Greenheck HSD-401 Installation Manual

Document number 464604
®
HSD-401
Leakage Rated Smoke Dampers
Installation, Operation and Maintenance Instructions
These instructions apply to the installation of HSD-401 series leakage rated smoke dampers. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555S UL listing R13317.
D
H*
W*
HSD-401 Dampers are intended for installation in accordance with smoke damper requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, & 105
ICBO Uniform Building Codes IBC International Building Codes
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
UL Standard 555S (Classification #R13317)
C
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 120°F (49ºC).
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
1. SMOKE DAMPER REQUIREMENTS AND APPLICATION
Smoke dampers are required to close and prevent the
passage of air and smoke through ducts or ventilation openings in smoke barriers. Smoke dampers are also applied in engineered smoke control systems to establish air pressure differentials and thereby prevent the spread of smoke. HSD-401 damper is designed to operate with blades running horizontally. Dampers can be vertically or horizontally installed at, in accordance with NFPA-90A, or adjacent to the point where the duct passes thru the smoke barrier.
2. LOCATION OF DAMPER IN DUCTWORK
Place the damper assembly in its proper position relative
to the barrier. The plane of the closed damper blades must be within 24 in. (610mm) of the rated smoke barrier and before any duct inlets or outlets.
3. ATTACHING DAMPER TO THE DUCT
HSD-401 damper is a flange mounted to the duct, sleeve,
3
or wall opening with
/8 in. (10mm) minimum diameter bolts and spaced a maximum of 6 in. (152mm) apart, on center. Dampers can be attached directly to the fan, if required.
4. SEALING THE INSTALLATION
After installing the damper in the ductwork, seal the
joint between the damper frame and the duct using Dow Corning RTV 732 Sealant. Make sure to press the sealant into the joint to guarantee a proper seal. Use the minimum amount of material required to completely seal the joint.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations.
3
4
1
5
Item Description
1. Damper frame
2. Duct outlet
3. Fan (not limited to centrifugal)
4.
5. Actuator The actuators are to be installed to function per system requirements and to be controlled by smoke detection devices.
FAN ISOLATION APPLICATION
For air handling equipment isolation, leakage rated
3
/8 in. (10mm) minimum diameter bolts
dampers are designed to operate with blades running horizontally. Dampers can be installed in a vertical or horizontal position. Sealants and damper seal materials meet the requirements of NFPA90A for smoke developed rating (<50) and flame spread index (<25) as tested per UL723/ASTME84-91A/NFPA 255. Dampers can be attached to the fan system discharge or inlet without being 24 in. (610mm) of a smoke barrier when used as an air handling equipment isolation damper.
2
Size Limitations
in inches (mm)
HSD-401 60 x 60
Maximum single section size
(1524 x 1524)
Maximum single section size when multi-section assembly
48 x 60
(1219 x 1524)
* All multiple section assemblies are factory assembled.
Maximum overall multi-section size*
120 x 60
(3048 x 1524) or
48 x 120
(1219 x 3048)
Loading...
+ 1 hidden pages