Greenheck GGD121.1U-B User Manual

centering
2-Position, 15-second Runtime, 15-second Spring Return Time
Operating Voltage Shaft Adapter Packaging
Product Number
GGD121.1U GGD121.1U/B GGD121.3U GGD221.1U GGD221.1U/B GGD221.3U GGD321.1U GGD321.1U/B GGD321.3U
24 Vac ± 20%,
50/60 Hz
115 Vac
± 15%,
50/60 Hz
230 Vac
± 10%,
50/60 Hz
Self-
to 1 Inch
Oversized
to 1.05 Inches
Standard
single
pack
Eight
pack of
Standard
Technical Data
Torque Running 142 lb-in (16 Nm),
spring return 108 lb-in (12 Nm),
minimum stall 350 lb-in (39 Nm) Torque reduction at elevated temperature Less than 10% Runtime for 90° operating with motor at 60 Hz 15 sec. nominal closing (on power loss) with spring return 15 sec. maximum Nominal angle of rotation 95° nominal Power consumption, running 150 VA running, 10 VA holding Life expectancy Minimum 35,000 full stroke cycles Damper shaft size, standard 3/8 to 1 inch (8 to 25.6 mm) Damper shaft size, oversize 1.05 inch (26.6 mm) maximum Damper shaft size, minimum 3/4 inch (20 mm) Agency listings UL873, C-UL C22.2 No. 24-93,
AS/NZS 2064 1/2:1997 Ambient temperature, operating 0 to 130°F (-18 to 55°C),
one time 350°F (177°C) Ambient temperature, storage/transport -25 to 158°F (-32 to 70°C) Ambient humidity (non-condensing) Maximum 95% R.H.
®
Teflon
cable 400°F (200°C) Enclosure NEMA 1 Housing material Die cast aluminum alloy Pre-cabled connection AWG 18 Weight §OEVNJ
Description
The OpenAir direct-coupled, 2-position, spring return electronic damper actuators are UL listed for smoke control dampers or for combination fire/smoke rated dampers. Actuators are designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories, Inc. UL555S rating up to 350°F (177°C).
N474
Features
High-temperature rated drive system
Reversible fail-safe spring return
All metal housing
Precabled Teflon
lead wires
Mechanical range adjustment
Multiple shaft couplings
available; will accommodate up to 1.05-inch (26.6 mm) shafts
Fifteen second nominal open time; 15 second maximum spring return time
Models available for 24, 115, and 230 Vac
Submittal Sheet
Document No. 154-026
October 25, 2002
®
insulated
Siemens Building Technologies, Inc.
OpenAir™ GGD Electronic Damper Actuators for UL Listed Fire/Smoke and Smoke Control Dampers Submittal Sheet
Document No. 154-026
October 25, 2002
Dimensions
9
5
3-3/8 in.
86 mm
100 mm
˚
OPENING
FOR 3/8"
FLEX CONDUIT
1-23/32 in.
30 mm
min. 1/4 in.
7 mm
EA0953R1
min. 4 in.
100 mm
1-11/32
34 mm
1-19/32
37 mm
min. 8 in.
200 mm
min.
2-1/2 in.
60 mm
11 in.
279 mm
1-1/8 in.
7-3/4 in. 197 mm
28 mm
3-15/16 in.
Maintenance
The National Fire Protection Association (NFPA) National Fire Codes®: NFPA 92A, and UL, require weekly self test for dedicated smoke control equipment used in a smoke control system. The actuator was designed such that no special cycling is required during long-term holding when used as a fire damper. Cycling once a year is recommended as a safety precaution for the fire control systems.
Wiring Diagrams
24 Vac:
RED
(SUPPLY)
M
BLACK
(NEUTRAL)
EA0941R1
115 Vac:
BLACK
(LINE)
WHITE
EA0942R1
(NEUTRAL)
230 Vac:
BROWN
(LINE)
BLUE
(NEUTRAL)
EA0943R1
NOTE: Wire the 230 Vac actuator with a
230 Vac line with respect to neutral and connect the ground lead for proper protection of the actuator. Any other connection such as phase-to-phase, can damage the actuator.
(GROUND)
M
(GROUND)
M
GREEN
(GROUND)
GREEN
GREEN
Information in this publication is based on current specifications. The company reserves the right to make c hanges i n specifications and models as design improvements are introduced. Powermite is a trademark of Siemens Building Technologies, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2002 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc. 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A.
Your feedback is important to us. If you have comments about this document, please send them to technical.editor@sbt.siemens.com
Document No. 154-026
Printed in the U.S.A.
Page 2