Greenheck Microprocessor Controller, pCOe, c.pCOe Reference Manual

Document 483586
Microprocessor Controller for
®
Dedicated Outdoor Air System
Reference Guide for Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
DOAS v3.001
Introduction
Program Features
The microprocessor controller offers control through easy monitoring and adjustment of unit parameters by way of a lighted graphical display and an integral push­button keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer multiple control sequences to provide tempered air. Factory default settings allow for easy setup and commissioning. The sequence parameters are fully adjustable. Refer to the Sequence of Operation for details.
BMS Communication
The user can remotely adjust setpoints, view unit status points and alarms. The microprocessor controller is capable of communicating over several protocols:
• BACnet® MSTP • Modbus RTU
• BACnet® IP • Modbus TCP
• LonWorks®
Reference Points List for a complete list of BMS points.
Internal Time Clock (Schedule)
The controller has an internal programmable time clock, allowing the user to set occupancy schedules for each day of the week. The controller option also has morning warm-up and cool down capability for improved comfort at the time of occupancy.
Alarm Management
The microprocessor controller will monitor the unit’s status for alarm conditions. Upon detecting an alarm, the controller will record the alarm description, time,
DOAS Technical Support
Call 1-866-478-2574
date, and input/output status points for user review. A digital output is reserved for remote alarm indication. Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of determining occupancy: a digital input, the internal time clock or the BMS. If in the unoccupied mode, the unit will either be shut down, continue normal operation utilizing adjustable unoccupied setpoints, recirculate with unoccupied setpoints or will cycle on to maintain adjustable unoccupied room temperature and humidity setpoints (room temperature and humidity sensor is optional).
Remote Display Panel (if equipped)
A touch pad display panel allows for remote monitoring and adjustment of parameters, allowing ease of control access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury or equipment damage. Service must be performed only by personnel that are knowledgeable in the operation of the equipment being controlled.
WARNING
Mechanical high static protection cutoffs must be installed by others to protect the system and equipment from over-pressurization when using factory provided control sensors. The manufacturer does not assume responsibility for this.
®
Microprocessor Controller for DOAS 1
Table of Contents
Sequence of Operation
General Operation . . . . . . . . . . . . . . . . 3-4
Setpoint Control (Occupied) . . . . . . . . . . . . 4
Setpoint Control (Unoccupied). . . . . . . . . . . 4
Heating . . . . . . . . . . . . . . . . . . . . . . . 4
Cooling . . . . . . . . . . . . . . . . . . . . . . . 4
Economizer. . . . . . . . . . . . . . . . . . . . . 5
Dehumidification . . . . . . . . . . . . . . . . . . 5
Reheat . . . . . . . . . . . . . . . . . . . . . . . 5
Supply Fan VFD Sequence. . . . . . . . . . . . . 5
Exhaust Fan VFD Sequence . . . . . . . . . . . . 5
OA and Recirc Air Damper Control. . . . . . . . . 6
Energy Recovery Wheel . . . . . . . . . . . . . . 6
Alarms . . . . . . . . . . . . . . . . . . . . . . . 7
Controller Overviews
Large Controller . . . . . . . . . . . . . . . . . . 8
Medium Controller . . . . . . . . . . . . . . . . . 9
c.pCOe - Expansion Board Overview, Medium . . 10
pCOe - 4:1 Furnace. . . . . . . . . . . . . . . . .11
pCOe - High Turndown Furnace . . . . . . . . . . 11
Display Use . . . . . . . . . . . . . . . . . . . . .12
Example of Parameter Adjustment . . . . . . . .12
Example of Web User Interface . . . . . . . . . .13
Main Menu . . . . . . . . . . . . . . . . . . . . . 14
Unit Status Overview. . . . . . . . . . . . . . 15-17
Unit Enable . . . . . . . . . . . . . . . . . . . . . 18
Menus
Control Variables
Temp Control . . . . . . . . . . . . . . . . 18-20
Dehumidification . . . . . . . . . . . . . . 20-21
Refrigeration. . . . . . . . . . . . . . . . . . .22
Damper Control . . . . . . . . . . . . . . . 22-23
Energy Recovery . . . . . . . . . . . . . . . . 24
Fan Control
Supply Fans Control . . . . . . . . . . . . . 25
Exhaust Fans Control. . . . . . . . . . . . .26
Occupancy . . . . . . . . . . . . . . . . . . . 27
Advanced
Manual Overrides. . . . . . . . . . . . .28-30
Network Settings . . . . . . . . . . . . . 30-31
Backup/Restore . . . . . . . . . . . . . 32-33
I/O Configuration . . . . . . . . . . . . . . .34
Unit Configuration . . . . . . . . . . . . . .34
Alarms . . . . . . . . . . . . . . . . . . . . . . 35
IG Furnace Alarm Descriptions . . . . . . . . . . 35
Appendix
Remote Display . . . . . . . . . . . . . . . . . .36
Carel
®
NTC Temp Sensor Chart . . . . . . . . 36
I/O Expansion Board Quick Start . . . . . . . . .37
Room Thermostat Quick Start. . . . . . . . .38-39
GreenTrol
®
Airflow Monitoring Quick Start . . . . 40
Points List . . . . . . . . . . . . . . . . . . . 41-52
Modbus Connections . . . . . . . . . . . . . . . 53
Maintenance Log . . . . . . . . . . . . . . . .53-54
Our Commitment . . . . . . . . . . . . . Backcover
Microprocessor Controller for DOAS2
®
Sequence of Operation
The microprocessor controller can be configured for air handler, energy recovery, and dedicated outdoor air systems. Each application utilizes similar technologies for heating and cooling: chilled water, hot water, indirect gas, electric heat, packaged DX cooling, and packaged DX cooling with digital and inverter scrolls. All setpoints, lockouts and delays are user adjustable via the integral keypad display, remote display, or web user interface.
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation. The unit can then be commanded on or off by this digital input, keypad, the BMS or internal time clock. When a start command becomes active the following steps occur:
• Energy recovery wheel starts, if equipped
• Factory mounted and wired dampers are powered (Outdoor air, exhaust air, and recirculation air dampers, if equipped)
• Exhaust fan, if equipped, starts after adjustable delay
• Supply fan starts after adjustable delay
• Tempering operation starts after adjustable delay
UNIT STOP COMMAND: A shutdown occurs when there is not an occupied or unoccupied start command. The following shutdown methods can occur.
Hard shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the supply temperature is less than the soft shutdown enable setpoint.
• Occupancy is commanded to unoccupied while there is no unoccupied start command, and the supply temperature is less than the soft shutdown enable setpoint.
When a hard shutdown occurs:
• The unit shuts down immediately.
• Dampers spring-return to their off position.
Soft shutdown occurs under the following conditions:
• A user or the BMS disables the system, and the supply temperature is greater than or equal to the soft shutdown enable setpoint.
• There is no unoccupied or occupied start command and the supply temperature is greater than or equal to the soft shutdown enable setpoint.
The following occurs during a soft shutdown:
• Tempering outputs immediately revert back to their off value; while
• Dampers remain open and fans continue to run; until
– The supply air temperature falls below the soft
shutdown enable setpoint minus 5.0°F; or
– The soft shutdown delay timer has expired.
UNIT/SYSTEM DISABLED COMMAND:
The unit becomes disabled due to the following:
• The unit was disabled from the controller’s Unit Enable screen.
• The unit was disabled from the BMS.
• The shutdown input is in the shutdown position.
• A shutdown alarm was activated.
When disabled the following actions occur:
• The unit shuts down immediately; and
• Dampers spring-return to their off position.
OCCUPIED/UNOCCUPIED MODES: The microprocessor controller offers three modes of determining occupancy: digital input, the internal time clock or the BMS. When in the unoccupied mode, the unit can be configured to shut down, or cycle on to maintain the unoccupied room setpoints. The unit can be temporarily overridden to the occupied mode via a digital input, keypad display, or room thermostat, if equipped.
The controller can be configured with morning warm­up and cool down to bring the space to the occupied setpoint prior to occupancy.
Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to
Energy Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
Unoccupied Mode (Unit Off): Unit remains off when in unoccupied mode.
• Normal Operation with Unoccupied Setpoints:
Optional unoccupied mode will operate as if in occupied mode but will utilize adjustable unoccupied setpoints.
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel Control (refer to Energy
Recovery Wheel section), if equipped
- Damper Control (refer to Outdoor Air and
Recirculated Air section), if equipped
• Recirculation with Unoccupied Setpoints: Optional unoccupied mode when there is an unoccupied recirculation damper. The unit will continue to run, but in full recirculation.
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
®
Microprocessor Controller for DOAS 3
Sequence of Operation
Unoccupied Mode (Cycle on Room): Optional unoccupied mode when there is an unoccupied recirculation damper and room temperature and/ or humidity sensor(s) connected to the controller. The unit will cycle on to maintain unoccupied room setpoints if there is a call for unoccupied heating, cooling or dehumidification.
- Exhaust fan off, if equipped
- Supply fan on
- Recirculation air damper open
- OA damper closed
- Tempering operations begin
Setpoint Control (Occupied)
Supply air temperature setpoint can be configured as constant, or can be reset by either outside air temperature, or room temperature setpoint. If equipped with BMS communications, the user can also directly command the supply temperature setpoint, or room temperature setpoint, if equipped.
Outdoor Air Temperature Reset Function: The controller will default to supply temperature reset based on outdoor air temperature. The controller will monitor the OA temperature and reset the supply temperature setpoint based upon the outdoor air reset function.
• Room Temperature Reset (optional): With a room temperature sensor, the controller will adjust the supply air temperature setpoint between the minimum (55°F) and maximum (90°F), to satisfy the desired room temperature. Room temperature setpoint can be adjusted locally at the microprocessor by BMS or room thermostat, if equipped.
Setpoint Control (Unoccupied)
When equipped with an unoccupied recirculation damper and optional room temperature and/or humidity sensors, the unit will cycle on to maintain the unoccupied room setpoints.
Unoccupied Heating: If equipped with heating, the unit is enabled when the room temperature is less than the unoccupied heating setpoint minus differential (60°F). The supply air temperature setpoint will be set to the supply maximum reset limit (90°F). The unit cycles off when the room temperature reaches the unoccupied heating setpoint.
• Unoccupied Cooling: If equipped with cooling, the unit is enabled when the room temperature is greater than the unoccupied cooling setpoint plus differential (80°F+5°F). The supply air temperature setpoint will be set to the supply minimum reset limit (55°F). The unit cycles off when the room temperature reaches the unoccupied cooling setpoint.
• Unoccupied Dehumidification: If equipped with cooling, the unit is enabled when the room relative humidity exceeds the unoccupied room relative humidity setpoint plus differential (50%+5%). The supply air temperature setpoint will be set to the equivalent occupied supply setpoint.
• Morning Warm-Up/Cool Down: The unit uses adjustable preset time to temper the space to occupied setpoint prior to occupancy (room temperature sensor is optional).
Heating
The heating is controlled to maintain the supply temperature setpoint. The heating will be locked out when the outside air temperature is above the heating lockout (80°F adj).
Indirect Gas Furnace: Microprocessor controller will modulate the indirect gas furnace to maintain the supply temperature setpoint.
Hot Water Coil: Microprocessor controller will modulate a hot water valve (provided by others) to maintain the supply temperature setpoint. Coil freeze
protection must be provided by others in the field!
Electric Heater: Microprocessor controller will modulate an electric heater to maintain the supply temperature setpoint.
Cooling
The cooling is controlled to maintain the supply temperature setpoint. The mechanical cooling will be locked out when the outside air temperature is below the cooling lockout (55°F).
Chilled Water: Microprocessor controller will modulate a chilled water valve (provided by others) to maintain supply air setpoint. Coil freeze protection
must be provided by others in the field!
Packaged/Split DX Cooling (Standard Scroll): Microprocessor controller will enable stages of cooling to maintain the supply air setpoint.
Packaged DX Cooling (Digital Scroll): Microprocessor controller will modulate the digital scroll to maintain the supply air temperature setpoint.
Packaged DX Cooling (Inverter Scroll): Microprocessor controller will modulate the inverter scroll to maintain the supply air temperature setpoint.
Microprocessor Controller for DOAS4
®
Sequence of Operation
Economizer
If the application requires cooling, and the outdoor air conditions are suitable for free cooling, the controller may enter the economizer state. If the unit is economizing and the discharge temperature setpoint is not being met, the controller may bring on mechanical cooling. If equipped with a modulating outdoor air and recirculated air damper, the dampers will modulate between the minimum OA and maximum positions to maintain the supply temperature setpoint. If equipped with an energy wheel, Reference Energy Recovery Wheel Sequence.
Temperature: The economizer will be locked out when:
- The outside air is greater than the economizer
high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Temperature/Enthalpy: The economizer will be locked out when:
- The outside air is greater than the economizer
high lockout (65°F dry-bulb).
- The outside air is greater than the economizer
high enthalpy lockout (23 btu/lb).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil setpoint. The dehumidification sequence will be locked out when the OA is less than the dehumidification lockout (10°F) above the cold coil setpoint. If equipped with BMS communications, the user can also directly set the cold coil leaving air setpoint.
Optional Room Relative Humidity Sensor or Thermostat: The controller will adjust the cold coil leaving air temperature setpoint between the minimum (50°F) and maximum (55°F) setpoint to satisfy the desired room relative humidity setpoint.
Reheat
While the unit is in dehumidification mode, the supply air can be reheated via Primary Heating Source, On/Off Hot Gas Reheat or Modulating Hot Gas Reheat.
Modulating Hot Gas Reheat (valve): The microprocessor controller will modulate the hot gas reheat valve to maintain the supply temperature setpoint.
Reheat Plus: The primary heat source configured to act as secondary reheat.
Supply Fan VFD Sequence
The factory installed VFD is wired to the controller. Supply fan speed needs to be set during test and balance of the unit. If equipped with BMS communications, the user can also directly command the supply fan speed.
Optional Space/Duct CO
Sensor: The controller
2
will modulate the supply fan based upon a comparison of the CO2 setpoint to the actual CO2 levels reported from the sensor.
Optional Duct Static Pressure Sensor: The controller will modulate the supply fan based upon a comparison of the duct static pressure setpoint to the actual duct static pressure level reported from the sensor.
• Optional Building Static Pressure Sensor: The controller will modulate the supply fan based upon a comparison of the building static pressure setpoint to the actual building static pressure level reported from the sensor.
Optional Single Zone VAV (SZ): The controller will control the supply air temperature and supply fan speed to maintain the room temperature setpoint. This sequence requires a room temperature sensor. Heating - When the room requires heating, the controller will reset the supply air temperature setpoint up to the maximum (90°F) while increasing the supply fan speed up to its maximum heating speed. Cooling - When the room requires cooling, the controller will first reset the supply air temperature setpoint down to the minimum (55°F) while the supply fan remains at the minimum cooling speed. After a time delay, the supply fan speed will increase up to its maximum cooling speed to maintain the room temperature setpoint.
Exhaust Fan VFD Sequence
The factory installed VFD is wired to the controller. Exhaust fan speed needs to be set during test and balance of the unit. If equipped with BMS communications, the user can also directly command the exhaust fan speed.
Optional Building Static Pressure Sensor: The controller will modulate the exhaust fan based upon a comparison of the building static pressure setpoint to the actual building static pressure level reported from the sensor.
Optional Supply Fan Tracking: The controller will proportionally modulate the exhaust fan based upon the supply fan speed.
Optional Outdoor Air Damper Tracking: The controller will proportionally modulate the exhaust fan based upon the outdoor air damper position.
®
Microprocessor Controller for DOAS 5
Sequence of Operation
Outdoor Air and Recirculated (Recirc) Air Damper Control
If equipped with a modulating outdoor air and recirculated air damper, the recirculated air damper will operate inverse of the outdoor air damper. The outdoor air damper will open to a Minimum Outdoor Air Position (Min OA) when in occupied mode. If the controller is configured to modulate the supply fan speed, the minimum and maximum OA positions can be reset based on supply fan speed. If equipped with BMS communications, the user can also directly reset the damper position up to the maximum OA position.
Optional Space CO proportionally modulate the OA/RA dampers based upon a comparison of the CO CO2 level reported from the sensor. As the CO2 level rises, the controller will proportionally modulate the outdoor air damper open, between the minimum OA damper position and maximum CO
Optional Building Pressure: The OA/RA dampers will modulate based upon the signal from a building static pressure sensor. The controller will modulate the dampers, between the minimum and maximum OA positions, based upon a comparison of the building static pressure setpoint to the actual building static pressure level reported from the sensor.
Sensor: The controller will
2
setpoint to the actual
2
position.
2
Energy Recovery Wheel Sequences
Economizer (optional): If the unit is equipped with an
energy recovery wheel, the economizer will modulate/ stop the energy wheel to achieve free cooling. Jog wheel control is available during stop wheel economizer operation. This sequence allows the wheel to rotate for a short period of time exposing a new section to the air stream.
Stop Wheel: When economizer mode is enabled and there is a signal for cooling, the wheel will stop rotating to allow free cooling.
Modulate Wheel: When economizer mode is enabled and there is a signal for cooling, the controller modulates wheel speed to maintain the supply temperature setpoint.
Energy Wheel Bypass Dampers, if equipped: During normal operation, the dampers shall remain closed to allow full operation of the energy wheel. During economizer sequences, the dampers will be open to bypass the energy wheel.
Frost Control (optional): The microprocessor controller will activate the frost control method when the outdoor air temperature is less than the defrost setpoint (5°F) and the wheel pressure switch is closed due to a high wheel pressure drop. Once the pressure drop decreases below the pressure switch point or the outdoor air temperature increases, the unit will resume normal operation.
Electric Preheater: When frosting is occurring, the preheater is energized to defrost the wheel.
Modulate Wheel: When frosting is occurring, the wheel slows to allow defrosting to occur.
Cycle Wheel: When frosting is occurring, the energy wheel is cycled off for a defrost cycle time (5 minutes). After the defrost cycle time, the wheel is re-energized to continue normal operation. The controller will not allow another defrost cycle for a minimum normal operating cycle time (30 minutes).
Timed Exhaust: When frosting is occurring, the supply fan is cycled off along with the tempering for a defrost cycle time (5 minutes). The exhaust fan will continue to run allowing the warm exhaust air to defrost the wheel. After the defrost cycle time, the supply fan and tempering are re-energized to continue normal operation. The controller will not allow another defrost cycle for a minimum normal operating cycle time (30 minutes).
Microprocessor Controller for DOAS6
®
Sequence of Operation
Alarms
The microprocessor controller includes a digital output for remote indication of an alarm condition, which connects via the J15 port. Possible alarms include:
Dirty Filter Alarm: If the outside air or return air filter differential pressure rises above the differential pressure switch setpoint, the microprocessor controller will activate an alarm.
Supply and Exhaust Air Proving Alarm: Microprocessor controller monitors proving switch on each blower and displays an alarm in case of blower failure.
Sensor Alarm: Microprocessor controller will send an alarm if a failed sensor is detected (temperature, pressure, relative humidity).
Supply Air Low Limit: If the supply air temperature drops below the supply air low limit (35°F), the microprocessor controller will de-energize the unit and activate the alarm output after a preset time delay (300s).
Other Alarms: Wheel Rotation, High Wheel Pressure, High/Low Refrigerant Pressure.
®
Microprocessor Controller for DOAS 7
Large Controller Overview
24VAC to Controller
Room RH
CO2 Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Outdoor Air Damper Analog Output
Heating Analog Output
Cooling/VSC Cond Fan Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure Limit
Wheel Rotation Alarm
Unit On/Off Input
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter Input
Outdoor Relative Humidity Sensor
Building Pressure Sensor
Duct Pressure Sensor
Compressor Limit Circuit A
Compressor Limit Circuit B
Compressor Limit Circuit C
Compressor Limit Circuit D
Supply Fan VFD Output
Exhaust Fan VFD Output
Room Temperature Sensor
Discharge Pressure Circuit B (VSC)
2 Speed Fan Input
2 Position Damper Input
G
G0
+Vter m
GND
+5 V
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
J1
J10
J11 pLAN
J24 J2 J3
REF
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
J12
C1
NO1
J25
J4 J5 J7
BMS2
J26
drac SMBdrac suBdleiF
ID15H
ID15
J19
IDC15
ID16
J6
ID16H
Y5
Y6
U9
J20
GND
U10
GND
ID17
ID18
IDC17
FBus2
4321
NO14
J21
NC14
NO15
NC15
NO16
J22
NO17
NO18
J23 FBus2
NO2
NO3
C1
C4
J13
NO4
NO5
NO6
C4
C7
J14
NO7
C7
C14
NO8
J15
C8
NC8
C15
J16
C9
NO9
C16
NO10
NO11
C9
C16
NO12
J17
C12
NC12
NO13
J18
C13
NC13
24 VAC When Unit On
Wheel Frost Mode
Supply Fan Enable
Exhaust Fan Enable
24 VAC from Supply Fan Proving
Heating Enable
Staged Compressor 1
Staged Compressor 2
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Staged Compressor 3
Staged Compressor 4
Energy Recovery Wheel Enable
Inverter Compressor E-Stop (VSC)
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Compressor Fan 1 Enable (VSC)
Compressor Fan 2 Enable (VSC)
Optional LonWorks cards are
located in BMS Card port.
Microprocessor Controller for DOAS8
Optional Modbus RTU/BACnet MSTP connections are made to the J26 FBus2 terminal.
®
Medium Controller Overview
24VAC to Controller
Refrigerant Pressure Circuit A
Refrigerant Pressure Circuit B
Supply Discharge Air Temperature
Sensor B1, B2, B3 Commons
After Cold Coil Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Cooling Analog Output
Condenser Fan Circuit A or Heating Analog Output
Hot Gas Reheat Analog Output
Condenser Fan Circuit B or Heating Analog Output
Supply Fan Proving
High Pressure Switch Circuit A
Low Pressure Switch Circuit A
Occupied/Unoccupied Input
OA/RA Damper End Switch
Unit On/Off Input
High Pressure Switch Circuit B
Low Pressure Switch Circuit B
Outdoor Relative Humidity Sensor
Outdoor Air Damper Output
Supply Fan VFD Output
Exhaust Fan Proving
Dirty Filter Input
Wheel Rotation Alarm
Freeze Stat Input
Condensate Drain Pan Switch
Remote Start Input
G
G0
+Vterm
GND
+5 V
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
U6
U7
U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
J1
J10
J11 pLAN
J24 J2 J3
REF
Remote Display
• Six conductor RJ25 cable
• Connects to J10
Optional BACnet IP, Modbus TCP, Web UI, Ethernet Connections
J12
C1
NO1
J25
J4 J5 J7
drac SMBdrac suBdleiF
ID15H
ID15
J19
IDC15
ID16
J6
ID16H
Y5
Y6
U9
J20
GND
U10
GND
ID17
ID18
IDC17
BMS2
J26 FBus2
NO14
J21
NC14
NO15
NC15
NO16
J22
NO17
NO18
J23 FBus2
NO2
NO3
C1
C4
J13
NO4
NO5
NO6
J14
J16
J17
J15
J18
C4
C7
NO7
C7
NO8
C8
NC8
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
NO13
C13
NC13
4321
C14
C15
C16
C16
24 VAC When Unit On
Stagged Compressor 1
Stagged Compressor 2
Stagged Compressor 3
24 VAC from Supply Fan Proving
Stagged Compressor 4
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Condenser Fan VFD Start
Condenser Fan Stage 2 Start
Condenser Fan Stage 3 Start
Inverter Compressor E-Stop (VSC)
Optional LonWorks cards are
located in BMS Card port.
®
Optional Modbus RTU/BACnet MSTP connections are made to the J26 FBus2 terminal.
Microprocessor Controller for DOAS 9
c.pCOe - Expansion Board Overview, Medium Controller Arrangement
24 VAC Power
Heating Output
Exhaust Fan VFD Output
Energy Recovery Output
Space Temperature
Mixed Air Temperature
Exhaust Air Temperature
Space Static Pressure
Supply Air Duct Static Pressure
Space Setpoint Adjustment
Address Ext. ProtBaud
OFF
ON
8
38.4 K
57.6 K
CAREL
Modbus
9.6 K
Address Ext Baud Prot
1234567
9101112131415
19.2 K
Wheel Enable
Furnace Heating Stage 1
Furnace Heating Stage 2
Preheater Enable
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from medium board controller.
Microprocessor Controller for DOAS10
®
pCOe - 4:1 Furnace Overview
High Speed Pressure Switch
24 VAC to Controller
Main Gas Valve
Ignition Controller Alarm
Low Speed Pressure Switch
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
Ignition Controller 24 VAC
High Speed Fan 24 VAC
Modbus Address Switches
pCOe - High Turndown Furnace
24 VAC to Controller
Main Gas Valve - Small Manifold
Main Gas Valve - Large Manifold
Ignition Controller Alarm
24 VAC for Analog Outputs
Modulating Gas Valve
Modbus Connection
Low Speed Pressure Switch
Modbus Address Switches
High Speed Pressure Switch
Ignition Controller - Small Manifold 24 VAC
High Speed Fan 24 VAC
Ignition Controller - Large Manifold 24 VAC
®
Microprocessor Controller for DOAS 11
Display Use
The microprocessor controller is located in the unit control center. The face of the controller has six buttons, allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre-programmed with easy to use menus. A remote display is also available, which connects via the J10 port. A six wire patch cable is needed.
Keypad Description
Button Description Functions
Main Menu Press to go directly to the Main Menu from any screen.
From the Main Menu, navigate to the following screens:
• Unit Enable
• Unit Status
• Ctrl Variables
• Alarm Menu
Alarm The Alarm button flashes when there is an active alarm.
Press to view active alarms. Press twice to go to the alarms reset screen.
Escape Press from the Main Menu to view the Unit Status screen.
Press to go back one menu level. Press when editing a variable to cancel editing.
Up Press to navigate through the menus/screens.
Press after entering a variable to increase a current value.
Enter Press to enter a highlighted menu or screen item.
Press to enter a writable variable and press again to confirm the new variable value.
Down Press to navigate menus/screens.
Press after entering a variable to decrease the current value.
Virtual keypad/display on web interface only. These two buttons on the virtual keypad/display are used to simulate two-button actions on the handheld keypad/display.
To simulate pressing two buttons simultaneously:
1. Click on 2-Button Click.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
To simulate pressing and holding two buttons simultaneously:
1. Click on 2-Button Hold.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
Supply air low limit
Alarm when supply is below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be blinking. Press the button to move the cursor down for parameter adjustment.
Once the cursor has reached the desired parameter, press the adjust the value.
buttons to
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Microprocessor Controller for DOAS12
When satisfied with the adjustment, press the button to save the parameter. When finished, make certain the cursor is in the upper left corner. If the cursor is not in the upper left corner, the changes will not be saved. The cursor must be in the upper left corner to enable screen advancement.
®
Web User Interface
The Web User Interface allows access to the unit controller through the building network. Reference Cntrl Variables/ Advanced/Network Settings to set the IP network protocol. Once proper communication is established, the user can click on the follow tabs:
Overview – Includes a functioning unit graphic, monitoring points, and active setpoint adjustment.
Alarm – Shows current and cleared alarms.
Unit Display – Mimics the unit controller display. Allows the user full access to the controller without physically
being at the unit.
Trending – User can view past and present controller points.
Information – Provides manufacturer support information as well as IOM resources.
Service – User must be logged with service access criteria (9998). Once proper login is established, the user can
view configured input/output points associated with the unit controller
®
Microprocessor Controller for DOAS 13
Main Menu Navigation
Unit Enable
Main Status Ctrl Variables Alarm Menu
Unit Status
Input Output Status
Note: Additional status screens are displayed depending on unit configuration. Screens may include, but are not limited to:
Occupancy Damper positions Fan status Airflow Setpoints Economizer Energy recover y Cooling Circuit pressure Heating Dehumidification Static pressure
Temp Control
Dehumidification
Refrigeration Compressor Control
Pressure Control
Damper Control
Energy Recovery
Fan Control Supply Fan Control
Exhaust Fan Control
Occupancy
Advanced
Note: The Advanced menu is read­only. The service password is required to change these settings. Reference the Advanced menu section for more information.
*Consult factory for more information.
Login
Manual Overrides
Adv. Setpoints*
Network Settings
Backup/Restore
IO Status/Offset*
IO Config
Unit Config
Unit Settings*
Active Alarms
Reset Alarms
Alarm History
Clear History
Export History
Service Info*
Alarm
Management
Shutdown
Alarms
General
Alarms
Microprocessor Controller for DOAS14
®
Unit Status Overview
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the operating conditions of the unit. Scroll through the menu screens by using the
THE INITIAL MENU SCREEN DISPLAYS THE JOB NAME, UNIT TAG , UNIT STATUS, OUTSIDE
AIR CONDITIONS, SPACE CONDITIONS AND SETPOINTS.
Possible modes include:
• Off/Standby
• Unoccupied Start
• Dampers Open
• Fan Start Delay
• Fans Starting
• Startup Delay
• System On
• Soft Shutdown
• System Disabled
• Remote Off
Unit Status Screen Symbols
Symbol Indicates
Supply air fan status. Rotation indicates airflow; static blades indicate no airflow.
Cooling
Heating
• Shutdown Alarm
• Fans Only
• Economizing
• Cooling
• Dehumidifying
• Heating
• HGRH Purging
• Defrost Active
• Overrides Active
• Expansion Offline
buttons.
Dehumidifying
Economizing
Defrost
INPUT OUTPUT STATUS
Displays real time conditions from sensors located in the unit and building space if equipped with space mounted sensors. Controller output conditions can also be viewed from this screen. To view the desired input/output point, the user must select the desired channel. Reference the Controller Overview section in this IOM for individual point locations.
OCCUPANCY STATU S
Displays current status of occupancy and the configured occupancy control method and time zone.
DAMPER COMMANDED POS
This screen appears if equipped with modulating outdoor air and recirculated air dampers. Displays current position of the outdoor air damper. Recirculating air damper position is the inverse of outside damper position.
®
SUPPLY FAN STATUS
This screen displays the fan enable command, fan proving status, and the supply fan ramp being sent from the controller to the VFD. The minimum and maximum speeds are set in the VFD (Reference unit Installation and Operation Manual for VFD programming). The controller can modulate the fan between the min and max speeds via an analog output.
Microprocessor Controller for DOAS 15
Unit Status Overview
EXHAUST FAN STATU S
This screen displays the fan enable command, fan proving status, and the exhaust fan ramp being sent from the controller to the VFD. The minimum and maximum speeds are set in the VFD (Reference unit Installation and Operation Manual for VFD programming). The controller can modulate the fan between the min and max speeds via an analog output.
AIRFLOW STATUS
This screen displays the current status of airflow volumes if the unit is provided with airflow monitoring.
AMBIENT LOCKOUT STATUS
Displays heating and cooling lockout status based on the outside air ambient temperature. Ambient lockouts for heating and cooling can be altered by entering Main Menu/Ctrl Variables/Temp Control/Cooling or Heating.
OUTSIDE RESET
This screen will be active if the controller is configured for outside air reset. The heating and cooling devices modulate to maintain the supply air temperature setpoint as determined by the outside reset calculation.
ACTIVE RESET
This screen will be active if temperature control mode is set for space or return air reset. The supply temperature setpoint is calculated based on the active setpoint and the current space or return temperature. The calculated setpoint is scaled between the supply temperature minimum and maximum setpoints determined by the current mode of operation.
SUPPLY SETPOINT
Displays current supply temperature and supply temperature setpoint to be achieved.
ECONOMIZER RAMP
The economizer ramp screen will be active if the unit is configured for an economizer control method. This screen displays the economizer setpoint, supply air discharge temperature, economizer ramp status, and economizer control mode of control. Economizer control mode options include, outside dry bulb, outside enthalpy, comparative dry bulb, and comparative enthalpy.
CO2 RAMP OUTPUT
The CO2 Ramp Output screen will be active if the unit is configured for CO
2
control. This screen displays the CO2 setpoint, CO2 level from the space, and the status of the control ramp.
ENERGY RECOVERY WHEEL STATUS
This screen provides overall status of the energy recovery wheel.
Microprocessor Controller for DOAS16
®
Unit Status Overview
DEFROST RAMP OUTPUT
This screen only appears if the unit has an energy recovery wheel and a frost control method was provided on the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will go into defrost if the outside air temperature is below the defrost temperature setpoint.
COOLING RAMP
This screen displays the active setpoint, supply discharge temperature, cooling enable/disable, cooling ramp being sent from the controller, and the overall capacity being demanded.
COMPRESSOR REQUEST
The compressor request screen will be active if the unit is equipped with DX cooling. Screen displays overall status of individual compressor operation being sent from the unit controller. Example: Circuit A compressor enable (On) with modulating value of 26%.
HEATING RAMP
This screen displays the active setpoint, supply air temperature, heating enable/ disable, and heating ramp being sent from the controller.
DEHUMIDIFICATION
This screen will display the overall dehumidification status and selected mode of dehumidification control.
The following dehumidification modes are available when the space is in occupied mode:
• Cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point *Available during unoccupied mode.
HGRH RAMP OUTPUT
This screen will display overall hot gas reheat status which includes active setpoint, supply air discharge temperature, hot gas reheat enable/disable, and hot gas reheat control loop being sent from the controller.
SUPPLY SPACE STATIC
This screen displays status points if the unit is configured for space static pressure control. Status points include controller output ramp, static pressure in the space, and the space static pressure setpoint. Similar status screen will appear for the exhaust fan if the unit is configured for exhaust fan space static control.
®
SUPPLY/RETURN DUCT STATIC
This screen displays status points if the unit is configured for duct static pressure control. Status points include controller output ramp, static pressure in the duct, and the duct static pressure setpoint. Similar status screen will appear for the exhaust fan if the unit is configured for exhaust fan duct static control.
Microprocessor Controller for DOAS 17
Menu
The controller is equipped with several menus to help guide users with altering program parameters. The following menus can be accessed by pressing the
button. To enter the desired menu, press the button.
Unit Enable
Control Variables
Control Variables
Temp Control
The Unit Enable menu allows the user to enable and disable the unit through the controller. Reference sequence of operation for additional unit starts/stop details.
The unit ships from the factory in a disabled state. To allow the unit to operate, the controller must receive a run command from digital input ID4. Jumper unit
terminals R - G to allow the unit to operate.
Change to (Enabled/Disabled): Enables user to manually turn unit on/off via
display. Unit terminal G must have 24 VAC power to enable the unit.
The Controls Variables menu allows the user to view and adjust unit control parameters.
The Temperature Control menu allows the user to view and adjust temperature control conditions of the unit.
METHOD FOR TEMPERATURE CONTROL
Possible Setpoint Sources:
Supply Temp Control – The supply discharge setpoint to be a constant value (e.g. 72°F). Reference Temperature Setpoint screen for setpoint adjustment.
Space Reset – The controller will reset the supply air temperature set point to maintain the room temperature set point (requires room temp sensor). Reference the Temperature Setpoint screen for room setpoint adjustment.
Return Reset – The controller will reset the supply air temperature set point to maintain the return air temperature set point (requires duct mounted return air temp sensor). Reference the Temperature Setpoint screen for return air setpoint adjustment.
OA Reset – The controller monitors the outdoor air temperature and adjusts the desired supply temperature set point accordingly. For example, when the outdoor air is below 55°F, the controller will change the supply set point to 70°F. If the outdoor air is above 65°F, the controller will change the supply set point to 55°F. If the outdoor air temperature is between 55°F and 65°F, the supply set point changes according to the outdoor air reset function. A visual representation of the outdoor air reset function is shown below. Reference Outside Setpoints for minimum and maximum outside air limits.
Microprocessor Controller for DOAS18
Outdoor Air Reset Function
75°
70°
65°
60°
55°
50°
Supply Air Set Point (°F)
45°
50° 55° 60° 65° 70°
Outside Air Temperature (°F)
®
Menu
OUTSIDE SETPOINTS
This screen only appears if outside reset is selected as the reset control mode.
TEMPERATURE SETPOINT
This screen only appears if supply temp control, space reset, or return reset is selected as the reset control mode.
Possible Setpoint Sources:
Local – The room set point will be constant; set from screen (e.g. 72°F). BMS – The BMS can directly control the room temperature set point (requires
BMS communication option). T-Stat – The room set point will be adjustable from the room thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
HEAT COOL DEADBAND
This screen only appears if space reset or return air reset is selected as the reset control mode. The heat cool deadband allows for separate cooling and heating setpoints when the reset control mode is set for space reset or return air reset.
SUPPLY SETPOINTS
Cooling and heating supply setpoints screens only appear if outdoor reset, space reset, or return air reset is selected. These screens allow the user to set the minimum and maximum setpoint limits for cooling or heating operation. The controller will adjust the supply temperature setpoint between the set limits depending on mode of operation.
MODE SWITCH DISPLAY
This screen displays the delay time required before switching between heating and cooling mode.
STAR TUP DISPLAY
This screen displays the delay time after the fans have started and tempering begins
®
COOLING LOCKOUT
This screen displays the cooling lockout temperature. Cooling will be disabled when outside air is below the cooling lockout temperature (55ºF).
Microprocessor Controller for DOAS 19
Menu
HEATING LOCKOUT
This screen displays the heating lockout temperature. Heating will be disabled when outside air is above the cooling lockout temperature (80ºF).
SPACE SETPOINTS DURING THE UNOCCUPIED MODE
The controller will have separate screens for unoccupied cooling and heating setpoints. Reference Occupied control variables for further detail.
Unoccupied Cooling Example: If setpoint = 80ºF, unoccupied cooling is enabled when room equals 80ºF and above. Unoccupied cooling is disabled when room temperature is below 75ºF.
Unoccupied Heating Example: If setpoint = 60ºF, unoccupied heating is enabled when room temperature equals 60ºF and below. Unoccupied heating is disabled when room temperature is above 65ºF.
Control Variables
Dehumidification
The Dehumidification menu allows the user to view and adjust dehumidification control parameters.
THIS SCREEN DISPLAYS METHOD FOR DEHUMIDIFICATION.
Possible Methods:
• Outside Air Temp is greater than cold coil setpoint plus offset (10ºF)
• Inside RH*
• Inside dew point*
• Outside dew point
• Inside RH or inside dew point*
• Inside RH or inside dew point or outside dew point
• Inside RH and inside dew point*
• Inside RH and inside dew point or outside dew point *Available during unoccupied mode.
There must be a constant call for dehumidification for the duration of the enable delay for dehumidification mode to become enabled. The call remains active until conditions are satisfied and dehumidification mode has been active for the minimum active time. Reference Ctrl Variables/Advanced/Unit Config/Unit Configuration Occupied Dehum Call for dehumidification method options.
THIS SCREEN DISPLAYS METHOD FOR DEHUMIDIFICATION IN UNOCCUPIED MODE.
If the unit is unoccupied while there is a dehumidification call, the unit will start and dehumidify until the unoccupied dehumidification setpoints are satisfied. The above dehumidification modes marked with an * indicate availability during unoccupied mode. The unoccupied dehumidification mode can be set differently than the occupied dehumidification mode. Reference Ctrl Variables/Advanced/ Unit Config/Unit Configuration Unoccupied Dehum Call for dehumidification method options.
Microprocessor Controller for DOAS20
®
Menu
THIS SCREEN DISPLAYS HYSTERESIS FOR ENABLING DEHUMIDIFICATION DURING O
CCUPIED AND UNOCCUPIED CONDITIONS.
%RH for indoor RH control and ºF for indoor dew point control. Example: If indoor RH setpoint = 50%, dehumidification is enabled when indoor RH equals 50% and above. Dehumidification is disabled when indoor RH is below 44%.
THIS SCREEN ALLOWS ADJUSTMENT FOR DELAY AND MINIMUM ON TIME FOR DEHUMIDIFICATION MODE.
Times are in place to prevent short cycling between dehumidification and other control modes.
THIS SCREEN DISPLAYS THE TEMPERATURE SETPOINTS FOR THE COOLING COIL.
This screen only appears if the unit is equipped with cooling. When in dehumidification mode, the controller will maintain the active cold coil set point. The active set point will be determined by the set point source.
Possible Set Point Sources:
Local – The supply set point will be constant; set from screen (e.g. 55°F). BMS – The cold coil leaving air temperature set point can be adjusted over the
BMS via the dehumidification set point (Reference Points List).
THESE SCREENS DISPLAY DEHUMIDIFICATION PRIORITY SELECTIONS.
The following priorities are used to determine what is more important in the unit: temperature over dehumidification or heating over dehumidification. Both priority selections determine when the unit is allowed to dehumidify.
1. Temperature over Dehumidification
Determines when the unit is allowed to dehumidify based on the space/return air temperatures.
a. Temperature - If temperature is set as the priority and the space or return air is over cooled, dehumidification is locked out until the space or return temperature is no longer over cooled.
b. Dehumidification - If the priority is dehumidification and the space or return air is over cooled, the coil offset will be added to the coil leaving setpoint. (Default 0ºF offset).
c. Over Cooled - If space or return reset is enabled, the target is considered over cooled when it is 4°F below setpoint for 5 minutes. It remains over cooled until the target is at setpoint and over cooled has been active for a minimum of 5 minutes.
2. Heating over Dehumidification
Determines when the unit is allowed to dehumidify when heating is active.
a. Heating - If priority is set to heating, the unit locks out dehumidification while heating is active.
b. Dehumidification - If priority is set to dehumidification, the unit is allowed to switch to dehumidification when heating is active.
®
THIS SCREEN DISPLAYS THE COMPRESSOR DEHUMIDIFICATION FORCE.
In dehumidification mode, the lead compressor will continue to run as long as the dehumidification mode sequence has been enabled in order to prevent compressor cycling and potential reevaporation of moisture. To disable this operation and allow the compressor to cycle in dehumidification mode, uncheck the applicable cooling ramps.
Microprocessor Controller for DOAS 21
Menu
Control Variables
Refrigeration
Control Variables
Damper Control
The Refrigeration menu allows the user to view and adjust compressor and condenser settings, if equipped.
REFRIGERATION MENU
Consult factory prior to adjusting parameters in Refrigeration Menu.
The Damper Control menu’s allows the user to adjust damper control setpoints. Economizer setpoint adjust will also be found at this location if the unit is equipped with outside air and recirculation dampers.
THIS SCREEN ALLOWS ADJUSTMENT FOR DELAY TIME BETWEEN DAMPER OPENING
AND FAN OPERATION.
This timer allows the damper to open before the fan start sequence begins. This prevents the fans from having to overcome higher static pressure when the damper(s) are opening.
THIS SCREEN DISPLAYS THE OUTDOOR AIR DAMPER SET POINT AND ONLY APPEARS IF
UNIT IS EQUIPPED WITH A MODULATING OUTDOOR AIR AND RECIRCULATING DAMPE R.
The set point is the proportional percentage of the outdoor air damper being open.
0% = Full recirculation air 100% = Full outdoor air
Minimum Position – When in the occupied mode, the active set point will be equal to a local minimum OA set point, which may be constant or reset by fan speed if equipped with a modulating supply fan. The OA damper set point can then be further adjusted between the minimum and maximum OA settings with sequences such as DCV CO
, Building Pressure and Economizer.
2
Maximum Position – Each sequence that can adjust the OA damper set point contains a maximum position to prevent excess OA. The active set point will be determined based on the greatest demand of the configured sequences. For example, if a unit is equipped with a DCV CO
and an economizer sequence, the
2
OA damper set point will react to an economizer demand even if the CO2 set point is satisfied. Likewise, if economizer is not available but CO2 is above set point, the OA damper will open to satisfy the CO
set point.
2
Economizer – The active set point will be reset based on Economizer demand, between the minimum and maximum positions.
Possible Setpoint Sources:
Local – The minimum outdoor air percentage is constant; set by the controller.
SF Reset – The min and max positions are reset by the supply fan speed.
BMS – The BMS can directly control the OA damper position up to the max BMS
percentage.
Building Pressure – Damper position is reset by a building pressure control loop.
DCV CO
loop based on room CO
– Damper position is reset by a demand-controlled ventilation control
2
levels.
2
2 Position – Damper position is reset to “2-Pos/Max Econ:” set point when a contact closure is made. The 2-position damper operation can also be setup to bring the unit into temporary occupied mode until the contact is broken (Max Ventilation Mode - enabled in manufacturer menu settings).
Microprocessor Controller for DOAS22
®
Menu
SCREENS DISPLAY ECONOMIZER CONTROL VARIABLES.
This screen only appears if economizer functionality was provided with a modulating outdoor air damper.
The outside air damper will modulate between the minimum and maximum position to maintain the supply temperature setpoint.
The user can select the economizer control method from the following options:
Outside Dry Bulb – Economizing is allowed when the outside dry bulb is less than the economizer temperature enable setpoint.
Outside Enthalpy - Economizing is allowed when outside enthalpy is less than the economizer enthalpy setpoint.
Comparative Dry Bulb - Economizing is allowed when outside temperature is less than the space or return temperature.
Comparative Enthalpy - Economizing is allowed when outside enthalpy is less than the space or return enthalpy.
THIS SCREEN DISPLAYS THE HYSTERESIS SETTINGS FOR ECONOMIZER CONTROL.
There is a built-in hysteresis that disables economizer above the economizer setpoint.
(Example: If Economizer Outside Dry Bulb = 65°F, economizer operation is disabled above 67°F).
THIS SCREEN DISPLAYS THE ENERGY REDUCTION ONLY CONTROL.
If enabled, the OA damper and recirculation damper will not modulate during economize. Instead, only the energy recovery wheel will be stopped to ensure no energy is transferred from the supply airstream and exhaust airstream.
®
Microprocessor Controller for DOAS 23
Menu
Control Variables
Energy Recovery
The Energy Recovery menu allows the user to adjust energy recovery wheel sequence setpoints.
THIS SCREEN DISPLAYS THE TEMPERATURE AT WHICH THE UNIT WILL ENABLE FROST C
ONTROL MODE IF NECESSARY (FACTORY DEFAULT=5ºF)
This screen only appears if the unit has an energy recovery wheel and a frost control method was provided with the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will enter defrost mode if the outside air temperature is below this temperature setting. Max Active Time and Min Off Time will be available if the frost control method was provided as timed exhaust or cycle wheel.
THIS SCREEN DISPLAYS THE ENERGY RECOVERY WHEEL JOG FUNCTION
This screen display the energy recovery wheel jog function.
This screen only appears if the unit has an energy recovery wheel and stop wheel economizer method for control.
Momentarily enables the wheel in order to expose a new section to the airstream.
Microprocessor Controller for DOAS24
®
Menu
Control Variables
Fan Control
Supply Fan Control
The Supply Fan Control menu allows the user to adjust exhaust control setpoints
THIS SCREEN DISPLAYS THE SUPPLY FAN DELAY.
The supply fan delay will begin once the damper sequence is complete. This delay can be used to offset starting times between the supply fan and exhaust fan.
THIS SCREEN DISPLAYS MINIMUM AND MAXIMUM SUPPLY FAN SPEED PERCENTAGES.
The speed set point is the proportional percentage of the analog output from the controller to the VFD.
50% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication
option).
Duct Pressure – Fan speed is determined by duct pressure control loop.
Space Pressure – Fan speed is determined by building pressure control loop.
CO
– Fan speed is determined by CO2 control loop.
2
Single Zone VAV - The supply fan is modulated in addition to the supply air
temperature to satisfy the room temperature set point. A room temperature sensor is required.
2-Speed (High Speed Set Point) - Supply fan speed is reset to maximum speed when a contact closure is made. (Max Ventilation Mode).
®
THIS SCREEN DISPLAYS SOFT SHUTDOWN ENABLE CONDITIONS.
During a soft shutdown the following will occur:
• Tempering outputs immediately revert back to their off value; while
• Dampers remain open and fans continue to run; until
- The supply air temperature falls below the soft shutdown enable setpoint minus 5.0ºF; or
- The soft shutdown delay timer has expired.
Microprocessor Controller for DOAS 25
Menu
Control Variables
Fan Control
Exhaust Fan Control
The Exhaust Fan Control menu allows the user to adjust exhaust control setpoints.
THIS SCREEN DISPLAYS THE EXHAUST FAN DELAY AND ENABLE BASED ON OUTSIDE AIR DAMPER POSITION.
The exhaust fan delay will begin once the damper sequence is complete. This delay can be used to offset starting times between the supply fan and exhaust fan. This screen also provides the ability to enable the exhaust fan on a set outdoor air damper position if the unit is equipped with a modulating outdoor air damper.
THIS SCREEN DISPLAYS MINIMUM AND MAXIMUM EXHAUST FAN SPEED PERCENTAGES.
The speed set point is the proportional percentage of the analog output from the controller to the VFD.
25% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication
option).
Space Pressure – Fan speed is determined by building pressure control loop.
Supply Fan Tracking with Offset – The exhaust fan will track the supply fan,
between a minimum and maximum position. An offset can be added to achieve the proper balance.
Outdoor Air Damper Tracking – The exhaust fan will proportionally track the outdoor air damper, between a minimum and maximum position.
Return Duct Static Pressure – Fan speed is determined by duct pressure control loop.
Microprocessor Controller for DOAS26
®
Menu
Control Variables
Occupancy
The Occupancy menu allows the user to adjust occupancy control parameters which includes occupancy control mode and schedule.
THIS SCREEN DISPLAYS THE CURRENT MODE OF OPERATION FOR OCCUPANCY CONTROL. STATU S OF THE OTHER MODE OPTION CAN ALSO BE FOUND ON THIS
SCREEN.
This screen allows the user to select the source of determining occupancy. The factory default is terminal ID6 on the controller.
BMS: BMS control (Reference Points List). BMS can be overridden with ID6.
Digital Input: Typically used with a remote time clock, motion sensor or switch.
Always Occ: Controller will always remain in occupancy mode.
Always Unocc: Controller will always remain in unoccupancy mode.
Schedule: Allows the user to set an occupancy schedule for each individual day
of the week.
THIS SCREEN ALLOWS THE USER TO ADJUST THE SCHEDULE.
Requires the user to enter a start time, stop time and the applicable days of the schedule.
THIS SCREEN DISPLAYS UNOCCUPIED START ENABLE MODES.
This screen only appears if unit is provided with unoccupied recirculation.
This screen allows the user to enable/disable modes of operation when in unoccupied recirculation control.
THIS SCREEN DISPLAYS OCCUPANCY OVERRIDE CONDITIONS.
Screen allows the user to override occupancy for a set duration.
®
Microprocessor Controller for DOAS 27
Menu
Control Variables
Advanced
Control Variables
Advanced
Manual Overrides
The Advanced menu allows the user to access several submenus regarding controller information, controller overrides, network settings, I/O configuration, and unit configuration. Submenu options are read only and will require the user to input proper login criteria. The service password (9998) is required to change service access menus. Consult factory for factory level access.
The Manual Overrides menus are for start-up, commissioning, and troubleshooting.
THIS SCREEN ALLOWS THE USER TO ACCESS THE IG FURNACE COMMISSIONING MENU.
This screen only appears if an indirect gas furnace was provided with the unit. Entering the furnace commissioning menu will step the user through the furnace start-up.
MANUAL OVERRIDE MODE
The Manual Overrides menu is for start-up, commissioning, and troubleshooting. This menu allows the user to override the control loops and specific inputs and outputs.
To access the Manual Overrides submenus, enter the service password (9998). Manual overrides must be enabled at this screen to allow the user to override control loops. Override options must be changed from Auto to Manual for manual control.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE UNIT ON OR OFF.
When manual override is set to enable, use the arrow buttons to turn the unit on or off.
THIS SCREEN ALLOWS THE USER TO OVERRIDE OCCUPANCY CONTROL.
When manual override is set to enable, use the arrow buttons to change occupancy control.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE SUPPLY FAN VFD SPEED.
The speed is the proportional percentage of the analog output from the controller to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
Microprocessor Controller for DOAS28
®
Menu
THIS SCREEN ALLOWS THE USER TO OVERRIDE EXHAUST FAN VFD SPEED.
This screen only appears if the unit is equipped with a exhaust fan VFD controlled by the microprocessor.
The speed is the proportional percentage of the analog output from the controller to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE POSITION OF THE OUTDOOR AIR D
AMPER.
This screen only appears if the unit is equipped with a modulating outdoor air and recirculation damper. The recirculation damper position will be the inverse of the outdoor air damper position shown.
0% = Outdoor air damper closed
100% = Outdoor air damper fully open
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE COMPRESSOR OPERATION
This screen only appears if the unit is equipped with DX cooling. When manual override is set to enable, use the arrow buttons to turn individual compressor requests on or off.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE MODULATING COMPRESSOR CONTROL LOOP.
When manual override is set to enable, use the arrow buttons to change the compressor modulation value.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE COOLING OPERATION.
When the cooling control is in the manual mode, use the arrow buttons to vary the cooling output.
Chilled Water: The cooling percent is directly proportional to the 0 - 10 VDC output signal.
0% Cooling = 0 VDC
100% Cooling = 10 VDC
Packaged Cooling: The cooling percent displays compressor engagement as a percent. The compressors are subject to the minimum on/off times and heating/ cooling lockouts.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE ELECTRIC HEATER OPERATION.
This screen only appears if the unit is equipped with electric post heat. Electric heater percentage is directly proportional to the 0 – 10 VDC output signal.
®
Microprocessor Controller for DOAS 29
Menu
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE HEATING OPERATION.
When the heating control is in the manual mode, use the arrow buttons to vary the heating output.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE ECONOMIZER CONTROL OPERATION.
When the heating control is in the manual mode, use the arrow buttons to vary the heating output.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE HOT GAS REHEAT OPERATION.
This screen only appears if modulating hot gas reheat option was provided with the unit. When the hot gas reheat loop control is in the manual mode, use the arrow buttons to vary the reheat output.
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE ENERGY RECOVERY DEFROST OPERATION.
This screen only appears if modulating wheel frost control is equipped. When the defrost control ramp is in manual mode, use the arrow buttons to vary the defrost output.
0% = Maximum Wheel Speed
100% = Minimum Wheel Speed
Control Variables
Advanced
Network Settings
The Network Settings Menus allows the user to view and modify network settings. The service password (9998) is required to make changes.
THIS SCREEN ALLOWS THE USER TO VIEW AND ADJUST CONTROLLER TCP/IP SETTINGS.
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when the Web User Interface will be utilized. The controller may have a DHCP server­assigned address or a manually-assigned static IP address. Factory settings are shown in the screen to the left.
To change pCO Board Address parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view pCO Board Address screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the controller to initialize.
6. View pCO Board Address Config. If changed values did not save, contact the factory.
THIS SCREEN ALLOWS THE USER TO VIEW AND ADJUST CONTROLLER BACNET IP CONFIG SETTINGS.
This screen will appear if the unit is set for BACnet IP and allows the user to set the device and port settings.
Microprocessor Controller for DOAS30
®
Menu
THIS SCREEN ALLOWS THE USER TO VIEW AND ADJUST CONTROLLER MODBUS TCP S
LAVE.
This screen will appear if the unit is set for Modbus TCP and allows the user to set device ID number.
THIS SCREEN ALLOWS THE USER TO ADJUST BACNET AND MSTP PARAMETERS.
This screen only appears if the selected BMS protocol is set to BACnet MSTP. Factory settings are shown in the screen to the left.
To change BACnet MSTP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view BACnet MSTP Config screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the controller to initialize.
6. View BACnet MSTP Config. If changed values did not save, contact the factory.
THIS SCREEN ALLOWS THE USER TO ADJUST MODBUS PARAMETERS.
This screen only appears if the selected BMS protocol is set to Modbus. Factory settings are shown in the screen to the left.
To change Modbus RTU parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view Modbus RTU Config screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the controller to initialize.
6. View Modbus RTU Config. If changed values did not save, contact the factory.
®
THIS SCREEN ALLOWS THE USER TO ENABLE THE BMS WATCH D OG FUNCTION.
The BMS watchdog function verifies BMS connectivity. The watchdog is required for the BMS to take the place of a hardwired sensor. The BMS toggles the watchdog variable from true to false within the timeout delay. If the timer expires, the controller falls back to hardwired sensors until the BMS connection can be established. At this time, a BMS watchdog alarm activates.
The following variables may be used by the BMS in place of hardwired sensors:
• Outside_RH_from_BMS
• Outside_Temp_from_BMS
• Return_RH_from_BMS
• Return_Temp_from_BMS
• Space_1_CO2_from_BMS
• Return_CO2_from_BMS
• Space_RH_from_BMS
• Space_Static_from_BMS
• Space_Temp_from_BMS
SENSOR SOURCE SPACE TEMP
The sensor source can be changed to source by BMS through the controller or by a dedicated BMS point. Reference Points List above and in the Appendix for more detailed point information. Screen to the left is an example of the sensor source type. Source can be set for local or BMS at this screen.
Microprocessor Controller for DOAS 31
Menu
Control Variables
Advanced
Backup/Restore
The Backup/Restore Menus allows the user to create a backup file of setpoints and configuration variables on a USB drive or in the controller’s internal memory.
Connecting to USB Drives
The controller has built-in USB ports for connecting to USB drives. The USB drives can be used for backing up all settings and reported conditions such as alarm history and current values. This creates a file named User_Backup.txt.
USB Type A
USB Type B
CREATING A BACKU P FILE
Important:
• At first startup or commissioning, or prior to communicating with Technical Support about performance issues, we recommend creating a backup file for each controller.
• Name each file with the unit sales order–line number found on the silver nameplate attached to the electrical access door.
• Also consider creating a backup file whenever significant program changes are made.
To create a system backup file using the handheld or virtual keypad/display buttons:
1. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter
and Up or Down arrow buttons to enter the service password, which is 9998.
2. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
3. Press the Up or Down arrow buttons to navigate to the Backup Settings screen.
4. Press the Enter and Up or Down arrow buttons to select the backup location
(internal memory or USB). If creating a backup to a USB drive, insert a USB drive into the main controller.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the Save
checkbox. This action creates the backup file.
Microprocessor Controller for DOAS32
®
Menu
RESTORING FROM A BACKUP FILE
From USB
1. Place the restore file in the root directory of a USB drive. (Do not place the file within a folder on the USB drive.) The file must be named: User_Backup.txt
2. Insert the USB drive into the controller’s USB port.
3. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down arrow buttons to disable the unit.
4. Go to the Main Menu/Ctrl Variables/Advanced/Login and Up or Down arrow buttons to enter the service password (9998).
5. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
6. Press the Up or Down arrow buttons to navigate to the USB Restore screen.
7. Press Enter to highlight and then the Up or Down arrow buttons to fill the Restore checkbox. This action restores the backup file. If there is an error during the process, the specific error is displayed on this screen.
8. Cycle power to the controller.
From internal memory
1. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down arrow buttons to disable the unit.
2. Go to the Main Menu/Ctrl Variables/Advanced/Login and Up or Down arrow buttons to enter the service password, which is 9998.
3. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
4. Press the Up or Down arrow buttons to navigate to the Internal Restore screen. This screen is only available when a backup file exists in internal memory.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the Restore checkbox. This action restores the backup file. If there is an error during the process, the specific error is displayed on this screen.
6. Cycle power to the controller.
screen. Press the Enter
screen. Press the Enter
®
Microprocessor Controller for DOAS 33
Menu
Control Variables
Advanced
I/O Configuration
Control Variables
Advanced
Unit Configuration
The IO Configuration Menu allows the user to view and modify controller input and output points.
THIS SCREEN ALLOWS THE USER TO VIEW AND EDIT I/O POINTS.
This screen is read only and will require the factory password to make changes. Screen to the left is an example of an analog input configuration screen. Similar screens appear for remaining I/O when selected.
To monitor individual I/O points:
1. Press the enter button to highlight the I/O type.
2. Press the up and down arrows to change the IO type.
3. Press the enter button to highlight the controller channel.
4. Press the up and down arrows to change the channel.
THIS SCREEN ALLOWS THE USER TO ENABLE I/O CONFIGURATION EDITS.
Changes to the IO configuration requires the factory login password. Consult factory for IO configuration changes.
ADJUSTMENT OF I/O CONFIGURATION MUST ONLY BE DONE UNDER FACTORY GUIDANCE! IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM DAMAGE!
The Unit Configuration menus allows the user to view unit configuration provided from factory. Configuration menus listed below can be altered with the factory password. Consult factory for unit configuration changes!
THIS SCREEN ALLOWS THE USER TO VIEW AND CHANGE THE EXHAUST FAN CONTROL T
YPE.
Reference control variables for possible exhaust fan control methods.
THIS SCREEN ALLOWS THE USER TO VIEW AND CHANGE THE UNOCCUPIED DEHUMIDIFICATION CALL.
Reference control variables for possible unoccupied dehumidification call methods.
THIS SCREEN ALLOWS THE USER TO VIEW AND CHANGE THE UNOCCUPIED UNIT OPERATION.
Possible unoccupied unit operation methods include:
• Unit Off
• Night Setback Cycle*
• Recirculation with Unoccupied Setpoints*
• Normal Operation with Unoccupied Setpoints
Note: An askterisk indicates method is only available if the unit is equipped with an unoccupied recirculation damper.
THIS SCREEN ALLOWS THE USER TO ENABLE MORNING WARM UP AND COOL DOWN.
The user can enable morning warm up, morning cool down, and set the duration for the sequence.
Microprocessor Controller for DOAS34
®
Alarms
Menu
The Alarms menu allows the user to view active alarms, reset active alarm (if possible), and alarm history.
ACTIVE ALARMS
If an alarm occurs, the button will glow red on the controller and the remote display (if installed).
To view alarm, press the Alarm button once. This will display the most recent alarm. If the alarm cannot be cleared, the cause of the alarm has not been fixed. Press the up and down buttons to view any additional occurring alarms.
RESET ACTIVE ALARMS
This screen allows the user to clear active alarms.
ALARM EVENT HISTORY
This screen allows the user view recent alarms. To view all saved alarms, press the “down” button to enter the data logger.
CLEAR ALARM LOG
This screen allows the user to clear all alarms in alarm log history.
IG Furnace Alarm (AL) Descriptions
IG no flame 3 try AL
IG combustion fan high pressure switch failure
IG furnace ignition control Indicates an alarm from the ignition controller. Alarm only
Pressure switch closed with combustion fan off
Combustion fan not proved
IG furnace max retry Indicates that the max number of retries was reached. Alarm and Furnace lockout
IG High Temp AL
IG offline Indicates communication with furnace control has failed. Alarm only
IG Lg Man No Flame AL No flame after 3 trials for ignition on the large manifold. Alarm only
Indicates a furnace failure to light or properly sense flame after 3 trials.
Indicates a call for high speed combustion fan but high pressure switch did not close.
Indicates low pressure switch was closed with no call for combustion fan.
Indicates a call for low speed combustion fan but low pressure switch did not close.
Indicates that power was lost from the High Temp Limit Sensor. Check for high limit trip.
Alarm only
Alarm only
Alarm only
Alarm only
Alarm only
®
Microprocessor Controller for DOAS 35
Appendix: Remote Display (pGD1)
The pGD1 is an optional remote display for use with manufacturer’s microprocessor controllers. The remote display allows for remote monitoring and adjustment of parameters of the unit mounted controller. The remote display allows identical access to menus and screens as the unit mounted controller display.
Specifications
Carel Model PGD1000W00
Power Supply
Max distance from unit controller 150 feet
Required Cable 6P6C RJ25/RJ12 Cable (straight)
Operating Conditions
Display Type Backlit LED with lighted buttons
Installation
The remote display connects to the unit mounted controller through a six-wire RJ25 or RJ12 telephone cable (straight). When ordered from the factory, a 10 ft. cable is provided with the remote display. The display and cable can be used to assist with start-up and maintenance.
Connecting Cable
If mounted remotely, the factory cable can either be extended or replaced with a longer cable to obtain the necessary distance. The resulting cable connections should be a “straight through cable,” where pins on one end correspond identically to the pins on the opposite end. If making your own cable, use the same pin-out for each end.
12
3
Power supplied from unit controller through RJ25 cable
-4°F to 140°F, 90%RH (non-condensing)
5
4
6 12
3
5
4
6
NTC Temperature Sensor Chart
120
110
100
90
80
70
60
50
Temperature (ºF)
40
30
20
10
0
4 6 8 10 12 14 16 18 20 22 24 26 28
Resistance (k:)
Microprocessor Controller for DOAS36
®
Appendix: I/O Expansion Board (c.pCOe) Quick Start
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from large board controller. It allows the user to view and control:
6 Universal Inputs (Digital Input*, NTC, 0/1VDC, 0/10VDC, 0/20mA, 4/20mA, 0/5VDC) *Only dry to ground contacts
24 VAC
Power
Address Ext. ProtBaud
OFF
ON
1234567
8
9101112131415
Address Ext Baud Prot
can be utilized for digital inputs. Applying voltage will result in damage to the I/O expansion board.
4 Analog Outputs (VDC)
6 Digital Outputs
The inputs and outputs can be monitored and controlled by the Building
Universal
Inputs
Analog
Outputs
57.6 K
Modbus
9.6 K
38.4 K
CAREL
19.2 K
Digital
Outputs
Management System. Reference Points List for detailed point information.
Setup
In order for the controller to communicate with the c.pCOe, several parameters must be adjusted. If you have a c.pCOe installed from the factory, the controller is already set up for communication with the main controller. The factory password is required for expansion board and I/O configuration updates. Consult factory for I/O configuration changes.
Enabling the pCOe in the Main Controller. - To enable the c.pCOe expansion I/O module, go to Ctrl Variables/Advanced/Unit Config. User will have to enter the Factory Password to make any edits at this point. Consult factory for factory password and configuring the expansion board. The expansion board must be enabled to configure spare I/O points. Once enabled, the user must reboot the controller. See screens to the left for expansion board enable points.
Configuring the I/O Type - In order to edit and configure the I/O configuration of the unit, go to Ctrl Variables/Advanced/I/O Configuration. The user must enable the Editable option for configuring I/O points. If configuring a new I/O point, ‘Scroll by All Configured’ must be deselected to view all I/O options.
Change or Update the I/O Point - Once the editable option is selected, the user must scroll to the I/O Configuration Menu. At this menu the desired I/O type can be selected. Once selected the user can configure the desired channel at the expansion board. The channel will have an ‘E’ designation for expansion board. Aux In Customer 1–6, Aux Analog Out 1-4, and Aux Digital Out 1-6 will be allocated for the I/O expansion board. See example to the left.
Viewing c.PCOe Auxiliary Values – Once the expansion board I/O is configured, the user can view and/or change the I/O type by navigating to Ctrl Variables/Aux I/O Config.
®
Microprocessor Controller for DOAS 37
Appendix: Room Thermostat Quick Start
The room thermostat gives users the ability to view the room temperature and relative humidity (optional) and control the active room set points from the adjustable display. The room thermostat also has the ability to send the unit into temporary occupied mode. It is also provides the functionality to average up to 4 temperature readings through the microprocessor. The room thermostat is shipped loose with installation by others and is a Modbus connected device.
Room thermostat functions:
• Temporary occupancy override control
• Temperature and relative humidity monitoring
• Temperature and relative humidity set point adjustability
• Status icon on LCD display with push buttons
• Optional temperature monitoring up to 4 sensors
Display
If more than one room thermostat is provided for averaging, only one room thermostat will be provided with a display and push buttons for adjustment.
Adjusting SET POINT - The default display will show the current temperature value for the room. Use the scroll button to index through additional sensor parameters. Parameters with the "SET POINT" icon displayed above the temperature display are adjustable. Use the Up/Down buttons to adjust the set point, and use the scroll button to view the next parameter or return to the normal display mode.
Up/Down Button Function - The Up/Down buttons are used to adjust editable parameters including the temperature and humidity set point.
Override Button Function - The display shows a person in the lower left corner of the display at all times. If the person is solid, the unit is operating in occupied mode. If it is an outline of the person, the unit is in unoccupied mode. Pushing the Override button when the unit is in unoccupied mode will allow a temporary override sequence to Occupied mode for a period of 1 to 3 hours (adjustable at the unit microprocessor).
Initial Setup and Communication Configuration
The room thermostat is a Modbus connected device There can be up to three additional Modbus temperature sensors added for room temperature averaging. The sensors must all be connected in a daisy chain configuration.
The microprocessor controller will be pre-configured for one room thermostat. If room temperature averaging is desired, additional field setup will be required both in the controller and on the Modbus room sensors:
• Each room sensor must have the DIP switches adjusted on the back of the sensor to the corresponding switches. Reference Room Thermostat Modbus Address chart on the following page for DIP switches settings.
• Once the address is set and the wires are connected the “Status” LED should be a steady green and the “Network” LED should be a quick blinking amber/green color.
• In the Controller, enter the Ctrl Variables Menu/Temperature and scroll down in the Temperature Menu to select BAPI Modbus Stat. Choose the number of room sensor being used (1-4).
Microprocessor Controller for DOAS38
®
Appendix: Room Thermostat Quick Start
Status LED
Green indicates that the unit is operating properly. Red indicates that there is a problem with the unit.
Terminal Description
GND Power Supply Ground (common to the controller)
Net B RS485 network connection (Data - )
Net A RS485 network connection (Data +)
Power Power supply hot
Unit
Controller
+Vtermo
GND
-
TAP-Stat
POWER
GND
NET B
Tx/Rx
+
NET A
Network LED
Flashing Red Slowly indicates that there has been no communications for 60 seconds.
Flashing Green Slowly indicates that there have been normal communications within
the last 60 seconds.
Flashing Green Slowly with Quick Red Flashes; the quick red flashes indicate active communications.
Room Thermostat Modbus Address
T-Stat 1 (Display) T-Stat 2 T-Stat 3 T-Stat 4
Address in Microprocessor 10 11 12 13
Dip Switch Set on Stat Sw 2 + Sw 8 Sw 1 + Sw 2 + Sw 8 Sw 4 + Sw 8 Sw 1 + Sw 4
In order for the room thermostat to communicate with the microprocessor, the correct baud rate must be set in the room thermostat. To set the baud rate:
• The “PROG” DIP switch on the back of the room thermostat must be flipped to the right side.
• Use the Setpoint Down button to display P11 on the room thermostat.
• Push the Scroll button and use the Setpoint Up/Down buttons to adjust the baud rate to 192.
• Once 192 is displayed, push the Scroll button again to save the setting. Once the setting is saved, P11 should appear on the display.
• Flip the “PROG” DIP switch on the back of the room thermostat back to the left. The room thermostat should communicate and be set back to normal mode.
If the occupancy override time needs to be adjusted:
• If the occupancy override is enabled from the room thermostat or the unit microprocessor, it will override for the period of time set on this menu screen.
• To adjust the temperature override time, enter the following menu options at the controller, Cntrl Variables/Occupancy. Scroll down at the Occupancy Menu and select Occ Timed Override. This menu will allow the user to enable occupancy override from the controller and set override duration.
®
Baud Rate Setting
Occupancy Override Time Adjustment
Microprocessor Controller for DOAS 39
Appendix: GreenTrol® Airflow Monitoring Quick Start
The GreenTrol® airflow monitoring station measures airflow using advanced thermal dispersion technology. An integral LCD display provides a local indication of airflow measurement and device configuration. The airflow monitor also features Modbus communication allowing the main unit microprocessor to monitor the airflow as well. The GreenTrol also accepts up to two airflow probes for averaging.
GreenTrol Airflow Monitor functions:
• LCD readout of measured airflow
• Dual airflow probe averaging
• Modbus connectivity
Display and Navigation
The LCD screen will by default show the current airflow that is being measured. To enter the menu to set up the monitoring station the user must remove the front cover of the GreenTrol to uncover the navigation buttons. Press and hold the UP and DOWN buttons at the same time for 3 seconds to enter the menu.
Enter Button Function - The ENTER button allows the user to go into the selected menu or function, as well as save the selected value.
Up/Down Button Function - The Up/Down buttons are used to navigate the menu and to change values in the menu.
Esc Button Function - The ESC button allows the user to exit the current menu or function.
Microprocessor Controller for DOAS40
®
VARIABLE DESCRIPTION
Cold_Coil_1_Temp_
Analog_Input
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Outside_Air_Temp_
Analog_Input
Space_Temp_Analog_
Input
Supply_Temp_Analog_
Input
Outside_RH_Analog_
Input
Space_RH_Analog_
Input
Space_Static_
Pressure_Analog_Input
Supply_Duct_Static_
Pressure_Analog_Input
Space_CO2_1_
Analog_Input
Circuit_A_Discharge_
Pressure_Analog_Input
Circuit_B_Discharge_
Pressure_Analog_Input
Aux_In_Customer_1
Aux_In_Customer_2
Aux_In_Customer_3
Aux_In_Customer_4
Aux_In_Customer_5
Aux_In_Customer_6
Cold Coil 1 Temperature 25 AI
Controls Lite Cooling Coil
Setpoint Temperature value
Controls Lite Supply
Setpoint Temperature value
Outside Air Temperature 37 AI
Space Temperature 44 AI
Supply Temperature 45 AI
Outside % Relative
Humidity
Space % Relative Humidity 89 AI
Space Static Pressure 94 AI
Supply Duct Static Pressure 95 AI
Space 1 CO2 ppm 116 AI
Circuit A Discharge
Pressure
Circuit B Discharge
Pressure
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Customer defined auxiliary
input
Appendix: Points List
ACTIVE
TEXT
INACTIVE
TEXT
Analog Inputs - Read Only
OBJECT
INSTANCE
31 AI
32 AI
86 AI
119 AI
121 AI
640 AI
642 AI
644 AI
646 AI
648 AI
650 AI
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0.1 30243 Input 2
0.1 30255 Input 2
0.1 30257 Input 2
0.1 30267 Input 2
0.1 30281 Input 2
0.1 30283 Input 2
0.1 30349 Input 2
0.1 30355 Input 2
0.01 30365 Input 2
0.01 30367 Input 2
10 30401 Input 2
0.1 30407 Input 2
1 30411 Input 2
0.1 30639 Input 2
0.1 30641 Input 2
0.1 30643 Input 2
0.1 30645 Input 2
0.1 30647 Input 2
0.1 30649 Input 2
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 41
VARIABLE DESCRIPTION
Main Temperature Set
Temperature_Setpoint
point. Supply, Space, or
Return target temperature
Heat/Cool Spt Deadband
when Room or Return
Temperature_Heat_
Cool_Deadband
control is active. Clg Spt =
Deadband /2 + Temp Spt.
Htg Spt = Deadband /2 -
Temp Spt.
Cooling_Coil_Setpoint_
Min
Dehumidification_
Setpoint
Outside_Dewpoint_
Setpoint
Indoor_Dewpoint_
Setpoint
Unocc_Indoor_
Dewpoint_Setpoint
Unoccupied_Cooling_
Setpoint
Unoccupied_
Dehumidification_
Setpoint
Unoccupied_Heating_
Setpoint
Economizer_Temp_
Enable_Setpoint
Economizer_Enthalpy_
Enable_Setpoint
Outside_RH_from_
BMS
Outside_Temp_from_
BMS
Space_1_CO2_from_
BMS
Cooling Coil Leaving Air
Setpoint
Dehumidification Setpoint.
%RH for Space or Return
control.
Outside Dewpoint
Dehumidification Trigger
Setpoint
Indoor Dewpoint
Dehumidification Trigger
Setpoint
Unoccupied Indoor
Dewpoint Dehumidification
Trigger Setpoint
Unoccupied Cooling
Setpoint
Unoccupied
Dehumidification %RH
Setpoint
Unoccupied Heating
Setpoint
Economizer Ambient Temp
Enable Setpoint. Allow Econ
when OAT<Spt
Economizer Enthalpy
Enable Setpoint. Allow Econ
when OA Enthalpy<Spt
Outside RH from BMS. Used
when source selection is
set to BMS.
Outside Temp from BMS.
Used when source selection
is set to BMS.
Space 1 CO2 from BMS.
Used when source selection
is set to BMS.
Space RH from BMS. Used
Space_RH_from_BMS
when source selection is
set to BMS.
Space_Static_from_
BMS
Space_Temp_from_
BMS
Cooling_Lockout_
Setpoint
Heating_Lockout_
Setpoint
Space_Static_
Pressure_Setpoint
Space Static from BMS.
Used when source selection
is set to BMS.
Space Temp from BMS.
Used when source selection
is set to BMS.
Cooling Ambient Lockout
Setpoint
Heating Ambient Lockout
Setpoint
Space Static Pressure
Setpoint
Appendix: Points List
ACTIVE
TEXT
INACTIVE
TEXT
OBJECT
INSTANCE
Analog Values - Read/Write - Commandable
1AV
2AV
3AV
5AV
6AV
7AV
9AV
10 AV
11 AV
12 AV
16 AV
17 AV
21 AV
22 AV
25 AV
28 AV
29 AV
30 AV
31 AV
32 AV
37 AV
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
0 40001 Holding 2
0 40003 Holding 2
0 40005 Holding 2
0 40009 Holding 2
0 40011 Holding 2
0 40013 Holding 2
0 40017 Holding 2
0 40019 Holding 2
0 40021 Holding 2
0 40023 Holding 2
0 40031 Holding 2
0 40033 Holding 2
0.1 40041 Holding 2
0.1 40043 Holding 2
0.1 40049 Holding 2
0.1 40055 Holding 2
0.1 40057 Holding 2
0.1 40059 Holding 2
0.1 40061 Holding 2
0.1 40063 Holding 2
0.1 40073 Holding 2
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS42
®
Appendix: Points List
VARIABLE DESCRIPTION
Supply_Duct_Static_
Pressure_Setpoint
Supply Duct Static Pressure
Setpoint
ACTIVE
TEXT
Space_CO2_Setpoint Space CO2 Setpoint 39 AV
SF_Control_Signal_
BMS
EF_Control_Signal_
BMS
OAD_Control_Signal_
BMS
Outside_Air_Damper_
Minimum_Setpoint
Aux_BMS_Analog_
Output_1
Aux_BMS_Analog_
Output_2
Aux_BMS_Analog_
Output_3
Aux_BMS_Analog_
Output_4
BMS to control signal for
supply fan speed
BMS to control signal for
exhaust fan speed
Allows the BMS to control
OAD position. True = BMS.
False = Local.
Outside Air Damper
Minimum Setpoint
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
BMS Commanded auxilary
analog output
INACTIVE
TEXT
OBJECT
INSTANCE
38 AV
133 AV
134 AV
136 AV
137 AV
138 AV
139 AV
140 AV
141 AV
OBJECT
BACNET MODBUS
TYPE
ACCESS HYST INDEX
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
0.1 40075 Holding 2
0.1 40077 Holding 2
0.1 40083 Holding 2
0.1 40085 Holding 2
0.1 40089 Holding 2
1 40091 Holding 2
0.1 40093 Holding 2
0.1 40095 Holding 2
0.1 40097 Holding 2
0.1 40099 Holding 2
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 43
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
0: Off/Standby 1: Unoccupied Start 2: Occupied Start 5: Dampers Open 6: Fan Start Delay 7: Fans Starting 9: Heat/Cool Delay 10: System On 11: Soft Shutdown 12: System Disabled 13: Remote Off
Unit_Status_Mode
14: Shutdown Alarm 19: Fans Only 20: Economizing 21: Cooling 22: Heating 23: Dehumidifying 25: HGRH Purging 26: Defrost Active 28: Cooling & Heating 29: Dehum w/Heat 30: Overrides Active 31: Expansion Offline 51: IO Test. Sys Disabled
Supply_Temperature_
Calculated_Setpoint
Cooling_1_Ramp_
Capacity
Active Supply Temperature
Setpoint
Cooling Ramp 1 Status
Value
Defrost_Ramp Defrost Ramp 47 AV
Economizer_Ramp Economizer Ramp 48 AV
Exhaust_Fan_Space_
Static_Pressure_Ramp
Exhaust_Fan_Supply_
Tracking_Ramp
Head_Pressure_
Control_Ramp_1_
Ramp
Head_Pressure_
Control_Ramp_2_
Ramp
Exhaust Fan Space Static
Pressure Ramp
Exhaust Fan Supply
Tracking Ramp
Head Pressure Control
Ramp 1
Head Pressure Control
Ramp 2
Heating_Ramp Heating Ramp 60 AV
Hot_Gas_Reheat_
Ramp
Space_CO2_Control_
Ramp
Supply_Duct_Static_
Pressure_Ramp
Supply_Fan_Space_
Static_Pressure_Ramp
Hot Gas Reheat Ramp 61 AV
Space CO2 Control Ramp 71 AV
Supply Duct Static Pressure
Ramp
Supply Fan Space Static
Pressure Ramp
Winter_Ramp_Output Winter Ramp Output 75 AV
Outside_Dewpoint Outside Dewpoint 82 AV
Outside_Enthalpy Outside Enthalpy 83 AV
Space_Dewpoint Space Dewpoint 88 AV
Space_Enthalpy Space Enthalpy 89 AV
Total_Exhaust_Fan_
CFM_BMS
Total Exhaust Fan CFM 107 AV
OAD_CFM_BMS OAD CFM 129 AV
OAD_Space_Static_
Pressure_Ramp
OAD Static Pressure Ramp 131 AV
INACTIVE
TEXT
OBJECT
INSTANCE
Analog Values - Read Only
40 AV
41 AV
43 AV
49 AV
50 AV
51 AV
52 AV
72 AV
74 AV
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 30001 Input 2
0.1 30003 Input 2
1 30007 Input 2
1 30015 Input 2
1 30017 Input 2
1 30019 Input 2
1 30021 Input 2
1 30023 Input 2
1 30025 Input 2
1 30041 Input 2
1 30043 Input 2
1 30063 Input 2
1 30065 Input 2
1 30069 Input 2
1 30071 Input 2
0.1 30085 Input 2
0.1 30087 Input 2
0.1 30097 Input 2
0.1 30099 Input 2
10 30135 Input 2
10 30173 Input 2
1 30177 Input 2
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS44
®
VARIABLE DESCRIPTION
Active_Temperature_
Setpoint
Chilled_Water_1_
Valve_Analog_Output
Condenser_1_Analog_
Output
Condenser_2_Analog_
Output
Electric_Heater_1_
Analog_Output
Energy_Recovery_
Analog_Output
Exhaust_Fan_Speed_
Analog_Output
Hot_Gas_Reheat_
Analog_Output
Hot_Water_Valve_1_
Analog_Output
Mod_Gas_Furnace_1_
Analog_Output
Outside_Air_Damper_
Analog_Output
Supply_Fan_Speed_
Analog_Output
Modulating_
Compressor_Analog_
Output_BMS
Circuit_A_Sat_
Discharge_
Temperature
Circuit_B_Sat_
Discharge_
Temperature
Active Temperature Set
point
Chilled Water 1 Valve
Analog Output
Condenser 1 Analog Output 205 AV
Condenser 2 Analog Output 206 AV
Electric Heater 1 Analog
Output
Energy Recovery Analog
Output
Exhaust Fan Speed Analog
Output
Hot Gas Reheat Analog
Output
Hot Water Valve 1 Analog
Output
Mod Gas Furnace 1 Analog
Output
Outside Air Damper Analog
Output
Supply Fan Speed Analog
Output
Modulating Compressor
Analog Output - Valent BMS
Circuit A Saturated
Discharge Temperature
Circuit B Saturated
Discharge Temperature
Appendix: Points List
ACTIVE
TEXT
INACTIVE
TEXT
OBJECT
INSTANCE
132 AV
201 AV
221 AV
229 AV
231 AV
235 AV
236 AV
242 AV
250 AV
264 AV
285 AV
286 AV
287 AV
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0.1 30179 Input 2
0.1 30473 Input 2
0.1 30481 Input 2
0.1 30483 Input 2
0.1 30513 Input 2
0.1 30517 Input 2
0.1 30521 Input 2
0.1 30523 Input 2
0.1 30525 Input 2
0.1 30537 Input 2
0.1 30541 Input 2
0.1 30557 Input 2
0.1 30585 Input 2
0.1 30587 Input 2
0.1 30589 Input 2
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 45
Appendix: Points List
VARIABLE DESCRIPTION
Exhaust_Fan_1_
Status_Digital_Input
Occupancy_Digital_
Input
Outside_Filter_Alarm_
Digital_Input
Shutdown_Alarm_
Digital_Input
Supply_Fan_1_Status_
Digital_Input
Unit_Enable_Digital_
Input
Wheel_Status_Digital_
Input
Exhaust Fan 1 Status Active Inactive 23 BI
Occupancy Digital Input
Status
Outside Filter Alarm Digital
Input Status
Shutdown Alarm Digital
Input Status
Supply Fan 1 Status Active Inactive 78 BI
Remote Unit Enable Digital
Input Status
Heat Wheel Status Active Inactive 83 BI
ACTIVE
TEXT
Active Inactive 53 BI
Active Inactive 54 BI
Active Inactive 75 BI
Active Inactive 82 BI
BMS Watchdog command.
Used to determine comm
BMS_Watchdog
status. Must heartbeat
within the watchdog
Active Inactive 1 BV
timeout delay to detect
comm status.
System_Enable
BMS_Occupancy_
Command
Master system enable/
disable point.
Occupancy Command. True
= Unoccupied. False =
Occupied.
Enable Disable 2 BV
Unoccupy Occupy 3 BV
Reset_All_Alarms Alarm Reset Command. Reset Normal 4 BV
Outside_RH_Source_
BMS
Outside_Temp_
Source_BMS
Space_1_CO2_
Source_BMS
Space_RH_Source_
BMS
Space_Static_Source_
BMS
Space_Temp_Source_
BMS
SF_Control_Source_
BMS
EF_Control_Source_
BMS
OAD_Control_Source_
BMS
Outside RH Source
Selection. True = BMS.
False = Local.
Outside Temp Source
Selection. True = BMS.
False = Local.
Space 1 CO2 Source
Selection. True = BMS.
False = Local.
Space RH Source Selection.
True = BMS. False = Local.
Space Static Source
Selection. True = BMS.
False = Local.
Space Temp Source
Selection. True = BMS.
False = Local.
Allows the BMS to control
supply fan speed. True =
BMS. False = Local.
Allows the BMS to control
exhaust fan speed. True =
BMS. False = Local.
Allows the BMS to control
OAD position. True = BMS.
False = Local.
BMS Local 5 BV
BMS Local 6 BV
BMS Local 9 BV
BMS Local 12 BV
BMS Local 13 BV
BMS Local 14 BV
BMS Local 56 BV
BMS Local 57 BV
BMS Local 59 BV
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Inputs - Read Only
Binary Values - Read/Write - Commandable
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
Read_
Commandable
0 24 Discrete
0 54 Discrete
0 55 Discrete
0 76 Discrete
0 79 Discrete
0 83 Discrete
0 84 Discrete
0 2 Coil
0 3 Coil
0 4 Coil
0 5 Coil
0 6 Coil
0 7 Coil
0 10 Coil
0 13 Coil
0 14 Coil
0 15 Coil
0 19 Coil
0 20 Coil
0 22 Coil
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS46
®
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
Occupied Occupied Status. Occupied
Unoccupied Unoccupied Status. Unoccupied Occupied 17 BV
Unoccupied_Cooling_
Call
Unoccupied_
Dehumidification_Call
Unoccupied_Heating_
Call
Occupied_Start
Unoccupied_Start
Unoccupied Cooling Call
Status
Unoccupied
Dehumidification Call
Status
Unoccupied Heating Call
Status
Occupied Start Command
Status
Unoccupied Start Command
Status
Active Inactive 18 BV
Active Inactive 19 BV
Active Inactive 20 BV
Active Inactive 21 BV
Active Inactive 22 BV
Status to indicate startup
Enable_Controls
is complete and the unit is
Enabled Disabled 23 BV
ready.
General alarm point.
Global_Alarm
Optionally set to indicate
any alarm is active, or a
Alarm Normal 24 BV
shutdown alarm is active.
Shutdown alarm status.
System_Shutdown_
Alarm
When true, System Enable will be set to false and the
Shutdown Normal 25 BV
unit will remain off.
Indicates there is a open
Damper_Open
air path and the supply fan
Open Closed 26 BV
can run.
Cooling_is_On
Economizer_is_On
Heating_is_On
Dehumidification_
Mode_Enabled
Manual_Override_
Active
Cooling_Not_Locked_
Out
Heating_Not_Locked_
Out
Preheat_Not_Locked_
Out
HGRH_Purging
Allow_Dampers
Indicates that the unit is
cooling.
Indicates that the unit is
economizing.
Indicates that the unit is
heating.
Indicates that the unit is
dehumidifying.
Indicates that manual
overrides are active.
Indicates that cooling is
allowed.
Indicates that heating is
allowed.
Indicates that preheat is
allowed.
Indicates that the hot gas
reheat value is purging.
Startup sequence command
to open dampers
Active Inactive 27 BV
Active Inactive 28 BV
Active Inactive 29 BV
Active Inactive 31 BV
Override Normal 32 BV
Allowed
Allowed
Allowed
Active Inactive 37 BV
Yes No 43 BV
Startup sequence command
Allow_Exhaust_Fans
to trigger exhaust fans to
Yes No 44 BV
start
Startup sequence command
Allow_Supply_Fans
to trigger supply fans to
Yes No 48 BV
start
BMS_Watchdog_Active
BMS_Occupancy_
Status
Compressor_1_
Enable_Digital_Output
Compressor_2_
Enable_Digital_Output
Compressor_3_
Enable_Digital_Output
Status of the BMS
watchdog ping.
Status of the BMS
occupancy command.
Compressor 1 Enable
Digital Output
Compressor 2 Enable
Digital Output
Compressor 3 Enable
Digital Output
Active Inactive 49 BV
Occupied
Active Inactive 111 BV
Active Inactive 112 BV
Active Inactive 113 BV
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Values - Read Only
Unoccupied
Locked_
Out
Locked_
Out
Locked_
Out
Unoccupied
16 BV
33 BV
34 BV
36 BV
50 BV
BACNET MODBUS
OBJECT
TYPE
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10002 Discrete
0 10003 Discrete
0 10004 Discrete
0 10005 Discrete
0 10006 Discrete
0 10007 Discrete
0 10008 Discrete
0 10009 Discrete
0 10010 Discrete
0 10011 Discrete
0 10012 Discrete
0 10013 Discrete
0 10014 Discrete
0 10015 Discrete
0 10017 Discrete
0 10018 Discrete
0 10019 Discrete
0 10020 Discrete
0 10022 Discrete
0 10023 Discrete
0 10029 Discrete
0 10030 Discrete
0 10034 Discrete
0 10035 Discrete
0 10036 Discrete
0 10164 Discrete
0 10165 Discrete
0 10166 Discrete
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 47
VARIABLE DESCRIPTION
Compressor_4_
Enable_Digital_Output
Condenser_Fan_1_
Digital_Output
Condenser_Fan_2_
Digital_Output
Condenser_Fan_3_
Digital_Output
Exhaust_Fan_1_Start_
Stop_Digital_Output
Furnace_1_Stage_1_
Digital_Output
Furnace_2_Stage_1_
Digital_Output
Heat_Wheel_Enable_
Digital_Output
PreHeat_Enable_
Digital_Output
Supply_Fan_1_Start_
Stop_Digital_Output
BMS_Offline_Alarm.
Active
Cold_Coil_1_
Temperature_Sensor_
Alarm.Active
Comp_Maintenance_
Alarm.Active
Exhaust_Fan_1_Alarm.
Active
Expansion_Board_1_
Alarm.Active
Expansion_Board_2_
Alarm.Active
Expansion_Board_3_
Alarm.Active
Internal_Board_Temp_
Alarm.Active
Multi_Channel_Conf_
Alarm.Active
Outside_Air_
Temperature_Sensor_
Alarm.Active
Outside_Filter_Alarm.
Active
Outside_RH_Sensor_
Alarm.Active
Space_CO2_1_
Analog_Input_Alarm.
Active
Space_High_Static_
Alarm.Active
Space_RH_Sensor_
Alarm.Active
Space_Setpoint_
Slider_Alarm.Active
Space_Static_
Pressure_Analog_
Input_Alarm.Active
Space_Temperature_
Sensor_Alarm.Active
Shutdown_Input_
Alarm.Active
Supply_Air_Temp_
Low_Limit.Active
Compressor 4 Enable
Digital Output
Condenser Fan 1 Digital
Output
Condenser Fan 2 Digital
Output
Condenser Fan 3 Digital
Output
Exhaust Fan 1 Start Stop
Digital Output
Furnace 1 Stage 1 Digital
Output
Furnace 2 Stage 1 Digital
Output
Heat Wheel Enable Digital
Output
PreHeat Enable Digital
Output
Supply Fan 1 Start Stop
Digital Output
BMS Offline Alarm
(0=Normal 1=Alarm)
Cold Coil 1 Temperature
Sensor Alarm (0=Normal
1=Alarm)
Comp Maintenance Alarm
(0=Normal 1=Alarm)
Exhaust Fan 1 Alarm (0=Normal 1=Alarm)
Expansion Board 1 Alarm
(0=Normal 1=Alarm)
Expansion Board 2 Alarm
(0=Normal 1=Alarm)
Expansion Board 3 Alarm
(0=Normal 1=Alarm)
Internal Board Temp Alarm
(0=Normal 1=Alarm)
Multi Channel Conf Alarm
(0=Normal 1=Alarm)
Outside Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Outside Filter Alarm
(0=Normal 1=Alarm)
Outside RH Sensor Alarm
(0=Normal 1=Alarm)
Space CO2 1 Analog Input
Alarm (0=Normal 1=Alarm)
Space High Static Alarm
(0=Normal 1=Alarm)
Space RH Sensor Alarm
(0=Normal 1=Alarm)
Space Setpoint Slider Alarm
(0=Normal 1=Alarm)
Space Static Pressure
Analog Input Alarm
(0=Normal 1=Alarm)
Space Temperature Sensor Alarm (0=Normal 1=Alarm)
Shutdown Input Alarm
(0=Normal 1=Alarm)
Supply Air Temp Low Limit
Alarm (0=Normal 1=Alarm)
Appendix: Points List
ACTIVE
TEXT
Active Inactive 114 BV
Active Inactive 119 BV
Active Inactive 120 BV
Active Inactive 121 BV
Active Inactive 127 BV
Active Inactive 131 BV
Active Inactive 133 BV
Active Inactive 163 BV
Active Inactive 166 BV
Active Inactive 186 BV
Alarm Normal 313 BV
Alarm Normal 387 BV
Alarm Normal 411 BV
Alarm Normal 423 BV
Alarm Normal 434 BV
Alarm Normal 435 BV
Alarm Normal 436 BV
Alarm Normal 498 BV
Alarm Normal 503 BV
Alarm Normal 507 BV
Alarm Normal 508 BV
Alarm Normal 509 BV
Alarm Normal 535 BV
Alarm Normal 537 BV
Alarm Normal 538 BV
Alarm Normal 539 BV
Alarm Normal 540 BV
Alarm Normal 541 BV
Alarm Normal 546 BV
Alarm Normal 551 BV
INACTIVE
TEXT
OBJECT
INSTANCE
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10167 Discrete
0 10172 Discrete
0 10173 Discrete
0 10174 Discrete
0 10180 Discrete
0 10184 Discrete
0 10186 Discrete
0 10208 Discrete
0 10211 Discrete
0 10231 Discrete
0 10264 Discrete
0 10338 Discrete
0 10362 Discrete
0 10373 Discrete
0 10384 Discrete
0 10385 Discrete
0 10386 Discrete
0 10448 Discrete
0 10453 Discrete
0 10457 Discrete
0 10458 Discrete
0 10459 Discrete
0 10485 Discrete
0 10487 Discrete
0 10488 Discrete
0 10489 Discrete
0 10490 Discrete
0 10491 Discrete
0 10496 Discrete
0 10501 Discrete
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS48
®
VARIABLE DESCRIPTION
Supply_Air_
Temperature_Sensor_
Alarm.Active
Supply_Duct_Static_
Pressure_Analog_
Input_Alarm.Active
Supply_Fan_1_Alarm.
Active
Supply_High_Duct_ Static_Alarm.Active
Supply_RH_Sensor_
Alarm.Active
Supply_Temp_High_
Limit_Alarm.Active
TMem_Error.Active
Wheel_Rotation_
Alarm.Active
Al_Batt_EVD_1.Active
Al_ConfigErr_EVD_1.
Active
Al_DscgHiP_COMP_1.
Active
Supply Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Supply Duct Static Pressure
Analog Input Alarm
(0=Normal 1=Alarm)
Supply Fan 1 Alarm
(0=Normal 1=Alarm)
Supply High Duct Static
Alarm (0=Normal 1=Alarm)
Supply RH Sensor Alarm
(0=Normal 1=Alarm)
Supply Temp High Limit
Alarm (0=Normal 1=Alarm)
TMem Error Alarm
(0=Normal 1=Alarm)
Wheel Rotation Alarm
(0=Normal 1=Alarm)
EVD Battery Alarm
(0=Normal 1=Alarm)
EVD Configuration Alarm
(0=Normal 1=Alarm)
Compressor Envelope -
High Discharge Pressure
Alarm (0=Normal 1=Alarm)
Compressor Envelope
Al_DscgHiTemp_
COMP_1.Active
- High Discharge
Temperature Alarm
(0=Normal 1=Alarm)
Al_DscgLowP_
COMP_1.Active
Al_EEPROM_EVD_1.
Active
Al_EEV_A_EVD_1.
Active
Al_EmergencyClosing_
EVD_1.Active
Al_EVD_Offline_
EVD_1.Active
Al_FW_CompatibErr_
EVD_1.Active
Al_HiCurr_COMP_1.
Active
Al_HiRatioP_COMP_1.
Active
Al_HiT_Cond_EVD_1.
Active
Al_IncompleteClosing_
EVD_1.Active
Al_LOP_A_EVD_1.
Active
Al_Low_SH_A_EVD_1.
Active
Al_LowDeltaP_ COMP_1.Active
Al_LowRatioP_ COMP_1.Active
Al_LowSuct_A_EVD_1.
Active
EVD Low Discharge
Pressure Alarm (0=Normal
1=Alarm)
EVD EEPROM Alarm
(0=Normal 1=Alarm)
ExV Motor Alarm - Valve 1
(0=Normal 1=Alarm)
EVD Emergency Closing
Alarm (0=Normal 1=Alarm)
EVD Offline Communication Alarm (0=Normal 1=Alarm)
EVD Firmware Compability
Alarm (0=Normal 1=Alarm)
Compressor Envelope
- High Current Alarm (0=Normal 1=Alarm)
Compressor Envelope -
High Pressure Ratio Alarm
(0=Normal 1=Alarm)
Al_HiT_Cond_EVD_1 (0=Normal 1=Alarm)
EVD Incomplete Closing
Alarm (0=Normal 1=Alarm)
EVD Low Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
EVD Low SuperHeat
Alarm - Valve 1 (0=Normal
1=Alarm)
Compressor Envelope -
Low Pressure DeltaAlarm
(0=Normal 1=Alarm)
Compressor Envelope -
Low Pressure Ratio Alarm
(0=Normal 1=Alarm)
Low Suction Refrigerant
Temperature - Valve 1
(0=Normal 1=Alarm)
Appendix: Points List
ACTIVE
TEXT
Alarm Normal 552 BV
Alarm Normal 553 BV
Alarm Normal 554 BV
Alarm Normal 563 BV
Alarm Normal 564 BV
Alarm Normal 565 BV
Alarm Normal 567 BV
Alarm Normal 576 BV
Alarm Normal 589 BV
Alarm Normal 590 BV
Alarm Normal 591 BV
Alarm Normal 592 BV
Alarm Normal 593 BV
Alarm Normal 594 BV
Alarm Normal 595 BV
Alarm Normal 597 BV
Alarm Normal 598 BV
Alarm Normal 599 BV
Alarm Normal 600 BV
Alarm Normal 601 BV
Alarm Normal 602 BV
Alarm Normal 603 BV
Alarm Normal 604 BV
Alarm Normal 606 BV
Alarm Normal 608 BV
Alarm Normal 609 BV
Alarm Normal 610 BV
INACTIVE
TEXT
OBJECT
INSTANCE
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10502 Discrete
0 10503 Discrete
0 10504 Discrete
0 10513 Discrete
0 10514 Discrete
0 10515 Discrete
0 10517 Discrete
0 10526 Discrete
0 10539 Discrete
0 10540 Discrete
0 10541 Discrete
0 10542 Discrete
0 10543 Discrete
0 10544 Discrete
0 10545 Discrete
0 10547 Discrete
0 10548 Discrete
0 10549 Discrete
0 10550 Discrete
0 10551 Discrete
0 10552 Discrete
0 10553 Discrete
0 10554 Discrete
0 10556 Discrete
0 10558 Discrete
0 10559 Discrete
0 10560 Discrete
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 49
VARIABLE DESCRIPTION
Al_MOP_A_EVD_1.
Active
EVD Max Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
EVD-S1 Suction Pressure
Al_S1_EVD_1.Active
Sensor Alarm (0=Normal
1=Alarm)
EVD-S2 Suction
Al_S2_EVD_1.Active
Temperature Sensor Alarm
(0=Normal 1=Alarm)
EVD-S4 Discharge
Al_S4_EVD_1.Active
Temperature Sensor Alarm
(0=Normal 1=Alarm)
Al_SuctHiP_COMP_1.
Active
Al_SuctLowP_
COMP_1.Active
Comp_Staging_Order_
Skipped.Active
EVD_PrePosition_
Alarm_1.Active
ER_Wheel_High_
DP.Active
Aux_BMS_Digital_
Output_1
Aux_BMS_Digital_
Output_2
Aux_BMS_Digital_
Output_3
Aux_BMS_Digital_
Output_4
Aux_BMS_Digital_
Output_5
Aux_BMS_Digital_
Output_6
Compressor Envelope -
SuctHiP_COMP (0=Normal
1=Alarm)
Compressor Envelope
- SuctLowP_COMP
(0=Normal 1=Alarm)
Compressor Staging
Order is Skipped Warning
(0=Normal 1=Alarm)
Unexpected EEV Position
(0=Normal 1=Alarm)
Energy Recovery Wheel
high differential pressure
(0=Normal 1=Alarm)
BMS Commanded auxilary
digital output
BMS Commanded auxilary
digital output
BMS Commanded auxilary
digital output
BMS Commanded auxilary
digital output
BMS Commanded auxilary
digital output
BMS Commanded auxilary
digital output
Startup Sequence Fan
Allow_Fan_Delay_
Remaining
Damper Delay. Time before
enabling Fan startup
sequence.
Supply_Fan_Delay_
Remaining
Exhaust_Fan_Delay_
Remaining
LatestAlm
Supply Fan startup
sequence. Time before
starting supply fan.
Exhaust Fan startup
sequence. Time before
starting exhaust fan.
Most recent alarm. See
alarm table.
Appendix: Points List
ACTIVE
TEXT
Alarm Normal 612 BV
Alarm Normal 614 BV
Alarm Normal 615 BV
Alarm Normal 617 BV
Alarm Normal 618 BV
Alarm Normal 619 BV
Alarm Normal 632 BV
Alarm Normal 634 BV
Alarm Normal 731 BV
Active Inactive 207 BV
Active Inactive 208 BV
Active Inactive 209 BV
Active Inactive 210 BV
Active Inactive 211 BV
Active Inactive 212 BV
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Values - Commandable
Integer Values - Read Only
1IV
2IV
3IV
7IV
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
Commandable
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10562 Discrete
0 10564 Discrete
0 10565 Discrete
0 10567 Discrete
0 10568 Discrete
0 10569 Discrete
0 10580 Discrete
0 10582 Discrete
0 10679 Discrete
0 24 Coil
0 25 Coil
0 26 Coil
0 27 Coil
0 28 Coil
0 29 Coil
1 30181 Input 2
1 30183 Input 3
1 30185 Input 4
1 30193 Input 5
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS50
®
VARIABLE DESCRIPTION
High_Low_Press_
Circ_A_Alarm.Active
High_Low_Press_
Circ_B_Alarm.Active
High_Low_Press_
Circ_C_Alarm.Active
High_Low_Press_
Circ_D_Alarm.Active
Greentrol_1_Alarm.
Active
Greentrol_2_Alarm.
Active
Greentrol_3_Alarm.
Active
Mixed_Temp_Analog_
Input
Exhaust_Fan_Speed_
Analog_Input
Supply_Fan_Speed_
Analog_Input
Comp_Circ_A_High_
Pressure_Digital_Input
Comp_Circ_A_Low_
Pressure_Digital_Input
Comp_Circ_B_High_
Pressure_Digital_Input
Comp_Circ_B_Low_
Pressure_Digital_Input
Drain_Pan_Alarm_
Digital_Input
EAD_End_Switch_
Digital_Input
OAD_End_Switch_
Digital_Input
High Low Pressure Switch
Alarm Circuit A
High Low Pressure Switch
Alarm Circuit B
High Low Pressure Switch
Alarm Circuit C
High Low Pressure Switch
Alarm Circuit D
Greentrol Device Alarm Alarm Normal 737 BV
Greentrol Device Alarm Alarm Normal 738 BV
Greentrol Device Alarm Alarm Normal 739 BV
Mixed Temperature 35 AI
Exhaust Fan Speed Remote
Command Analog Input
value
Supply Fan Speed Remote
Command Analog Input
value
Circuit A High Pressure
Switch
Circuit A Low Pressure
Switch
Circuit B High Pressure
Switch
Circuit B Low Pressure
Switch
Drain Pan Alarm Digital
Input Status
Exhaust Air Damper End
Switch Digital Input Status
OAD End Switch Digital
Input Status
Appendix: Points List
ACTIVE
TEXT
Alarm Normal 733 BV
Alarm Normal 734 BV
Alarm Normal 735 BV
Alarm Normal 736 BV
Active Inactive 3 BI
Active Inactive 4 BI
Active Inactive 5 BI
Active Inactive 6 BI
Active Inactive 21 BI
Active Inactive 22 BI
Active Inactive 52 BI
INACTIVE
TEXT
OBJECT
INSTANCE
Large Board Points
Binary Values - Read Only
Medium Board Points
Analog Inputs - Read Only
143 AI
155 AI
Binary Inputs - Read Only
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10682 Discrete
0 10683 Discrete
0 10684 Discrete
0 10685 Discrete
0 10686 Discrete
0 10687 Discrete
0 10688 Discrete
0.1 30263 Input 2
1 30455 Input 2
1 30461 Input 2
0 10052 Discrete
0 10053 Discrete
0 10054 Discrete
0 10055 Discrete
0 10070 Discrete
0 10071 Discrete
0 10101 Discrete
REGISTER
TYPE
SIZE
®
Microprocessor Controller for DOAS 51
VARIABLE DESCRIPTION
Condenser_Fan_4_
Digital_Output
Condenser_Fan_5_
Digital_Output
Condenser_Fan_6_
Digital_Output
Condenser_Fan_7_
Digital_Output
Condenser_Fan_8_
Digital_Output
Comp_Circ_A_High_
Pressure_Alarm.Active
Comp_Circ_A_Low_
Pressure_Alarm.Active
Comp_Circ_B_High_
Pressure_Alarm.Active
Comp_Circ_B_Low_
Pressure_Alarm.Active
Damper_End_Switch_
Alarm.Active
Drain_Pan_Alarm.
Active
Exhaust_Fan_1_AMD_
analog_input_Alarm.
Active
Freeze_Stat_Alarm.
Active
Mixed_Temperature_
Sensor_Alarm.Active
OAD_AMD_analog_
input_Alarm.Active
Condenser Fan 4 Digital
Output
Condenser Fan 5 Digital
Output
Condenser Fan 6 Digital
Output
Condenser Fan 7 Digital
Output
Condenser Fan 8 Digital
Output
Comp Circ A High Pressure Alarm (0=Normal 1=Alarm)
Comp Circ A Low Pressure
Alarm (0=Normal 1=Alarm)
Comp Circ B High Pressure Alarm (0=Normal 1=Alarm)
Comp Circ B Low Pressure
Alarm (0=Normal 1=Alarm)
Damper End Switch Alarm
(0=Normal 1=Alarm)
Drain Pan Alarm (0=Normal
1=Alarm)
Exhaust Fan 1 CFM Analog
Input Alarm (0=Normal
1=Alarm)
Freeze Stat Alarm
(0=Normal 1=Alarm)
Mixed Temperature Sensor Alarm (0=Normal 1=Alarm)
OAD CFM Analog Input
Alarm (0=Normal 1=Alarm)
Appendix: Points List
ACTIVE
TEXT
Active Inactive 122 BV
Active Inactive 123 BV
Active Inactive 124 BV
Active Inactive 125 BV
Active Inactive 126 BV
Alarm Normal 395 BV
Alarm Normal 396 BV
Alarm Normal 397 BV
Alarm Normal 398 BV
Alarm Normal 420 BV
Alarm Normal 422 BV
Alarm Normal 424 BV
Alarm Normal 441 BV
Alarm Normal 502 BV
Alarm Normal 506 BV
INACTIVE
TEXT
OBJECT
INSTANCE
Binary Values - Read Only
OBJECT
TYPE
BACNET MODBUS
ACCESS HYST INDEX
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
ReadCOV_
NoWrite
0 10175 Discrete
0 10176 Discrete
0 10177 Discrete
0 10178 Discrete
0 10179 Discrete
0 10346 Discrete
0 10347 Discrete
0 10348 Discrete
0 10349 Discrete
0 10371 Discrete
0 10372 Discrete
0 10374 Discrete
0 10391 Discrete
0 10452 Discrete
0 10456 Discrete
REGISTER
TYPE
SIZE
Microprocessor Controller for DOAS52
®
Appendix: Factory ModBus Connections
T
TERM
SHIELDED CABLE
PWR
GND
PWR
GND
+V
J24
GND
UNIT CONTRO LLER
NETB
NETB
NETA
NETA
Tx­Rx+
J26
GND
SHIELDED
CABLE
I/O EXPANSION FURNACE 1
Tx-
COMPONENTS FIELD MOUNTED AND WIRED IN ROOM/S PACE
ROOM THERMOSTAT 1 ROOM THERMOST AT 2 ROOM THERMOST AT 3
PWR
(OPTIONAL) (OPTIONAL) (OPTIONAL) (OPTIONAL)
NET
B
NET
A
GND
SHIELDED CABLE
PWR
NET
B
NET
A
GND
SHIELDED
CABLE
SHIELDED
CABLE
SHIELDED
CABLE
Rx+
GND
_
+ COM
_
+ COM
(OPTIONAL) (OPTIONAL) (OPTIONAL) (OPTIONAL) (OPTIONAL)
COMPONENTS MOUNTED AND WIRED BY FACTORY
MAIN UNIT CONTROL CENTER
MONITORI NG 1
AIRFLOW
MONITORI NG 2
AIRFLOW
FACTORY MODBUS CONNECTIONS
SHIELDED CABLE
INVERTER EEV
Tx-
(OPTIONAL)
Rx+
PWR
NET
B
NET
A
GND
SHIELDED CABLE
ROOM THERMOSTAT 4
PWR
NET
B
NET
A
GND
DRWG:2948063-00
®
GND
SHIELDED
CABLE
Tx-
FURNACE CONTROL CENTER
Rx+
SHIELDED
CABLE
GROUND
SNIPPED
SHIELD
GND
Tx-
Rx+
FURNACE 2
GND
FACTORY WI R ING
FIELD WIRING
SHIELDED
CABLE
SERVICE COMPARTMEN
INVERTER DRIVE
COMPRESSOR
(OPTIONAL)
REFRIGERATION
RS485
Microprocessor Controller for DOAS 53
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Microprocessor Controller for DOAS54
®
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
®
Microprocessor Controller for DOAS 55
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
483586 • Microprocessor Controller, Rev. 1, December 2018 Copyright 2018 © Greenheck Fan Corporation56
Loading...