Greenheck ODFD Series, OSSFD Series, OFSD Series, OFD Series Installation, Operation And Maintenance Instructions

Document Number 461337
®
OFSD-XXX, ODFD-XXX,
OFD-XXX, and OSSFD-XXX Series
1½ Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX series dampers are intended for installation in accordance with combination fire smoke dampers requirements established by: NFPA National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes New York City (MEA listing # 260-91-M) California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
“UL Classified (see complete marking on product)” “UL Classified to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Electrical Guidelines
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Safety Warning:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
Safety Caution!
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Table of Contents
Pre-Installation Guidelines ................................................................................................................................ 2
Installation ...................................................................................................................................................... 2-6
• Clearances Requirements ................................................................................................................. 3
• Duct to Sleeve Connections ...................................... ........................................................................9
• Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........................................9-10
• Actuator Connections ................................... ...................................................................................10
• Recommended Preparation of Openings in Wood and Metal Stud Walls .................................... 10
• Breakaway Connections ...................................... ...........................................................................11
Maintenance .................................................................................................................................................... 12
Troubleshooting ............................................................................................................................................... 12
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.
1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a ‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.
5) Damper must be installed into duct or opening square and free of twist or other misalignment. Damper
must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray
7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.
9) ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Installation - Failure to follow these instructions will void all warranties.
These instructions apply to 1½ hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry, block, wood or metal stud walls, or concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL555. Installation shall comply with the requirements of NFPA 90A (Installation of Air Conditioning and Ventilating Systems) and UL listing R13317.
2
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE
Factory Supplied Thermal Blanket
7 1/2 in.
Max.
Damper
#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.
Masonry floor
Steel stud
Flange
Grille (Supplied by others)
Factory Supplied Thermal Blanket
Factory Supplied Thermal Blanket
7 1/2 in.
Max.
7 1/2 in.
Max.
Damper
Damper
#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly.
Masonry floor
OFSD-XXX
Figure 1 shows two approved installations for
combination fire smoke dampers: 1) “Through the grille access” and 2) installation in continuing duct. To provide “through the grille” access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the requirements of NFPA 90A.
Wooden Stud Construction
“Duct Continues”
Horizontal or Vertical Mount
Gypsum Wallboard
Retaining Angle (Refer to section 4)
Factory Supplied Thermal Blanket
Stud or Runner
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and maximum of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid
space conflicts with the grille assembly.
Note: Both installations for vertical mount.
Figure 1: Installation configurations for ‘Out of Wall’ combination fire smoke dampers.
ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2
shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A.
Grille (Supplied by others)
6 1/2 in.
Max.
Fire damper or combination fire smoke damper
“Duct Terminates” Wood Stud“Duct Terminates” Metal Stud
2. CLEARANCE REQUIREMENTS
There is no minimum clearance requirement between
the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no maximum allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by ½ in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method.
3
Figure 2
Concrete or
Masonry
Wall
Flange
7 1/2 in. (191mm)
maximum
Damper
Flange
Factory Supplied Thermal Blanket
Type A- Vertical Mount, Duct Terminates
Flange Method
Steel Stud
Wood
Stud
Flange
Concrete or
Masonry Wall
7 1/2 in.
Damper
(191mm)
max.
Factory Supplied Thermal Blanket
Retaining
Angle
Steel Stud
Alternate Retaining
Location
Type A- Vertical Mount, Duct Terminates
Single Angle Method
Damper
Factory Supplied Thermal Blanket
Retaining Angle
7 1/2 in. (191mm)
Angle
max.
Wood
Stud
Flange
Masonry or Concrete Floor
Factory Supplied Thermal Blanket
7 1/2 in. (191mm)
Damper
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
max.
Type A - Horizontal Mount Above Floor/Wall,
Duct Terminates Single Angle Method
Retaining Angle
7 1/2 in. (191mm)
Factory Supplied Thermal Blanket
Damper
Concrete or
Masonry
Floor
Concrete or
Masonry
Floor
max.
4
Type A - Horizontal Mount Below Floor/Wall, Duct
Terminates Single Angle Method
Figure 2 cont...
Masonry or Concrete Wall
7 1/2 in. (191mm)
Damper
Factory Supplied Thermal Blanket
Retaining
max.
Angle
Metal
Stud
Retaining
Angle
Type A- Vertical Mount, Thru Duct with Two
Retaining Angles
Damper
Wood
Stud
Concrete or
Masonry Wall
7 1/2 in. (191mm)
Damper
maximum
Factory Supplied Thermal Blanket
Retaining
Angle
Alternate Retaining
Type A- Vertical Mount, Thru Duct with
Single Retaining Angle
Wood Stud
Angle Location
Damper
Retaining
Angle
Masonry or Concrete Floor
Factory Supplied Thermal Blanket
Type A - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Retaining
Angle
Masonry or
Concrete
Floor
Retaining
Angle
Factory Supplied Thermal Blanket
7 1/2 in. (191mm)
max.
Retaining
Angle
7 1/2 in. (191mm)
max.
Retaining
Angle
Concrete or
Masonry
Floor
Factory Supplied Thermal Blanket
Type A - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Concrete or
Masonry Floor
Factory Supplied Thermal Blanket
7 1/2 in. (191mm)
maximum
Retaining
Angle
7 1/2 in. (191mm)
maximum
Type A - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
Damper
Type A - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
5
Figure 2 cont....
Damper
7 1/2 in. (191mm) maximum
Factory Supplied Thermal Blanket
Wood Stud
Steel Stud
Flange
Masonry or Concrete
7 1/2 in.(191mm) Maximum
Damper
Metal Stud
Factory Supplied Thermal Blanket
Retaining Angle
Retaining Angle
Type B2- Vertical Mount, Thru Duct with
Two Retaining Angles
Wood Stud
Masonry or Concrete
Type B2- Vertical Mount, Duct Terminates
Flange Method
Flange
Masonry or Concrete
Factory Supplied
Thermal Blanket
7 1/2 in. (191mm)
maximum
Damper
Type B2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
Damper
Factory Supplied Thermal Blanket
Retaining Angle
Retaining Angle
7 1/2 in. (191mm)
maximum
Type B2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Factory Supplied
Masonry or Concrete
Thermal Blanket
7 1/2 in. (191mm)
maximum
Retaining Angle
Masonry or Concrete
Retaining Angle
6
Damper
Type B2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
Figure 2 cont....
Thermal Blanket
Retaining
7 1/2 in. (191mm)
Damper
maximum
Factory Supplied Thermal Blanket
Retaining Angle
Type B2- Vertical Mount, Duct Terminates
Single Angle Method
Factory Supplied Thermal Blanket
Retaining Angle
Concrete or Masonry
Alternate Retaining Angle Location
Damper
7 1/2 in. (191mm)
maximum
Metal Stud
Retaining Angle
Alternate Retaining Angle Location
Damper
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) maximum
Type B2- Vertical Mount, Thru Duct with
Single Retaining Angle
Retaining Angle
Concrete or Masonry
Damper
7 1/2 in. (191mm)
maximum
Wood Stud
Type B2 - Horizontal Mount Above Floor/Wall,
Duct Terminates Single Angle Method
Angle
Factory Supplied Thermal Blanket
Damper
Concrete or Masonry
Concrete or Masonry
7 1/2 in. (191mm)
maximum
Concrete or Masonry
Factory Supplied
Type B2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) maximum
Retaining Angle
Damper
Concrete or Masonry
Type B2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Single Angle Method
Type B2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
7
Figure 2 cont....
Flange
Flange
Metal Stud
Wood Stud
Concrete or Masonry
Damper
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) maximum
Type C2- Vertical Mount, Duct Terminates
Flange Method
Factory Supplied Thermal Blanket
Damper
7 1/2 in. (191mm)
maximum
Metal Stud
Retaining Angle
Wood Stud
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) maximum
Retaining Angle
Type C2- Vertical Mount, Thru Duct with
Two Retaining Angles
Factory Supplied Thermal Blanket
Retaining Angle
Concrete or Masonry
Damper
7 1/2 in. (191mm)
maximum
Concrete or Masonry
Flange
Type C2 - Horizontal Mount Above Floor/
Wall, Duct Terminates Flange Method
Factory Supplied Thermal Blanket
Concrete or Masonry
7 1/2 in. (191mm)
maximum
Damper
Retaining Angle
Type C2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Two Retaining Angles
Retaining Angle
Retaining Angle
Factory Supplied Thermal Blanket
7 1/2 in. (191mm)
Damper
Concrete or Masonry
Concrete or Masonry
maximum
Type C2 - Horizontal Mount Below Floor/Wall, Duct
Terminates Flange Method
8
Type C2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Two Retaining Angles
Figure 2 cont....
Wood Stud
Metal Stud
Alternate Retaining Angle Location
Concrete or Masonry
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) maximum
Type C2- Vertical Mount, Thru Duct with
Single Retaining Angle
Factory Supplied Thermal Blanket
Damper
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with actuators (on applicable
models) and sleeves from the factory and can be installed without the need for additional field installed sleeves.
Sleeve gauges of 20-14 (.9mm - 2mm) are to be used.
UL Standard 555 requires all ducts to terminate at fire damper sleeves. Sleeve thickness must not be less than the gauge of the connecting duct.
Duct to sleeve breakaway connections must be of the
type described on page 5. Factory furnished round duct collars on type R and CR dampers are also considered to be breakaway connections and may be used.
Flange
Thermal Blanket (installed around entire outside surface of sleeve)
Retaining Angle
7 1/2 in. (191mm)
maximum
Concrete or Masonry
Type C2 - Horizontal Mount Above Floor/Wall,
Thru Duct with Single Retaining Angle
Retaining Angle
Concrete or Masonry
7 1/2 in. (191mm)
maximum
Factory Supplied Thermal Blanket
Damper
Type C2 - Horizontal Mount Below Floor/Wall, Thru
Duct with Single Retaining Angle
Wall
Figure 3: Sleeved damper with Thermal
Blanket (duct termination).
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS.
Damper/sleeve assemblies must be installed in wall
openings using flanges and sheet metal screws as illustrated and described below.
• Flange on front (grille end) of sleeve must be a minimum
5
of 16 gauge (1.5mm) steel and have a
8 in. (16mm) minimum flange leg (refer to Figure 3). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). No retaining angles are required on the side of wall opposite from the grille.
• Retaining angles for 1½ hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1¼ in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm)(see Figure 4).
9
12 in.
24 in. o.c. Maximum
Floor Runner
Ceiling Runner
24 in. o.c.
Maximum
(metal studs)
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
16 in. o.c.
Maximum
(wood studs)
2 in. (51mm)
2 in. (51mm)
2 Panhead Screws
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS continued....
• Retaining angles must be attached to the sleeve using one or more of the following methods of attachment:
• Tack or spot welds
• #10 (19mm) sheet metal screws
1
4 in. (6mm) bolts and nuts
3
16 in. (4.7mm) steel pop rivets
Attachments must be spaced a minimum of 6 in.
(152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.
Caution! Do not tear the thermal blanket during
installation.
Dampers are tested for correct operation and are
square and straight before shipment from the factory. Dampers must be installed square and straight and must not be twisted or racked. Failure to install the damper square and straight may prevent the damper blades from operating open and closed.
5. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see
Electrical Guidelines).
6 Recommended Preparation of Openings in
Wood and Metal Stud Walls
• Frame wall openings as shown (see Figure 5 & 5A)
• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 5 & 5A).
• Prepare opening between studs and sleeve assembly as shown (Figure 6 & 7).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.
Retaining Angle
Thermal Blanket (installed around entire outside surface of sleeve)
2 in. Max.
6 in. Max.
6 in. Max.
2 in. Max.
Wall
Figure 4: Sleeved damper with Thermal
Blanket (duct continuation).
Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufactured by Venture Tape Company.
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Figure 5A
10
Metal stud only
Figure 5
Drive Slip Joint
Fire Damper Sleeve
Sleeve
6 in.
Std. Clip Length
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
3 Req’d.
24 in. Duct
2 Req’d.
Clip Spacing
6 in. 6 in.
9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Metal Stud Construction
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Gypsum Wallboar d
Stud or Runner
Retaining Angle
1 in. Min.
Damper Sleeve
Metal Stud Construction
Gypsum Wallboar d
Wooden Stud Construction
Gypsum Wallboard
Stud or Runner
Retaining Angle
Damper Sleeve
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Figure 6
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.
• The breakaway connections shown (Figure 8) can be applied with maximum of two #10 (19mm) sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.
• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm) See Figure 7.
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows:
• Ducts to 22 in. (558mm) wide (or dia.) and smaller shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have five screws.
NOTE: All breakaway connections described may have
duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.
Manufactured Flanged System Breakaway Connections
Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Figure 9).
Retaining
1 in. Min.
Angle
Damper Sleeve
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
Figure 7
Breakaway Connections
Plain “S” Slip Hemmed “S” Slip Double “S”Slip
Inside Slip Joint Standing “S” Standing “S” (Alt.)
Figure 7
Standing “S” (Alt.) Standing “S” Standing “S” (Bar Reinforced) (Angle Reinforced)
Figure 8
6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side)
Flanged system angles
(Attach per manufacturer's instructions)
Duct
Figure 9
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure
10. 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces (see Figure 11).
Stud or Runner
1 in. Min.
Neoprene gasket between all angles
Typical TDC/TDF joint
Do not bolt corners
Duct
11
Duct End
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
Clip Spacing
6 in.
3 Req’d.
24 in. Duct
2 Req’d.
18 in. Duct &
Smaller
1 Req’d.
Std. Clip Length
6 in. 6 in.
5 in. 5 in.
Duct
9 in.
5 in.5 in.
C
L
Flange
Corner Piece
7 in.7 in.
3/8 in. bolt (optional)
Figure 11
Figure 10: Detail of proprietary flanged system
breakaway connections.
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Frame is 'racked' causing blades
Adjust frame such that it is square and plumb
to bind on jamb seals
Actuator linkage loose Close damper, disconnect power, adjust and
Damper does not fully open and/or close
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out
tighten linkage
to line as designated on damper label
Contaminants on damper Clean with a non-oil based solvent (see
Damper Maintenance)
RRL or TOR sensor tripped
Damper does not
Heat Push reset button located on backside of
RRL or TOR
No power supplied to the actuator Add power supply
operate
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
461337• ODFD OFD Rev. 14, August 2013 Copyright 2013 © Greenheck Fan Corporation
12
Loading...