Greenheck FAJ-402 Installation Manual

®
Fabricated Steel Adjustable Louver
J Blade
Application and Design
FAJ-402 is fabricated adjustable louver designed to protect air intake and exhaust openings in building exterior walls that require tight air shut off. Design incorporates adjustable J style blades that may be motorized or manually operated. The FAJ­402 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Frame . . . . . . . .4 in. x 16 gauge galvanized steel wall
thickness
Blades . . . . . . . .J Style, 16 gauge galvanized steel wall
thickness, positioned at 45º on approximately
4.5 in. centers
Seals . . . . . . . . .Dual-durometer extruded vinyl blade seals
Compressible stainless steel jamb seals
Linkage . . . . . . . Side linkage out of airstream (concealed in
frame)
Bearings . . . . . .Synthetic sleeve type
Axles . . . . . . . . .½ in. diameter zinc plated steel
Construction . . .Mechanically fastened
Birdscreen . . . . .½ in. x ½ in. mesh 19 gauge galvanized steel in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 ½ in. H
Maximum Single Section Size . . .60 in. W x 96 in. H
Options (at additional cost)
• A variety of bird and insect screens
• A variety of electric, pneumatic or manual actuators
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Security bars
• Stainless steel frame and blade
• A variety of architectural finishes including: Baked enamel paint Kynar paint
FAJ-402
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height Inches
12 18 24 30 36 42 48 54 60
12.5 0.21 0.34 0.47 0.60 0.74 0.87 1.00 1.14 1.27
18 0.37 0.61 0.84 1.10 1.34 1.58 1.82 2.06 2.30
24 0.52 0.85 1.18 1.52 1.85 2.19 2.52 2.86 3.19
30 0.66 1.09 1.51 1.94 2.37 2.80 3.22 3.65 4.08
36 0.95 1.56 2.17 2.79 3.40 4.01 4.63 5.24 5.85
42 1.09 1.80 2.50 3.21 3.92 4.62 5.33 6.04 6.74
48 1.21 2.00 2.78 3.57 4.36 5.13 5.93 6.72 7.50
54 1.52 2.51 3.49 4.48 5.46 6.45 7.44 8.42 9.41
60 1.66 2.74 3.82 4.90 5.98 7.06 8.14 9.22 10.30
66 1.81 2.98 4.15 5.32 6.50 7.67 8.84 10.01 11.18
72 2.09 3.45 4.81 6.17 7.53 8.88 10.24 11.60 12.96
78 2.24 3.69 5.14 6.59 8.04 9.49 10.95 12.40 13.85
84 2.38 3.93 5.47 7.01 8.56 10.10 11.65 13.19 14.74
90 2.67 4.40 6.13 7.86 9.59 11.32 13.05 14.78 16.51
96 2.67 4.40 6.13 7.86 9.59 11.32 13.05 14.78 16.51
Louver Width in Inches
FAJ-402PERFORMANCE DATA
Adjustable Louver J Blade
Fabricated Steel
Greenheck Fan Corporation certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
the FAJ­402 louvers shown
®
herein are
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90 80
70
60
50
40
30
0.09
20
0.08
0.07
Static Pressure Drop
0.06
0.05
10
0.04
9 8
0.03
7
6
5
0.02
ft/min:
m/s:
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
200 300 400 500 600 700 800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model FAJ-402 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2
oz/ft2
0.30
Test Size 48 in. x 48 in.
80
0.25
0.20
60
0.15
40
0.10
20
0.05
Water Penetration per Unit Free Area
0.00
0
ft/min:
m/s:
Test Period 15 minutes
Standard Air - .075 lb/ft
600 650 700 750 800 850 900
3.5 4.0
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
The beginning point of water penetration for Model FAJ-402 is
* 691 fpm free area velocity. These perfor mance ratings do not guarantee
a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Loading...