disabled
when outside air is below the cooling lockout temperature (55ºF).
Microprocessor Controller for DOAS19
Menu
HEATING LOCKOUT
This screen displays the heating lockout temperature. Heating will be disabled
when outside air is above the cooling lockout temperature (80ºF).
SPACE SETPOINTSDURINGTHE UNOCCUPIED MODE
The controller will have separate screens for unoccupied cooling and heating
setpoints. Reference Occupied control variables for further detail.
Unoccupied Cooling Example: If setpoint = 80ºF, unoccupied cooling is enabled
when room equals 80ºF and above. Unoccupied cooling is disabled when room
temperature is below 75ºF.
Unoccupied Heating Example: If setpoint = 60ºF, unoccupied heating is enabled
when room temperature equals 60ºF and below. Unoccupied heating is disabled
when room temperature is above 65ºF.
Control Variables
Dehumidification
The Dehumidification menu allows the user to view and adjust dehumidification
control parameters.
THISSCREENDISPLAYS METHODFOR DEHUMIDIFICATION.
Possible Methods:
• Outside Air Temp is greater than cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point
*Available during unoccupied mode.
There must be a constant call for dehumidification for the duration of the enable
delay for dehumidification mode to become enabled. The call remains active
until conditions are satisfied and dehumidification mode has been active for
the minimum active time. Reference Ctrl Variables/Advanced/Unit Config/Unit
Configuration Occupied Dehum Call for dehumidification method options.
If the unit is unoccupied while there is a dehumidification call, the unit will start
and dehumidify until the unoccupied dehumidification setpoints are satisfied.
The above dehumidification modes marked with an * indicate availability during
unoccupied mode. The unoccupied dehumidification mode can be set differently
than the occupied dehumidification mode. Reference Ctrl Variables/Advanced/
Unit Config/Unit Configuration Unoccupied Dehum Call for dehumidification
method options.
Microprocessor Controller for DOAS20
®
Menu
THISSCREENDISPLAYS HYSTERESISFOR ENABLING DEHUMIDIFICATIONDURING
O
CCUPIEDAND UNOCCUPIED CONDITIONS.
%RH for indoor RH control and ºF for indoor dew point control. Example: If indoor
RH setpoint = 50%, dehumidification is enabled when indoor RH equals 50% and
above. Dehumidification is disabled when indoor RH is below 44%.
THISSCREENALLOWS ADJUSTMENTFOR DELAYAND MINIMUM ON TIMEFOR
DEHUMIDIFICATION MODE.
Times are in place to prevent short cycling between dehumidification and other
control modes.
THISSCREENDISPLAYSTHE TEMPERATURE SETPOINTSFORTHE COOLING COIL.
This screen only appears if the unit is equipped with cooling.
When in dehumidification mode, the controller will maintain the active cold coil set
point. The active set point will be determined by the set point source.
Possible Set Point Sources:
Local – The supply set point will be constant; set from screen (e.g. 55°F).
BMS – The cold coil leaving air temperature set point can be adjusted over the
BMS via the dehumidification set point (Reference Points List).
The following priorities are used to determine what is more important in the unit:
temperature over dehumidification or heating over dehumidification. Both priority
selections determine when the unit is allowed to dehumidify.
1. Temperature over Dehumidification
Determines when the unit is allowed to dehumidify based on the space/return
air temperatures.
a. Temperature - If temperature is set as the priority and the space or return
air is over cooled, dehumidification is locked out until the space or return
temperature is no longer over cooled.
b. Dehumidification - If the priority is dehumidification and the space or return
air is over cooled, the coil offset will be added to the coil leaving setpoint.
(Default 0ºF offset).
c. Over Cooled - If space or return reset is enabled, the target is considered
over cooled when it is 4°F below setpoint for 5 minutes. It remains over cooled
until the target is at setpoint and over cooled has been active for a minimum of
5 minutes.
2. Heating over Dehumidification
Determines when the unit is allowed to dehumidify when heating is active.
a. Heating - If priority is set to heating, the unit locks out dehumidification while
heating is active.
b. Dehumidification - If priority is set to dehumidification, the unit is allowed to
switch to dehumidification when heating is active.
In dehumidification mode, the lead compressor will continue to run as long as
the dehumidification mode sequence has been enabled in order to prevent
compressor cycling and potential reevaporation of moisture. To disable this
operation and allow the compressor to cycle in dehumidification mode, uncheck
the applicable cooling ramps.
Microprocessor Controller for DOAS21
Menu
Control Variables
Refrigeration
Control Variables
Damper Control
The Refrigeration menu allows the user to view and adjust compressor and
condenser settings, if equipped.
REFRIGERATION MENU
Consult factory prior to adjusting parameters in Refrigeration Menu.
The Damper Control menu’s allows the user to adjust damper control setpoints.
Economizer setpoint adjust will also be found at this location if the unit is
equipped with outside air and recirculation dampers.
THISSCREENALLOWS ADJUSTMENTFOR DELAY TIME BETWEEN DAMPER OPENING
AND FAN OPERATION.
This timer allows the damper to open before the fan start sequence begins.
This prevents the fans from having to overcome higher static pressure when the
damper(s) are opening.
THISSCREENDISPLAYSTHE OUTDOOR AIR DAMPER SET POINTANDONLYAPPEARSIF
UNITISEQUIPPEDWITHAMODULATINGOUTDOORAIRANDRECIRCULATINGDAMPE R.
The set point is the proportional percentage of the outdoor air damper being
open.
0% = Full recirculation air
100% = Full outdoor air
Minimum Position – When in the occupied mode, the active set point will be
equal to a local minimum OA set point, which may be constant or reset by fan
speed if equipped with a modulating supply fan. The OA damper set point can
then be further adjusted between the minimum and maximum OA settings with
sequences such as DCV CO
, Building Pressure and Economizer.
2
Maximum Position – Each sequence that can adjust the OA damper set point
contains a maximum position to prevent excess OA. The active set point will be
determined based on the greatest demand of the configured sequences. For
example, if a unit is equipped with a DCV CO
and an economizer sequence, the
2
OA damper set point will react to an economizer demand even if the CO2 set point
is satisfied. Likewise, if economizer is not available but CO2 is above set point, the
OA damper will open to satisfy the CO
set point.
2
Economizer – The active set point will be reset based on Economizer demand,
between the minimum and maximum positions.
Possible Setpoint Sources:
Local – The minimum outdoor air percentage is constant; set by the controller.
SF Reset – The min and max positions are reset by the supply fan speed.
BMS – The BMS can directly control the OA damper position up to the max BMS
percentage.
Building Pressure – Damper position is reset by a building pressure control loop.
DCV CO
loop based on room CO
– Damper position is reset by a demand-controlled ventilation control
2
levels.
2
2 Position – Damper position is reset to “2-Pos/Max Econ:” set point when a
contact closure is made. The 2-position damper operation can also be setup to
bring the unit into temporary occupied mode until the contact is broken (Max
Ventilation Mode - enabled in manufacturer menu settings).
Microprocessor Controller for DOAS22
®
Menu
SCREENSDISPLAY ECONOMIZER CONTROL VARIABLES.
This screen only appears if economizer functionality was provided with a
modulating outdoor air damper.
The outside air damper will modulate between the minimum and maximum
position to maintain the supply temperature setpoint.
The user can select the economizer control method from the following options:
Outside Dry Bulb – Economizing is allowed when the outside dry bulb is less
than the economizer temperature enable setpoint.
Outside Enthalpy - Economizing is allowed when outside enthalpy is less than
the economizer enthalpy setpoint.
Comparative Dry Bulb - Economizing is allowed when outside temperature is
less than the space or return temperature.
Comparative Enthalpy - Economizing is allowed when outside enthalpy is less
than the space or return enthalpy.
There is a built-in hysteresis that disables economizer above the economizer
setpoint.
(Example: If Economizer Outside Dry Bulb = 65°F, economizer operation is
disabled above 67°F).
THISSCREENDISPLAYSTHE ENERGY REDUCTION ONLY CONTROL.
If enabled, the OA damper and recirculation damper will not modulate during
economize. Instead, only the energy recovery wheel will be stopped to ensure no
energy is transferred from the supply airstream and exhaust airstream.
®
Microprocessor Controller for DOAS23
Menu
Control Variables
Energy Recovery
The Energy Recovery menu allows the user to adjust energy recovery wheel
sequence setpoints.
THISSCREENDISPLAYSTHE TEMPERATUREATWHICHTHEUNITWILL ENABLE FROST
C
ONTROL MODEIFNECESSARY (FACTORY DEFAULT=5ºF)
This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided with the unit.
Upon sensing a high differential pressure across the energy wheel, the unit
will enter defrost mode if the outside air temperature is below this temperature
setting. Max Active Time and Min Off Time will be available if the frost control
method was provided as timed exhaust or cycle wheel.
THISSCREENDISPLAYSTHE ENERGY RECOVERY WHEEL JOG FUNCTION
This screen display the energy recovery wheel jog function.
This screen only appears if the unit has an energy recovery wheel and stop wheel
economizer method for control.
Momentarily enables the wheel in order to expose a new section to the airstream.
Microprocessor Controller for DOAS24
®
Menu
Control Variables
Fan Control
Supply Fan Control
The Supply Fan Control menu allows the user to adjust exhaust control
setpoints
THISSCREENDISPLAYSTHE SUPPLY FAN DELAY.
The supply fan delay will begin once the damper sequence is complete. This delay
can be used to offset starting times between the supply fan and exhaust fan.
THISSCREENDISPLAYS MINIMUMAND MAXIMUM SUPPLY FAN SPEED PERCENTAGES.
The speed set point is the proportional percentage of the analog output from the
controller to the VFD.
50% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication
option).
Duct Pressure – Fan speed is determined by duct pressure control loop.
Space Pressure – Fan speed is determined by building pressure control loop.
CO
– Fan speed is determined by CO2 control loop.
2
Single Zone VAV - The supply fan is modulated in addition to the supply air
temperature to satisfy the room temperature set point. A room temperature
sensor is required.
2-Speed (High Speed Set Point) - Supply fan speed is reset to maximum speed
when a contact closure is made. (Max Ventilation Mode).
• Tempering outputs immediately revert back to their off value; while
• Dampers remain open and fans continue to run; until
- The supply air temperature falls below the soft shutdown enable setpoint
minus 5.0ºF; or
- The soft shutdown delay timer has expired.
Microprocessor Controller for DOAS25
Menu
Control Variables
Fan Control
Exhaust Fan Control
The Exhaust Fan Control menu allows the user to adjust exhaust control
setpoints.
THISSCREENDISPLAYSTHE EXHAUST FAN DELAYAND ENABLEBASEDON OUTSIDE
AIR DAMPER POSITION.
The exhaust fan delay will begin once the damper sequence is complete. This
delay can be used to offset starting times between the supply fan and exhaust
fan. This screen also provides the ability to enable the exhaust fan on a set
outdoor air damper position if the unit is equipped with a modulating outdoor air
damper.
THISSCREENDISPLAYS MINIMUMAND MAXIMUM EXHAUST FAN SPEED
PERCENTAGES.
The speed set point is the proportional percentage of the analog output from the
controller to the VFD.
25% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication
option).
Space Pressure – Fan speed is determined by building pressure control loop.
Supply Fan Tracking with Offset – The exhaust fan will track the supply fan,
between a minimum and maximum position. An offset can be added to achieve
the proper balance.
Outdoor Air Damper Tracking – The exhaust fan will proportionally track the
outdoor air damper, between a minimum and maximum position.
Return Duct Static Pressure – Fan speed is determined by duct pressure control
loop.
Microprocessor Controller for DOAS26
®
Menu
Control Variables
Occupancy
The Occupancy menu allows the user to adjust occupancy control parameters
which includes occupancy control mode and schedule.
THISSCREENDISPLAYSTHE CURRENT MODEOF OPERATIONFOR OCCUPANCY
CONTROL. STATU SOFTHE OTHER MODEOPTIONCANALSOBEFOUNDONTHIS
SCREEN.
This screen allows the user to select the source of determining occupancy. The
factory default is terminal ID6 on the controller.
BMS: BMS control (Reference Points List). BMS can be overridden with ID6.
Digital Input: Typically used with a remote time clock, motion sensor or switch.
Always Occ: Controller will always remain in occupancy mode.
Always Unocc: Controller will always remain in unoccupancy mode.
Schedule: Allows the user to set an occupancy schedule for each individual day
of the week.
THISSCREENALLOWSTHEUSERTOADJUSTTHESCHEDULE.
Requires the user to enter a start time, stop time and the applicable days of the
schedule.
THISSCREENDISPLAYSUNOCCUPIEDSTARTENABLEMODES.
This screen only appears if unit is provided with unoccupied recirculation.
This screen allows the user to enable/disable modes of operation when in
unoccupied recirculation control.
THISSCREENDISPLAYSOCCUPANCYOVERRIDECONDITIONS.
Screen allows the user to override occupancy for a set duration.
®
Microprocessor Controller for DOAS27
Menu
Control Variables
Advanced
Control Variables
Advanced
Manual Overrides
The Advanced menu allows the user to access several submenus regarding
controller information, controller overrides, network settings, I/O configuration,
and unit configuration. Submenu options are read only and will require the
user to input proper login criteria. The service password (9998) is required to
change service access menus. Consult factory for factory level access.
The Manual Overrides menus are for start-up, commissioning, and
troubleshooting.
This screen only appears if an indirect gas furnace was provided with the unit.
Entering the furnace commissioning menu will step the user through the furnace
start-up.
MANUAL OVERRIDE MODE
The Manual Overrides menu is for start-up, commissioning, and troubleshooting.
This menu allows the user to override the control loops and specific inputs and
outputs.
To access the Manual Overrides submenus, enter the service password (9998).
Manual overrides must be enabled at this screen to allow the user to override
control loops. Override options must be changed from Auto to Manual for manual
control.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE UNIT ONOR OFF.
When manual override is set to enable, use the arrow buttons to turn the unit on
or off.
When manual override is set to enable, use the arrow buttons to change
occupancy control.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE SUPPLY FAN VFD SPEED.
The speed is the proportional percentage of the analog output from the controller
to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
Microprocessor Controller for DOAS28
®
Menu
THISSCREENALLOWSTHEUSERTO OVERRIDE EXHAUST FAN VFD SPEED.
This screen only appears if the unit is equipped with a exhaust fan VFD controlled
by the microprocessor.
The speed is the proportional percentage of the analog output from the controller
to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
THISSCREENALLOWSTHEUSERTO OVERRIDETHE POSITIONOFTHE OUTDOOR AIR
D
AMPER.
This screen only appears if the unit is equipped with a modulating outdoor air and
recirculation damper. The recirculation damper position will be the inverse of the
outdoor air damper position shown.
This screen only appears if the unit is equipped with DX cooling. When manual
override is set to enable, use the arrow buttons to turn individual compressor
requests on or off.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE MODULATING COMPRESSOR
CONTROL LOOP.
When manual override is set to enable, use the arrow buttons to change the
compressor modulation value.
When the cooling control is in the manual mode, use the arrow buttons to vary the
cooling output.
Chilled Water: The cooling percent is directly proportional to the 0 - 10 VDC
output signal.
0% Cooling = 0 VDC
100% Cooling = 10 VDC
Packaged Cooling: The cooling percent displays compressor engagement as a
percent. The compressors are subject to the minimum on/off times and heating/
cooling lockouts.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE ELECTRIC HEATER OPERATION.
This screen only appears if the unit is equipped with electric post heat. Electric
heater percentage is directly proportional to the 0 – 10 VDC output signal.
When the heating control is in the manual mode, use the arrow buttons to vary the
heating output.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE ECONOMIZER CONTROL
OPERATION.
When the heating control is in the manual mode, use the arrow buttons to vary the
heating output.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE HOT GAS REHEAT OPERATION.
This screen only appears if modulating hot gas reheat option was provided with
the unit. When the hot gas reheat loop control is in the manual mode, use the
arrow buttons to vary the reheat output.
THISSCREENALLOWSTHEUSERTO OVERRIDETHE ENERGY RECOVERY DEFROST
OPERATION.
This screen only appears if modulating wheel frost control is equipped. When the
defrost control ramp is in manual mode, use the arrow buttons to vary the defrost
output.
0% = Maximum Wheel Speed
100% = Minimum Wheel Speed
Control Variables
Advanced
Network Settings
The Network Settings Menus allows the user to view and modify network
settings. The service password (9998) is required to make changes.
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when
the Web User Interface will be utilized. The controller may have a DHCP serverassigned address or a manually-assigned static IP address. Factory settings are
shown in the screen to the left.
To change pCO Board Address parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view pCO Board Address screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option
and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the
controller to initialize.
6. View pCO Board Address Config. If changed values did not save, contact the
factory.
THISSCREENALLOWSTHEUSERTO VIEWAND ADJUST CONTROLLER BACNET IP
CONFIG SETTINGS.
This screen will appear if the unit is set for BACnet IP and allows the user to set
the device and port settings.
Microprocessor Controller for DOAS30
®
Menu
THISSCREENALLOWSTHEUSERTO VIEWAND ADJUST CONTROLLER MODBUS TCP
S
LAVE.
This screen will appear if the unit is set for Modbus TCP and allows the user to set
device ID number.
This screen only appears if the selected BMS protocol is set to BACnet MSTP.
Factory settings are shown in the screen to the left.
To change BACnet MSTP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view BACnet MSTP Config screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option
and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the
controller to initialize.
6. View BACnet MSTP Config. If changed values did not save, contact the factory.
This screen only appears if the selected BMS protocol is set to Modbus. Factory
settings are shown in the screen to the left.
To change Modbus RTU parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view Modbus RTU Config screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option
and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the
controller to initialize.
6. View Modbus RTU Config. If changed values did not save, contact the factory.
®
THISSCREENALLOWSTHEUSERTO ENABLETHE BMS WATCH D OG FUNCTION.
The BMS watchdog function verifies BMS connectivity. The watchdog is required
for the BMS to take the place of a hardwired sensor. The BMS toggles the
watchdog variable from true to false within the timeout delay. If the timer expires,
the controller falls back to hardwired sensors until the BMS connection can be
established. At this time, a BMS watchdog alarm activates.
The following variables may be used by the BMS in place of hardwired sensors:
• Outside_RH_from_BMS
• Outside_Temp_from_BMS
• Return_RH_from_BMS
• Return_Temp_from_BMS
• Space_1_CO2_from_BMS
• Return_CO2_from_BMS
• Space_RH_from_BMS
• Space_Static_from_BMS
• Space_Temp_from_BMS
SENSOR SOURCE SPACE TEMP
The sensor source can be changed to source by BMS through the controller or by
a dedicated BMS point. Reference Points List above and in the Appendix for more
detailed point information. Screen to the left is an example of the sensor source
type. Source can be set for local or BMS at this screen.
Microprocessor Controller for DOAS31
Menu
Control Variables
Advanced
Backup/Restore
The Backup/Restore Menus allows the user to create a backup file of setpoints
and configuration variables on a USB drive or in the controller’s internal memory.
Connecting to USB Drives
The controller has built-in USB ports for connecting to USB drives. The USB
drives can be used for backing up all settings and reported conditions such as
alarm history and current values. This creates a file named User_Backup.txt.
USB Type A
USB Type B
CREATINGA BACKU P FILE
Important:
• At first startup or commissioning, or prior to communicating with Technical
Support about performance issues, we recommend creating a backup file for
each controller.
• Name each file with the unit sales order–line number found on the silver
nameplate attached to the electrical access door.
• Also consider creating a backup file whenever significant program changes are
made.
To create a system backup file using the handheld or virtual keypad/display
buttons:
1. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter
and Up or Down arrow buttons to enter the service password, which is 9998.
2. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
3. Press the Up or Down arrow buttons to navigate to the Backup Settings screen.
4. Press the Enter and Up or Down arrow buttons to select the backup location
(internal memory or USB). If creating a backup to a USB drive, insert a USB
drive into the main controller.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the Save
checkbox. This action creates the backup file.
Microprocessor Controller for DOAS32
®
Menu
RESTORINGFROMA BACKUP FILE
From USB
1. Place the restore file in the root directory of a USB drive. (Do not place the file
within a folder on the USB drive.) The file must be named: User_Backup.txt
2. Insert the USB drive into the controller’s USB port.
3. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down
arrow buttons to disable the unit.
4. Go to the Main Menu/Ctrl Variables/Advanced/Login
and Up or Down arrow buttons to enter the service password (9998).
5. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
6. Press the Up or Down arrow buttons to navigate to the USB Restore screen.
7. Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error
during the process, the specific error is displayed on this screen.
8. Cycle power to the controller.
From internal memory
1. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down
arrow buttons to disable the unit.
2. Go to the Main Menu/Ctrl Variables/Advanced/Login
and Up or Down arrow buttons to enter the service password, which is 9998.
3. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
4. Press the Up or Down arrow buttons to navigate to the Internal Restore
screen. This screen is only available when a backup file exists in internal
memory.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error
during the process, the specific error is displayed on this screen.
6. Cycle power to the controller.
screen. Press the Enter
screen. Press the Enter
®
Microprocessor Controller for DOAS33
Menu
Control Variables
Advanced
I/O Configuration
Control Variables
Advanced
Unit Configuration
The IO Configuration Menu allows the user to view and modify controller input
and output points.
This screen is read only and will require the factory password to make changes.
Screen to the left is an example of an analog input configuration screen. Similar
screens appear for remaining I/O when selected.
To monitor individual I/O points:
1. Press the enter button to highlight the I/O type.
2. Press the up and down arrows to change the IO type.
3. Press the enter button to highlight the controller channel.
4. Press the up and down arrows to change the channel.
Changes to the IO configuration requires the factory login password. Consult
factory for IO configuration changes.
ADJUSTMENT OF I/O CONFIGURATION MUST ONLY BE DONE UNDER
FACTORY GUIDANCE! IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM
DAMAGE!
The Unit Configuration menus allows the user to view unit configuration
provided from factory. Configuration menus listed below can be altered with the
factory password. Consult factory for unit configuration changes!
THISSCREENALLOWSTHEUSERTO VIEWAND CHANGETHE EXHAUST FAN CONTROL
T
YPE.
Reference control variables for possible exhaust fan control methods.
The user can enable morning warm up, morning cool down, and set the duration
for the sequence.
Microprocessor Controller for DOAS34
®
Alarms
Menu
The Alarms menu allows the user to view active alarms, reset active alarm (if
possible), and alarm history.
ACTIVE ALARMS
If an alarm occurs, the button will glow red on the controller and the remote
display (if installed).
To view alarm, press the Alarm button once. This will display the most recent
alarm. If the alarm cannot be cleared, the cause of the alarm has not been fixed.
Press the up and down buttons to view any additional occurring alarms.
RESET ACTIVE ALARMS
This screen allows the user to clear active alarms.
ALARM EVENT HISTORY
This screen allows the user view recent alarms. To view all saved alarms, press
the “down” button to enter the data logger.
CLEAR ALARM LOG
This screen allows the user to clear all alarms in alarm log history.
IG Furnace Alarm (AL) Descriptions
IG no flame 3 try AL
IG combustion fan high
pressure switch failure
IG furnace ignition controlIndicates an alarm from the ignition controller.Alarm only
Pressure switch closed
with combustion fan off
Combustion fan not
proved
IG furnace max retryIndicates that the max number of retries was reached.Alarm and Furnace lockout
IG High Temp AL
IG offlineIndicates communication with furnace control has failed.Alarm only
IG Lg Man No Flame ALNo flame after 3 trials for ignition on the large manifold.Alarm only
Indicates a furnace failure to light or properly sense flame after
3 trials.
Indicates a call for high speed combustion fan but high pressure
switch did not close.
Indicates low pressure switch was closed with no call for
combustion fan.
Indicates a call for low speed combustion fan but low pressure
switch did not close.
Indicates that power was lost from the High Temp Limit Sensor.
Check for high limit trip.
Alarm only
Alarm only
Alarm only
Alarm only
Alarm only
®
Microprocessor Controller for DOAS35
Appendix: Remote Display (pGD1)
The pGD1 is an optional remote display for use with manufacturer’s microprocessor controllers. The remote display
allows for remote monitoring and adjustment of parameters of the unit mounted controller. The remote display
allows identical access to menus and screens as the unit mounted controller display.
Specifications
Carel ModelPGD1000W00
Power Supply
Max distance from unit controller150 feet
Required Cable6P6C RJ25/RJ12 Cable (straight)
Operating Conditions
Display TypeBacklit LED with lighted buttons
Installation
The remote display connects to the unit mounted controller
through a six-wire RJ25 or RJ12 telephone cable (straight).
When ordered from the factory, a 10 ft. cable is provided with
the remote display. The display and cable can be used to
assist with start-up and maintenance.
Connecting Cable
If mounted remotely, the factory cable can either be extended
or replaced with a longer cable to obtain the necessary
distance. The resulting cable connections should be a “straight
through cable,” where pins on one end correspond identically
to the pins on the opposite end. If making your own cable, use
the same pin-out for each end.
12
3
Power supplied from unit controller
through RJ25 cable
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from
large board controller. It allows the user to view and control:
can be utilized for digital inputs.
Applying voltage will result in
damage to the I/O expansion board.
• 4 Analog Outputs (VDC)
• 6 Digital Outputs
The inputs and outputs can be
monitored and controlled by the Building
Universal
Inputs
Analog
Outputs
57.6 K
Modbus
9.6 K
38.4 K
CAREL
19.2 K
Digital
Outputs
Management System. Reference Points
List for detailed point information.
Setup
In order for the controller to communicate with the c.pCOe, several parameters must be adjusted. If you have
a c.pCOe installed from the factory, the controller is already set up for communication with the main controller.
The factory password is required for expansion board and I/O configuration updates. Consult factory for I/O
configuration changes.
Enabling the pCOe in the Main Controller. - To enable the c.pCOe expansion
I/O module, go to Ctrl Variables/Advanced/Unit Config. User will have to enter
the Factory Password to make any edits at this point. Consult factory for factory
password and configuring the expansion board. The expansion board must be
enabled to configure spare I/O points. Once enabled, the user must reboot the
controller. See screens to the left for expansion board enable points.
Configuring the I/O Type - In order to edit and configure the I/O configuration of
the unit, go to Ctrl Variables/Advanced/I/O Configuration. The user must enable
the Editable option for configuring I/O points. If configuring a new I/O point, ‘Scroll
by All Configured’ must be deselected to view all I/O options.
Change or Update the I/O Point - Once the editable option is selected, the
user must scroll to the I/O Configuration Menu. At this menu the desired I/O
type can be selected. Once selected the user can configure the desired channel
at the expansion board. The channel will have an ‘E’ designation for expansion
board. Aux In Customer 1–6, Aux Analog Out 1-4, and Aux Digital Out 1-6 will be
allocated for the I/O expansion board. See example to the left.
Viewing c.PCOe Auxiliary Values – Once the expansion board I/O is configured,
the user can view and/or change the I/O type by navigating to Ctrl Variables/Aux
I/O Config.
®
Microprocessor Controller for DOAS37
Appendix: Room Thermostat Quick Start
The room thermostat gives users the ability to view the room temperature
and relative humidity (optional) and control the active room set points from
the adjustable display. The room thermostat also has the ability to send
the unit into temporary occupied mode. It is also provides the functionality
to average up to 4 temperature readings through the microprocessor. The
room thermostat is shipped loose with installation by others and is a Modbus
connected device.
Room thermostat functions:
• Temporary occupancy override control
• Temperature and relative humidity monitoring
• Temperature and relative humidity set point adjustability
• Status icon on LCD display with push buttons
• Optional temperature monitoring up to 4 sensors
Display
If more than one room thermostat is provided for
averaging, only one room thermostat will be provided
with a display and push buttons for adjustment.
Adjusting SET POINT - The default display will
show the current temperature value for the room. Use
the scroll button to index through additional sensor
parameters. Parameters with the "SET POINT"
icon displayed above the temperature display are
adjustable. Use the Up/Down buttons to adjust the
set point, and use the scroll button to view the next
parameter or return to the normal display mode.
Up/Down Button Function - The Up/Down buttons
are used to adjust editable parameters including the
temperature and humidity set point.
Override Button Function - The display shows a person in the lower left corner of the display at all times. If the
person is solid, the unit is operating in occupied mode. If it is an outline of the person, the unit is in unoccupied
mode. Pushing the Override button when the unit is in unoccupied mode will allow a temporary override sequence to
Occupied mode for a period of 1 to 3 hours (adjustable at the unit microprocessor).
Initial Setup and Communication Configuration
The room thermostat is a Modbus connected device There can be up to three additional Modbus temperature
sensors added for room temperature averaging. The sensors must all be connected in a daisy chain configuration.
The microprocessor controller will be pre-configured for one room thermostat. If room temperature averaging is
desired, additional field setup will be required both in the controller and on the Modbus room sensors:
• Each room sensor must have the DIP switches adjusted on the back of the sensor
to the corresponding switches. Reference Room Thermostat Modbus Address chart
on the following page for DIP switches settings.
• Once the address is set and the wires are connected the “Status” LED should be a
steady green and the “Network” LED should be a quick blinking amber/green color.
• In the Controller, enter the Ctrl Variables Menu/Temperature and scroll down in the
Temperature Menu to select BAPI Modbus Stat. Choose the number of room sensor
being used (1-4).
Microprocessor Controller for DOAS38
®
Appendix: Room Thermostat Quick Start
Status LED
Green indicates that the unit is operating properly.
Red indicates that there is a problem with the unit.
TerminalDescription
GNDPower Supply Ground (common to the controller)
Net BRS485 network connection (Data - )
Net ARS485 network connection (Data +)
PowerPower supply hot
Unit
Controller
+Vtermo
GND
-
TAP-Stat
POWER
GND
NET B
Tx/Rx
+
NET A
Network LED
Flashing Red Slowly indicates that there has been no communications for 60 seconds.
Flashing Green Slowly indicates that there have been normal communications within
the last 60 seconds.
Flashing Green Slowly with Quick Red Flashes; the quick red flashes indicate active
communications.
In order for the room thermostat to communicate with the microprocessor, the correct baud rate must be set in the
room thermostat. To set the baud rate:
• The “PROG” DIP switch on the back of the room thermostat must be flipped to the right side.
• Use the Setpoint Down button to display P11 on the room thermostat.
• Push the Scroll button and use the Setpoint Up/Down buttons to adjust the baud rate to 192.
• Once 192 is displayed, push the Scroll button again to save the setting. Once the setting is saved, P11 should
appear on the display.
• Flip the “PROG” DIP switch on the back of the room thermostat back to the left. The room thermostat should
communicate and be set back to normal mode.
If the occupancy override time needs to be adjusted:
• If the occupancy override is enabled from the room thermostat or the unit
microprocessor, it will override for the period of time set on this menu screen.
• To adjust the temperature override time, enter the following menu options at the
controller, Cntrl Variables/Occupancy. Scroll down at the Occupancy Menu and
select Occ Timed Override. This menu will allow the user to enable occupancy
override from the controller and set override duration.
The GreenTrol® airflow monitoring station measures
airflow using advanced thermal dispersion technology.
An integral LCD display provides a local indication of
airflow measurement and device configuration. The
airflow monitor also features Modbus communication
allowing the main unit microprocessor to monitor the
airflow as well. The GreenTrol also accepts up to two
airflow probes for averaging.
GreenTrol Airflow Monitor functions:
• LCD readout of measured airflow
• Dual airflow probe averaging
• Modbus connectivity
Display and Navigation
The LCD screen will by default show the current airflow that is being measured. To enter the menu to set up the
monitoring station the user must remove the front cover of the GreenTrol to uncover the navigation buttons. Press
and hold the UP and DOWN buttons at the same time for 3 seconds to enter the menu.
Enter Button Function - The ENTER button allows the user to go into the selected menu or function, as well as
save the selected value.
Up/Down Button Function - The Up/Down buttons are used to navigate the menu and to change values in the
menu.
Esc Button Function - The ESC button allows the user to exit the current menu or function.
Microprocessor Controller for DOAS40
®
VARIABLE DESCRIPTION
Cold_Coil_1_Temp_
Analog_Input
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Outside_Air_Temp_
Analog_Input
Space_Temp_Analog_
Input
Supply_Temp_Analog_
Input
Outside_RH_Analog_
Input
Space_RH_Analog_
Input
Space_Static_
Pressure_Analog_Input
Supply_Duct_Static_
Pressure_Analog_Input
Space_CO2_1_
Analog_Input
Circuit_A_Discharge_
Pressure_Analog_Input
Circuit_B_Discharge_
Pressure_Analog_Input
Aux_In_Customer_1
Aux_In_Customer_2
Aux_In_Customer_3
Aux_In_Customer_4
Aux_In_Customer_5
Aux_In_Customer_6
Cold Coil 1 Temperature25AI
Controls Lite Cooling Coil
Setpoint Temperature value
Controls Lite Supply
Setpoint Temperature value
Outside Air Temperature37AI
Space Temperature44AI
Supply Temperature45AI
Outside % Relative
Humidity
Space % Relative Humidity89AI
Space Static Pressure94AI
Supply Duct Static Pressure95AI
Space 1 CO2 ppm116AI
Circuit A Discharge
Pressure
Circuit B Discharge
Pressure
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Appendix: Points List
ACTIVE
TEXT
INACTIVE
TEXT
Analog Inputs - Read Only
OBJECT
INSTANCE
31AI
32AI
86AI
119AI
121AI
640AI
642AI
644AI
646AI
648AI
650AI
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0.130243Input2
0.130255Input2
0.130257Input2
0.130267Input2
0.130281Input2
0.130283Input2
0.130349Input2
0.130355Input2
0.0130365Input2
0.0130367Input2
1030401Input2
0.130407Input2
130411Input2
0.130639Input2
0.130641Input2
0.130643Input2
0.130645Input2
0.130647Input2
0.130649Input2
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS41
VARIABLE DESCRIPTION
Main Temperature Set
Temperature_Setpoint
point. Supply, Space, or
Return target temperature
Heat/Cool Spt Deadband
when Room or Return
Temperature_Heat_
Cool_Deadband
control is active. Clg Spt =
Deadband /2 + Temp Spt.
Htg Spt = Deadband /2 -
Temp Spt.
Cooling_Coil_Setpoint_
Min
Dehumidification_
Setpoint
Outside_Dewpoint_
Setpoint
Indoor_Dewpoint_
Setpoint
Unocc_Indoor_
Dewpoint_Setpoint
Unoccupied_Cooling_
Setpoint
Unoccupied_
Dehumidification_
Setpoint
Unoccupied_Heating_
Setpoint
Economizer_Temp_
Enable_Setpoint
Economizer_Enthalpy_
Enable_Setpoint
Outside_RH_from_
BMS
Outside_Temp_from_
BMS
Space_1_CO2_from_
BMS
Cooling Coil Leaving Air
Setpoint
Dehumidification Setpoint.
%RH for Space or Return
control.
Outside Dewpoint
Dehumidification Trigger
Setpoint
Indoor Dewpoint
Dehumidification Trigger
Setpoint
Unoccupied Indoor
Dewpoint Dehumidification
Trigger Setpoint
Unoccupied Cooling
Setpoint
Unoccupied
Dehumidification %RH
Setpoint
Unoccupied Heating
Setpoint
Economizer Ambient Temp
Enable Setpoint. Allow Econ
when OAT<Spt
Economizer Enthalpy
Enable Setpoint. Allow Econ
when OA Enthalpy<Spt
Outside RH from BMS. Used
when source selection is
set to BMS.
Outside Temp from BMS.
Used when source selection
is set to BMS.
Space 1 CO2 from BMS.
Used when source selection
is set to BMS.
Space RH from BMS. Used
Space_RH_from_BMS
when source selection is
set to BMS.
Space_Static_from_
BMS
Space_Temp_from_
BMS
Cooling_Lockout_
Setpoint
Heating_Lockout_
Setpoint
Space_Static_
Pressure_Setpoint
Space Static from BMS.
Used when source selection
is set to BMS.
Space Temp from BMS.
Used when source selection
is set to BMS.
Cooling Ambient Lockout
Setpoint
Heating Ambient Lockout
Setpoint
Space Static Pressure
Setpoint
Appendix: Points List
ACTIVE
TEXT
INACTIVE
TEXT
OBJECT
INSTANCE
Analog Values - Read/Write - Commandable
1AV
2AV
3AV
5AV
6AV
7AV
9AV
10AV
11AV
12AV
16AV
17AV
21AV
22AV
25AV
28AV
29AV
30AV
31AV
32AV
37AV
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
040001Holding2
040003Holding2
040005Holding2
040009Holding2
040011Holding2
040013Holding2
040017Holding2
040019Holding2
040021Holding2
040023Holding2
040031Holding2
040033Holding2
0.140041Holding2
0.140043Holding2
0.140049Holding2
0.140055Holding2
0.140057Holding2
0.140059Holding2
0.140061Holding2
0.140063Holding2
0.140073Holding2
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS42
®
Appendix: Points List
VARIABLE DESCRIPTION
Supply_Duct_Static_
Pressure_Setpoint
Supply Duct Static Pressure
Setpoint
ACTIVE
TEXT
Space_CO2_SetpointSpace CO2 Setpoint39AV
SF_Control_Signal_
BMS
EF_Control_Signal_
BMS
OAD_Control_Signal_
BMS
Outside_Air_Damper_
Minimum_Setpoint
Aux_BMS_Analog_
Output_1
Aux_BMS_Analog_
Output_2
Aux_BMS_Analog_
Output_3
Aux_BMS_Analog_
Output_4
BMS to control signal for
supply fan speed
BMS to control signal for
exhaust fan speed
Allows the BMS to control
OAD position. True = BMS.
False = Local.
Outside Air Damper
Minimum Setpoint
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
INACTIVE
TEXT
OBJECT
INSTANCE
38AV
133AV
134AV
136AV
137AV
138AV
139AV
140AV
141AV
OBJECT
BACNET MODBUS
TYPE
ACCESS HYST INDEX
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
0.140075Holding2
0.140077Holding2
0.140083Holding2
0.140085Holding2
0.140089Holding2
140091Holding2
0.140093Holding2
0.140095Holding2
0.140097Holding2
0.140099Holding2
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS43
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
0: Off/Standby
1: Unoccupied Start
2: Occupied Start
5: Dampers Open
6: Fan Start Delay
7: Fans Starting
9: Heat/Cool Delay
10: System On
11: Soft Shutdown
12: System Disabled
13: Remote Off
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety
information. This publication can be obtained from AMCA International, Inc. at www.amca.org.