These instructions apply to the external field installation of Invensys actuators on Greenheck model VCD Control Dampers when they are duct mounted or sleeved.
Invensys actuators rotate to their energized position when power is applied and spring return to their fail position when power is interrupted, except for the MC-431 which drives under power in both directions.
Part No. Qty Description
1 1 Actuator
2 1 Mounting Bracket
3 1 Mounting Plate
4 4
5 3
1
/4- 20 x 1/2 in. Threadstud
1
/4- 20 x 3/4 in. Threadcutting
Screw
6 10
7 3
8 3
9 3
10 1
11 1
1
/4- 20 Spinlock Nut
1
/2 in. Crankarm
5
/16- 18 x 11/2 in. Bolt
5
/16- 18 Spinlock Nut
1 in. Crankarm
3
/8- 16 x 21/2 in. Carriage Bolt
Part No. Qty Description
12 1
13 2
14 2
15 1
16 1
17 4
18 1
19 1
20 4
21 2
3
/8- 16 Spinlock Nut
Linkage Adjustment Pin
1
/4 in. E-ring
Drive Link
Stand Off Bracket
1
/4- 20 x 1/2 in. Thread Cutting Screw
Ball Bearing
1
/4 x 1/2 in. Knurl Pin
1
/4- 20 x 1/2 in. Hex Bolt
#10 Tek Screw
Instructions
A
A
Power Position
Fail Position
Power
Return
Damper Shaft
2 1/4 in.
Tools Required:
Wrenches:
(1) 3/8 in., (2) 1/2 in., (1) 7/16 in.,
and (1) 9/16 in. and (1) Hammer
1. Install the stand off bracket to the damper.
Dampers with a jackshaft
1a. Mount the stand off bracket onto the jackshaft bracket
with (4) 1/4- 20 X 1/2 in. thread cutting screws. Use the orientation shown on this page.
Dampers without a jackshaft (Shaft Extension)
1b. Mount the stand off bracket spanning across the damper
frame flanges positioned over the control shaft. Use the orientation shown to the right. The damper shaft must be centered in the stand off bracket. Fasten to the damper frame with (4) #14 Tek screws or equal, supplied by others. Be sure not to run the screws into the damper linkage which is between the flanges.
2. Fasten the mounting plate to the mounting bracket using (4) 1/4- 20 x 1/2 in. thread studs and (4) 1/4- 20 spinlock nuts through the matching four hole pattern on the mounting bracket labeled “A” on the illustration. Note that the mounting plate has only one pattern that will match the mounting plate pattern.
3. Mount the mounting bracket to the stand off bracket using (4)1/4- 20 x 1/2 in. bolts and (4) 1/4- 20 Spinlock nuts included with this kit. Use the outer four holes of the mounting bracket for jackshafted models and the inner four holes for directly driven models.
Orientation of Stand Off
Bracket for a jackshaft
driven damper
Mounting Plate
Orientation of Stand Off
Bracket for a directly driven
damper
Damper
4. If the damper has a 1/2 in. dia. damper shaft, mount the ball bearing into the mounting bracket with two #10 Tek screws. The Tek screws are required to keep the thrust forces from pushing the bearing out of the mounting bracket. If the damper shaft is 1 in. in diameter, then no ball bearing is required.
5. Mount the actuator to the mounting plate in the corresponding holes using (3)1/4- 20 x 3/4 in. thread cutting screws. Note that the actuator must be mounted with the shaft in the horizontal position.