Greenheck OSSFD-XXX Installation Manual

Part Number 461337
OFSD-XXX, ODFD-XXX,
OFD-XXX, and OSSFD-XXX Series
1½ Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
IBC International Building Codes New York City (MEA listing # 260-91-M) California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
“UL Classified (see complete marking on product)” “UL Classified to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Electrical Guidelines
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Safety Warning:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
Safety Caution!
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
1
Table of Contents
Pre-Installation Guidelines ................................................................................................................................ 2
Installation ...................................................................................................................................................... 2-6
•ClearancesRequirements ................................................................................................................. 3
•DucttoSleeveConnections ...................................... ........................................................................9
•SecuringtheDamper/SleeveAssemblytoWallandFloorOpenings ........................ .....................9
•ActuatorConnections ................................... ...................................................................................10
•RecommendedPreparationofOpeningsinWoodandMetalStudWalls .................................... 10
•BreakawayConnections ...................................... ...........................................................................10
Maintenance .................................................................................................................................................... 11
Troubleshooting ............................................................................................................................................... 11
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.
1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.
5) Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or
opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray
7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.
9) ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Installation - Failure to follow these instructions will void all warranties.
These instructions apply to 1½ hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry, block, wood or metal stud walls, or concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems) and UL listing R13317.
2
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE
Factory Supplied Thermal Blanket
7 1/2 in.
Max.
Damper
#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.
Masonry floor
Steel stud
Flange
Grille (Supplied by others)
Factory Supplied Thermal Blanket
Factory Supplied Thermal Blanket
7 1/2 in.
Max.
7 1/2 in.
Max.
Damper
Damper
#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.
Masonry floor
OFSD-XXX
Figure 1 shows two approved installations for
combination fire smoke dampers: 1) “Through the grille access” and 2) installation in continuing duct. To provide “through the grille” access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the requirements of NFPA 90A.
Wooden Stud Construction
“Duct Continues”
Horizontal or Vertical Mount
Gypsum Wallboard
Retaining Angle (Refer to section 4)
Factory Supplied Thermal Blanket
Stud or Runner
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and maximum of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid
space conflicts with the grille assembly.
Note: Both installations for vertical mount.
Figure 1: Installation configurations for ‘Out of Wall’ combination fire smoke dampers.
ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2
shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A.
Grille (Supplied by others)
6 1/2 in.
Max.
Fire damper or combination fire smoke damper
“Duct Terminates” Wood Stud“Duct Terminates” Metal Stud
2. CLEARANCE REQUIREMENTS
There is no minimum clearance requirement between
the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no maximum allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by ½ in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method.
3
Figure 2
Concrete or
Masonry
Wall
Flange
7 1/2 in. (191mm)
maximum
Damper
Flange
Factory Supplied Thermal Blanket
Type A- Vertical Mount, Duct Terminates
Flange Method
Steel Stud
Wood
Stud
Flange
Concrete or
Masonry Wall
7 1/2 in.
Damper
(191mm)
max.
Factory Supplied Thermal Blanket
Retaining
Angle
Steel Stud
Alternate Retaining
Location
Type A- Vertical Mount, Duct Terminates
Single Angle Method
Damper
Factory Supplied Thermal Blanket
Retaining Angle
7 1/2 in. (191mm)
Angle
max.
Wood
Stud
Flange
Masonry or Concrete Floor
Factory Supplied Thermal Blanket
7 1/2 in. (191mm)
Damper
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
max.
Type A - Horizontal Mount Above Floor/Wall,
Duct Terminates Single Angle Method
Retaining Angle
7 1/2 in. (191mm)
Factory Supplied Thermal Blanket
Damper
Concrete or
Masonry
Floor
Concrete or
Masonry
Floor
max.
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Single Angle Method
4
Loading...
+ 8 hidden pages