UL Listed Fire/Smoke and Smoke Control Dampers
2-Position, 15-second Run Time,
15-second Spring Return Time
Description
N474
The OpenAir™ direct coupled, fast-acting, two-position, spring return electronic actuators
are available as 24 Vac/dc, 120 Vac, and 230 Vac models. They are intended for use on
UL listed smoke control dampers and combination fire/smoke rated dampers.
Features
Application
• Optional built-in auxiliary switches: Fixed switch points at 5° and 85 ° rotation.
• Optional built-in Electronic Fusible Link (EFL) capability with four temperature
• Fifteen-second operation at rated torque, temperature and voltage.
This actuator is used for the control of dampers requiring up to 53 lb-in (6Nm) driving
torque. It is intended for control of UL listed smoke control dampers and combination
fire/smoke HVAC dampers. This actuator is designed to meet the 2002 revisions to the
UL 555/555S and the AMCA Standard 520 specifications.
Siemens Building Technologies, Inc.
Technical Instructions OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers
Document No. 155-746
March 17, 2005
Product Numbers
Direct-coupled Electronic Fire and Smoke Damper Actuator
G
Spring Return 53 lb-in (6 Nm)
N
15 second run time
D
24 Vac/dc
1
120 Vac
2
230 Vac
3
2-position
2
Standard version
1
Two auxiliary switches
6
Fire and smoke shaft adapter
.1
Assembled in USA
U
Bulk pack 10
/B
Electronic Fusible Link (EFL) connection
/F
EFL connection and bulk pack 10
/F/B
Warning/Caution Notations
Service
WARNING
CAUTION:
WARNING:
Do not open the actuator. Personal injury may occur if opened. Opening the
actuator voids the warranty.
If the actuator is inoperative, replace the unit.
Personal injury/loss of life may occur if you do
not perform a procedure as specified.
Equipment damage may occur if you do not
perform a procedure as specified.
Page 2 of 7Siemens Building Technologies, Inc.
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers Technical Instructions
Document No. 155-746
March 17, 2005
Specifications
Power supply
Operating voltage 24 Vac ±20%
24 Vdc +20%, -10%
120 Vac ±10%
230 Vac ±10%
Frequency 50/60 Hz
Power consumption 24 Vac/dc
running 20 VA/12W
holding 8 VA/6W
Power Consumption 120 Vac/230 Vac
running 20 VA
holding 9 VA
Function
Running torque 53 lb-in (6 Nm) (minimum)
Stall torque (minimum) 160 lb-in (18 Nm)
Torque reduction at elevated temperature Less than 10%
Runtime for 90° 15 seconds nominal
closing (on power loss) with spring return 15 seconds maximum
Nominal angle of rotation 95°
Operation 0°F to 140°F (-18°C to 60°C)
one time 350°F (177°C)
Storage and transport –40°F to 158°F (–40°C to 70°C)
Ambient humidity (non-condensing) Maximum 95% rh non-condensing
Teflon® cable 400°F (200°C)
UL873
cUL C22.2 No. 24-93
AS/NZS 2064 1/2:1997
Conforms to CE requirements for the
EMC and low voltage directives
When power is applied, the actuator coupling moves toward the open position, "90°".
The actuator opens in 15 seconds nominal, 90° at 60 Hz. In the event of a power failure
or when operating voltage is turned off, the actuator returns to the "0" position. The
return time is 15 seconds nominal for 90°.
The National Fire Protection Association NFPA 92A Standard for Recommended
Practice for Smoke-Control System and UL 864 Standard for Control Units and
Accessories for Fire Alarm Systems, require weekly self-tests for dedicated smoke
control equipment used in a smoke control system. The National Fire Protection
Association NFPA 72 Standard for National Fire Alarm Codes states that all life-safety
systems are to be functionally checked at least annually.
The GND actuator does not require any periodic cycling to function properly as an
integral part of an active smoke control damper system. Check the smoke control
damper/actuator every time you functionally check your smoke detectors, emergency
lights, and/or power generators for operation.
Refer to the installation instructions for detailed guidelines. (See 129-402)
CAUTION:
Read and carefully follow the Installation Instructions to avoid equipment
damage.
Page 4 of 7Siemens Building Technologies, Inc.
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers Technical Instructions
Document No. 155-746
March 17, 2005
Wiring
Wire Designations
24 Vac/dc
120 Vac
All wiring must conform to NEC and local codes and regulations.
RED
(SUPPLY)
M
Function Color
Supply Red
Neutral Black
Ground Green
EA0941R1
BLACK
(NEUTRAL)
GREEN
(GROUND)
Figure 2.
BLACK (Line)
Function Color
Line Black
M
Neutral White
Ground Green
EA1167R2
WHITE
(Neutral)
GREEN
(Ground)
Figure 3.
230 Vac
Auxiliary Switches
EA0609R2
BROWN (Line)
M
BLUE
(Neutral)
Figure 4.
85∞5∞
YELLOW
EA1163R2
Figure 5.
GREEN
(Ground)
FunctionColor
Line Brown
Neutral Blue
Ground Green
CAUTION:
The actuator must be wired
with a 230 Vac line with respect
to neutral and the ground lead
must be connected for proper
protection of the actuator. Any
other connection, such as
phase-to-phase, can damage
the actuator.
Switch
Wire
Color
Switch
Makes
Switch
Breaks
5° Gray < 5° > 5°
85° Yellow > 85° < 85°
GRAY
NOTE:
Both sets of contacts are open when actuator is
between 5° and 85°.
Siemens Building Technologies, Inc. Page 5 of 7
Technical Instructions OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers
Document No. 155-746
March 17, 2005
Wiring, Continued
NOTE:
When ordered, GND
Electronic Fusible Link
models come pre-wired
for coupling with EFL
sensor.
EA1166R1
Figure 6.
Molex connector
for use with
Siemens EFL
Figure 7.
EA1165R1
Page 6 of 7Siemens Building Technologies, Inc.
OpenAir GND Series Electronic Damper Actuator UL Listed Fire/Smoke Control Dampers Technical Instructions
Document No. 155-746
March 17, 2005