Greenheck GWEW, GWCW, GWFW, GWAW, GWSW Specifications

April 2005
Part # 458292
Read and Save These Instructions
Installation Instructions
for
Waterwash Kitchen Hoods
®
April 2005
TABLE OF CONTENTS
How To Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Waterwash System Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Waterwash Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Continuous Capture Plenum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Double Island Style Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
U Channel Strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Installation Instructions for the External Supply Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Installation Instructions for the Backsupply Plenum BSP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Installing the Supply Duct Collar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Hanging the Backsupply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Hanging the Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Air Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Enclosure Panel Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Filler Panel Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
End Skirt Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Backsplash Panel Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Duct Collar Installation Instructions for GH, GW, GK and GX Series Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Startup, 24/7 Timer, Pump Settings, Detergent Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Daily Operation of Waterwash Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-29
Balancing the Kitchen Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Short Circuit Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
®
April 2005
TABLE OF CONTENTS CONT’D
Field Wiring for Ansul Snap-Action Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Overall Wiring Plan View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Wiring for Hood Switch Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Circuit Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Waterwash Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39-44
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45-49
Replacement Parts/Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50-51
Waterwash Start-up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52-53
Notes for Maintenance Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54-55
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
®
April 2005
HOW TO USE THIS MANUAL
Read and save these instructions. This manual is designed to assist qualified field service, operating and maintenance personnel with the installation, operation, and maintenance of Greenheck canopy type kitchen hoods and accessories.
Procedures described in this manual should be followed in the order they appear, with attention to all safety and caution statements.
RECEIVING, HANDLING & STORAGE:
Upon receiving the equipment, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check also to be sure that all parts of the shipment, including accessories, are accounted for.
If a kitchen hood must be stored prior to installation, (or for any long period) it must be protected from dirt and moisture. Indoor storage is recommended. For outdoor storage, cover the hood with a tarp to keep it clean, dry, and protected from UV (Ultra Violet) radiation damage.
NOTE: The kitchen hood is shipped with a plastic film attached to the surface. The film is to protect the panels from minor scratches during handling and shipment. This film must be removed prior to assembling the system. When the system is operating, the film will melt and bake on to the surface. Once the film is removed caution should be used in handling the parts.
Improper storage which results in damage to the unit will void the warranty.
NOTE: The functions listed above require the control center to be wired to the exhaust fan and plumbed.
WATERWASH SYSTEM FUNCTIONS:
Greenheck waterwash hoods are designed for three primary functions:
1) Capture and contain the effluent produced by the cooking process.
2) Remove grease and other contaminants from the airstream with a series of extraction baffles.
3) Wash the baffles and other surfaces within the exhaust plenum to remove contaminants.
Normal Exhaust Operation and Contaminant Collection:
The system's exhaust fan is manually controlled by a push-button switch (Start Fan) located on the face of the waterwash control station. The exhaust system operates until the Stop Fan/Start Wash push-button switch is pressed.
Optional Continuous Cold Water Mist:
The optional continuous cold water mist is controlled by the same push-button switch (Start Fan). With this option, all hoods with this option are sprayed continuously when the fan is on. This feature acts as a spark arrestor for solid fuel applications, as per NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. This does not have to be all hoods - can be just the solid fuel hoods.
Cleaning Cycle:
A factory programmed controller triggers the waterwash function when the exhaust fans are shut down at the end of each day’s cooking operations. A pressurized spray of hot water and detergent cleans the hood in a timed cycle. When the cleaning cycle is complete, the controller runs the exhaust fans briefly to remove steam from the exhaust system. The controller then automatically resets itself. If the kitchen is closed for a day, the wash cycle will skip as long as the start fan button has not been pushed
.
For multiple hoods totalling over 20 ft. 0 in. in length, systems are designed to wash each hood or group of hoods sequentially. (Hoods totalling up to 20 ft.0 in. in length can be washed as a single unit.)
®
April 2005
Fire Mode (Optional):
The waterwash system also provides water spray for the exhaust plenum when the system is in fire mode. This is in addition to the hood’s automatic fire suppression system. When the fire suppression system discharges, it activates the waterwash system (without the detergent) and the optional continuous cold water mist to spray water within the exhaust plenum and turns on the fan circuit. The system will shut off when the fire protection system is reset. It can also be shut off manually by turning off the water flow in the waterwash control station. Exhaust fan will be on, Supply fan off
Waterwash Hood
Junction Box ­Hood Lights
Exhaust Duct Collar
Drain Pipe
Waterwash Control Station
Hot Water Supply to Control Station
Optional
Cold Water Supply to Control Station
Vacuum Breaker
Detergent Line
Hot Water/Detergent to Hood
Detergent Check Valve
Optional Continuous Cold Water Mist Supply Line
Internal components of hood and control station are factory piped and wired. All external piping and wiring is by others.
Fig. 1
115 VAC 20 AMP service Fire Sup. System NC Switch Fan Control Center Opt. Solenoid Valve
for Seq. Wash
Wiring to:
The system shown includes a vacuum breaker for backflow prevention. Some state plumbing codes require a reduced pressure backflow preventer. See page 7 for detailed control panel layouts of each type.
Typical Installation:
®
April 2005
SYSTEM COMPONENTS:
Hood:
The hood is shipped from the factory prepiped and ready to install. All waterwash components within the hood are complete and ready for connection to hot water, electrical sources, the sanitary sewer drain and optional cold water. All piping to and from the waterwash control station and the hood is by others. Wiring from the control panel to the hood (for lights) is by others. All plumbing and wiring must conform to plumbing and electrical codes. See Figure 1(previous page) for typical installation and location of electrical and plumbing components.
Duct collars are also mounted at the factory unless requested otherwise.
Waterwash Control Station:
The waterwash control station contains all of the water and electrical controls in two separate compartments. (See Figs. 2, 3, 4, 5, 6 & 7). The electrical side includes all electrical components, connections, and on/off switches. These switches are illuminated and are mounted on the face of the cabinet. The water side includes hot water connections, pressure/temperature gauges, the detergent reservoir and pump, water hammer arrestor, the water solenoid valves, and optional continuous cold water mist piping.
Vacuum Breaker (shipped loose for field installation):
The vacuum breaker is installed at the highest point in the system’s piping to prevent backflow when there is no water pressure to the hood. It must be installed a minimum of 6 in. above the hood water supply line (See Figs. 2, 3 & 4).
Reduced Pressure Backflow Preventer - RPBP (shipped loose for field installation):
Where building codes require a reduced pressure backflow preventer, it will be provided in lieu of a vacuum breaker when ordered. The reduced pressure backflow preventer is installed beneath the control panel (See Fig. 5, 6 & 7). May by ordered mounted in 48 in. tall cabinet.
Detergent Pump-Related Components (shipped loose for field installation—installed in RPBP systems. See page 42 ):
• Detergent line check valve
• Detergent tube (1/4 in. I.D., 3/8 in. O.D.)
Optional Features:
24 Hour / 7 Day Timer:
This feature allows the cleaning cycle to begin at any preset time after the fans are shut down, rather than immediately after. This allows time, for instance, for completion of dishwashing to avoid a shortage of hot water. Fans must be turned OFF just as with the standard cleaning cycle. Maximum six start times.
Multiple Hoods Sequenced Wash:
Where more than one hood must be washed, the control station is set up to wash each hood individually in a prescribed sequence. This ensures that there will be adequate hot water for all hoods. Individual water solenoid valves are provided for each hood to be washed in a multiple sequence. Maximum five sequences.
(Sequence solenoid valves are shipped loose for systems with vacuum breakers or optional continuous cold water mist. They are mounted in the control station for standard systems with reduced pressure backflow preventers.)
Low Detergent Indicator Light:
A sensor and indicator light are available to alert the operator when the detergent tank requires filling.
Continuous Cold Water Mist:
This feature continuously sprays a fine water mist in the exhaust plenum of the hood. The continuous cold water mist is controlled by the same push button switch as the fan.
®
April 2005
Fig. 3 Optional Piping for Sequence Wash
Fig. 6 Optional Piping for Sequence Wash
Reduced Pressure Backflow Preventer
Field Wiring Terminal Strip
Fan Relay
Optional 24 Hour Timer
Fuse Block
Programmable Controller
Factory Wiring Terminal Strip
Disconnect Switches
Water Solenoid Valve(s)
Water
Solenoid Valve
Detergent
Injection Point
Detergent
Pump
Water Solenoid Valve(s)
6 in.
6 in.
Optional Low Detergent Indicator Light
Stop Fan/Start Wash Switch
Start Fan Switch
Fire Mode Indicator Light
Hood Lights
Vacuum Breaker
Union
Hand Valve
Detergent Line Strainer
Water Hammer
Arrestor
Pressure
Reducing Valve
and Strainer
Hand Valve
Pressure and
Temperature
Gauge
Fig. 2 Std. Piping with Vacuum Breakers
Fig. 5 Std. Piping with Reduced Pressure
Backflow Preventer
Fig. 7 Piping with Reduced Pressure
Backflow Preventer and Optional
Continuous Cold Water Mist
Piping
by
Others
Piping by
others
To Hood 3/4 in. or 1 in. Connection
Hot Water Inlet
To Hood 3/4 in. or 1 in. Connection
To Hood 3/4 in. or 1 in. Connection
Detergent Tank
Cold Water Inlet
Detergent
Check Valve
Pressure
Gauge
Solenoid Valve
To Hood 3/8 in. Connection
Fig. 4 Piping with Vacuum Breakers and
Optional Continuous Cold Water Mist
®
April 2005
Hood Model Width (in feet)
Wall Canopy 4 4.5 5 5.5
GWEW 53 lbs/ft. 56 lbs/ft. 59 lbs/ft. 62 lbs/ft. GWFW 60 lbs/ft. 60 lbs/ft. 62 lbs/ft. NA GWAW NA 60 lbs/ft. 65 lbs/ft. 70 lbs/ft. GWCW NA 65 lbs/ft. 70 lbs/ft. 75 lbs/ft. GWSW 60 lbs/ft. 65 lbs/ft. 70 lbs/ft. 75 lbs/ft.
For double island hoods, multiply the weight by two.
SUPPO
3. FASTEN TOP ANGLES TOGETHER USING 1/4 in. BOLTS &
4. FASTEN HOODS TOGETHER USING U-CLIPS, 1/4 in. BOLT
.
.
HOOD
Continuous Capture Plenum Hoods
Remove the support angles on the open end panels. (See Fig. 8A) Use the installation procedure described above, for single island hoods to install and level both hoods. After leveling, secure the hoods together by tack welding and/or bolting the top angles. Fasten the hoods together using u-clips and bolts. (See Fig. 8B) Caulk this joint with NSF approved silicone caulk (GE SCS-1009 or its equivalent). The caulk is not provided.
Fig. 8A
Fig. 8B
INSTALLATION
NOTE: If you have a Backsupply Plenum (BSP), this must be installed before the hood. Please
see Page 13.
For Wall/Single Island Style Hoods, prior to installation, check with local authorities having jurisdiction on clearances to combustible surfaces, etc.
With the hood still inside its packing crate, position the unit beneath its installation location. Carefully remove the packing
crate. Place some protective material on the floor next to the crate to avoid damaging the hood as it is tipped on its side. (See Fig. 8) Tip the hood carefully onto the protective material. If you have filler panels, install them now. Please see page 16.
If you have integral filler panels, no additional installation is needed.
Insert
1
2 in. diameter threaded rod (by others) into hanger brackets on hood top. (Fig. 9, Pg. 10) Check the engineering drawings for proper hood height above finished floor. Greenheck recommends that the hoods be hung 6 feet 6 inches above the finished floor. Raise and hang hood from adequate roof or ceiling supports. All hanger brackets must be used and hood must be properly supported while lifting to prevent damage or distortion to the hood. The hood must be hung level
to or slightly pitched toward the grease drain.
Fig. 8
Note: If a utility distribution system (UDS) is part of the kitchen package, allow adequate room for it before mounting hood(s) and welding ductwork. Check construction documents.
Bottom
Pallet
Protective Material
1. REMOVE SUPPORT ANGLE ON OPEN END PANEL
2. RAISE ALL HOODS INTO APPROPRIATE LOCATION RT PER CONSTRUCTION PLANS.
AND
& CAP NUTS AS INDICATED.
5. CAULK ALL SEAMS AS NECESSARY
®
April 2005
Double Island Style Hoods
Before hanging the hoods, please verify the hood marks to make sure the correct hood is hung on the correct side.
A double island hood is created by installing two wall style hoods back to back. Use the installation procedure described on page 8, for single island hoods to install and level both hoods. After leveling, secure the hoods together by tack welding and/or bolting the rear mounting brackets. Caulk this joint with NSF approved silicone caulk (GE SCS-1009 or its equivalent). The caulk is not provided.
Installing U Channel Trim Strip
1. After the hood is hung in position
and leveled, apply caulk to the inside edge of the double island clip (see detail).
2. Position and install the clip by
tapping into position along clip (friction fit).
3. Caulk edges to seal out grease and allow for ease of cleaning.
Caulk with NSF approved silicone caulk (GE SCS­1009 or its equivalent). The caulk is not provided.
Note: The installation of the canopy hoods shall be in accordance with NFPA 96 (latest edition), Removal of Smoke and Grease-laden Vapors from Commercial Cooking Equipment.
See separate instructions for proper installation of enclosure panels, backsplash panels, and end skirts when provided. Please see Pages 15 -19 for the installation instructions.
After the hood is installed, remove all protective plastic.
Note: GFC does not recommend walking or standing on the hood top as damage can result. If you must walk on the hood top, protect the hood with additional support or planks for flooring.
HOOD FRONT
ITEM-1B
DOUBLE ISLAND
CLIP
ITEM-1A
HOOD-1A
HOOD-1B
SILICONE CAULK (GE SCS 1009)
DOUBLE ISLAND CLIP
®
10
April 2005
Installation: All seams, joints, penetrations, and duct to hood collar connections shall have a liquid tight external weld. If you have an Automatic Fire Damper please refer to that manual for installation instructions.
Supply
Supply ductwork (where applicable) should be connected to the hood in a manner approved by the local code authorities.
Note: For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning and inspection shall be provided in the duct. This panel shall be as close to the hood as possible and not exceed 18 inches from any hood damper.
For proper installation of duct collars when they are shipped unattached, see page 20.
DUCTWORK Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the following manner:
Materials. Ducts shall be constructed of and supported by carbon steel not less than 1.37mm (.054 in.) (No. 16 MSG) in thickness or stainless steel not less than
1.09mm (0.043 in.) (No. 18 MSG) in thickness.
1
Fig. 9
others
/2 in. threaded rod by
Front
®
11
April 2005
HANGER BRACKET
ATTACH HANGING CLIP TO HOOD STANDING SEAM WITH THE SUPPLIED "C" CLAMPS
(OPTIONAL: DRILL AND BOLT A 1/4-20 SS BOLT THROUGH THE CLIP AND HOOD STANDING SEAM)
TOP VIEW HOOD
TOP VIEW SUPPLY PLENUM
2 CLIPS ARE NEEDED
3 CLIPS ARE NEEDED
FOR PLENUMS > 96"
FOR PLENUMS <= 96"
THE THIRD CLIP IS LOCATED IN THE CENTER OF THE PLENUM
LENGTH
OPTION #1
ON THE END OF THE HOOD
HANGING CLIP COULD BE 23.5" FROM END IF THERE IS A UTILITY CABINET
OPTION #1
OPTION #1
OPTION #2
UNI-STRUT SUPPLIED BY OTHERS
OPTIONAL UTILITY CABINET
11. 5
23.5
Using the Supply Plenum Clip
1. Bolt the hanging clip to the supply plenum - 2 clips are needed for plenums less than 96 in. long and 3 for plenums greater than 96 in. The third clip is located in the center of the plenum length. If there is a utility cabinet, the hanging clip should be 23.5 in. from the end to the hood.
2. Using the C-Clamps provided, clamp the supply plenum hanging clip to the hood standing seam. Option: Drill and bolt a 1/4-20 SS bolt through the clip and hood standing seam.
INSTALLATION INSTRUCTIONS FOR EXTERNAL SUPPLY PLENUMS USING THE SUPPLY PLENUM CLIP or UNI STRUT
Supply Plenum Clip
Using the UNI-STRUT
1. The uni-strut (supplied by others)
that holds the hood up cantilevers over the end of the hood and is mounted to the supply plenum hanger brackets.
END VIEW
THREADED ROD
HOOD
THREADED ROD
OPTION #3
THE HOOD AND IS MOUNTED TO THE ASP
HOOD UP CANTILEVERS OVER THE END OF
THE UNI-STRUT (U-CHANNEL) THAT HOLDS THE
HANGER BRACKETS
OPTION #2
OPTION #2 = UNI-STRUT OPTION #3 = THREADED ROD
SUPPLIED BY OTHERS
ASP, FSP, VSP
"C" CLAMP
HOOD FRONT
HOOD STANDING SEAM
HANGING CLIP BOLTED TO PLENUM SHELL
HANGING CLIP
SUPPLY PLENUM SHELL
OPTION #1 HANGING CLIP
®
12
April 2005
INSTALLATION INSTRUCTIONS FOR EXTERNAL SUPPLY PLENUMS USING A THREADED ROD
ASP - Air Curtain Supply Plenum
VSP - Variable Supply Plenum
Using the UL Listed Fastener Provided
1. Drill a 9/32 in. hole for the 1/4 in. bolt from the inside of the supply plenum to inside the hood. Fasteners are to be located max. 6 in. from the end of the hood with max. spacing between bolts 36 in.
DO NOT include utility cabinets or fillers when figuring bolt placement.
DO NOT bolt the supply plenum to a fire/utility cabinet.
2. Push bolt through hole, using the washer and nut.
3. Hand tighten, then use a wrench until fully tightened. Caulk around bolts from inside of hood as necessary.
SUPPLY PLENUM WEIGHTS
Hood Height 24 in. 24 in. 30 in. 30 in.
Hanging Height 78 in. 84 in. 78 in. 84 in.
ASP 9.5 lbs/ft. 11.7 lbs/ft. 11.7 lbs/ft. 13.9 lbs/ft. VSP 16.5 lbs/ft. 18.7 lbs/ft. 18.7 lbs/ft. 20.9 lbs/ft. BSP 42 lbs/ft. 42.2 lbs/ft. 42.2 lbs/ft. 44.4 lbs/ft.
Installing External Supply Plenum
1. Insert 1⁄2 in. diameter threaded rod (by others) into hanger brackets on the supply plenum top. Raise and hang the external supply plenum from adequate roof or ceiling supports.
2. The external supply plenum should be resting lightly against the hood. The hood is used to position the plenum only, it is not intended to support the plenum. All hanger brackets must be used and the plenum must be properly supported while lifting to prevent damage or distortion. The supply plenum must be hung level to operate properly.
(Optional fastening of supply plenum to hood - see directions below)
3. It is recommended that caulk be applied at the mating seams and surfaces of the plenum, the hood, and the wall. If the supply plenum is next to a wall, you will also need to caulk around the surface next to the wall. Caulk the joints with NSF approved silicone caulk (GE SCS-1009, or its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
1. Place the duct collar(s) over the opening, fastening with tack welds at 1 in. to 2 in. intervals, or sheet metal screws at 3 in. to 6 in. intervals.
1/4 - 20 UNC - 2A
SS BOLT
HOOD
1/4 in.
SS NUT
®
SS FLAT WASHER
13
April 2005
These fasteners are to help maintain the location of the Backsupply, and are not intended to hold the weight
of the Backsupply Unit.
The fasteners should not interfere with the removable air diffusers.
The 31.25 in. height is based upon the canopy hood hanging height of 78 in. from the finished floor to the
bottom of the hood.
Fig. 11
)
/2
/4
/4
Fig. 10B
• The 4 in. high duct collar is to be attached
to the backsupply.
Hanging the Backsupply Plenum
5. Hang the Backsupply Plenum from the ceiling. (The Backsupply Plenum needs to be mounted 31.25 in. above the floor (based upon a canopy hood that will
be hung at 6 ft. 6 in. above the finished floor. This is measured from the lowest rear edge of the Backsupply Plenum to the finished floor. Leave 6 to 10 inches of space below the plenum for access to the air diffusers.)
6. Fasten the Backsupply to the wall, going through the lower Backsupply wall. (See Fig. 12)
INSTALLATION INSTRUCTIONS FOR THE BACKSUPPLY PLENUM BSP
Installing the Supply Duct Collar
1. Find the center of the Backsupply Plenum.
2. If the Backsupply Plenum is less than 9 ft. 10 in. wide, cut opening at
the suggested location, centering the opening over the center of the backsupply Plenum. (see Fig. 10A)
3. If the Backsupply Plenum is greater than 9 ft. 10 in. wide, divide the
width of the backsupply by four. This will give you the center of each half. Cut openings at the suggested location, centering the duct collar over the center measurement of each half. (see Fig. 10B)
4. Place the duct collar(s) over the opening, fastening with screws or tack
welds every four to six inches. (see Fig. 11)
/2
/2
)
W
Fig. 10A
W
W (MODULE WIDTH
W
W
(MODULE WIDTH
W
W
®
14
April 2005
Fig. 12
Hanging the Hood
Before hanging the hood according to the hood installation instructions, please check the following:
1. Make sure the Backsupply Plenum is properly secured, as described in steps 5 and 6, page 13.
2. If the ductwork for the Backsupply will not interfere with the hood installation, it should be connected now.
3. Any filler panels should be attached to the hood before the hood installation. See page 16 for instructions.
4. For Canopy Hoods: Lift the hood, and position it so the filler panels are resting lightly on the top outside edges of the Backsupply. The Backsupply is used to position the hood only, it is not intended to hold any hood weight. (See Fig. 13)
5. Connect the remaining ductwork for the Backsupply and the hood. It is recommended that caulk be applied at the mating seams and surfaces of the Backsupply, the hood, and the wall.
Fig. 13
Air Diffusers
The air diffusers, located at the bottom of the backsupply (See Fig. 14), will need to be cleaned as often as the application dictates. Inspect periodically to determine the cleaning schedule.
1. To clean the air diffusers, unfasten the screws. Remove the air diffusers from the Backsupply Unit, and wash in the sink or dishwasher.
2. Insert the air diffusers at an angle from the bottom, and rotate so the forms are downward. Rest the diffuser on the internal angles. (See Fig. 15)
3. Refasten with the stainless steel screws.
Return to Page 8.
Fig. 14
Fig. 15
Fasteners holding the backsupply to the wall
31.25 in. Critical Dimension
Removable Air Diffusers
®
15
April 2005
OSURE
OP
OSURE
S
L
E
.
H
S
ENCLOSURE PANEL INSTALLATION INSTRUCTIONS
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork attached and electrical connections completed.
Fig. 16
1. Position the end enclosure panels on the hood, and clamp into place with clamps provided or tack weld the panels into place (see Fig 16).
2. Fasten the end enclosure panels to the wall, method depends on wall construction. (fasteners are not provided)
If the hood is a double island, bolt the end enclosure panels together. (fasteners are not provided)
3. Position the front enclosure panel(s) on the hood, and bolt to the end enclosure panels with the 5/16 in. bolts provided in the hardware package.
4. Tack weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be positioned 4 inches from the ends, and in the center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS-1009, or its equivalent). The caulk is not provided.
6. Installation instructions may not be applicable for concrete ceilings.
Return to Page 9.
FRONT ENCL
FASTENERS TO WAL BY OTHER
3/8 IN. DIA HOL
ND ENCL
HOOD T
PANE
5/16 IN. BOLTS WIT
NUTS AND WASHER
LAMP
®
16
April 2005
OO
G
L
H
S
CK
FILLER PANEL INSTALLATION INSTRUCTIONS
1. Uncrate the hood and lay it on the floor with protective material between the hood and the floor (See Fig. 8, page 8).
2. Bolt the filler panels together with 5/16 in. bolts provided in the hardware package.
3. Position the filler panels to the hood back, and tack weld them into place (see Fig. 17).
4. To allow for ease of cleaning, caulk the external seams with NSF approved silicone caulk (GE SCS-1009, or its equivalent). The caulk is not provided.
Return to Page 8.
Fig. 17
HOOD
HOOD
H
D
HT FILLER PANE
RI
TACKWELDED TO HOOD BA
5/16 IN. X 3/4 IN. BOLTS WIT WASHERS & NUT
®
17
April 2005
END SKIRT INSTALLATION INSTRUCTIONS
1. After the hood is hung in position, slide the hemmed form on top of the end skirt onto the end panels of the
hood.
2. Drill a hole in the hood end panel to line up with the hole in the end skirt. Attach the end skirt with a 1/4 in.
bolt and cap nut to the inside of the hood, or tack weld the end skirt to the hood.
3. Position the end skirt against the wall and attach. The method depends on the wall construction. (fasteners
for this are not provided)
4. Caulk the internal joint formed by the end skirt and the hood end panel with NSF approved silicone caulk
(GE SCS-1009 or its equivalent). The caulk is not provided.
5. To allow for ease in cleaning, also caulk all the external seams.
Return to Page 9.
Fig. 18
®
Loading...
+ 39 hidden pages