Greenheck GUW Installation Manual

READ AND SAVE THESE INSTRUCTIONS
Utility Distribution System
Installation, Operation and Maintenance Manual
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when you complete the job.
Receiving and Handling
Upon receiving the equipment, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
GREENHECK
KITCHEN VENTILATION SYSTEMS
¨
SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171 www.greenheck.com
October 1999
2
Table of Contents
Installation Page
Wall System Model GUW ............................................................................................3
Island System Model GUI ............................................................................................4
Electrical Connections ..................................................................................................5
Electrical Fire Fuel Connections ..................................................................................6
Plumbing Connections ................................................................................................7
Hose Assemblies Installation ......................................................................................8
Operating Instructions
Ground Fault Connection Plate ....................................................................................9
Power Sensitive Ground Fault Relay ..........................................................................10
Fire Fuel Shut Off..........................................................................................................11
Gas 5 Second Delay ....................................................................................................11
Remote Status Indicator Lights ..................................................................................11
Ventilator Light Switch..................................................................................................11
Exhaust Motor Fan Motor Controls ............................................................................12
Emergency Stop ..........................................................................................................12
General Plumbing Instructions ....................................................................................13
This manual will acquaint you with the operation and proper maintenance of your Utility Distribution System. IT IS IMPORTANT THAT YOU READ THIS MANUAL
THOROUGHLY AND FOLLOW ITS RECOMMENDATIONS.
In certain instances the manual make reference to features which may or may not be part of your equipment. To determine whether such references apply to you, please consult your submittal and electrical drawings which have been prepared for you as part of this manual.
GREENHECK
¨
October 1999
3
UTILITY DISTRIBUTION SYSTEM
Model GUW Installation
A. WALL MOUNTED:
1. Read entire manual and study drawings before starting installation.
2. Check that all electrical and plumbing rough-ins are as specified and agree with the drawing.
3. The GUW system consists of the following parts:
a. Riser
b. Raceway
c. Pedestal (optional)
4. Remove all access panels on raceway, riser and pedestal to reveal internal plumbing, electrical systems, and internal flanges.
5. Place GUW sections according to the drawing to determine the proper mounting positions.
6. Once sections are in position, join field joints (if any) by bolting internal flanges together and applying NSF approved silicone caulk (GE SCS-1009, or its equivalent ) over seams. Caulk is not provided.
7. GUW mounting procedures:
a. Mount stainless steel channel (shipped loose) in proper location on wall.
b. Place unit on channel and insert studs, on the unit, into the holes in the channel.
c. Drill holes through unit as shown on drawing and secure properly to wall.
8. If height of GUW interferes with perimeter of hood at time of installation, proceed as follows:
a. Remove pedestals
b. Slip riser up into hood
c. Reattach pedestals
9. Secure field joint support pedestal(s) to the floor as required, and seal the unit to the wall and floor with an NSF approved silicone caulk, (GE SCS-1009, or its equivalent). Caulk not provided.
Wall Mounted
GREENHECK
¨
October 1999
4
UTILITY DISTRIBUTION SYSTEM
Model GUI Installation
B. ISLAND MOUNTED:
1. Read entire manual and study drawings before starting installation.
2. Check that all electrical and plumbing rough-ins are as specified and agree with the drawing.
3. The GUI system consists of the following parts:
a. Riser (optional)
b. Raceway
c. Pedestal (optional)
4. Remove all access panels on raceway, riser and
pedestal to reveal internal plumbing, electrical systems, and internal flanges.
5. Place GUI sections according to the drawing to
determine the proper mounting positions.
6. Once sections are in position, join field joints (if any) by
bolting internal flanges together and applying NSF approved silicone caulk (GE SCS-1009, or its equivalent ) over seams. Caulk is not provided.
7. GUI mounting procedures:
a. Drill holes in floor to match the hole pattern of
the riser bolt flanges.
b. Insert fasteners, (supplied by others) through the holes in the riser bolt flanges and secure to the
floor.
c. Seal around teh bottom of the riser with an NSF approved silicone caulk, (GE SCS-1009, or its
equivalent). Caulk not provided.
8. If height of GUI interferes with perimeter of hood at time of installation, proceed as follows:
a. Remove pedestals
b. Slip riser up into hood
c. Reattach pedestals
9. Secure field joint support pedestal(s) to the floor as required, and seal around the bottom with an NSF
approved silicone caulk, (GE SCS-1009, or its equivalent). Caulk not provided.
Island Mounted
GREENHECK
¨
October 1999
5
ELECTRICAL CONNECTIONS
Installation
1. If system has field joint(s), wiring must be interconnected at the joint(s) before attaching main service.
a. Connect corresponding busbars together
with the brass bolts and nuts that are provided.
b. Connect control wiring (if supplied) to
corresponding terminals or quick disconnect device.
2. Connect the electrical service(s) to the system as follows:
a. Secure service conduit to the electrical
housing. A service entrance knockout must be provided.
b. Attach main service wires to the
corresponding terminals.
c. For instructions regarding the fire fuel
shut-off, Please see Page 6.
d. Check and tighten all connections.
e. Connect all cord assemblies to the appropriate
equipment as shown on submittal drawing. Cut cord assemblies if necessary to make a neat appearance.
f. Wire conduit from hood light switch (if provided)
to hood lights. See electrical drawing.
g. Wire from steam timer terminal block (if
provided) to remote steam timer. See electrical drawing.
h. Wire to exhaust fan motor starter or controls (if
provided). See electrical drawing.