Greenheck EXA User Manual

Part #474047
®
®
Supplementary Information
This unit is equipped with a Model PVF Indirect Gas­Fired furnace that has a 4:1 turndown. The primary gas control valve used in this unit is a Honeywell combination valve. It controls the high fire gas supply and acts as an on/off switch. The EXA valve is located just after the Honeywell combination valve and the EXA valve is the device that modulates or changes the gas volume that is being supplied to the furnace manifold. These valves require adjustment at time
of unit start-up.
Typical Honeywell
Combination Valve
The EXA gas valve has a built-in digital controller that will accept user settings for High Fire and Low Fire and will provide minimal hysteresis throughout the entire range of modulation. The EXA valve controls the amount of combustion gas that goes to the burner, rather than just a simple on/off. During normal use, the amount of combustion gas will vary constantly, depending on the settings put in by the owner. This allows the EXA valve to regulate the heat output from the furnace and maintain a constant space temperature with minimal variation, or hysteresis.
The EXA Modulating Valve is controlled by a user interface known as the FX05 Controller, made by Johnson Controls. The FX05 Controller sends an analog signal to the EXA modulating valve that causes the valve to send more or less gas to the furnace.
Typical EXA
Furnace Model PVF
4:1 Modulating Valve
Both the Honeywell and the Maxitrol gas valves have been set at the factory for ideal operating gas pressures. Vibration during shipment of the unit and field conditions require that both valves be readjusted at the time of start-up. At start-up,
• Set the High Fire set point on the EXA valve by opening it all the way.
• Set the High Fire set point on the Honeywell valve to 3.5 inch WC for natural gas or 10.0 inch WC for LP gas.
• Set the Low Fire set point on the EXA gas valve at 0.3 inch WC for natural gas or 1.0 inch WC for LP gas.
The Maxitrol EXA valve has four electrical connections on board. Two are for the 24 VAC needed to power the valve and the circuit board and two are for the input signal from the FX05. The location of the 24VAC power source varies, see the unit-specific wiring diagram. The input signal that causes the EXA valve to change gas volume is always provided by the FX05 Controller and varies from 2 – 10 VDC.
When a call for heat is provided to the FX05 Controller, the controller will provide a 10 VDC signal to the EXA valve so that it will always start in a high fire condition. After ignition, the controller will change its output signal, causing the volume of combustion gas to be reduced to as little as 25% of full flow (4:1 turndown).
For every installation of this indirect gas-fired furnace, it is necessary to set the High Fire and the Low Fire settings on the EXA valve. This is a simple process that must be done in the field after the rest of the unit is operational. To enter the High Fire and Low Fire settings, it is necessary to have access to the EXA valve on-board printed circuit board and to be able to observe the LED on the printed circuit board.
Remove the cover from the circuit board housing by loosening the two Phillips head retaining screws. Identify Button #1 and Button #2 and also locate the LED indicator light.
4:1 Modulating Valve
1
Adjust High and Low Fire Settings
Terminals 1 & 2
(signal)
Button #1
EXA Modulating Gas Valve
(with cover removed)
EXA Valve High Fire Setting / Button #1
Buttons #1 and #2 are used to set desired high fire setting. To enter the High Fire setting mode, press and hold button #1 until the LED lights solid red. Release. The valve is now in the high fire setting mode.
Terminals 3 & 4
(power)
Button #2
LED Light
EXA Valve Low Fire Setting / Button #2
To enter into the low fire setting mode, press and hold button #2 until the LED light blinks red. Release. The valve is now in the low fire setting mode. Buttons #1 and #2 are used to set the desired low fire setting.
Press or hold button #1 to increase gas flow. Each press of the button is equal to the minimum available step size and will increase gas flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the button. Use this feature to rapidly increase the gas flow to the maximum setting available.
To save the High Fire setting, simultaneously hold buttons #1 and #2 until the LED turns off.
NOTE: Controls left in the High Fire setting mode will default to the current setting after five (5) minutes of inactivity.
After adjusting the High Fire setting on the EXA Modulating Valve, then adjust the High Fire setting on the Honeywell combination valve as described in the furnace IOM.
High Fire Settings
Natural Gas 3.5 inches WC
LP Gas 10.0 inches WC
Press or hold button #2 to decrease gas flow. Each press of the button is equal to the minimum available step size and will decrease gas flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the button. Use this feature to rapidly decrease the gas flow.
Press or hold button #1 to increase gas flow. Each press of the button is equal to the minimum available step size and will increase gas flow slowly. Holding the button down auto steps and eliminates the need to repeatedly press the button. Use this feature to rapidly increase the gas flow.
Low Fire Settings
Natural Gas 0.30 inches WC
LP Gas 1.0 inches WC
To save the Low Fire setting, simultaneously hold buttons #1 and #2 until the LED turns off.
NOTE: Controls left in the Low Fire setting mode will default to the current settings after 5 minutes of inactivity.
Follow the instructions in the PVF Furnace IOM and unit IOM to complete the rest of the startup
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
474047 • 4:1 Modulating Valve, Rev. 1, August 2010 Copyright 2010 © Greenheck Fan Corporation
2
Loading...