Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
could result in personal injury and/or property damage! Retain instructions for future reference.
Installation,Operation and Maintenance Manual
Model GGH2O
General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if seismic activity
is present. If more information is needed, contact a
licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
DANGER
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Model GGH20 Grease Grabber Auto-Cleaning Hood
1
®
Page 2
Receiving
Upon receiving the product check to make sure all
items are accounted for by referencing the bill of
lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. A Carrier Inspection Report should be filled out
by the carrier upon arrival and the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
The unit should be stored at least 3½ in. (89 mm) off
the floor on wooden blocks covered with moisture
proof paper or polyethylene sheathing. Aisles between
parts and along all walls should be provided to permit
air circulation and space for inspection.
Inspection and Maintenance during Storage
While in storage, inspect once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location,
they should be protected and maintained in a similar
fashion, until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
Handling
Units are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle in such a manner as to keep from scratching
or chipping the coating. Damaged finish may reduce
ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the unit and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
The ideal environment for the storage of units and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain, or snow. Temperatures should
be evenly maintained between 30°F (-1°C) and
110°F (43°C) (wide temperature swings may cause
condensation and “sweating” of metal parts). All
accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To
avoid “sweating” of metal parts allow cold parts to
reach room temperature. To dry parts and packages
use a portable electric heater to get rid of any
moisture build up. Leave coverings loose to permit air
circulation and to allow for periodic inspection.
Model GGH2O
2
®
Page 3
Table of Contents
Grease Grabber™ H2O System Function .................... 3
Cleaning Cycle
Manual and Automatic Engagement ........................ 4
Fire Mode ...................................................................... 4
Greenheck GGH2O hoods are designed for three
primary functions:
• Capture and contain the effluent produced by the
cooking process.
• Remove grease and other contaminants from the
airstream with two stages of mechanical filters
(Primary Grease X-Tractor filters and secondary
Grease Grabber filters).
• Wash the filters and other surfaces within the
exhaust plenum to remove contaminants.
NOTE
The wash sequence of the hood is not designed for
fire suppression and will not engage in the event of
a fire.
NOTE
The functions listed above require the control center
to be wired to the exhaust fan(s) and the hood
plumbed.
NOTE
For a complete list of functions, please refer to the
sequence of operations.
Normal Exhaust Operation and
Contaminant Collection
The system’s exhaust fan is manually controlled by
a press-button switch (FAN ON/OFF) on the graphic
keypad (included with hood). The exhaust system
operates until the FAN ON/OFF button is pressed. The
wash cycle can be manually engaged to run on a preprogrammed control sequence by pressing the CLEAN
HOOD button or automatically engaged to run at the
same time each day through a programmable timer.
®
Model GGH2O
3
Page 4
Cleaning Cycle
Manual Engagement
The wash function is triggered by pressing the Clean
Hood button after the exhaust fans are shut down at
the end of each day’s cooking operations (pressing
the Fans On/Off button).
Hot water and detergent will fill the hood reservoir.
The soapy water will then be cycled through the hood
by the attached recirculation pump, cleaning both the
filter banks and the exhaust plenum area on a timed
cycle.
When the cleaning cycle is complete, the water
is purged from the reservoir by the pump and the
reservoir will again fill with clean hot water.
A rinse cycle will then run on a timed cycle and the
water will again be purged by the pump.
When the cycle is complete, the controller runs the
exhaust fans briefly to remove steam and excess
moisture from the exhaust system.
Automatic Engagement
The hood is equipped with an automatic timer. The
timer will automatically initiate the wash sequence
at the programmed time each day. All other washing
functionality will be the same as the manual
engagement sequencing.
Fire Mode
In the event of a fire, the hood exhaust fan(s) will turn
on at full power and the supply fan will turn off (default
setting controlled by others) regardless of current fan
operation. If the hood is in a wash cycle, the hood will
drain and the fans will turn on.
NOTE
The wash sequence of the hood is not designed for
fire suppression and will not engage in the event of
a fire.
Model GGH2O
4
®
Page 5
System Components
Hood
The hood is shipped from the factory pre-piped and
ready to install. All wash components within the hood
are complete and ready for connection to hot water,
sanitary sewer drain and the electrical sources. Wiring
from the control panel to the hood (for lights) is by
Greenheck. All plumbing and wiring must conform to
plumbing and electrical codes. Duct collars are factory
mounted unless specified otherwise.
NOTE
Filters are shipped loose with the hood and installed
in the field. See page 25 for installation details.
Grease Grabber H2O Control Cabinet
The control cabinet contains all of the water and
electrical components, and connections including
the Programmable Logic Controller (PLC), that
controls the wash sequencing and operations. The
control cabinet also includes the detergent reservoir,
detergent pump, recirculation pump, solenoid valves
and other water piping.
NOTE
The recirculation pump is shipped loose with the
hood. See pages 16 for installation details.
Graphic Keypad
The graphic keypad is the interface between the
control functions of the GGH2O hood and the user.
This keypad is typically mounted on the Grease
Grabber H2O control cabinet, but can also be shipped
loose for remote mounting. The keypad consists
of three main buttons: hood lights, fan on/off and
clean hood. The keypad also has system fault and fill
detergent indicator lights to alert of any fault in the
system or when the detergent tank is low.
HOOD
LIGHTS
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
GGH2O Keypad
If the GGH2O is being used with the Vari-Flow Air
Management system, there will be an additional
FAN 100% button for sending fan speeds to 100%.
For detailed information on the Vari-Flow Air
Management system, please refer to the Greenheck
website, www.greenheck.com
CLEAN
HOOD
FAN
ON/OFF
SYSTEM
FAULT
472619
NOTE
HOOD
LIGHTS
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
FAN
100%
CLEAN
HOOD
FAN
ON/OFF
SYSTEM
FAULT
472620
GGH2O and Vari-Flow Keypad
CLEAN
HOOD
FILL
DETERGENT
After pressing “CLEAN HOOD”, Fans will automatically stop.
In case of emergency, the wash cycle can be stopped by pressing “CLEAN HOOD”.
SYSTEM
FAULT
LIGHTS
LUCES
CLEAN
FAULT
Melink Customer Service USA: 877-477-4190
%
FANS
VENTILADORES
HOOD
RESET
SETUP
Listed 33 x 7
100%
GGH2O and Melink® Intelli-Hood® Keypad
NOTE
If the GGH2O is being used with the Melink IntelliHood system, there will be two keypads. The Melink
Keypad will control the fans and lights. The GGH2O
Keypad will control the wash system.
NOTE
For information on PLC programming, please
consult the factory.
®
Model GGH2O
5
Page 6
Unpacking
1
2
Front LiftingSkid
Profile of Hood
Profile of Hood
Remove side, back and top lumber.Remove 3-inch lag screws. Holding the front lifting skid in place and position the skid infront of bottom skid.
Carefully rotate hoodas shown.
1
2
3
Front LiftingSkid
Profile of Hood
Profile of Hood
Profile of Hood
Remove side, back and top lumber.Remove 3-inch lag screws. Holding the front lifting skid in place and position the skid infront of bottom skid.
Carefully rotate hoodas shown.
Carefully slide the hoodonto the lifting skid.
The lifting skid should be used tolife the hood into it’s final position. If the lifting skid is not used, the hood will be damaged during theinstallation process.
1
Front LiftingSkid
Profile of Hood
Remove side, back and top lumber.Remove 3-inch lag screws. Holding the front lifting skid in place and position the skid infront of bottom skid.
Front Lifting
Skid
Remove side, back
and top lumber.
Remove 3-inch
lag screws while
holding the front
lifting skid in place.
When front lifting
skid is detached,
position it in front
of bottom skid.
Profile of Hood
Hood Width
inches
(cm)
48
(121.92)
51
(129.54)
54
(137.16)
57
(144.78)
60
(152.40)
63
(160.02)
66
(167.64)
69
(175.26)
72
(182.88)
Hood Width and Base Weights
Base Weight
without Water
lbs.
(kg)
440
(199.58)
449
(203.66)
457
(207.29)
465
(210.92)
474
(215.00)
483
(219.09)
491
(222.71)
499
(226.34)
508
(230.43)
Base Weight
with Water
lbs.
(kg)
488
(221.35)
497
(225.44)
505
(229.06)
513
(232.69)
522
(236.78)
531
(240.86)
539
(244.49)
547
(248.12)
556
(252.20)
Profile of Hood
Profile of Hood
Carefully slide the
hood onto the lifting
skid. The lifting skid
should be used to lift
the hood into its final
position. If the lifting
skid is not used,
the hood will be
damaged during the
installation process.
Profile of Hood
Carefully rotate
the hood as
shown.
Base weight is based on 48 inches (121.92 cm) hood
length. For each additional foot of hood in length, add
55 lb/ft (24.95 kg/m) in weight of hood and 67lb/ft
(30.39 kg/m) in weight of hood filled with water.
Example of a 10 foot hood:
Dry:48 inch width x 120 inch length
= 440 lbs. + (6 ft. x 55 lb/ft)
= 440 lbs. + 330 lbs.
= 770 lbs.
With Water: 48 inch width x 120 inch length
= 488 lbs. + (6 ft. x 67 lb/ft)
= 488 lbs. + 402 lbs.
= 890 lbs.
DANGER
The maximum weight (weight with water) should be
used for the maximum weight of the hood to ensure
the ceiling structure can support the weight of the
hood when filled with water.
CAUTION
To ensure proper structural support, all hanger
brackets must be used for hanging the hood.
Model GGH2O
6
®
Page 7
Installation Overview
Filler Panels
1. Unpack the hood and lay it on the lifting skid.
2. Bolt the filler panels together with 5/16 in. bolts
provided in the hardware package.
3. Position the filler panels to the hood back, and
tack-weld them into place.
4. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk
(GESCS1000, or its equivalent). The caulk is not
provided.
Hood
Hood
Hood
NOTE
If you have a Back Supply Plenum (BSP), this must
be installed before the hood. Refer to page 11 for
instructions on installing the BSP.
NOTE
All hanger brackets must be used and the hood
must be properly supported while lifting to prevent
damage or distortion to the hood. The hood must be
hung level to operate properly.
After the hood is secured, make the exhaust duct
connections. The fire system distributor must be
contacted at this time. After the fire system has been
installed, mount the enclosures, then the supply
plenums. If an Horizontal Supply Plenum is provided,
it should be installed before the enclosures. The hood
and accessories are now installed.
Finally, make the electrical connections from the
controls to the fans and complete the fire system
circuits as required by the job specification (job
specific wiring diagram located inside the cabinet
cover).
Tack-welded to
hood back
5/16 inch x 3/4 inch bolts
with washers and nuts
Bottom Filler Panel
Right Filler Panel
®
Model GGH2O
7
Page 8
Hood
Bolt
Caulk
U-Clip
Acorn Nut
H
oo
d
F
ro
nt
F
ro
nt
Hood Hanging Height
Ho
o
d
-
1
B
Ho
o
d
-
1A
Ho
o
d
Fro
n
t
The hood hanging height is critical. Hanging the hood
at the incorrect height may significantly reduce the
ability for the hood to function properly and may be in
violation of codes. The hood hanging height (typically,
78 in. (198.12 cm) above the finished floor) is given on
the UL label located on the inside of the hood on the
end panel. The hood must be hung level to operate
properly.
NOTE
Before hanging the hoods, please verify the hood
marks to make sure the correct hood is hung on the
correct side.
Double Island Style Hoods
A double island hood is created by installing two
wall style hoods back to back. Use the installation
procedure for single island hoods; install and level
both hoods. After leveling, secure the hoods together
by tack-welding and/or bolting the rear mounting
brackets. Caulk this joint with NSF Approved silicone
caulk (GE SCS1000 or its equivalent). The caulk is not
provided.
NOTE
The installation of the canopy hoods shall be
in accordance with NFPA 96 (latest edition),
Standard for Ventilation Control & Fire Protection of
Commercial Cooking Operations.
NOTE
Greenheck does not recommend walking or
standing on the hood top as damage can result. If
you must walk on the hood top, protect the hood
with additional support or planks for flooring.
Continuous Capture Plenum Hoods
Remove the support angles on the open end panels.
Use the installation procedure described for single
island hoods; install and level both hoods. After
leveling, secure the hoods together by tack-welding
and/or bolting the top angles. Fasten the hoods
together using u-clips and bolts. Caulk this joint with
NSF Approved silicone caulk (GE SCS1000 or its
equivalent). The caulk is not provided.
Installing U-Channel Strip
1. After the hood is hung in position and leveled,
apply caulk to the inside edge of the double island
clip.
2. Position and install the clip by tapping into
position along clip (friction fit).
3. Caulk edges to seal out grease and allow for ease
of cleaning. Caulk with NSF Approved silicone
caulk, GE SCS1000, or its equivalent. The caulk is
not provided.
B
1
-
d
o
Ho
1A
-
d
o
Double Island Clip
Ho
Ho
Hood-1A
Fro
d
o
t
n
Hood-1B
Silicone Caulk
nt
ro
F
d
oo
H
nt
ro
F
d
oo
H
Hood
NOTE
• For multiple hood systems that have more than
14 lights total (incandescent or fluorescent), the
hood lights must be wired to multiple circuits.
Each circuit must have less than 14 lights total.
• Light bulbs are not provided. Standard light bulbs
up to 100 watts may be used.
Model GGH2O
8
Double Island Clip
®
Page 9
Ductwork
Hood
UTILITY
CABINET
TOP VIEW
HOOD
TOP VIEW
SUPPLY PLENUM
END VIEW
Option #2
Uni-Strut supplied by others
Option #3
Threaded Rodsupplied by others
Threaded Rod
Option #2
The uni-strut (U channel) that holds the hood up, cantilevers over the end of the hood and ismounted to the Air Curtain Supply Plenum (ASP)hanger brackets
Option #1
For plenums < than or = 96 inches Two (2) clips are needed.
For plenums > than 96 inchesThree (3) clips are needed.
The third clip is located in the center of the plenum length.
Option #1
Attach hanging clip to hoodstanding seam with the supplied ‘C’ clamps.
Optional:Drill and bolt a 1/4-20 SS bolt through theclip and hood standing seam
Option #1
Hanging clip could be 23.5 inches from end if there is a utility cabinet on theend of the hood.
Hanger Bracket
Hanging methods for supply plenums ASP: Air Curtain Supply PlenumFSP: Face Supply PlenumVSP: Variable Supply Plenum
Option #1: Hanging ClipOption #2: Uni-StrutOption #3: Threaded Rod
11.5
23.5
Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition),
exhaust duct systems must be constructed in the
following manner:
Materials: Ducts shall be constructed of and
supported by carbon steel not less than 1.37 mm
(0.054 in.) (No. 16 MSG) in thickness or stainless steel
not less than 1.09 mm (0.043 in.) (No. 18 MSG)
in thickness.
Installation: All seams, joints, penetrations, and duct
to hood collar connections shall have a liquid-tight
external weld. If you have an Automatic Fire Damper
please refer to that manual for installation instructions
now.
Supply
Supply ductwork (where applicable) should be
connected to the hood in a manner approved by the
local code authorities.
For proper installation of duct collars when they are
shipped unattached see Installing Duct Collars on
page10.
Installing External Supply Plenums
Option #2
Uni-Strut supplied by others
TOP VIEW
HOOD
Option #1
For plenums < than or = 96 inches
Two (2) clips are needed.
For plenums > than 96 inches
UTILITY
CABINET
11.5
23.5
Three (3) clips are needed.
The third clip is located in the
center of the plenum length.
Option #1
Attach hanging clip to hood
standing seam with the
supplied ‘C’ clamps.
Optional: Drill and bolt a
1/4-20 SS bolt through the
clip and hood standing seam
TOP VIEW
SUPPLY PLENUM
Hanger Bracket
NOTE
For hoods with fire dampers in the exhaust and
supply duct collars, an access panel for cleaning
and inspection shall be provided in the duct. This
panel shall be as close to the hood as possible but
should not exceed 18 in. (45.72 cm).
Option #1
Hanging clip could be 23.5 inches from end if there is a utility cabinet on the
end of the hood.
Using the Supply Plenum Clip - Option #1
1. Bolt the hanging clip to the supply plenum. Two
clips are needed for plenums less than 96 in.
(243.84 cm) long and three for plenums greater
than 96 in. (243.84 cm). The
third clip is located in the
center of the plenum length.
If there is a utility cabinet,
the hanging clip should be
23.5 in. (59.69 cm) from the
end to the hood.
2. Using the c-clamps provided, clamp the supply
plenum hanging clip to the hood standing seam.
Option: Drill and bolt a 1/4-20 SS bolt through the
clip and hood standing seam.
Option #1 : Hanging Clip
‘C’ Clamp
HOOD FRONT
Hood Standing Seam
SUPPLY PLENUM SHELL
NOTE
The supply plenum is provided with plenum clips
that assist in hanging the plenum. The plenum
should not be hung only with the plenum clips;
threaded rod or uni-strut must also be used.
For plenums < than or = 96 inches Two (2) clips are needed.
For plenums > than 96 inchesThree (3) clips are needed.
The third clip is located in the center of the plenum length.
Option #1
Attach hanging clip to hoodstanding seam with the supplied ‘C’ clamps.
Optional:Drill and bolt a 1/4-20 SS bolt through theclip and hood standing seam
11.5
Exhaust Duct
Connection
Exhaust duct connection is to be
a continuous liquid-tight weld to hood.
1. The uni-strut (supplied by others) that holds the
hood up cantilevers over the end of the hood and
is mounted to the supply plenum hanger brackets.
Option #3
Threaded Rod
Threaded Rod
Option #2
The uni-strut (U channel) that holds the hood up,
cantilevers over the end of the hood and is
mounted to the Air Curtain Supply Plenum (ASP)
hanger brackets
END VIEW
Hood
Variable Supply Plenum
(HSP or VSP)
supplied by others
Using the Threaded Rod - Option #3
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the supply plenum
top. Raise and hang the external supply plenum
from adequate roof or ceiling supports.
2. The external supply plenum should be resting
lightly against the hood. The hood is used to
position the plenum only, it is not intended to
support the plenum. All hanger brackets must be
used and the plenum must be properly supported
while lifting to prevent damage or distortion. The
supply plenum must be hung level to operate
properly.
(Optional fastening of supply plenum to hood. See
directions).
3. It is recommended that caulk be applied at the
mating seams and surfaces of the plenum, the
hood, and the wall. If the supply plenum is next
to a wall, you will also need to caulk around the
surface next to the wall. Caulk the joints with
NSF Approved silicone caulk (GE SCS1000, or its
equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the
Plenum
1. Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm)
intervals, or sheet metal screws at 3 to 6 in.
(7.62to 15.24 cm) intervals.
Supply duct connection to be
tack-welded with 1 to 2 inch
tacks or sheet metal screws
at 3 to 6 inch spacing to hood.
Air Curtain Supply Plenum
(ASP)
External Supply Plenum Weights, Dimensions and Supply Rates
WeightWidthHeight
External Supply
Plenum Type
(lbs/ft)(kg/ft)(in)(mm)(in)(mm)(ft)(m)
Back Supply35.015.8786152.4Variable Variable 3 to 16
Air Curtain Supply
• 14 inch
Air Curtain Supply
• 24 inch
9.54.3114355.6102543 to 16
12.55.6724609.6102543 to 16
Variable Supply16.07.2612304.818457.203 to 16
Horizontal Supply14.06.3512304.818457.203 to 16
Model GGH2O
10
Length per
section
.91 to
4.88
.91 to
4.88
.91 to
4.88
.91 to
4.88
.91 to
4.88
curtain
face
Supply Duct
Connection
Recommended
Supply Rate
145 cfm/ft
(246.36 m
110 cfm/ft
(186.89 m
145 cfm/ft
(246.36 m
3
3
3
/hr)
/hr)
/hr)
0-80 cfm/ft
(0-135.92 m
80-160 cfm/ft
(135.92 -271.84 m
150 cfm/ft
(254.85 m
3
/hr)
3
/hr)
3
/hr)
®
Page 11
Using the UL Listed Fastener Provided
Holesize9/32-inch
STEP 2
L (MODULE LENGTH)
L/2
L/4
L/4
STEP 1
(IF MODULE > 6 ft.)
(IF MODULE < 6 ft.)
STEP 1
4 in. TO 6 in.
FASTEN WITH SCREWS, OR TACK WELDS EVERY
PLACE THE DUCT COLLAR OVER THE OPENING,
STEP 2
STEP 1
(IF MODULE > 6 ft.)
4 in. TO 6 in.
FASTEN WITH SCREWS, OR TACK WELDS EVERY
PLACE THE DUCT COLLAR OVER THE OPENING,
STEP 2
1. Drill a 9/32 in. hole for the 1/4 in. bolt from the
inside of the supply plenum to inside the hood.
Fasteners are to be located max. 6 in. (15.24cm)
from the end of the hood with max. spacing
between bolts 36 in. (91.44 cm)
DO NOT iNcluDeuTiliTycabiNeTsOrfillerswheN
figuriNgbOlTplacemeNT.
DO NOT bOlTThesupplypleNumTOafire/uTiliTy
cabiNeT.
2. Push bolt through hole, attach the washer and nut.
3. Hand tighten; then use a wrench until fully
tightened. Caulk around bolts from inside of hood
as necessary.
Hood
1/4 - 20 UNC - 2A
SS Bolt
1/4 inch SS Nut
3. If the back supply plenum is greater than 9 ft.
10 in. (299.72 cm) long, divide the length of the
back supply by four. This will give you the center
of each half. Cut openings at the suggested
location, centering the duct collar over the center
measurement of each half.
L/4
L (MODULE LENGTH)
L/2
L/4
SS Flat Washer
Installing the Back Supply Plenum
Installing the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is less than 9 ft. 10 in.
(299.72 cm) long, cut opening at the suggested
location, centering the opening over the center of
the back supply plenum.
L (MODULE LENGTH)
L/2
L/2
4. Place the duct collar(s) over the opening, fastening
with screws or tack-welds every 4 to 6 in. (10.16 to
15.24 cm).
The 4 in. (10.16 cm)
high duct collar is to
be attached to the
back supply.
Hanging the Back Supply Plenum
5. Hang the back supply plenum from the ceiling.
The back supply plenum needs to be mounted
31.25 in. (79.375 cm) above the floor (based
upon a canopy hood that will be hung at 78in.
(198.12cm) above the finished floor. This is
measured from the lowest rear edge of the back
supply plenum to the finished floor. Leave 6 to
10inches (15.24 to 25.4 cm) of space below the
plenum for access to the air diffusers.
®
Model GGH2O
11
Page 12
6. Fasten the back supply to the wall, going through
STEP 3
Furnished by Others
0.500 in. Threaded &
0.500 in. Threaded Nuts(Furnished by Others)
Hanger Bracket Detail
1) Hang Backsupply Modules from theceiling (the example shows the modulebeing supported with threaded rod)
The backsupply is to be 31.25 in. from thefloor. This is measured from the lowestrear edge of the backsupply module to thefinished floor.
2) Fasten backsupply to wall through thelower backsupply wall. These fastenersare to help maintain location of thebacksupply, and are NOT intended to holdany weight of the unit. Fasteners shouldnot interfere with the removable air diffuser.
31.25 in.
Critical
Dimension
Fasteners holding the
back supply to the wall
HANG THE HOOD
CANOPY STYLE HOOD
4. LIFT THE HOOD; POSITION IT SO THE TOP OF THEHOOD IS LEVEL WITH THE TOP OF THE BACKSUPPLY; AFTERTHE HOOD IS HUNG FROM THE CEILING AS PER IT'S INSTALLATION
1. THE HOOD IS TO BE HUNG AS PER THE HOODS INSTALLATION
SHOULD BE CONNECTED BEFORE THE HOOD IS HUNG.
3. DUCTWORK FOR THE BACKSUPPLY; IF IT WILL NOT INTERFERE,
2. BEFORE THE HOOD IS HUNG THE BACKSUPPLY MUST BE SECURED
INSTRUCTIONS AND THE FOLLOWING.
PROPERLY, AS DESCRIBED IN "STEP 3 in.
STEP 4
Step 5 / Air Diffusersa. Insert the air diffusers at an angle from the bottom.b. Rotate the diffusers so teh forms are downward.c. Rest the diffuser on the internal angles.
Step 5 / Air Diffusersa. Insert the air diffusers at an angle from the bottom.b. Rotate the diffusers so teh forms are downward.c. Rest the diffuser on the internal angles.
the lower back supply wall.
• These fasteners are to help maintain the location
of the Back Supply, and are not intended to hold
the weight of the back supply unit.
• The fasteners should not interfere with the
removable air diffusers.
• The 31.25 in. (79.375 cm) height is based upon
the canopy hood hanging height of 78 in.
(198.12 cm)
5. Connect the remaining ductwork for the back
supply and the hood. It is recommended that
caulk be applied at the mating seams and
surfaces of the back supply, the hood, and the
wall.
Air Diffusers
The air diffusers, located at the bottom of the back
supply, will need to be cleaned as often as the
application dictates. Inspect periodically to determine
the cleaning schedule.
1. To clean the air diffusers, unfasten the screws.
Remove the air diffusers from the back supply
unit, and wash in the sink or dishwasher.
2. Insert the air diffusers at an angle from the bottom,
and rotate so the forms are downward. Rest the
diffuser on the internal angles.
3. Refasten with the stainless steel screws.
Hanging the Hood
Before hanging the hood according to the hood
installation instructions, please check the following:
1. Make sure the back supply plenum is properly
secured, as described in steps 5 and 6.
2. If the ductwork for the back supply plenum will not
interfere with the hood installation, it should be
connected now.
3. Any filler panels should be attached to the hood
before the hood installation.
4. Lift the hood, and position it so the filler panels
are resting lightly on the top outside edges of the
back supply. The back supply is used to position
the hood only. It is not intended to hold any hood
weight.
Model GGH2O
12
Removable Air Diffusers
®
Page 13
Installing Enclosure Panels
Before installing the enclosure panels, make sure
the hood is hung in position with all the ductwork
attached, electrical connections and fire system
connections completed.
1. Position the end enclosure panels on the hood,
and clamp into place with clamps provided or
tack-weld the panels into place.
2. Fasten the end enclosure panels to the wall,
method depends on wall construction. (Fasteners
are not provided).
If the hood is a double island, bolt the end
enclosure panels together. (Fasteners are not
provided).
3. Position the front enclosure panel(s) on the hood,
and bolt to the end enclosure panels with the
5/16in. bolts provided in the hardware package.
4. Tack-weld or clamp the front enclosure panel(s)
to the hood. If clamps are used, they must be
positioned 4 in. (100 mm) from the ends, and in the
center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk
(GESCS1000, or its equivalent). The caulk is not
provided.
Note: Installation instructions may not be applicable
for concrete ceilings.
Bolt panels together with 5/16-inch bolts.
Supplied by mfg.
Installing End Skirts
1. After the hood is hung in position, slide the
hemmed form on top of the end skirt onto the end
panels of the hood.
2. Drill a hole in the hood end panel to line up with
the hole in the end skirt. Attach the end skirt with
a 1/4 in. bolt and cap nut to the inside of the hood,
or tack-weld the end skirt to the hood.
3. Position the end skirt against the wall and attach.
The method depends on the wall construction.
(Fasteners for this are not provided).
4. Caulk the internal joint formed by the end skirt and
the hood end panel with NSF Approved silicone
caulk (GE SCS1000 or its equivalent). The caulk is
not provided.
5. To allow for ease in cleaning, also caulk all the
external seams.
H
OOD FR
O
NT P
ANE
L
Exploded
view
below
Full End Skirt
End Enclosure
Panel
Attach to wall.
Fasteners by others
H
Clamp panels to hood standing seam with hardware.
Supplied by mfg.
Front Enclosure Panel
H
OO
D
T
O
P
OOD
BA
C
K
End Enclosure
Panel
Attach to wall
Fasteners by others
Exploded View
Hemmed Edge
Holes drilled by installer
1/4-inch bolt and cap nut
Supplied by mfg.
®
Model GGH2O
13
Page 14
Installing Backsplash Panels
Wall
Heigth
Length
Flat backsplash panel
Material gauge – Stainless
Wall
Length
Heigth
1. After the hood is hung in position, slide the flat
flange of the backsplash panel behind the back of
the hood.
Note: If the backsplash panel length is greater
than 45 in. (114.3 cm), it will be shipped in multiple
pieces.
2. After the backsplash panel has been positioned,
drill holes in the panel and fasten to the wall.
(Fasteners provided by others).
Note: The holes should be spaced to adequately
secure the panel to the wall.
3. Caulk the joints between the hood and the
backsplash panel with NSF Approved silicone
caulk (GE SCS1000, or its equivalent). The caulk is
not provided.
4. Caulk the joint between the backsplash panels
when multiple panels are required, with NSF
Approved silicone caulk (GE SCS1000, or its
equivalent). The caulk is not provided.
NOTE
Panels up to 47 inches (119.4 cm) wide ship in one
piece. Over 47 inches (119.4 cm) in multiple pieces.
Insulated backsplash panel
Material gauge – Stainless
Insulation – 1 inch (25.4 mm)
1 inch (25.4 mm)
Wall
Height
Hood End Panel
Backsplash Panel
Hood Front Panel
Slide flange
behind back
of the hood.
Section view of
backsplash panel
overlap
Length
NOTE
Panels up to 45 inches (114.3 cm) wide ship in one
piece. Over 45 inches (114.3 cm) in multiple pieces.
Model GGH2O
14
Holes should be spaced
to adequately secure the
panel to the wall studs.
(Hole spacing and fasteners
provided by others).
®
Page 15
Exhaust Duct
Connection
Exhaust duct connection is to be
a continuous liquid-tight weld to hood.
Supply DuctConnection
Supply duct connection to be tack-welded with 1 to 2 inch tacks or sheet metal screws at 3 to 6 inch spacing to hood.
Installing Duct Collar
Overview of exhaust and supply plenum locations
TOP VIEW
Hanger Bracket
3.0
8.0
BACK VIEW
8.0
1.0
12.0
Dimensions are shown in inches.
Exhaust Plenum
Duct cut out area
Front of Hood
Hood Length
Top of Hood
Exhaust Plenum
Duct cut out area
14.0
Hood
Width
3.0
8.0
8.0
1. The exhaust duct connection needs to be located
within 48 in. (121.92 cm) from the center of the
hood length to the center of the duct connection.
2. The exhaust duct connection is to be a continuous
liquid-tight weld. Weld with a non-ferrous filler
wire, such as silicon bronze or stainless steel filler
wire. Protect all stainless steel areas from weld
splatter.
®
Model GGH2O
15
Page 16
Plumbing
Plumbing Connections
Once the hood is hung, the recirculation pump and
detergent tank (both shipped loose) must be installed
in the controls cabinet.
Pump Installation
• Remove bolts from pump mounting plate in cabinet.
• Place the pump on the isolators located on the
mounting plate with the bolts removed.
• Secure the pump to the mounting plate with the four
previously removed bolts.
• Wire pump motor to the control cabinet per wiring
diagram on the cabinet.
• The wires to power the motor are already connected
to the pump motor. It only needs to be wired to the
control cabinet.
Position pump on
(4) isolators and attach
using provided nuts.
Connect to control
cabinet per
Wiring Diagram
in panel
Field
1-inch female NPT
Connect to drain
connect
1-inch
unions
A
E
D
C
A. One-inch unions
B. Detergent tank
C. Mounting plate
D. Isolators (qty of four)
E. Detergent pump
1. Connect the inlet and outlet piping on the
recirculation pump to the respective piping in the
cabinet via the threaded 1 in. unions.
2. Bring the inlet water piping to the connection
located on the top of the hood and connect to the
threaded connection on the 3/4 in. solenoid valve.
A ball valve needs to be placed in the connection
line before the 3/4 in. solenoid valve. Depending
on water pressure, the inlet valve might need to
be closed slightly to reduce water pressure. Water
temperature should be 140°F.
A
B
Inlet Solenoid
Connection
3. Bring the drain piping connection to the 1 in.
solenoid valve in the control cabinet and connect
to the threaded connection. This is a pressurized
drain system and needs a properly sized drain to
accommodate the pressurized drain water.
NOTE
As the suggested detergent is non-caustic and
biodegradable, waste water from the hood can be
drained in any typical grease trap.
Model GGH2O
16
®
Page 17
Detergent Tank Installation
The detergent tank is located as shown in the photo.
When installing the detergent tank, the low detergent
indicator float and the detergent pump inlet tubing will
need to be lifted. Once the tank is in position, the low
detergent indicator float and detergent inlet tube must
be lowered into place inside the tank.
A. One-inch unions
B. Detergent tank
C. Mounting plate
D. Isolators (qty of four)
E. Detergent pump
Detergent Requirements
The detergent brand Formula G-510 (by 2010
Products, Inc.) is recommended by Greenheck for use
in the wash system. Use Formula G-510 full strength.
This product is biodegradable, non-caustic, and safe
for kitchen staff to use. If G-510 detergent is not
used, the cleanliness of the exhaust plenum and filters
cannot be guaranteed.
Preventative Maintenance
The following practices will prolong the life of the
detergent pump:
• Keep detergent tank filled.
• Avoid spilling detergent on the exterior of the
pump.
• Clean the detergent tank at least every six
months.
• Clean the detergent line strainer at least every six
months.
• Check tightness of all fittings periodically.
The detergent pump motor has sealed bearings which
do not require lubrication.
Electrical
Electrical Wiring
All wiring must be done according to NEC (National
Electrical Code NFPA #70) and local building codes.
Two sources of power need to be brought into
the electrical control cabinet. A 120 volt, 30 amp
service with 12 gauge wire needs to be connected
to terminals L1 on the disconnect switch and N. A
120volt, 15 amp service with 14 gauge wire needs to
be brought into the electrical cabinet and connected
to terminal L2 on the disconnect switch and N1.
NOTE
The wash control station will provide a dry contact
for a fan starter so the fans can be controlled by the
PLC. The fan starter is not provided with the wash
control station.
The main recirculating pump needs to be wired after it
is installed in the hood. There are three 12 gauge wires
in flexible conduit wired to the pump. Wiring to the
pump is complete from the factory. The whip from the
pump needs to be wired into the control cabinet.
NOTE
G-510 is manufactured by 2010 Products, Inc., Food
Service Division, Salem, Oregon 97303. For details
and ordering information, call 800-286-2010.
®
Model GGH2O
17
Page 18
Timer Programming –
24 Hour / 7 Day
Setting the Clock
1. Press and hold the CLOCK button.
2. Press and hold the DAY button until the display
shows the current day.
3. Press the HOUR button until the display shows the
current hour.
4. Press the MIN (minute) button until the display
shows the current minute.
Setting the Programs
1. Press the PROG (program) button once. You will
now set the time in which you want the wash to
start. The number 1 in the lower left hand corner
indicates that you are now programming Event 1.
2. Press the DAY button repeatedly until the display
shows the day(s) when you want the timer to turn
on. The options are:
- Days of the week
MO, TU, WE, TH, FR, SA, SU
- Individual days of the week
MO etc.
- Weekdays only
MO, TU, WE, TH, FR
- Weekends only
SA, SU
3. Press the HOUR and MIN (minute) buttons to set
the time when you want the timer to turn on.
4. Press the PROG (program) button again.
5. Repeat steps 2-4 to set the OFF time for Event 1.
This should be set one minute after the ON time.
6. When programming is complete, press the CLOCK
button to display the current time.
Things you should know about programming events:
•
You can repeat the ON and OFF programming
procedures outlined above for up to seven (7)
events as needed.
NOTE
While setting events, the timer may prematurely turn
on the load, if you press the MODE button.
• Three kinds of settings can cause the timer to
work in an unexpected way:
a. Set up events in progressive order of time, for
example:
8:00 pm ON, 9:00 pm ON, 10:00 pm ON
Not 8:00 pm ON, 10:00 pm ON, 9:00 pm ON
b. Do not overlap event times, for example:
8:00 pm ON / 12:00 pm OFF and
9:00 pm ON / 11:00 pm OFF
c. Set the OFF time for one minute after the ON
time.
Reviewing Events Programmed
In your current time display, press the PROG (program)
button repeatedly to check your settings.
When finished, press the CLOCK button to return the
display to the time of day.
Clearing (Deleting an Event)
1. Press the PROG (program) button as many times
as necessary to locate the setting you want to
clear.
2. Press and hold the MODE button.
3. Press the PROG button to clear the setting.
4. When finished, press the CLOCK button to return
the display to the time of day.
Operating the Time Switch
Press the MODE button repeatedly to set the timer to
Automatic, Random or Manual mode.
NOTE
For the time switch to run programmed events, it
must be set to AUTO mode.
• AUTO runs all events automatically according to the
schedule you have set. The word AUTO appears in
the display.
• RND (random) runs all events in a RANDOM mode.
This is a security feature in which ON and OFF
times randomly differ +/- 15 minutes from the
programmed times, creating a more “lived-in” look.
The word RND appears on the display.
NOTE
Do NOT set this timer to RND mode. It will not wash
at the exact time you programmed.
• MANUAL turns ON and OFF only when the user
presses the ON or OFF button. The display is blank,
showing neither RND or AUTO.
Overriding Timer Settings
The ON or OFF buttons override the current
programmed events. To override the current program
(either ON or OFF), press the ON or OFF button.
Model GGH2O
18
®
Page 19
Initial System Start-Up
1. Check electrical power (see wiring diagram)
• Correct supply voltage
• Proper connections to fire
suppression system
2. Check to make sure the
disconnect switch on the
electrical control cabinet is
switched to the “ON” position.
3. Prime the recirculation pump. Remove the plug on
top of pump and use a funnel to add water to the
pump. This only needs to be done one time prior to
initial start-up.
4. Add detergent to the detergent tank in the cabinet.
5. Clean the control cabinet of any debris that may
have entered the cabinet during installation.
6. Close the cabinet doors and press the Fan On/Off
button.
7. Check the exhaust and supply air volumes.
8. Press the Fan On/Off button to turn the fans off.
9. Press the Clean Hood button.
When the hood is filling, check to ensure water is not
leaking through the edges of the access doors. If so,
the inlet water pressure is too high. Slowly close ball
valve located before the inlet solenoid on the hood top
until no water leaks pasT the access doors.
After the hood fills with water and starts washing the
primary filters, open water valve slowly until water
mist is felt above equipment. Then slowly close valve
until water mist is no longer felt above equipment.
Once the valve is set it will not need to be moved
again.
Verify the Grease Grabber H2O sequence of operation
(see the diagram of wash sequence on page 20)
during the detergent pump cycle.
Daily Operation of the GGH2O Hood
Pressing the FAN ON/OFF button will start/stop the
exhaust and supply fans if interlocked.
Pressing the HOOD LIGHTS button will turn on/off the
hood lights.
Initiating the wash cycle:
The Grease Grabber H2O has an automatic timer
that can be set to control the wash schedule and
automatically start the cycle. See Timer Programming
on page 18.
To initiate the wash cycle manually, press the CLEAN
HOOD button on the keypad. If you press this button
while the fans are running, the system will stop the
fans and then start the wash cycle. When the wash is
completed, the system will automatically reset itself.
If the fans are controlled by a building management
system (BMS), the steps above still apply unless a
special program is requested to bypass having to
initiate the wash cycle by pushing the FAN ON/OFF
and CLEAN HOOD buttons.
Refer to the Grease Grabber™ H
on page 27 for detailed instructions on start-up
operations.
O Hood checklist
2
C
E
D
A
B
Interior of Cabinet
A. Recirculating pump
B. Detergent tank
C. Water valve to adjust front primary filter nozzles
D. Pump plug for priming
E. Detergent pump
®
Model GGH2O
19
Page 20
SEQUENCE OF OPERATION - GREASE GRABBER H2O
ShutOFFexhaustfan(s)
TurnONexhaustfan(s)
TurnOFFexhaustfan(s)
Stage 1:
Fillhoodtank (hot water)
Stage2:Wash primary filters DetergentpumpON
Stage3:
Wash secondary filters
DetergentpumpON
Stage5:
Wash secondary filters
DetergentpumpOFF
Stage6:
Drain soapy/dirty water
Stage10:
Drain rinse water
Stage4:
Wash primary filters
DetergentpumpOFF
2minutedelayfor
water settling
Sprayfor5minutes
Sprayfor5minutes
NORMAL FAN OPERATION
Hot Water Recovery:
(0min.)Adjustable
Sprayfor5minutes
Sprayfor5minutes
Stage 7:
Fillhoodtank (hot water)
Stage8:
Rinse primary filters
DetergentpumpOFF
Stage9:
Rinse secondary filters
DetergentpumpOFF
Sprayfor5minutes
Sprayfor5minutes
20minutedrytime
Wash,rinse&drycomplete
Sequence of Operation - Grease Grabber™ H2O
WASH
Hot Water Recovery:
(0 min.) Adjustable
Shut OFF exhaust fan(s)
Stage 1:
Fill hood tank (hot water)
Stage 2:
Wash primary filters
Detergent pump ON
Spray for 5 minutes
Stage 3:
Wash secondary filters
Detergent pump ON
Spray for 5 minutes
2 minute delay for
water settling
Stage 4:
Wash primary filters
Detergent pump OFF
Spray for 5 minutes
Stage 5:
Wash secondary filters
Detergent pump OFF
RINSEDRY
Stage 7:
Fill hood tank (hot water)
Stage 8:
Rinse primary filters
Detergent pump OFF
Spray for 5 minutes
Stage 9:
Rinse secondary filters
Detergent pump OFF
Spray for 5 minutes
Stage 10:
Drain rinse water
Turn ON exhaust fan(s)
20 minute dry time
Turn OFF exhaust fan(s)
Wash, rinse & dry complete
Spray for 5 minutes
Stage 6:
Drain soapy/dirty water
Normal Fan Operation
START FAN Fan(s) OFF
Fan(s) will run
No
FIRE
Yes
Exhaust
Fan(s) remain
ON
START FAN
Fan(s) will run
No
FIRE
Yes
Exhaust
Fan(s) will
turn OFF
Temperature Interlock Exhaust Mode in Fire -- STOP Exhaust Mode in Fire -- RUN
Exhaust Fan(s)
Temperature
> 95°F.
(Adjustable)
will turn ON
Model GGH2O
20
®
Page 21
Airflow Testing Procedure
After the appropriate number of readings have been
taken from the inlet slot of the hood, an average
reading can be calculated by summing the velocity
readings and dividing the total value by the number of
readings taken.
Short Ridge Meter Components
For measuring exhaust airflow rates (cubic feet per
minute = CFM), use a short ridge meter to measure
velocities along the inlet slot of the hood. To ensure
accurate data, all appliances should be on. Multiple
locations need to be tested as outlined below to
ensure an accurate reading.
Average Velocity=
Sum of Velocity Readings
Number of Readings
Next calculate the total hood airflow volume (CFM) by
using the following equation:
Hood CFM = [(Length of Hood in inches x 4.846) x
(Average inlet slot velocity x 2.47)] 144
NOTE
The constants 4.846 and 2.47 are factory derived for
use with the Grease Grabber™ H2O.
To take velocity readings along the length of the hood,
the edge of the short ridge meter must start/stop six
(6) inches from the end of the hood. Vertical placement
of the short ridge meter along the inlet is shown.
Hood Exhaust Rate (CFM) =
[(96 x 4.846) x (197 x 2.47)] 144 = 1572 CFM
®
Model GGH2O
21
Page 22
Amerex® Wiring Plan View
PRM
MICROSWITCH
INSTALLER PROVIDED JUNCTION BOXES
BASIC WIRING DIAGRAM
RED (COMMON)
YELLOW (N.O)
POWER SOURCE
POWER SOURCE
BLACK (N.C.)
MANUAL RESET RELAY
ELECTRIC GAS VALVE
MANUAL RESET RELAY
MICROSWITCH
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.
BASIC WIRING DIAGRAM
MANUAL RESET RELAY
RED (COMMON)
YELLOW (N.O)
MICROSWITCH
NOTES:
1. DENOTES FIELD INSTALLATION
2. DENOTES FACTORY INSTALLATION
3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,
12872, 12873, 12874, 12875 and 12876.
4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.
120V/60HZ
BLACK (N.C.)
L1
L2
K1b
CURRENT DRAW MAX:
8A RESISTIVE
8A INDUCTIVE
120VAC
K1
Ka
GAS VALVE
PUSHBUTTON SWITCH
GAS VALVE
SEE NOTE 3
Model GGH2O
22
®
Page 23
TYPICAL WIRING SCHEMATIC ELECTRIC EQUIPMENT SHUTDOWN
ANSUL file name: Typicalwiringschematicelectricgasshut-offvalveshutdowndetail.ai / File received on August 4, 2010
TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
DENOTES FACTORY INSTALLATION
DENOTES FIELD INSTALLATION
TYPICAL WIRING SCHEMATIC ELECTRIC EQUIPMENT SHUTDOWN
4.
1.
2.
3.
AUTOMAN IN THE COCKED POSITION)
(SWITCH CONTACTS SHOWN WITH ANSUL
13 AMP, 28 VDC
1/3 HP, 10 AMP, 120 VAC1/2 HP, 10 AMP, 240 VAC
MANUAL RESET RELAY
ANSUL SNAP-ACTION SWITCH
RESET
BA
RELAY COIL
ELECTRICAL RATING
PART NO. 426151
693
471
SCREW
INDICATOR
POWER
RED
GND
5
4
3
2
1
BLACK
RED
BROWN
110V/60HZ
NEUTRAL
HOT
1
L
2
L
NOTE:
ANSUL file name: Typicalwiringschematicelectricgasshut-offvalveshutdowndetail.ai / File received on August 4, 2010
GAS VALVES: "UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE
3.
DENOTES FIELD INSTALLATION
DENOTES FACTORY INSTALLATION
RED
GND
SCREW
5
4
3
2
1
SWITCH OR
THERMOSTAT
(CUSTOMER
SUPPLIED)
BLACK
RED
BROWN
TO HEATING
ELEMENT LOAD
CONTACTOR
(CUSTOMER SUPPLIED)
AND TEMPERATURE RATING, 110V/60HZ OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710. AND 17643.
DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. (USED ONLY FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
4.
L
NEUTRAL
110V/60HZ
TO POWER SUPPLY
220V/440V
2
L
HOT
1
®
Model GGH2O
23
Page 24
ECO
P.O.BOX 410 SCHOFIELD, WISCONSIN 54476-0410
CAD DRAWING NO.
REV.
PART NO.
-
IAN31295
LADDER DIAGRAM,
GGH2O
473596
Wiring Diagram
Wiring diagram is located on the inside cover of the control cabinet located on the end of the hood.
120VAC 1PH. 30 AMPS
SUPPLY POWER
WATER WASH
120VAC 1PH. 15AMPS
SUPPLY POWER
HOOD LIGHTS
FAN INTERLOCK
CONTACT
3POLE 32 AMPS
DISC
L1
L2
E1
E1
L3
12 GA
BK
L1
PR
L1
BK
BK
12 GA
BK
12 GA
AR
C
NO
21
Interlock
BK
Hood Lights
R1
Fan
83
BL
BL
BL
BL
L1
L1
BK
H1
14 GA
24
E2E1
PR
SC
GGH20/VAV Fan Mode
Interlock Connection
0VDC - Fan Auto
5VDC - Fan OFF
10VDC - Fan On for Dry
OR
OR
OR
41
Recirculating Pump
Motor Wiring
Recirculating Pump Size
1.0 HP
1.5 HP
67
67
67
3 AMP
25 AMP
H1
E2
WHT
FU3
FU1
LF1
(H)
L2
BK
18 GA
FU2
18 GA
5 AMP
41
RD
RD
BK
(IMC Interlock)
14
BK
BK
FL1
FL2
FL3
Temp Sensor
(Freeze
Protection)
(If used)
Temp Sensor
(If used)
R1
R5
R3
T1
18 GA
12 GA
H1
14 GA
18 GA18 GA
BL
83
BK
41
BK
41
BK
41
41
41
83
83
67
67
25
Tank Full
WHT
Tank Low
RD
Safety
BK
+VDC
COM
60
20
30
83
83
83
83
Timer
RD
C1 120VAC
L2L3
Recirculating
Pump
Contactor
PUMP
ON RECIRCULATING
WIRED FROM MOTOR
M2
F1
F2
F3
V1
VC
TS
TC
I1
IC
Brown
White
Blue
Orange
Yellow
PR
51
BK
BK
BL
BL
OR
OR
PR
PR
27
PR
28
PR
36
OR
72
BR
73
OR
2
BR
4
OR
5
BR
6
T2
LF3
11
1114
1114
FLA
17
22
Melink Fan
Stop Common
OR
OR
OR
Contact
BK
PR
BL
83 - 24V (H)
41 - DO1 COM
47 - DO3 COM
51 - DO4 COM
54 - DO5 COM
57 - DO6 COM
64 - DO8 COM
67 - DO9 COM
3 - Ext V
25 - DI
COM
27 - DI5
28 - DI6
36 - DI12
72 - AO1
73 - AO COM
2 - AI1
4 - AI COM
5 - AI2
6 - AI COM
6
2
3
15
RD
T2
Hood Lights
TR1
(N)
(H)
120VAC
24VAC
U1 (FX-14)
44 - DO2
COM
61 - DO7
COM
Lights Indicator
Low Det Indicator
R3 24 VAC
A2
R4 24 VAC
Fire Mode
R6 120 VAC
Wash Timer
Relay
T3 T3T2 T2L1 T1 T1
RP
RP
N
R5 120 VAC
A2
Hood Lights
LED Relay
BK
YW
82 - 24V (C)
1 - AI COM
Fan Indicator
Det Low
Lights On/O
A1A2
RP
42 - DO1
45 - DO2
48 - DO3
52 - DO4
55 - DO5
58 - DO6
62 - DO7
65 - DO8
68 - DO9
21 - DI
23 - DI2
24 - DI3
22 - DI1
26 - DI4
32 - DI9
7 - AI3
6 - AI COM
81 - Earth
L2
L1
L4
A1
A1A2
PB1
N
14 11
A1
COM
YW
YW
R2
BK
Hood Lights
N1
YW
RD
42
RD
45
RD
48
PR
52
RD
55
RD
BL
BL
RD
68
BR
PR
PR
PR
PR
PR
PR
OR
7
BR
6
F4
F4C
FS
N
BK
DP
WHT
S1 120 VAC
S1N
S2 120 VAC
S2
Nozzle 1
S3 120 VAC
S3N
Nozzle 2
Melink Fan Stop
M1
S4 120 VAC
S4N
58
62
65
5
Clean Hood
10
23
Start-Stop Fan
11
24
22
Wash Timer
26
Fire Mode
32
I2
Temp Sensor
(IMC Interlock)
IC
FL4
Fire System
FSFC
AR 24 VAC
BL
14
14
WHT
P2
DP
Detergent
Pump
Motor
P1
Recirculating
Pump
Motor
WHT
N1
82
Fill
Drain
C1 120 VAC
Recirc Pump
R1 24 VAC
Fan
R2 24 VAC
Detergent Pump
A2
Clean Hood
Indicator
1
21
PB3
PB2
R6
14
11
R4
24
21
R3
24
21
Det Low
(If used)
Det Low
YW
32
6
BK
WHT
FIELD INSTALLED WIRING
MOLEX PLUG FOR KEYPAD
(IF KEYPAD IS REMOTE MOUNTED, PLUG IS FIELD CONNECTED)
WHT
WHT
N
WHT
WHT
C1
95
96
95
A2A1
A1A2
A1
L3
PR
PR
PR
YW
YW
N
N
N
WHT
Overload
YW
82
YW
82
13
21
21
21
1
1
82
82
82
WHT
WHT
N
N
N
N
N
N
N
N
WHT
12 GA
18 GA
Model GGH2O
24
®
Page 25
Maintenance
Capture Tank
The interior surfaces of the hood capture tank should
be wiped down weekly.
Filters
The Grease Grabber filters (bead filters) require
visually inspection (not removed from hood) two
weeks after start-up, then once a month thereafter to
make certain the filters are positioned correctly in the
plenum. Positioned correctly means there are no gaps
between the filters.
To inspect the bead filters, remove the fasteners
holding the access doors; each door has five (5)
fasteners. Remove every other door to inspect the
filters.
After inspecting the filters, put the access doors
back on and put the fasteners back in. Be careful not
to over-tighten or cross thread the fasteners when
putting them back in.
The Grease Grabber filters
(bead filters) need to be
removed from the hood
once every three months to
visually inspect and ensure
the filters are structurally
sound.
Remove all the doors
and remove the filters for
inspection. Depending on
the equipment under the
hood, it will probably be
easier to remove the filters
from the right side of each
hood. Slide the other filters
down to the end access
door for removal.
After inspecting the filters,
place them back in the
hood. Be careful to install
the filters with the handles
up and make sure not to
hit the fire detection line
when removing or installing
the filters. Ensure no gaps
are between filters after
installation.
If any filter appears damaged, consult factory for
replacement.
Floats
The floats need to be
inspected two weeks after
start-up and then once a
month thereafter.
The float can be inspected
by first turning the
disconnect switch on the
control cabinet to the ‘OFF’
position. Then remove the
large access panel door.
Once the access panel
is removed, you will have
access to the floats.
Slide each float (Low Float,
High Float and Safety Float)
up the stem to its stop with
your finger and let go. If float
slides freely down the stem
with minimal resistance, the
float is operating as it should.
Put the access panel back
on and turn the disconnect
switch to the ‘ON’ position.
If the float does not slide
freely down the stem, the
stem and floats are dirty
and need to be wiped off with a clean cloth. Cleaning
the stem involves removing all the clips (stops). Slide
floats up and down on the shaft as required to access
and clean the entire length of the shaft. Return floats
to their location and reinstall stops.
Make sure all float stops are securely located in their
grooves and floats are located in their designated
spots.
If for some reason the floats
get taken off the stem, the
stamped circle on the top
side of the float needs to
face up.
Access Panel Door
Float Installed
Safety Float
High Float
Low Float
NOTE
Be careful when handling the float stops. These are
small clips and can easily be dropped. If you loose
one of these clips, consult factory for a replacement.
®
Model GGH2O
25
Page 26
TroubleshootingReplacement Parts
Hood is not cleaning
If the hood does not seem to be adequately cleaned,
look for the following:
Detergent tank — is it empty or filled with wrong
detergent?
Detergent pump — is the detergent pump running?
Is there power to the pump? Is the detergent level
low? If the hood plenum area is not sufficiently
cleaning, consult factory for information on
increasing duration of wash cycle and detergent
pump.
Nozzles — are any of them clogged? If so, they can
be removed and cleared using a small wire.
Water temperature — is it at least 140°F.
Hardness of water — test water for hardness level.
It is recommended that soft water be used.
Hood not draining properly — plugged drain.
Ensure all floats have stamped circles facing up.
Water leaks — water leaking through the access
panels when filling. Ensure access panels are securely
in place. If leak persists, partially close inlet water ball
valve (by others) upstream of fill solenoid to reduce
water pressure.
Condensation in the hood — large amounts of
condensation while hood is washing. Hood should
be washed after the hood and equipment is warm,
not hot. The warm equipment helps reduce the
condensation that forms in the hood.
Approved wash detergent
Formula G-510 from 2010 Products, Inc.
Phone: 800-286-2010
(Not provided by Greenheck).
When ordering parts, please be prepared to provide
us with your cabinet and hood system model
number, and serial number from labels on the hood
and cabinet. See the chart below to identify the
replacement parts needed.
Greenheck
Part
Number
Wash Nozzles
Above GG Filters472806
Below GG Filters472795
Before First Stage Filters472805
Repair Kits
Solenoid Model 1A579K-1180
Solenoid Model 1A578K-1172
Grainger®
Part
Number
Model GGH2O
26
®
Page 27
Grease Grabber™ H2O Start-Up
Checklist
Check boxes when item has been verified and gone
over with customer.
Hook-Up
o Electrical Connected
• 120V/1 30A to terminals L1 and N for wash
controls
• 120V/1 15A to terminals L2 and N1 for hood lights
• Fans to terminals E1 and E2 (dry contact)
If using variable volume controls, Melink will also
require connection to terminals M1 and M2, VariFlow will only require connection to terminals V1
and VC.
• Fire system microswitch to terminals FS and FC.
• Recirculating pump wired to cabinet terminals
RP and N.
• If keypad is shipped loose, connection completed
between keypad and cabinet with supplied cable.
If additional cable is required, consult factory for
ordering.
o Plumbing Connected
• Two 1-inch unions to recirculating pump
• Hot water supply ball valve open. Located up
stream of the inlet water solenoid valve.
o Detergent
• Suction tubing and strainer to bottom of detergent
tank.
• Low detergent sensor in bottom of detergent tank.
• Detergent tank filled with proper detergent.
Timer, 24 hours / 7 day
o
• Programmed - see instructions on page 18.
Start-Up
o Cooking Mode
• See sequence of operations on page 20.
• Hood lights on. Activate “Hood Lights” push
button.
• Hood light LED indicator should be lit.
• Fans on. Hold “Fan On/Off” push button for onehalf second.
• Fan LED indicator should be lit.
• Appliances on (gas and/or electric).
o
Stop Mode
• See sequence of operations on page 20.
• Fans off. Hold “Fan On/Off” push button for onehalf second.
• LED indicator turns off.
o Wash Mode
• See sequence of operations on page 20.
• If using 24 hour / 7 day timer, wash cycle will start
at scheduled time after “Fan On/Off” push button
has been pressed. (Refer to page 18for details on
programming 24 hour / 7 day timer). If 24 hour / 7
day timer is not being used, press “Clean Hood”
push button after pressing “Fan On/Off” push
button.
• Clean hood LED indicator should be lit.
_________ Record water pressure
(Should be between 30-50 psi)
_________ Record water temperature
(Should be between 140-160°F.)
o Stop Mode
• At end of wash cycle, system returns to Fan On
for 20 minutes dry cycle.
• Trip fire system microswitch or remove wire
from terminal FS or FC. (Water will not spray in
fire mode, fans will run. If wash cycle is running
during fire system trip, hood will drain and fan(s)
will run).
• System fault LED indicator should be on.
• Fan LED indicator should be lit.
o Low Detergent Mode
• Fill detergent tank with appropriate detergent.
• Low detergent LED indicator should go off.
Miscellaneous
o Hood Access
• Panels should fit tightly to prevent water spraying
out.
• When front nozzles are washing, adjust ball valve
in cabinet to reduce water pressure and minimize
overspray.
o Cleaning
• Is the hood cleaning properly?
• If not, refer to troubleshooting guide on page 26.
®
Model GGH2O
27
Page 28
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck catalog GGH2O provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.