The following instructions should be followed when
attempting to modify HPR series pressure relief
dampers for different damper orientations or startto-open pressures. Dampers shipped are set for the
specified start open pressure and flow direction.
Pressure relief dampers designed for horizontal flow
(vertical mounting) are equipped with two sets of arms
(Figure 2A). The first set is in the direction opposite
the blades and offset, or balance, the weight of the
blades. The second set of arms is always positioned
horizontally when the damper is closed (approximately
vertical with blades open) and hold the blades closed
until the start-open pressure is reached. Pressure
relief dampers with vertical up flow/relief (Figure 2B)
and vertical down flow (Figure 2C) only have one set
of arms, as the weight of the edge pivoted blades is
either added or subtracted from the weight necessary
to hold blades closed.
Damper will respond to a positive differential pressure
in the direction of blade opening,
Three (3) different crankarms may be used, depending
on damper size and magnitude of start open pressure.
See Figure 1.
The blades of this type damper exhibit a gradual “lift
off” as start-open pressure is reached. The operating
point is not sharply defined, as when a door suddenly
opens. There is a wide flow range where pressure is
approximately constant.
Instructions for Adjustment on
Pressure Relief Dampers
2
Small crankarm
8 1/2 in. (216mm)
Medium crankarm
12 1/2 in. (318mm)
Large crankarm
Figure 1
COUNTERBALANCE
PRESSURE SET
FLOW
Counterweight Set Procedure (Horizontal
flow only)
The counterbalance weights on a vertically mounted
damper (horizontal flow), must be adjusted first,
if the airflow direction is changed. This is covered
by a separate procedure. Basically, the damper is
adjusted for easy operation (blade weight is just
counterbalanced) before the pressure set arms and
weights are added.
Pressure Setting Procedure
Position damper in the proper orientation and flow
direction.
If a specific relief pressure is required, install a U-tube
manometer or other pressure measuring device in the
duct work to monitor the static pressure.
If damper flow direction must be changed in the field,
loosen fastener in pressure set crankarm and rotate
arms to correct position. See Figures 2A, 2B and 2C
for correct pressure set arm orientation with damper
blades closed.
DAMPER BLADE
Figure 2A Horizontal Flow
DAMPER BLADE
FLOW
Figure 2B Vertical Up Flow
Pressure Setting Procedure cont....
Start-open pressure is adjusted by either changing
weight center distance from axle center line, or
by increasing or decreasing the quantity of plates
mounted to arms. In extreme cases, the arm length
and quantity must be changed. See table at the end of
procedure for replacement parts.
Adjust weight center distance first. Loosen fasteners
holding weight plates to arm and move inward or
outward in arm slot as required. Moving plates toward
axle will reduce start-open pressure; increasing the
center distance will increase the pressure at which
blades start to open. If a greater range of pressure set
adjustment is required, add or remove plates from arms
as required to obtain the required start-open pressure.
Check all fasteners for tightness.
Table of Components
Components Applicable
Model
Axle adapter, 3/8” sq. to ¾” OD, 3”
long
Axle adapter, short, ¾” OD HPR-120 370120 416343
¾” crankarm All 653630 687738
3/8”-16 x 2 crankarm bolt All 415882 415924
3/8”-16 hex nut for crankarm All 415457 416168
Short counterweight arm (8½”) All 647344 689404
Long counterweight arm (12½”) All 657343 683951
3/8”-16 set screw for short/long arm All 415050 415763
3/8”-16 weld nut for short/long arm All 415127 415928
Counterweight plate, 1¼” x 3½” All 653144 687637
Counterweight plate, 2½” x 3½” All 653143 687636
Counterweight plate, 3½” x 3½” All 653142 687635
Bolt, ¼” - 20 x 1¼” All 415973 NA
Bolt, ¼” - 20 x 1½” All 415517 416103
Nut, ¼” - 20 All 415455 415575
HPR-120 458959 NA
DAMPER BLADE
Figure 2C Vertical Down Flow
Galvanized Part
Number
FLOW
Stainless Steel
Part Number
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specications without notice.
Specic Greenheck product warranties are located on greenheck.com within the product area tabs and in
the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
469134• HPR Series Rev. 2, October 2012 Copyright 2012 © Greenheck Fan Corporation