Greenheck IDHB Installation Manual

Document Number 478052
®
IDHB & IDHC Series
Duct Heaters
Installation Instructions
IDHB Series
The information and instructions in this sheet apply to duct heater models for zero clearance installation in ducts. They are approved for use with heat pumps, air conditioners, or other forced air systems and may be controlled by contactors, relays, sequencers or solid state devices.
The duct heaters are prewired, have voltage ratings to 600 volts, both single phase and three phase. The duct heaters are furnished with integral controls.
IDHB and IDHC series are intended for installation in accordance with electric heaters requirements established by:
National Fire Protection Association NFPA Standards 90A and 90B
NFPA Standard 70
Receiving and Handling
Inspect heater for any possible shipping damage. Check all insulators for breakage and inspect heater element wire for any deformation that could cause a
tight.
Electrical connections such as pressure terminals
should be checked for tightness.
IDHC Series
“UL Listed (see complete marking on product) ANSI/UL Standard 1996 (File E366239)
Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave with the owner when the job is complete.
Table of Contents
FIG. 2
FLANGE HEATER
WRAPPER
TERMINAL OR CONTROL BOX
HEATING ELEMENTS
1"
1"
DOUBLE
LIP
Category Pages
Installation ....................................................................................................................................................................2
Electrical Requirements ...............................................................................................................................................3
Minimum Air Velocities .................................................................................................................................................4
Insulated Duct Installation ...........................................................................................................................................5
Heaters with SSR or Electronic Step Controllers ........................................................................................................6
Troubleshooting Guide ............................................................................................................................................. 6-8
Installation -
Failure to follow instructions will void all warranties.
For safe operation and best performance, the following installation procedures must be adhered to. Heaters may be installed in the sides of either horizontal or vertical ducts but never in the top or bottom of a
horizontal duct. Heaters installed in vertical ducts are tested and approved for up airflow only!
1. Install heater a minimum of (4) feet from heat pumps or central air conditioners.
SLIP-IN HEATER
2. At least 4 feet downstream from an air
handler.
3. At least 2 feet either side of an elbow or
turn.
4. At least 4 feet from any canvas duct
connector or transition section for change in
WRAPPER
duct size.
5. At least 4 feet downstream from an air filter.
6. At least 4 feet upstream from a humidifier.
Refer to the back of this sheet for duct, electrical and air velocity requirements.
To install a slip-in heater (FIG.1), cut an opening as required in the side of the duct. Slide heater in the
TERMINAL OR CONTROL BOX
HEATING ELEMENTS
duct using the control box as template to mark the mounting screw holes. Remove unit and drill mounting holes. Mount unit to duct with sheet metal screws.
FIG. 1
Connect high and low voltage supplies along with fan interlock circuit (if no airflow switch is furnished). Larger heaters may require hangers.
To install a flange type heater (FIG.2), insert heater between two sections of flanged duct, and bolt in
DOUBLE
FLANGE HEATER
LIP
place. For additional strength, the duct flange should be doubled as shown in the figure. Large heaters may
1"
1"
require hanger straps. Connect high and low voltage supplies along with fan interlock circuit (if no airflow switch is furnished).
The air duct should be installed in accordance with the Standards of the National Fire Protection Agency
WRAPPER
for the Installation of Air-Conditioning and Ventilating Systems (Pamphlet No. 90A) and Warm-Air Heating and Air-Conditioning Systems (Pamphlet No. 90B).
Do not “bank” heaters (side by side). If greater capacity is required, proportion smaller heaters in separate runouts.
Heater control boxes must be completely accessible
TERMINAL OR CONTROL BOX
HEATING ELEMENTS
FIG. 2
and located to provide ventilation at all times.
2
WATTS PER SQUARE FOOT, DUCT AREA
Electrical Requirements
Refer to attached wiring diagram and wiring diagram on inside of cover. Make sure line and control voltage of system matches that noted on wiring diagram.
Wire in accordance with N.E.C. and any existing local codes. Check tightness of all factory and field electrical connections. Make sure fan interlock is wired in if the Duct Heater does not have an air flow switch.
Use 90°C (194°F) copper wire. Control must be wired for N.E.C. Class 1 unless
otherwise specified. When heater has integral transformer for control
voltage to thermostat, use thermostat with isolating contacts to prevent interconnection of Class 2 outputs.
Disconnect all electrical power before servicing. When servicing heater, make sure all components are repositioned in the proper location and reconnected per the wiring diagram.
Replacement parts must be identical to the original components. Contact factory for replacement parts.
Minimum Air Velocities
The minimum uniform airflow in a duct heater is directly related to the inlet air temperature. Consideration must be given to both airflow across the heater and inlet air temperature, (shown at left).
1. To calculate the watts per sq. ft. of duct area, divide the total watts required by the duct area.
EXAMPLE: Duct Size = 2ft. x 3ft. Total watts = 20,000 W/Sq. Ft. = 20,000 = 3333
6
2. If the air handler equipment is expressed in
F.P.M. then a direct cross reference can be made by comparing the temperature of the air (as it enters the Duct Heater) to the KW rating on the chart of rated velocity.
a. Draw a line horizontally from the Watts/
Sq. Ft. required to the inlet air temperature being used.
b. From this point of intersection on the Inlet
Air Curve, draw a line down vertically to establish the air velocity.
c. The velocity should never be lower than
the velocity as determined from the chart. In cases where this is not true, the velocity must be increased or the KW required must be reduced.
3. In cases where the air handling equipment
is expressed in C.F.M., convert to F.P.M. by dividing the C.F.M. by the duct area.
EXAMPLE: F.P.M. = CFM Duct Area
Minimum Air Velocities
22,000
20,000
18,000
16,000
14,000
12,000
10,000
8,000
6,000
4,000
2,000
Note: Minimum airflow must be
maintained at any point over the face of
Note: Observe at least one complete
heating cycle to insure that cycling of
the safety limit controls does not occur
before leaving the installation.
BELOW 78°F INLET AIR
78° TO 90°F INLET AIR
91° TO 110°F INLET AIR
Minimum Air Velocity (fpm)
the heater.
1,2001,000800600400200
1,400
3
Loading...
+ 5 hidden pages