Greenheck FSAF120 US User Manual

Page 1
110
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
Torque: 133 in-lb ●●●●
70 in-lb ●●●●●● 30 in-lb ●●●●
Power supply : 24 VAC ●● ●● ●●
120 VAC ●● ●● ●●
230 VAC ●● Control signal: on-off ●●●●●●●●●●●●●● Running time motor: <15 sec ●●●●●●●●●●
<75 sec ●●●●
spring: <15 sec ●●●●●●●●●●
<20 sec ●●●● Built-in auxiliary switch ●●●●●●● Manual override ●●●●
*FSNF230 (-S) data sheets are available at www.belimo.com
FS Series – at a glance
FSAF24 US (p. 112)
FSAF24-S US (p. 112)
FSAF120 US (p. 112)
FSAF120-S US (p. 112)
FSNF24 US (p. 114)
FSNF24-S US (p. 114)
FSNF120 US (p. 114)
FSNF120-S US (p. 114)
FSNF230 US*
FSNF230-S US*
FSLF24 US (p. 116)
FSLF24-S US (p. 116)
FSLF120 US (p. 116)
FSLF120-S US (p.
116
)
FS Series Fire and Smoke Actuation
Belimo is the worldwide leader in fire and smoke actuation
Belimo first produced actuators for the European fire and smoke damper market in 1978. Belimo has consistently offered new technology since entering the market. Since 1978 Belimos market share has grown as actuator variations were released to meet various worldwide requirements. The FSLF and FSAF are the latest models to be introduced for the United States and regions of the world requiring UL 555 and UL 555S listing.
Belimo is the dominant fire and smoke actuator manufacturer in Europe today with 80% market share and is growing in the rest of the world.
Radio Shack, Corporate Headquarters, Fort Worth Texas
The Louvre, Paris
Kärntner-Ringhof, Vienna
®
Page 2
111
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FS Series
FS Series Fire and Smoke Actuation
The Belimo Difference
Customer Commitment.
Extensive product range. Application assistance. Same-day shipments. Free technical support. Five year warranty.
Low Installation and Life-Cycle Cost.
Easy installation. Accuracy and repeatability. Low power consumption. No maintenance.
Long Service Life.
Components tested before assembly. Every product tested before shipment. 30+ years direct coupled actuator design.
A CLOSER LOOK…
True mechanical spring return the most reliable failsafe.
Reverse mount for clockwise or counterclockwise fail-safe.
Check damper position easily with clear position indicator.
Overload-proof throughout rotation.
Easy mechanical stop to adjust angle of rotation
(add ZDB-AF2 accessory/FSAF and FSNF only).
Built-in auxiliary switch is easy to use, offers feedback
or signal for additional device. (-S models)
Manual override crank speeds installation.
(only on FSAF models)
The same 100% steel toothed cold-weld clamp that Belimo
uses on all actuators is used on the FS Series. No slipping on damper shafts will occur.
Tested at high torque load for a minimum of 20,000 cycles
per UL555(S).
Reliable DC motorlow current draw.
Permanently lubricated gears.
FSNF and FSLF actuators meet Uniform Building
Code (UBC) requirements.
Belimo actuator is silent when holding at end position.
®
LISTED 94D5 TEMP. IND & REG. EQUIP.
U
L
Page 3
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FSAF120 (-S) US, FSAF24 (-S) US
Fire and smoke actuator, 133 in-lb, [15 Nm], spring return, meets 250°F [121°C] for half hour, 75 second
Torque min. 133 in-lb, for control of air dampers
Application
For two position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturers specifications.
The actuator is mounted directly to a damper shaft or jack­shaft 3/8 to 1.05 in diameter by means of its universal clamp. A crankarm and mounting brackets are available if the actua­tor cannot be direct coupled to the jackshaft or damper shaft.
Square footage of damper operated will depend on make and model of damper. Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S applications.
Operation
The FSAF series actuators provide true spring return operation for reliable fail-safe application and positive close­off on UL555S dampers. The spring return system provides constant torque to the damper with, and without, power applied to the actuator.
The FSAF series provides 95° of rotation and is provided with a graduated position indicator showing 0 to 95°. The FSAF has a manual positioning mechanism which allows the setting of any damper position within its 95° of rotation.
The actuator is shipped in the zero fail-safe position to pro­vide automatic compression against damper gaskets for tight shut-off. When power is applied, the manual mechanism is released and the actuator drives toward the open position where it stops rotating.
The manual override can also be released physically by the use of a crank supplied with the actuator.
Dimensions
(All numbers in brackets are metric.)
Technical Data FSAF120 (-S) US FSAF24 (-S) US
Power supply 120 VAC ± 10% 24 VAC ± 20%
50/60 Hz 24 VDC -10% +20%
Power consumption 50/60Hz:
Running: 9.5W 11VA .1A 7.5W 10VA .4A
Holding: 3.5W 6VA .05A 2W 4VA .15A Transformer sizing 10 VA (Class 2 power source 24V only) Electrical connection
Motor 3 ft, 18 ga, 2 color coded leads Auxiliary switches 3 ft, 18 ga, 4 leads appliance cable
1/2 conduit connectors Overload protection Electronic throughout 0 to 95° rotation Angle of rotation Mechanically limited to 95° Torque 133 in-lb [15 Nm] constant Direction of rotation Spring return reversible with CW/CCW
mounting. Position indication Visual indicator, 0° to 95° (0° is spring
return position) Manual override 3mm hex crank (shipped w/actuator) Running time <75 sec. constant, independent of load,
Spring return <20 seconds nominal Humidity 5 to 95% RH non-condensing Ambient temperature
- Normal duty -22°F to +122°F [-30°C to +50°C]
- Safety duty 3 on/off cycles after 30 minutes at ambient temperature of 250°F [121°C]
Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA type 1 / IP40 Housing material Zinc coated metal Gears Permanently lubricated Agency listings cULus listed to UL873 and
CAN/CSAC22.2 No.24
Noise level Maximum run 45 dB (A); spring 62dB Servicing Maintenance free Quality standard ISO 9001, 5 year Belimo warranty Weight FSAF120/-S US FSAF24/-S US
6.1/6.6 lbs (2.8/3 kg) 5.7/6.2 lbs (2.6/2.8 kg)
Auxiliary Switch
2xSPST 7A resistive, 2.5A inductive at 120V or 250V, UL listed, double-insulated, one switch at 10°, one adjustable from 30° to 90°
D004
112
®
Standard: 1/2" to 1.05"
Optional* 3/8" to 3/4"
3/8" to 5/8"
*with K4 US clamp
0.65" [16.5]
[57]
2.24"
3.10" [78]
0.19" [5]
0.39" [10]
0.35" [9]
3.86" [98]
3.15" [80]
1.97" [50]
2.64" [67]
10.59" [269]
5.85" [148.5]
0.26" [6.5]
1.93"
[49]
Page 4
113
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FS Series
FSAF120 (-S) US, FSAF24 (-S) US
Fire and smoke actuator, 133 in-lb, [15 Nm], spring return, meets 250°F [121°C] for half hour, 75 second
®
Accessories
AF series accessories may be employed: IND-AF2 Damper position indicator K4 US Universal clamp for 3/8 to 3/4 shafts K4-1 US Universal clamp for up to 1.05 dia. jackshafts K4-H Universal clamp for hexshafts 3/8 to 5/8 KH-AF Crankarm for up to 3/4 round shaft (Series 2) KH-AF-1 Crankarm for up to 1.05 jackshaft (Series 2) KH-AFV V-bolt kit for KH-AF and KH-AF-1 Tool-01 10 mm wrench ZDB-AF2 Angle of rotation limiter ZG-100 Universal mounting bracket ZG-101 Universal mounting bracket ZG-102 Multiple actuator mounting bracket ZG-103 Universal mounting bracket ZG-104 Universal mounting bracket ZG-106 Mounting bracket for Honeywell
®
Mod IV replace-
ment or new crankarm type installations
ZG-107 Mounting bracket for Honeywell
®
Mod III or Johnson
®
Series 100 replacement or new crankarm type installations
ZG-108 Mounting bracket for Barber Colman
®
MA 3../4..,
Honeywell
®
Mod III or IV or Johnson®Series 100
replacement or new crankarm type installations ZG-AF Crankarm adaptor kit for AF/NF ZG-AF108 Crankarm adaptor kit for AF/NF ZS-100 Weather shield (metal)
ZS-150 Weather shield (polycarbonate) ZS-300 NEMA 4X housing 22965-00001 12mm form fit square shaft adaptor
For an overview of how to apply the accessories, see Belimo Mechanical Accessories and refer to the Belimo Mounting Methods Guide.
Note: When using FSAFxx (-S) US actuators, only use accessories listed on this page.
Wiring diagrams
1
2
3 4
5
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power
consumption and input impedance must be observed. No ground connection is required. Double insulated. Actuator may also be powered by 24 VDC. Meets UL and CSA requirements without the need of an
electrical ground connection.
Line Volts
1 Com (Black) 2 + Hot (Red)
FSAF24 US
24 VA C Transformer
1 Neutral (White) 2 Hot (Black)
FSAF120 US
N N L1 H
4
5
1
1
2
2
120 VA C
3
2
1
3
4
3
For end position indication, interlock control, fan startup, etc., the FSAF24-S US and FSAF120-S US incorporates two built-in auxiliary switches: 2 x SPST, 7A resistive, 2.5 inductive @120/250 VAC, UL listed, one switch is fixed at 10°, one is adjustable from 30° to 90°.
Double insulated
Actuators may be connected in parallel. Power consumption must be observed.
FSAF24-S US FSAF120-S US
1
2
4
S1Violet
Violet
Gray
Gray
S2
S4
S6
NC
NC
NO
10°
30° to 90°
Meets UL requirements without the need of an electrical ground connection.
FSAF120 (-S) or FSAF24 (-S) Typical Specification
Large combination fire and smoke dampers are to be operated by Belimo FSAF series actuators. Manufacturer shall provide 5 year warranty.
Actuators shall draw no more than 11VA at 120V or 24V. Where auxiliary switches are required for signaling, starting fans, or
position indication, -S model actuators, damper blade, or proximity switches shall be provided.
Smaller dampers shall employ Belimo FSLF or FSNF actuators per damper manufacturer recommendations.
Safety Note
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
W220
W219
Page 5
I20651 - 06/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
1
Fire and smoke spring return actuators FSAF230 (-S) US, FSAF24 (-S) US
Fire and smoke actuator, 133 in-lb, [15 Nm], spring return, 250°F [121°C] for half hour, 75 second
Torque min. 133 in-lb, for control of air dampers
Application
For two position control of UL555S rated dampers in HVAC. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft or jack­shaft 3/8” to 1.05” in diameter by means of its universal clamp. A crankarm and mounting brackets are available if the actua­tor cannot be direct coupled to the jackshaft or damper shaft.
Square footage of damper operated will depend on make and model of damper. Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S applications.
Operation
The FSAF series actuators provide true spring return operation for reliable fail-safe application and positive close­off on UL555S dampers.The spr ing return system provides constant torque to the damper with, and without, power applied to the actuator.
The FSAF series provides 95° of rotation and is provided with a graduated position indicator showing 0 to 95°.The FSAF has a manual positioning mechanism which allows the setting of any damper position within its 95° of rotation.
The actuator is shipped in the zero fail-safe position to pro­vide automatic compression against damper gaskets for tight shut-off. When power is applied, the manual mechanism is released and the actuator drives toward the open position where it stops rotating.
The manual override can also be released physically by the use of a crank supplied with the actuator.
Dimensions
(All numbers in brackets are metric.)
Technical Data FSAF230 (-S) US FSAF24 (-S) US
Pow er supply 230 V AC ± 14% 24 V AC ± 20%
50/60 Hz 24 VDC -10% +20%
Power consumption 50/60Hz:
Running: 11W 12VA .07A 7.5W 10VA .4A
Holding: 3.5W 6VA .03A 2W 4VA .15A Transformer sizing 10 VA (Class 2 power source 24V only) Electrical connection
Motor 3 ft, 18 ga, 2 color coded leads Auxiliary switches 3 ft, 18 ga, 4 leads appliance cable
1/2conduit connectors Overload protection Electronic throughout 0 to 95° rotation Angle of rotation Mechanically limited to 95° Torque 133 in-lb [15 Nm] constant Direction of rotation Spring return reversible with CW/CCW
mounting. Position indication Visual indicator, 0° to 95° (0° is spring
return position) Manual override 3mm hex crank (shipped w/actuator) Running time <75 sec. constant, independent of load,
Spring return <20 seconds nominal Humidity 5 to 95% RH non-condensing Ambient temperature
- Normal duty -22°F to +122°F [-30°C to +50°C]
- Safety duty 3 on/off cycles after 30 minutes at ambient temperature of 250°F [121°C]
Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA type 1 / IP40 with flexible conduit Housing material Zinc coated metal Gears Permanently lubricated Agency listings cULus listed to UL873 and
CAN/CSA C22.2 No.24
Noise level Maximum run 45 dB (A); spring 62dB Servicing Maintenance free Quality standard ISO 9001, 5 year Belimo warranty Weight FSAF230/-S US FSAF24/-S US
6.9 lbs (3.1 kg) 6.0 lbs (2.7 kg)
Auxiliary Switch
2xSPST 7A resistive, 2.5A inductive at 120V or 250V, UL listed, double-insulated, one switch at <10°, one adjustable from >30°to 90°
70615-00001A
D004
®
Standard: 1/2" to 1.05"
Optional* 3/8" to 3/4"
3/8" to 5/8"
*with K4 US clamp
0.65" [16.5]
[57]
2.24"
3.10" [78]
0.19" [5]
0.39" [10]
0.35" [9]
3.86" [98]
3.15" [80]
1.97" [50]
2.64" [67]
10.59" [269]
5.85" [148.5]
0.26" [6.5]
1.93"
[49]
Page 6
I20651 - 06/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
2
Application Information
Accessories
AF series accessories may be employed: IND-AF2 Damper position indicator K4 US Universal clamp for 3/8to 3/4shafts K4-1 US Universal clamp for up to 1.05dia. jackshafts K4-H Universal clamp for hexshafts 3/8to 5/8 KH-AF Crankarm for up to 3/4round shaft (Ser ies 2) KH-AF-1 Crankarm for up to 1.05jackshaft (Series 2) KH-AFV V-bolt kit for KH-AF and KH-AF-1 Tool-01 10 mm wrench ZDB-AF2 Angle of rotation limiter ZG-100 Universal mounting bracket ZG-101 Universal mounting bracket ZG-102 Multiple actuator mounting bracket ZG-103 Universal mounting bracket ZG-104 Universal mounting bracket ZG-106 Mounting bracket for Honeywell
®
Mod IV replace-
ment or new crankarm type installations
ZG-107 Mounting bracket for Honeywell
®
Mod III or Johnson
®
Series 100 replacement or new crankarm type installations
ZG-108 Mounting bracket for Barber Colman
®
MA 3../4..,
Honeywell
®
Mod III or IV or Johnson®Series 100
replacement or new crankarm type installations ZG-AF Crankarm adaptor kit for AF/NF ZG-AF108 Crankarm adaptor kit for AF/NF ZS-100 Weather shield (metal)
ZS-150 Weather shield (polycarbonate) ZS-300 NEMA 4X housing 22965-00001 12mm form fit square shaft adaptor
For an overview of how to apply the accessor ies, see Belimo Mechanical Accessories and refer to the Belimo Mounting Methods Guide.
Note: When using FSAFxx (-S) US actuators, only use accessories listed on this page.
Wiring diagrams
1
2
3 4
5
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power
consumption and input impedance must be observed. No ground connection is required. Double insulated. Actuator may also be powered by 24 VDC. Meets UL and CSA requirements without the need of an
electrical ground connection.
Line Volts
1 Com (Black) 2 + Hot (Red)
FSAF24 US
24 VAC Transformer
1 Neutral (White) 2 Hot (Black)
FSAF230 US
N N L1 H
4
5
1
1
2
2
230 VAC
3
2
1
3
4
3
For end position indication, interlock control, fan startup, etc., the FSAF24-S US and FSAF230-S US incorporates two built-in auxiliary switches: 2 x SPST, 7A resistive, 2.5 inductive @120/250 VAC, UL listed, one switch is fixed at 10°, one is adjustable from 30° to 90°.
Double insulated
Actuators may be connected in parallel. Power consumption must be observed.
FSAF24-S US FSAF230-S US
1
2
4
S1Violet
Violet
Gray
Gray
S2
S4
S6
NC
NC
NO
<10°
>30° to 90°
Meets UL requirements without the need of an electrical ground connection.
FSAF230 (-S) or FSAF24 (-S) Typical Specification
Large combination fire and smoke dampers are to be operated by Belimo FSAF series actuators. Manufacturer shall provide 5 year warranty.
Actuators shall draw no more than 12VA at 230V or 10 VA at 24V. Where auxiliary switches are required for signaling, starting fans, or
position indication, -S model actuators, damper blade, or proximity switches shall be provided.
Smaller dampers shall employ Belimo FSLF or FSNF actuators per damper manufacturer recommendations.
Safety Note
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input and output wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
W440
W439
®
Page 7
Application:
The type FSNF spring-return actuator is intended for the oper­ation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing at 350°F. Square footage of damper operated will depend on make and model and the temperature required.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft (3/8 to 1.05) is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.
The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Accessories
All AF/NF linkages and parts may be employed.
Technical Data FSNF120(-S) FSNF24(-S)
Power supply 120 VAC ± 10% 24 VAC ± 20%
50/60 Hz 50/60 Hz
Power consumption Running: 27 VA, .23A
Holding: 10 VA, .09A
Transformer sizing 27 VA Class 2 power supply
Electrical connection 3 ft, 18 ga, 3 color coded leads (120V)
3 ft, 18 ga, 2 color coded leads (24V) 3 ft, 18 ga, appliance cable (-S models)
Overload protection Electronic throughout 0 to 95° rotation
Grounded enclosure,120V
Electrical protection Double insulated aux switches Control Microprocessor
Angle of rotation 95° Torque 70 in-lb [7.9 Nm] minimum
from 32°F to 350°F
Direction of rotation Spring return can be selected by
CCW/CW mounting Position indication Visual indicator, 0° to 95° Running time Between 32°F and 350°F
motor: < 15 sec at rated voltage and
torque
spring: < 15 sec Auxiliary switches 2 x SPDT 7A (2.5A inductive)@
125/250VAC, UL listed, 5° and 85° Humidity 5 to 95% RH noncondensing Ambient temperature 32°F to +122°F [0°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA type 1, zinc coated steel Gears Steel, permanently lubricated Agency listings cULus listed to UL873 and
CAN/CSA C22.2 No. 24 Servicing Maintenance free Quality standard ISO 9001 Weight 24,120, (-S) [kg] 6 lbs [2.75], 6.7 lbs [3.0], (+.5 lbs [+.23])
1.97"
3.15" [80]
3.86" [98]
3.10" [78]
2.24"
[57]
[5]
[50]
1.93"
[49]
2.89"
[73.5]
2.64" [67]
0.26" [6.5]
5.85" [148.5]
10.20" [259]
0.35" [9]
0.39" [10]
0.65" [16.5]
0.19" [5]
[ø41.2]
ø1.62"
[191.6]
7.54"
-S models only
Standard: 1/2" to 1.05"
Optional* 3/8" to 3/4"
*with K4 US clamp
0.19"
Dimensions (All ratings in brackets are millimeters.)
D058
Wiring
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power con-
sumption must be observed.
W177
2
1
(FSNF24-S/120-S)
120 VAC
24 VAC
Safety note:
The actuator contains no components which the user can replace or repair.
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FSNF120 (-S) US, FSNF24 (-S) US
Fire and smoke actuator, 70 in-lb, spring return, 350°F for half hour, 15 sec. cycle time
114
Wht
1
Blk
No ground on 24 V models
24V
C H
120V
N
L1
1 Neutral 2 Hot
3 Ground
FSNF24 US FSNF120 US
®
2
Page 8
Auxiliary switch wiring for FSNF24-S US, FSNF120-S US
Parallel actuator wiring
W175
1
1
Single section
for one
FSNF actuator
Large multi-section assembly
1
2
Gnd
1
2
Gnd
Wht Blk
24V
C H
120V
N
L1
Blank-off Channel
Blank-off Channel
Use of blank-offs between damper sections to
provide space for actuator mounting.
The typical fire and smoke damper requires from 5-15 in-lb of torque per square foot at 250°F - 350°F under dynamic load (2400 fpm velocity). The FSNF will operate multi-section
dampers using multiple actuators for multiple sections. Some of the methods used are shown left.
Multi-section damper assemblies – typical applications
Caution must be used when replacing failed motors with new Belimo actuators. Many old motors did not have internal springs and depended on external springs on the side of the damper or wrapped around the damper shaft to close the damper.
In some cases, the damper must be replaced because the damper would have to undergo major modifications to replace an actuator.
In many cases, replacing the actuator voids the UL555S listing of the damper.
No ground on 24 V models.
Smoke Control and Combination Fire and Smoke Control Damper Actuators
All smoke and combination fire and smoke dampers shall be provided with Belimo FSLF, FSNF, or FSAF actuators. No substitutions allowed.
Damper and actuator shall have UL555S Listing for 250°F (350°F) and shall comply with UBC if required by local codes.
Where proof of closure switches are required, blade switch­es, actuator auxiliary switches, or proximity switches are allowed.
Typical specification
This is a direct coupled actuator. If linkages are needed use the FSNF series. Square shaft adaptors are available: 22153-00002, 22153-00003, 22513-00004 for the 8mm, 10mm, and 12mm, form fit respectively.
Safety note: 1/2" Threaded Connector
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
3/8" Flexible Connector Models (-FC Screw Connector)
Mount the flexible conduit into the actuators metal bushing by means of the provided screw with a torque of 1.2 Nm. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Replacement applications
The number one "equal or better" requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements. In some cases a permit and inspection may be required.
Contact Belimo for a list of damper manufacturers with UL555S listing with Belimo FSAF, FSLF, & FSNF actuators.
115
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FS Series
FSNF120 (-S) US, FSNF24 (-S) US
Fire and smoke actuator, 70 in-lb, spring return, 350°F for half hour, 15 sec. cycle time
®
1
For end position indication, interlock control, fan startup, etc., FSNF24-S US and FSNF120-S US incorporate two built-in auxiliary switches: 2 x SPDT, 7A (2.5A inductive)@125/250 VAC, UL listed, 5° and 85°. Switch rating is for 250°F 1/2 hour only.
2
Meets UL and CSA requirements without the need of an electrical ground connection.
S1
NC
S2 S3
NO
S4
NC
S5 S6
NO
FSNF24-S US FSNF120-S US
5°
85°
1 2
Page 9
1
I20638 - 04/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
Fire and smoke spring return actuators FSNF230 (-S) US, FSNF24 (-S) US
70 in-lb [7.9 Nm], spring return, 350°F [177°C] for limited time, nominal 15 sec. operation
Application:
The type FSNF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing. Square footage of damper operated will depend on make and model and the temperature required.
Operation
Mounting of the actuator to the damper shaft or jackshaft (3/8” to 1.05”) is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.
The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Accessories
All AF/NF linkages may be applied. Order part 22965-00001 for square shafts.
Technical Data FSNF230(-S) FSNF24(-S)
Power supply 230 VAC ± 10% 24 VAC ± 20%
50/60 Hz 50/60 Hz
Power consumption running: 18 W, .13A 27 VA
holding: 6 W, .04A 10 VA Transformer sizing 24 VAC 27 VA Class 2 power supply Electrical connection 3 ft [1m], 18 ga, 3 color coded leads (230V)
3 ft [1m], 18 ga, 2 color coded leads (24V)
Aux switch: 3 f t [1m], 18 ga, appliance cable Overload protection Electronic throughout 0 to 95° rotation
Auto-restart after temporary overload Electrical protection Grounded enclosure 230 V
Double insulated aux switches Control Microprocessor Angle of rotation 95°
Torque 70 in-lb [7.9 Nm] minimum
from 32°F to 350°F [0°C to 177°C] Direction of rotation Spring return can be selected by
CCW/CW mounting Position indication visual indicator, 0° to 95° Running time Between 32°F and 350°F [0°C to 177°C]
motor: apx. 15 sec at rated voltage
and torque
spring: apx. 15 sec Auxiliary switches 2 x SPDT 7A (2.5A inductive)@
125/250VAC, UL listed, 5° and 85° Humidity 5 to 95% RH noncondensing Ambient temperature 32°F to +122°F [0°C to +50°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA 1, zinc coated steel Gears Steel - permanently lubricated Agency listings cULus listed to UL873 and
CAN/CSA C22.2 No. 24 Servicing Maintenance free Quality standard ISO 9001 Weight 24,230, (-S) [kg] 6 lbs [2.75], 6.7 lbs [3.0], (+.5 lbs [+.23])
1.97"
3.15" [80]
3.86" [98]
3.10" [78]
2.24"
[57]
[5]
[50]
1.93"
[49]
2.89"
[73.5]
2.64" [67]
0.26" [6.5]
5.85" [148.5]
10.20" [259]
0.35" [9]
0.39" [10]
0.65" [16.5]
0.19" [5]
[ø41.2]
ø1.62"
[191.6]
7.54"
-S models only
Standard: 1/2" to 1.05"
Optional* 3/8" to 3/4"
*with K4 US clamp
Dimensions (All ratings in brackets are millimeters)
D058
Wiring
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power
consumption must be observed.
W192
2
1
®
(FSNF24-S/230-S)
230 VAC
70101-00001B
Safety note:
The actuator contains no components which the user can replace or repair.
230V
US 3Φ
Eu
24V
C
Wht
1
H
Blk
L2
N
L1
L
No ground on 24 V models
1 C N (230V) 2 H H (230V) 3 Ground
FSNF24 US FSNF230 US
2
Page 10
Auxiliary switch wiring for FSNF24-S US, FSNF230-S US
Parallel actuator wiring
W436
1
1
I20638 - 04/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
1 2
Gnd
1 2
Gnd
Wht Blk
24V
C H
Eu
N L
US 3Φ
L2 L1
230V
The typical US fire-smoke damper requires from 5-15 in-lb torque per square ft. [6-17 Nm per square meter] at 350°F [171°C] under dynamic load (2400 fpm [12m/s] velocity).
Some of the methods used for multi-section dampers with the FSNF actuators are shown to the left.
Multi-section damper assemblies – typical applications
Application information
Replacement applications
The number one "equal or better" requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements. In some cases a permit and inspection may be required.
Contact Belimo for a list of damper manufacturers with UL555S listing with Belimo FSAF, FSLF, & FSNF actuators.
Caution must be used when replacing failed motors with new Belimo actuators. Many old motors did not have internal springs and depended on external springs on the side of the damper or wrapped around the damper shaft to close the damper.
In some cases, the damper must be replaced because the damper would have to undergo major modifications to replace an actuator.
In many cases, replacing the actuator voids the UL555S listing of the damper.
Smoke Control and Combination Fire and Smoke Control Damper Actuators
All smoke and combination fire and smoke dampers shall be provided with Belimo FSLF, FSNF, or FSAF actuators. No substitutions allowed.
Damper and actuator shall have UL555S Listing for 250°F (350°F) and shall comply with UBC if required by local codes.
Where proof of closure switches are required, blade switches, actuator auxiliary switches, or proximity switches are allowed.
Typical specification
No ground on 24 V models.
Single section
for one
FSNF actuator
Large multi-section assembly
Blank-off Channel
Blank-off Channel
Use of blank-offs between damper sections to
provide space for actuator mounting.
Safety note: 1/2" Threaded Connector
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
3/8" Flexible Connector Models (-FC Screw Connector)
Mount the flexible conduit into the actuators metal bushing by means of the provided screw with a torque of 1.2 Nm. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
®
S1
NC
S2 S3
NO
S4
NC
S5 S6
NO
FSNF24-S US FSNF230-S US
1
For end position indication, interlock control, fan startup, etc., FSNF24-S and FSNF230-S incorporate two built-in auxiliary switches: 2 x SPDT, 7A (2.5A inductive)@125/250 VAC, UL listed, 5° and 85°. Switch r ating 250°F [121°C] 1/2 hour only.
Meets UL and CSA requirements without the need of an
2
electrical ground connection.
5°
85°
1 2
Page 11
Application:
The type FSLF spring-return actuator is intended for the oper­ation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing.
Square footage of damper operated will depend on make and model and the temperature required.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.
The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (All ratings in brackets are metric.)
Wiring
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power con-
sumption must be observed.
1 Common, Neutral 2 Hot
3 Ground
1
2
FSLF24 US FSLF120 US
No ground on 24 V models
H=Red
L1=Blk
24V
120V
C=Blk
N=Wht
W0201
2
1
Technical Data FSLF120(-S) US FSLF24(-S) US
Nominal voltage 120 VAC 50/60 Hz 24 VAC 50/60 Hz Nominal voltage range 108 - 132 VAC 21.6 - 26.4 VAC Power consumption Running: 24 VAC: 50/60 Hz: 5.0 VA
120 VAC, 60 Hz: 18 VA (120 VAC, 50 Hz: 20 VA)
Holding: 24 VAC, 50/60 Hz: 3.5 VA
120 VAC, 60 Hz: 6.5 VA
(120 VAC, 50 Hz: 12 VA) Transformer sizing Safety note: 24 VAC Connect via safety isolating transformer,
Class 2 supply.
Electrical connection 18 ga, 3 color coded leads (120 V) 3 ft
18 ga, 2 color coded leads (24 V) 3 f t 3 ft, 18 ga, appliance cable (Aux switches)
Overload protection Electronic throughout 0 to 95° rotation
Auto-restart after temporary overload Electrical protection motor FSLF120 US grounded enclosure Electrical protection Double insulated
Auxiliary switches Angle of rotation 95°
Torque 30 in-lb [3.5 Nm] minimum
from 32°F to 350°F [0°C to 177°C] Direction of rotation Spring return can be selected by
CCW/CW mounting Position indication Visual indicator, 0° to 95° Running time Motor: < 15 sec at rated voltage and torque
32°F to +122°F [0°C to +50°C]
Spring:< 15 sec at ambient Control Microprocessor Auxiliary switches 2 x SPST 0.5 A inductive @ 120/250 V,
1 mA @ 5 VDC, 3 A resistive
@ 120/250 V, UL listed, 10° and 85° Humidity 5 to 95% RH noncondensing Ambient temperature
- Normal operation 32°F to +122°F [0°C to +50°C]
- Safety operation 3 On/Off cycles after 30 minutes
at ambient temperature of 350°F [177°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA type 1, zinc coated steel Type of action Type 1.B Software class A Shaft 3/8-1/2 rnd (7/16 sq) 1/2-3/4 rnd w/K6-1 Gears Permanently lubricated Agency listings cULus listed acc. to UL 60730-1, CE Servicing Maintenance free Quality standard ISO 9001 Weight 24, 120, (-S) [kg] 3.4 lbs [1.7], 4 lb [1.8], +.3 lb [+.14]
FSLF120-S US/24-S US
Safety note:
The actuator contains no components which the user can replace or repair.
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FSLF120 (-S) US, FSLF24 (-S) US
Fire and smoke actuator, 30 in-lb, [3.5 Nm], spring return, 350°F [177°C] for half hour, 15 sec. operation.
116
7.03" [179]
6.81" [173]
[11]0.45"
2.37" [60]
0.2 [5]
5.42" [138]
1.1" [28]
max 0.79"
min 0.5"
[12.7]
2.24" [57]
[19]0.75"
0.24"
®
[20]
"
3.86" [98]
[
6]
Page 12
117
I20618 - Subject to change. © Belimo Aircontrols (USA), Inc.
FS Series
FSLF120 (-S) US, FSLF24 (-S) US
Fire and smoke actuator, 30 in-lb, [3.5 Nm], spring return, 350°F [177°C] for half hour, 15 sec. operation.
®
Auxiliary switch wiring for FSLF24-S US, FSLF120-S US
Parallel actuator wiring
W200
1
1
Single section
for one
FSLF actuator
Two section for
two FSLF actuators
Maximum area
one actuator
Maximum area
for two actuators
1
2
Gnd
1
2
Gnd
C=Blk
H=Red
N=Wht L1=Blk
24V
120V
The typical fire and smoke damper requires from 5-15 in-lb of torque per square foot at 250°F - 350°F under dynamic load
(2000 fpm velocity). The FSLF is a single section damper actuator. For the multi section dampers, use the FSNF series.
Multi-section damper assemblies – typical applications
Replacement applications
The number one "equal or better" requirement for use as a replacement for obsolete defective motors is the UL555S list­ing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements.
Contact Belimo for a list of damper manufacturers with UL555S listing with Belimo FSAF, FSNF, & FSLF actuators.
Caution must be used when replacing failed motors with new Belimo actuators. Many old motors did not have internal springs and depended on external springs on the side of the damper or wrapped around the damper shaft to close the damper.
In some cases, the damper must be replaced because the damper would have to undergo major modifications to replace an actuator.
Most codes require that equal or better actuators be used to replace defectives.
Smoke Control and Combination Fire and Smoke Control Damper Actuators
All smoke and combination fire and smoke dampers shall be provided with Belimo FSLF, FSNF, or FSAF actuators. No substitutions allowed.
Damper and actuator shall have UL555S Listing for 250°F (350°F) and shall comply with UBC if required by local codes.
Where proof of closure switches are required, blade switch­es, actuator auxiliary switches, or proximity switches are allowed.
Typical specification
No ground on 24 V models.
This is a direct coupled actuator. If linkages are needed use the FSNF series. Square shaft adaptors are available: 22153-00002, 22153-00003, 22513-00004 for the 8mm, 10mm, and 12mm, form fit respectively.
Safety note: 1/2" Threaded Connector
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
3/8" Flex Connector (-FC models)
Mount the flexible conduit into the actuators metal bushing by means of the provided screw with a torque of 1.2 Nm. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Gray
S4 makes to S6 when the
1
actuator is powered open.
2
3
For end position indication, interlock control, fan startup, etc., FSLF24-S US and FSLF120-S US incorporate two built-in auxiliary switches.
Double insulated
S1Violet S2Violet
NC
10°
2
S4
3
S6Gray
NO
1
85°
FSLF24-S US FSLF120-S US
Page 13
1
I20632 - 04/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
Fire and smoke spring return actuators FSLF230 (-S) US, FSLF24 (-S) US
Fire and smoke actuator, 30 in-lb, [3.5 Nm], spring return, 350°F [177°C] for half hour, 15 sec. operation.
Application:
The type FSLF spring-return actuator is intended for the operation of smoke and combination fire and smoke dampers in ventilation and air-conditioning systems. The actuator will meet requirements of UL555 and UL555S when tested as an assembly with the damper and will meet requirements of UBC for 15 second opening and closing.
Square footage of damper operated will depend on make and model and the temperature required.
Operation
Mounting of the actuator to the damper axle shaft or jackshaft is via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection. The specially designed clamp will not crush hollow shafts. The bottom end of the actuator is held by an anti-rotation strap or by a stud provided by the damper manufacturer.
The actuator is mounted in its fail safe position with the damper blade(s) closed. Upon applying power, the actuator drives the damper to the open position. The internal spring is tensioned at the same time. If the power supply is interrupted, the spring moves the damper back to its fail-safe position.
Dimensions (All ratings in brackets are metric.)
Wiring
Provide overload protection and disconnect as required. Actuators may be connected in parallel. Power
consumption must be observed.
1 Common, Neutral 2 Hot
3 Ground
1
2
FSLF24 US FSLF230 US
No ground on 24 V models
H=Red
L1=Brn
24V
230V
N=Blu
C=Blk
W270
2
1
®
70266-00001C
Technical Data FSLF230(-S) US FSLF24(-S) US
Nominal voltage 230 VAC 50/60 Hz 24 VAC 50/60 Hz Nominal voltage range 207 - 253 VAC 21.6 - 26.4 VAC Power consumption Running: 24 VAC: 50/60 Hz: 5.0 VA
230 VAC, 60 Hz: 17 VA 230 VAC, 50 Hz: 17 VA
Holding: 24 VAC, 50/60 Hz: 3.5 VA
230 VAC, 60 Hz: 6 VA
230 VAC, 50 Hz: 8 VA Transformer sizing Safety note: 5 VA 24 VAC Connect via safety isolating transformer,
Class 2 supply.
Electrical connection 3 ft, 18 ga, 3 color coded leads (230 V)
3 ft, 18 ga, 2 color coded leads (24 V) 3 ft, 18 ga, appliance cable (Aux switches)
Overload protection Electronic throughout 0 to 95° rotation
Auto-restart after temporary overload Electrical protection motor FSLF230 US grounded enclosure Electrical protection Double insulated Auxiliary Switches Control Microprocessor Angle of rotation 95° Torque 30 in-lb [3.5 Nm] minimum
from 32°F to 350°F [0°C to 177°C] Direction of rotation Spring return can be selected by
CCW/CW mounting Position indication Visual indicator, 0° to 95° Running time Motor: < 15 sec at rated voltage
and torque, 32°F to +122°F [0°C to +50°C]
Spring: < 15 sec Auxiliary switches 2 x SPST 0.5 A inductive @ 120/250 V,
1 mA @ 5 VDC, 3 A resistive
@ 120/250 V, UL listed, 10° and 85° Humidity 5 to 95% RH noncondensing Ambient temperature
- Normal operation 32°F to +122°F [0°C to +50°C]
- Safety operation 3 On/Off cycles after 30 minutes
at ambient temperature of 350°F [177°C] Storage temperature -40°F to +176°F [-40°C to +80°C] Housing NEMA type 1, zinc coated steel. IP10 Type of action Type 1.B Software class A Shaft 3/8”-1/2” rnd (7/16” sq) 1/2”-3/4” rnd w/K6-1 Gears Permanently lubricated Agency listings cULus listed to UL 60730-1 and CAN/CSA
22.2 No 4. Servicing Maintenance free Quality standard ISO 9001 Weight 24, 120, (-S) [kg] 3.4 lb [1.55 kg], 4 lb [1.8], (+.3 lb [+.14])
FSLF230-S US/24-S US
Safety note:
The actuator contains no components which the user can replace or repair.
7.03" [179]
6.81" [173]
[11]0.45"
2.37" [60]
0.2 [5]
5.42" [138]
1.1" [28]
max 0.79"
min 0.5"
[12.7]
2.24" [57]
[19]0.75"
0.24"
[20]
"
3.86" [98]
[
6]
Page 14
2
I20632 - 04/-06 - Subject to change. © Belimo Aircontrols (USA), INC.
Auxiliary switch wiring for FSLF24-S US, FSLF230-S US
Parallel actuator wiring
W269
1
1
Single section
for one
FSLF actuator
Two section for
two FSLF actuators
Maximum area
one actuator
Maximum area
for two actuators
1
2
Gnd
1
2
Gnd
H=Red
L1=Brn
24V
230V
C=Blk N=Blu
The typical fire and smoke damper requires from 5-15 in-lb of torque per square foot at 250°F - 350°F under dynamic load
(2000 fpm velocity). The FSLF is a single section damper actuator. For the multi section dampers, use the FSNF series.
Multi-section damper assemblies – typical applications
Application information
Caution must be used when replacing failed motors with new Belimo actuators. Many old motors did not have internal springs and depended on external springs on the side of the damper or wrapped around the damper shaft to close the damper.
In some cases, the damper must be replaced because the damper would have to undergo major modifications to replace an actuator.
Most codes require that equal or better actuators be used to replace defectives.
No ground on 24 V models.
This is a direct coupled actuator. If linkages are needed use the FSNF series. Square shaft adaptors are available: 22153-00002, 22153-00003, 22513-00004 for the 8mm, 10mm, and 12mm, form fit respectively.
Safety note: 1/2" Threaded Connector
Screw a conduit fitting into the actuators metal bushing. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
3/8" Flex Connector (-FC models)
Mount the flexible conduit into the actuators metal bushing by means of the provided screw with a torque of 1.2 Nm. Jacket the actuators input wiring with suitable flexible conduit. Properly terminate the conduit in a suitable junction box.
Smoke Control and Combination Fire and Smoke Control Damper Actuator
All smoke and combination fire and smoke dampers shall be provided with Belimo FSLF, FSNF, or FSAF actuators. No substitutions allowed.
Damper and actuator shall have UL555S Listing for 250°F (350°F) and shall comply with UBC if required by local codes.
Where proof of closure switches are required, blade switches, actuator auxiliary switches, or proximity switches are allowed.
Typical specification
Replacement applications
The number one "equal or better" requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with the damper for the application. The local authority having jurisdiction sets the requirements.
Contact Belimo for a list of damper manufacturers with UL555S listing with Belimo FSAF, FSNF, & FSLF actuators.
®
Violet Violet
Gray Gray
S1 S2
S4 S6
NC
NO
1
S4 makes to S6 when the
1
actuator is powered open.
2
For end position indication, interlock control, fan startup, etc., FSLF24-S US and FSLF230-S US incorporate two built-in auxiliary switches.
Double insulated
3
FSLF24-S US FSLF230-S US
10°
85°
2
3
Loading...